Trane AUH1D120A9H51B, AUH1B060A9H31B, ADH1B040A9H21B, ADH1B065A9H31B, ADH1C085A9H41B Installation Manual

...
18-CD33D1-4
Installer’s Guide
High Efficiency Single Stage Upflow/ Horizontal and Downflow/ Horizontal Gas-Fired, Direct Vent Condensing Furnaces
*UH1B040A9H21B *UH1B060A9H31B *UH1B080A9H31C *UH1C100A9H41B *UH1D120A9H51B
ALL phases of this installation must comply with NATIONAL, STATE AND LOCAL CODES
IMPORTANT — This Document is customer property and is to remain with this unit.
Please return to service information pack upon completion of work.
*UH1-H
*DH1B040A9H21B *DH1B065A9H31B *DH1C085A9H41B *DH1D110A9H51B
*DH1-H
DOWNFLOW
UPFLOW/HORIZONTAL
UPFLOW
DOWNFLOW/HORIZONTAL
A341624P15
Installer’s Guide
WARNING
!
SAFETY SECTION
The following safety practices and precautions must be followed during the installation, servicing, and operation of this furnace.
1. Use only with the type of gas approved for this furnace. Refer to the furnace rating plate.
2. Install this furnace only in a location and position as specified in “Location and Clearances” (page 4), of these instructions.
3. Provide adequate combustion and ventilation air to the furnace space as specified in “Air for Combustion and Ventilation” (pages 8-9), of these instructions.
4. Combustion products must be discharged outdoors. Connect this furnace to an approved vent system only, as specified in the “Venting” section (pages 13-
22), of these instructions.
5. Never test for gas leaks with an open flame. Use a commercially available soap solution made specifically for the detection of leaks to check all connections, as specified in “Gas Piping” (pages 29-
30), of these instructions.
6. Always install the furnace to operate within the furnace’s intended temperature-rise range with a duct system which has an external static pressure within the allowable range, as specified on the unit rating plate. Airflow with temperature rise for cfm versus static is shown in the Service Facts accompanying this furnace.
7. When a furnace is installed so that supply ducts carry air circulated by the furnace to areas outside the space containing the furnace, the return air shall also be handled by a duct(s) sealed to the furnace casing and terminating outside the space containing the furnace.
8. A gas-fired furnace for installation in a residential garage must be installed as specified in “Location and Clearances” section (page 4), of these instructions.
9. The furnace may be used for temporary heating of buildings or structures under construction only when the following conditions have been met:
a. The furnace venting system must be complete
and installed per manufacturers instructions.
b. The furnace is controlled only by a room
thermostat (no field jumpers).
c. The furnace return air duct must be complete and
sealed to the furnace and clean air filters are in place.
d. The furnace input rate and temperature rise must
be verified to be within nameplate marking.
e. 100% of the furnace combustion air requirement
must come from outside the structure.
f. The furnace return air temperature range is
between 55 and 80 degrees Fahrenheit.
g. Clean the furnace, duct work, and components
upon substantial completion of the construction process, and verify furnace operating conditions including ignition, input rate, temperature rise and venting, according to the manufacturer's instructions.
10. This product must be gas piped by a Licensed Plumber or Gas Fitter in the Commonwealth of Massachusetts.
CARBON MONOXIDE POISONING HAZARD Failure to follow the steps outlined below for each ap­pliance connected to the venting system being placed into operation could result in carbon monoxide poi­soning or death. The following steps shall be followed for each appli­ance connected to the venting system being placed into operation, while all other appliances connected to the venting system are not in operation:
1. Seal any unused openings in the venting system.
2. Inspect the venting system for proper size and hor­izontal pitch, as required in the National Fuel Gas Code, ANSI Z223.1/NFPA 54 or the CAN/CGA B149 Installation Codes and these instructions. Deter­mine that there is no blockage or restriction, leak­age, corrosion and other deficiencies which could cause an unsafe condition.
3. As far as practical, close all building doors and windows and all doors between the space in which the appliance(s) connected to the venting system are located and other deficiencies which could cause an unsafe condition.
4. Close fireplace dampers.
5. Turn on clothes dryers and any appliance not con­nected to the venting system. Turn on any ex­haust fans, such as range hoods and bathroom ex­hausts, so they are operating at maximum speed. Do not operate a summer exhaust fan.
6. Follow the lighting instructions. Place the appli­ance being inspected into operation. Adjust the thermostat so appliance is operating continuously.
7. If improper venting is observed during any of the above tests, the venting system must be corrected in accordance with the National Fuel Gas Code, ANSI Z221.1/NFPA 54 and/or CAN/CGA B149.1 In­stallation Codes.
8. After it has been determined that each appliance connected to the venting system properly vents where tested as outlined above, return doors, win­dows, exhaust fans, fireplace dampers and any other gas-fired burning appliance to their previous conditions of use.
© 2013 Trane All Rights Reserved 18-CD33D1-4
Installer’s Guide
WARNING
!
Safety signal words are used to designate a degree or level of seriousness associated with a particular hazard. The signal words for safety markings are WARNING and CAUTION. a. WARNING indicates a potentially hazardous situation
which, if not avoided, could result in death or serious injury.
b. CAUTION indicates a potentially hazardous situation
which, if not avoided, may result in minor or moderate injury. It is also used to alert against unsafe practices and hazards involving only property damage.
FIRE OR EXPLOSION HAZARD Failure to follow the safety warnings exactly could re­sult in serious injury, death or property damage. Improper servicing could result in dangerous opera­tion, serious injury, death, or property damage.
GENERAL INSTALLATION INSTRUCTIONS
The manufacturer assumes no responsibility for equip­ment installed in violation of any code or regulation. It is recommended that Manual J of the Air Conditioning Contractors Association (ACCA) or A.R.I. 230 be followed in estimating heating requirements. When estimating heating requirements for installation at altitudes above 2000 ft., remember the gas input may need to be reduced (See High Altitude Installation).
Material in this shipment has been inspected at the factory and released to the transportation agency without known damage. Inspect exterior of carton for evidence of rough handling in shipment. Unpack carefully after moving equipment to approximate lo­cation. If damage to contents is found, report the damage immediately to the delivering agency.
Codes and local utility requirements governing the instal­lation of gas fired equipment, wiring, plumbing, and flue connections must be adhered to. In the absence of local codes, the installation must conform with latest edition of the National Fuel Gas Code ANSI Z223.1 • National In­stallation Code, CAN/CGA B149.1. The latest code may be obtained from the American Gas Association Labora­tories, 400 N. Capitol St. NW, Washington D.C. 20001. 1-800-699-9277 or www.aga.org These furnaces have been classified as CATEGORY IV furnaces in accordance with latest edition of ANSI Z21.47
• CAN/ CGA 2.3 standards.
Contents
INSTALLATION INSTRUCTIONS
General Installation Instructions 3 Location and Clearances 4 Outline Drawings 5 Upflow Installation 7 Downflow Installation 7 Horizontal Installation 7 Air For Combustion and Ventilation 8 Duct Connections 10 Return Air Filters 11 General Venting Instructions 14 Venting Material 15 Venting Tables 15 Horizontal Venting 16 Venting Through The Wall 20 Venting Through The Roof 20 Downward Venting 22 Venting Through a Masonry Chimney 22 Condensate Drain Instructions 25 Electrical Connections 27 Field Wiring Diagrams 27 Gas Piping 29 Combustion Input Checks 31
Start Up and Adjustment 33
Preliminary Inspections 33 Lighting Instructions 34 Sequence Of Operation 34 Control And Safety Switch Adjustments 34 Airflow Adjustment 35
Conditions Affecting Operation 35
IFC Error Flash Code 37
Category IV furnaces operate with positive vent static pressure and with a flue loss less than 17 percent. These conditions require special venting systems, which must be gas tight and water tight. These Category IV Direct Vent furnaces are approved for installation in Manufac­tured/Mobile housing when used with BAYMFGH100A.
18-CD33D1-4 3
Installer’s Guide
CAUTION
!
CAUTION
!
WARNING
!
To prevent shortening its service life, the furnace should not be used as a “Construction Heater” during the finishing phases of construction until the require­ments listed in item 9, a-g of the safety section of this publication have been met. Condensate in the pres­ence of chlorides and fluorides from paint, varnish, stains, adhesives, cleaning compounds, and cement create a corrosive condition which may cause rapid deterioration of the heat exchanger.
Do NOT install the furnace in a corrosive or contami­nated atmosphere.
EXPLOSION HAZARD! PROPANE GAS IS HEAVIER THAN AIR AND MAY COLLECT IN ANY LOW AREAS OR CONFINED SPAC­ES. IN ADDITION, ODORANT FADE MAY MAKE THE GAS UNDETECTABLE EXCEPT WITH A WARNING DEVICE. IF THE GAS FURNACE IS INSTALLED IN A BASEMENT, AN EXCAVATED AREA OR A CONFINED SPACE, IT IS STRONGLY RECOMMENDED TO CON­TACT A GAS SUPPLIER TO INSTALL A GAS DETECT­ING WARNING DEVICE IN CASE OF A GAS LEAK.
NOTE: The manufacturer of your furnace does NOT test any detectors and makes no representations regarding any brand or type of detector.
LOCATION AND CLEARANCES
The location of the furnace is normally selected by the ar­chitect, the builder, or the installer. However, before the furnace is moved into place, be sure to consider the fol­lowing requirements:
1. Is the location selected as near the vent and as cen­tralized for heat distribution as practical?
2. Do all clearances between the furnace and enclosure equal or exceed the minimums shown in the Table 1.
3. Is there sufficient space for servicing the furnace and other equipment? A minimum of 24 inches front ac­cessibility to the furnace must be provided. Any ac­cess door or panel must permit removal of the largest component.
4. Are there at least 3 inches of clearance between the furnace front panel and any closed panel or door provided?
5. Are the ventilation and combustion air openings large enough and will they remain unobstructed? If out­side air is used, are the openings set 12" minimum above the highest snow accumulation level (18" in Canadian applications)?
6. Allow sufficient height in supply plenum above or be­low the furnace to provide for cooling coil installation if the cooling coil is not installed at the time of this furnace installation.
7. A furnace shall be installed so electrical components are protected from water.
8. If the furnace is installed in a residential garage, it must be installed so that the burners and the ignition source are located not less than 18 inches above the floor and the furnace must be located or protected to avoid physical damage from vehicles.
IMPORTANT:
The furnace must be installed level. The only allowable variation would be slightly to the left and/or forward in upflow installations or slightly toward the front in horizontal installations. This is necessary for proper condensate drainage.
4 18-CD33D1-4
Installer’s Guide
From Dwg. 21C341884
APPLICATION.
REFER TO THE VENT LENGTH TABLE FOR PROPER
OR 3” ON SOME MODELS AT DIFFERENT ALTITUDES.
NOTES:
1. *UH1C100A9H41, & *UH1D120A9H51
REQUIRE 3” DIAMETER VENT PIPE.
2. DIAMETER OF VENT PIPE MAY BE LIMITED TO 2-1/2”
(ALL DIMENSIONS ARE IN INCHES)
*UH1-H OUTLINE DRAWING
18-CD33D1-4 5
Installer’s Guide
From Dwg. 21C341885
(ALL DIMENSIONS ARE IN INCHES)
*DH1-H DOWNFLOW/ HORIZONTAL OUTLINE DRAWING
6 18-CD33D1-4
UPFLOW INSTALLATION
WARNING
!
UPFLOW
FURNACE
CASED
COIL
SCREWS
(BOTH SIDES)
STANDOFFS
(BOTH SIDES)
STANDOFFS (4)
DRILL SCREWS (4)
Standoffs and screws (See Figure 1) are included with the cased coils for attachment to the furnace. There are clearance alignment holes near the bottom of the coil wrapper. Drill screws are used to engage the furnace top flanges. The standoff is inserted into the cabinet align­ment hole. The drill screws are inserted through the standoffs then screwed into the furnace flange. The coil is always placed downstream of the furnace air­flow.
1
FOR VERTICAL
INSTALLATIONS:
DOWNFLOW INSTALLATIONS
FIRE HAZARD Do NOT install the furnace directly on carpeting, tile or other combustible material other than wood floor­ing. For vertical downflow application, subbase (BAY­BASE205) must be used between the furnace and combustible flooring. When the downflow furnace is installed vertically with a cased coil, a subbase is not required.
Required floor opening:
Installer’s Guide
2
FURNACE
FRONT
HORIZONTAL INSTALLATION
The coil and furnace must be fully supported when used in the horizontal position. It is always recommended that an auxiliary drain pan be installed under a horizontally installed evaporator coil or 90% gas furnace. Connect the auxiliary drain line to a separate drain line (no trap is needed in this line). Three brackets (with screws) are included with downflow furnaces for installation to stabilize and secure the fur­nace and TXC cased coil in the horizontal position. See Figure 3.
IMPORTANT: The 2/4TXC cased coil must be placed downstream of the furnace. In horizontal installations, the apex of the coil may point either toward or away from the furnace. See the
2/4TXC coil Installer's Guide for more details.
The cased coil is secured to the furnace and both the fur­nace and the cased coil must be properly supported. The brackets mount using the rear screws on the coil case and use the screws provided to secure the bracket to the furnace. The remaining bracket is placed as close to cen­ter as possible (horizontally) between the coil case front and the furnace bottom channel (for downflow/horizon­tal furnace). Use four of the screws provided to secure the bracket. The upflow furnace, converted to horizontal, aligns and attaches the TXC coil as in Figure 1. However, the coil requires additional support.
3
CASED COIL CONNECTION
BRACKET FOR DOWNFLOW FUR-
NACE IN HORIZONTAL
A (width)
B (depth)
D
C
CABINET
WIDTH
17-1/2" 16-1/4" 16-5/8" 20-1/8" 15-5/8" 19-3/8"
21" 19-3/4" 20-1/8" 20-1/8" 19-1/8" 19-3/8"
24-1/2" 23-1/4" 23-5/8" 20-1/8" 22-5/8" 19-3/8"
18-CD33D1-4 7
SUBBASE CROSS SECTION
TABLE 1
RETURN
DUCT WIDTH
FLOOR OPENING PLENUM OPENING
"A" "B" "C" "D"
DOWNFLOW ONLY
The furnace may be installed in an attic or crawl space in the horizontal position by placing the furnace on the left side (as viewed from the front in the vertical position). The horizontal furnace installation in an attic should be on a service platform large enough to allow for proper clearances on all sides and service access to the front of the furnace (See Figure 4 & Clearance Table). Line con­tact is only permissible between lines formed by intersec­tions of the top and two sides of the furnace casing and building joists, studs, or framing.
Installer’s Guide
The furnace may be placed horizontally in a crawl space on a pad or other noncombustible material which will raise the unit for sufficient protection from moisture. The
furnace must be supported at both ends and the mid­dle when installed horizontally.
4
UPFLOW/ HORIZONTAL SHOWN
The furnace must also be elevated a minimum of 6 inches to allow clearance for the condensate drain to exit the cabinet in the horizontal position.
The horizontal furnace may also be suspended from the joists using 3/8" all-thread rods with pieces of angle iron underneath the furnace to form a hanging rack at both ends and the midpoint. The rods need to be of suf­ficient length to allow for proper clearances from combus­tible materials. The angle iron needs to be at least 32" in length to allow for access to service panels.
5
50 CU. FT. OR MORE PER 1000 BTU/HR. INPUT ALL EQUIP. INSTALLED
made in accordance with latest edition of Section 5.3, Air for Combustion and Ventilation, of the National Fuel Gas Code, ANSI Z223.1 — CAN/CGA B149.1 or applicable provisions of the local building codes. Special conditions created by mechanical exhausting of air and fireplaces must be con sidered to avoid unsatisfactory furnace op­eration.
OUTSIDE AIR IS RECOMMENDED
The use of indoor air for most applications is acceptable, unless there is the presence of corrosive chemicals
or contamination. Certain types of installation will re­quire the use of outside air for combustion.
The following types of installations will require use of OUTDOOR AIR for combustion, due to chemical expo­sures: * Commercial buildings * Buildings with indoor pools * Furnaces installed in “confined” laundry rooms * Furnaces installed in “confined” hobby or craft rooms * Furnaces installed near chemical storage areas.
Exposure to the following substances in the combustion air supply will also require OUTDOOR AIR for combus­tion: * Permanent wave solutions * Chlorinated waxes and cleaners * Chlorine based swimming pool chemicals * Water softening chemicals * Deicing salts or chemicals * Carbon Tetrachloride * Halogen type refrigerants * Cleaning solvents (such as perchloroethylene) * Printing inks, paint removers, varnish, etc. * Hydrochloric acid * Cements and glues * Antistatic fabric softeners for clothes dryers * Masonry acid washing materials
UNCONFINED
AIR FOR COMBUSTION AND VENTILATION
If these furnaces are installed in a nondirect vent capac­ity then the adequate flow of combustion and ventilating air must not be obstructed from reaching the furnace. Air openings provided for combustion air must be kept free of obstructions which restrict the flow of air. Airflow restric­tions affect the efficiency and safe operation of the fur­nace. Keep this in mind should you choose to remodel or change the area which contains your furnace. Furnaces must have a free flow of air for proper performance. Provisions for combustion and ventilation air shall be
8 18-CD33D1-4
Furnace locations may be in a “confined space” or an “unconfined space”.
Unconfined space is defined in Figure 5. These spac­es may have adequate air by infiltration to provide air for combustion and ventilation. Buildings with tight construction (for example, weather stripping, heavily insulated, caulked, vapor barrier, etc.), may need addi­tional air to be provided as described for confined space.
Confined spaces are installations with less than 50 cu. ft. of space per 1000 BTU/ hr input from all equipment in­stalled. Air for combustion and ventilation requirements can be supplied from inside the building as in Figure 8 or from the outdoors, as in Figure 9.
Installer’s Guide
6
MINIMUM AREA IN SQUARE FEET
FOR UNCONFINED SPACE INSTALLATIONS
FURNACE MAXI-
MUM BTUH INPUT
RATING
60,000
80,000 100,000 120,000
1. All air from inside the building as in Figure 8: The confined space shall be provided with two perma­nent openings communicating directly with an addi­tional room(s) of sufficient volume so that the com­bined volume of all spaces meets the criteria for an unconfined space. The total input of all gas utilization equipment installed in the combined space shall be considered in making this determination. Refer to Ta­ble 2 for minimum open areas requirements.
WITH 8 FT. CEILING
MINIMUM AREA IN SQUARE FEET
OF UNCONFINED SPACE
375 500 625 875
8
9
7
CONFINED
SPACE
2. All air from outdoors as in Figure 9: The confined
space shall be provided with two permanent open­ings, one commencing within 12 inches of the top and one commencing within 12 inches of the bottom of the enclosure. The openings shall communicate di­rectly, or by ducts, with the outdoors or spaces (crawl or attic) that freely communicate with the outdoors. Refer to Table 2, for minimum open areas require­ments.
TABLE 2
MINIMUM FREE AREA IN SQUARE INCHES
EACH OPENING (FURNACE ONLY)
Furnace
Maximum
BTUH/INPUT
Rating
40,000 60,000 80,000 97,000
110,000
Air
From
Inside
100 100 100 100 110
Air From Outside
Vertical
Duct
10 15 20 25 28
Horizontal
Duct
20 30 40 50 55
18-CD33D1-4 9
Installer’s Guide
DUCT CONNECTIONS
Air duct systems should be installed in accordance with standards for air conditioning systems, National Fire Protection Association Pamphlet No. 90. They should be sized in accordance with ACCA Manual D or whichever is applicable. Central furnaces, when used in connection with cooling units, shall be installed in parallel or on the upstream side of the cooling coil to avoid condensation in the heat ex­changer. With a parallel flow arrangement, the dampers or other means used to control flow of air shall be ade­quate to prevent chilled air from entering the furnace, and if manually operated, must be equipped with means to prevent operation of either unit unless the damper is in full heat or cool position. On any job, flexible connections of nonflammable mate­rial may be used for return air and discharge connections to pre vent transmission of vibration. Though these units have been specifically designed for quiet, vibration free op­eration, air ducts can act as sounding boards and could, if poorly installed, amplify the slightest vibration to the an­noyance level. When the furnace is located in a utility room adjacent to the living area, the system should be carefully designed with returns to minimize noise transmission through the return air grille. Although these furnaces are designed with large blowers operating at moderate speeds, any blower moving a high volume of air will produce audible noise which could be objectionable when the unit is locat­ed very close to a living area. It is often advisable to route the return air ducts under the floor or through the attic. Such design permits the installation of air return remote from the living area (i.e. central hall). When the furnace is installed so that the supply ducts carry air circulated by the furnace to areas outside the space containing the furnace, the return air shall also be handled by a duct(s) sealed to the furnace and terminat­ing outside the space containing the furnace.
RETURN AIR DUCT SYSTEMS Where there is no complete return duct system, the return connection must be run full size from the fur­nace to a location outside the utility room, basement, attic, or crawl space. Do Not install return air through the back of the furnace
cabinet Do Not install return air through the side of the furnace cabinet on horizontal applications.
PREPARATION FOR UPFLOW BOTTOM AND SIDE RETURN AIR FILTER INSTALLATION
All return air duct systems should provide for installation of return air filters.
1. Determine the appropriate position to set the furnace in order to existing supply and return ductwork.
2. The return air filter is shipped in either the bottom or side location. Remove the filter by first turning the two latches on the blower door and tilting the door forward to remove. Remove the filter by sliding it out.
3. For upflow side return installations, remove the insulation around the opening in the blower compart­ment.
4. The side panels of the upflow furnace include locat­ing notches that are used as guides for cutting an opening for return air, refer to Figure 10 and the outline drawing on page 5 for duct connection dimen­sions for various furnaces.
5. If a 3/4" flange is to be used for attaching the air inlet duct, add to cut where indicated by dotted lines in Figure 10. Cut corners diagonally and bend outward to form flange.
6. If flanges are not required, and a filter frame is installed, cut between locating notches (See Figure
10).
7. The bottom panel of the upflow furnace must be re­moved for bottom return air. After removing the filter, lay the furnace on its back. Remove the two 5/16" hex screws securing the front of the bottom chan­nel to the cabinet. Rotate the channel downward (or remove by lowering the front edge of the channel and pulling forward). Slide the bottom return air panel out of the cabinet. Rotate the front channel to its original position and reinstall the two 5/16” screws.
8. The filter retainer is factory supplied for upflow bot­tom return. Use the filter retainer on side or bottom if filter is to be used within the furnace cabinet on up­flow only installations.
NOTE: Minimum return air temperature is 55° F.
All return air duct systems should provide for installation of return air filters.
10 18-CD33D1-4
Installer’s Guide
Filter Rack
Furnace
Cabinet
Side
Filter Rack Retaining Screw/Pin
Engagement Hole For
Bottom Return
Filter Rack
Installation With
9. The horizontal installation of the upflow furnace requires an external filter section. Do NOT use the bottom return filter within the furnace. Filter kits are available for horizontal applications.
10. Connect duct work to furnace. See Outline Drawing for supply and return duct size and location. Flexible duct con nectors are recommended to connect both supply and return air ducts to the furnace. If only the front of the furnace is accessible, it is recommended that both supply and return air plenums are removable.
RETURN AIR FILTERS
TYPICAL UPFLOW RETURN AIR FILTER INSTALLATIONS
furnaces require high velocity type air filters. The filters may be installed within the furnace blower compartment for UPFLOW furnaces in either a BOTTOM or SIDE (left side or right side) return air inlet. Some filters may need to be trimmed for side or bottom filter use.
UPFLOW FURNACE ONLY
0
LOCATING NOTCH­ES PROVIDED FOR SIDE RETURN CUTOUT
CUT OUT FOR SIDE FILTER
TABLE 3
UPFLOW FURNACE RETURN AIR FILTERS
CABINET
WIDTH
14-1/2" 1 14" X 25" X 1" 17-1/2" X 25" X 1"
17-1/2" 1 17" X 25" X 1" 17-1/2" X 25" X 1"
21" 1 20" X 25" X 1" 17-1/2" X 25" X 1"
24-1/2" 1 24" X 25" X 1" 17-1/2" X 25" X 1"
**NOTE: For upflow 5 ton airflow models where the airflow requirement exceeds 1800 CFM - Models will require return air openings and filters on: (1) both sides, or (2) one side and the bottom, or (3) just on the bottom
NOTE: For upflow 5 ton airflow models where the air­flow requirement exceeds 1800 CFM - Models will re­quire return air openings and filters on: (1) both sides, or (2)1 side and the bottom, or (3) just the bottom.
QTY*
CABINET
BOTTOM FIL-
TER
CABINET
SIDE FILTER
The furnace and the bottom filter rack, BAYRACK960, in­stallation can be seen in Figure 11. The furnace filter in the bottom or side configuration can be removed by simply turning the two latches on the blower door and tilting the door forward.
ALTERNATE FILTER RACK INSTALLATION FOR BOTTOM RETURN - BAYRACK960
*SEE OUTLINE DRAWING
q
BOTTOM FILTER RACK INSTALLATION
Airflow
FRONT of Furnace
The following checklist should be used when installing a bottom return filter on an upflow furnace:
a. Remove the filter.
b. Remove the bottom panel.
c. With the filter removed, the filter rack is com-
pressed and then inserted into the bottom of the furnace. The retaining screw/pin on each side inserts into engagement holes at the bottom of the furnace cabinet side. See Figure 12.
d. Reinstall the furnace filter in the bottom position
by inserting the chamfer end first into the filter rack.
w
18-CD33D1-4 11
Loading...
+ 25 hidden pages