*Horizontal Conversion for these furnaces may be left or right side rotation.
Upflow / Horizontal*
A341789P10
Installer’s Guide
▲
WARNING
!
CARBON MONOXIDE POISONING HAZARD
Failure to follow the steps outlined below for each
appliance connected to the venting system being
placed into operation could result in carbon monoxide
poisoning or death.
The following steps shall be followed for each appliance
connected to the venting system being placed into
operation, while all other appliances connected to the
venting system are not in operation:
1. Seal any unused openings in the venting system.
2. Inspect the venting system for proper size and
horizontal pitch, as required in the National Fuel Gas
Code, ANSI Z223.1/NFPA 54 or the CAN/CGA B149
Installation Codes and these instructions. Determine
that there is no blockage or restriction, leakage,
corrosion and other deficiencies which could cause an
unsafe condition.
3. As far as practical, close all building doors and
windows and all doors between the space in which the
appliance(s) connected to the venting system are
located and other deficiencies which could cause an
unsafe condition.
4. Close fireplace dampers.
5. Turn on clothes dryers and any appliance not
connected to the venting system. Turn on any exhaust
fans, such as range hoods and bathroom exhausts, so
they are operating at maximum speed. Do not operate
a summer exhaust fan.
6. Follow the lighting instructions. Place the appliance
being inspected into operation. Adjust the thermostat
so appliance is operating continuously.
7. If improper venting is observed during any of the above
tests, the venting system must be corrected in
accordance with the National Fuel Gas Code,
ANSI Z221.1/NFPA 54 and/or CAN/CGA B149
Installation Codes.
8. After it has been determined that each appliance
connected to the venting system properly vents where
tested as outlined above, return doors, windows,
exhaust fans, fireplace dampers and any other gas-fired
burning appliance to their previous conditions of use.
▲
WARNING
!
The following safety practices and precautions must be
followed during the installation, servicing, and operation of
this furnace.
1. Use only with the type of gas approved for this furnace.
Refer to the furnace rating plate.
2. Install this furnace only in a location and position as
specified in “Location and Clearances” (page 3), of these
instructions.
3. Provide adequate combustion and ventilation air to the
furnace space as specified in “Air for Combustion and
Ventilation” (pages 7-8), of these instructions.
4. Combustion products must be discharged outdoors.
Connect this furnace to an approved vent system only,
as specified in the “Venting” section (pages 13-14), of
these instructions.
5. Never test for gas leaks with an open flame. Use a
commercially available soap solution made specifically
for the detection of leaks to check all connections, as
specified in “Gas Piping” (page 18) of these instructions.
6. Always install the furnace to operate within the furnace’s intended temperature-rise range with a duct system which has an external static pressure within the
allowable range, as specified on the unit rating plate.
Airflow with temperature rise for cfm versus static is
shown in the Service Facts accompanying this furnace.
7. When a furnace is installed so that supply ducts carry
air circulated by the furnace to areas outside the space
containing the furnace, the return air shall also be
handled by a duct(s) sealed to the furnace casing and
terminating outside the space containing the furnace.
8. A gas-fired furnace for installation in a residential
garage must be installed as specified in “Location and
Clearances” section (page 3) of these instructions.
9. The furnace may be used for temporary heating of
buildings or structures under construction only when
the following conditions have been met:
a. The furnace venting system must be complete and
installed per manufacturer’s instructions.
b. The furnace is controlled only by a room thermostat
(no field jumpers).
c. The furnace return air duct must be complete and
sealed to the furnace and clean air filters are in
place.
d. The furnace input rate and temperature rise must
be verified to be within nameplate marking.
e. 100% of the furnace combustion air requirement
must come from outside the structure.
f. The furnace return air temperature range is be-
tween 55 and 80 degrees Fahrenheit.
g. Clean the furnace, duct work, and components upon
substantial completion of the construction process,
and verify furnace operating conditions including
ignition, input rate, temperature rise and venting,
according to the manufacturer’s instructions.
10. This product must be gas piped by a Licensed Plumber
or Gas Fitter in the Commonwealth of Massachusetts.
Safety signal words are used to designate a degree or level
of seriousness associated with a particular hazard. The
signal words for safety markings are WARNING and CAUTION.
a. WARNING indicates a potentially hazardous situation
which, if not avoided, could result in death or serious
injury.
b. CAUTION indicates a potentially hazardous situation
which, if not avoided, may result in minor or moderate
injury. It is also used to alert against unsafe practices
and hazards involving only property damage.
FIRE OR EXPLOSION HAZARD
Failure to follow the safety warnings exactly could result
in serious injury, death or property damage.
Improper servicing could result in dangerous operation,
serious injury, death, or property damage.
Installer’s Guide
▲
CAUTION
!
▲
CAUTION
!
▲
WARNING
!
▲
WARNING
!
GENERAL INSTALLATION INSTRUCTIONS
The manufacturer assumes no responsibility for equipment
installed in violation of any code or regulation.
It is recommended that Manual J of the Air Conditioning
Contractors Association (ACCA) or A.R.I. 230 be followed
in estimating heating requirements. When estimating
heating requirements for installation at Altitudes above
2000 ft., remember the gas input must be reduced (See GAS
INPUT ADJUSTMENT).
Material in this shipment has been inspected at the
factory and released to the transportation agency
without known damage. Inspect exterior of carton
for evidence of rough handling in shipment. Unpack
carefully after moving equipment to approximate
location. If damage to contents is found, report the
damage immediately to the delivering agency.
Codes and local utility requirements governing the installation of gas fired equipment, wiring, plumbing, and flue
connections must be adhered to. In the absence of local
codes, the installation must conform with latest edition of
the National Fuel Gas Code ANSI Z223.1 • National Installation Code, CAN/CGA B149.1. The latest code may be
obtained from the American Gas Association Laboratories,
400 N. Capitol St. NW, Washington D.C. 20001.
1-800-699-9277 or www.aga.org
These furnaces have been classified as Fan Assisted Combustion system CATEGORY I furnaces as required by
ANSI Z21.47 “latest edition” and CAN/CGA 2.3. Therefore
they do not require any special provisions for venting other
than what is indicated in these instructions. (Category I
defined on page 13).
Contents
Installation Instructions 3
General Installation Instructions 3
Location and Clearances 3
Outline Drawing 4-5
Upflow Installation 6
Downflow Installation 6
Horizontal Installation 6
Air for Combustion and Ventilation 7
Duct Connections 8
Return Air Filters 9-13
General Venting Instructions 13
Venting into a Masonry Chimney 13
Electrical Connections 15
Field Wiring Diagrams 16-17
Gas Piping 18
Combustion and Input Check 18
High Altitude Derate 20
Start Up and Adjustment 21
Preliminary Inspections 21
Lighting Instructions 21
Sequence Of Operation 21
Control and Safety Switch Adjustment 22
Abnormal Conditions 23
IFC Error Flash Codes 24
To prevent shortening its service life, the furnace should
not be used as a “Construction Heater” during the finishing phases of construction until the requirements listed
in item 9, a-g of the safety section of this publication have
been met. Condensate in the presence of chlorides and
fluorides from paint, varnish, stains, adhesives, cleaning
compounds, and cement create a corrosive condition
which may cause rapid deterioration of the heat exchanger.
Do not install the furnace in a corrosive or contaminated
atmosphere.
These furnaces are not approved or intended for installation in manufactured (mobile) housing, trailers, or recreational vehicles. Failure to follow this warning could
result in property damage, personal injury, or death.
Do not install the furnace directly on carpeting, tile or
other combustible material other than wood flooring. For
vertical downflow application, subbase (BAYBASE205)
must be used between the furnace and combustible flooring. When the downflow furnace is installed vertically
with a cased coil, a subbase is not required.
LOCATION AND CLEARANCES
The location of the furnace is normally selected by the
architect, the builder, or the installer. However, before the
furnace is moved into place, be sure to consider the following requirements:
1. Is the location selected as near the chimney or vent and
as centralized for heat distribution as practical?
2. Do all clearances between the furnace and enclosure
equal or exceed the minimums stated in Clearance
Table on the Outline Drawings.
3. Is there sufficient space for servicing the furnace and
other equipment? A minimum of 24 inches front accessibility to the furnace must be provided. Any access
door or panel must permit removal of the largest component.
4. Are there at least 3 inches of clearance between the
furnace combustion air openings in the front panel and
any closed panel or door provided?
5. Are the ventilation and combustion air openings large
enough and will they remain unobstructed? If outside
air is used, are the openings set above the highest snow
accumulation level? (See the Air for Combustion and
Ventilation section.)
6. Allow sufficient height in supply plenum above the
furnace to provide for cooling coil installation, if the
cooling coil is not installed at the time of this furnace
installation.
18-CD31D1-5 3
Installer’s Guide
From Dwg. 21C341699 Rev. 4
(ALL DIMENSIONS ARE IN INCHES)
*UD2-9V OUTLINE DRAWING
17-1/2"9-5/8"16-1/4"16"
MODELDIM "A"DIM "B"DIM "C"DIM "D"
*UD2B060A9V3VB
*UD2B080A9V3VB
21"13-1/16"19-3/4"19-1/2"
*UD2B100A9V3VB
*UD2C080A9V4VB
*UD2C080B9V4VB
*UD2C100A9V5VB
*UD2C100B9V5VB
24-1/2"15-5/16"23-1/4"23"
*UD2D120A9V5VB
*UD2D120B9V5VB
*UD2D140A9V5VB
* - The First Letter May Be "A" or "T"
4 18-CD31D1-5
Installer’s Guide
From Dwg. 21C341700 Sh. 1 Rev. 0
(ALL DIMENSIONS ARE IN INCHES)
*DD2-9V OUTLINE DRAWING
MODELDIM "A"DIM "B"DIM "C"DIM "D"
*DD2B060A9V3VA
17-1/2"9-5/8"16-1/4"16"
*DD2B080A9V3VA
*DD2C100A9V5VA21"13-1/16"19-3/4"19-1/2"
*DD2D120A9V5VA24-1/2"15-5/16"23-1/4"23"
* - The First Letter May Be "A" or "T"
18-CD31D1-5 5
Installer’s Guide
UPFLOW
FURNACE
CASED
COIL
SCREWS
(BOTH SIDES)
STANDOFFS
(BOTH SIDES)
STANDOFFS (4)
DRILL SCREWS (4)
▲
WARNING
!
7. A furnace shall be installed so electrical components
are protected from water.
8. If the furnace is installed in a residential garage, it
must be installed so that the burners, and the ignition
source are located not less than 18 inches above the
floor and the furnace must be located or protected to
avoid physical damage from vehicles.
UPFLOW INSTALLATION
Standoffs and screws (See Figure 1, page 6) are included
with the cased coils for attachment to the furnace. There
are clearance alignment holes near the bottom of the coil
wrapper. Drill screws are used to engage the furnace top
flanges. The standoff is inserted into the cabinet alignment
hole. The drill screws are inserted through the standoffs
then screwed into the furnace flange. The coil is always
placed downstream of the furnace airflow. The above
instructions apply only if the coil is on top of an upflow
furnace.
1
FOR VERTICAL
INSTALLATIONS:
TABLE 1
CABINET
WIDTH
17-1/2"16-1/4"16-5/8"20-1/8"15-5/8"19-3/8"
21"19-3/4"20-1/8"20-1/8"19-1/8"19-3/8"
24-1/2"23-1/4"23-5/8"20-1/8"22-5/8"19-3/8"
HORIZONTAL INSTALLATION
The coil and furnace must be fully supported when used in
the horizontal.
Three brackets (with screws) are included with downflow
furnaces for installation to stabilize and secure the furnace
and TXC cased coil in the horizontal position. See Fig-
ure 4.
IMPORTANT:
The 2/4TXC cased coil must be placed downstream of the
furnace. In horizontal installations, the apex of the coil
may point either toward or away from the furnace. See the
2/4TXC coil Installer's Guide for more details.
The cased coil is secured to the furnace and both the furnace and the cased coil must be properly supported. The
brackets mount using the rear screws on the coil case and
use the screws provided to secure the bracket to the furnace. The remaining bracket is placed as close to center as
possible (horizontally) between the coil case front and the
furnace bottom channel (for downflow/horizontal furnace).
Use four of the screws provided to secure the bracket.
RETURN
DUCT WIDTH
FLOOR OPENING PLENUM OPENING
"A" "B""C""D"
DOWNFLOW INSTALLATION
Do not install the furnace directly on carpeting, tile or
other combustible material other than wood flooring. For
vertical downflow application, subbase (BAYBASE205)
must be used between the furnace and combustible flooring. When the downflow furnace is installed vertically
with a cased coil, a subbase is not required.
2
REQUIRED FLOOR OPENING: (DOWNFLOW)
See Figure 3 and Table 1
4
CASED COIL CONNECTION
BRACKET FOR DOWNFLOW FUR-
NACE IN HORIZONTAL
This furnace may be installed in an attic or crawl space in
the horizontal position by placing the furnace on the left or
right side (as viewed from the front in the upright position). The horizontal furnace installation in an attic should
be on a service platform large enough to allow for proper
clearances on all sides and service access to the front of
the furnace (See Clearance Table on Outline Drawings and
Figure 5).
5
3
A (width)
FURNACE
FRONT
6 18-CD31D1-5
B (depth)
Typical Upflow/Horizontal Attic Installation
If the furnace is suspended using perforated steel strap
(plumber’s strap), it must be supported at all four corners
D
C
and in the middle at the front of the furnace. The forward
most screw on the side of the furnace may be used to connect the strapping (See Figure 5). Line contact is only permissible between lines formed by the intersection of the top
and two sides of the furnace casing and the building joists,
studs, or framing.
A cutout is provided on both sides of the downflow furnace cabinet to allow a 90° elbow to be attached inside the
cabinet and the vent piping to connect there. In horizontal,
the downflow furnace may be vented through the top of the
cabinet if needed. In vertical configuration, the downflow
furnace may be vented using the side cabinet cutouts. This
venting configuration could be used if an electronic air
cleaner is installed.
When the downflow furnace is vented through the
left side of the furnace cabinet in horizontal or vertical configuration, Type B vent pipe must be used
within the cabinet.
6
Typical Suspended Upflow/Horizontal Furnace
AIR FOR COMBUSTION AND VENTILATION
Adequate flow of combustion and ventilating air must not
be obstructed from reaching the furnace. Air openings
provided in the furnace casing must be kept free of obstructions which restrict the flow of air. Airflow restrictions
affect the efficiency and safe operation of the furnace. Keep
this in mind should you choose to remodel or change the
area which contains your furnace. Furnaces must have a
free flow of air for proper performance.
Provisions for combustion and ventilation air shall be
made in accordance with “latest edition” of Section 5.3, Air
for Combustion and Ventilation, of the National Fuel Gas
Code, ANSI Z223.1, or Sections 7.2, 7.3 or 7.4 of CAN/CGA
B149 Installation Codes, and applicable provisions of the
local building codes. Special conditions created by mechanical exhausting of air and fireplaces must be considered to
avoid unsatisfactory furnace operation.
Furnace locations may be in “confined space” or “unconfined
space”. Unconfined space is defined in Table 2 and Figure
6. These spaces may have adequate air by infiltration to
provide air for combustion, ventilation, and dilution of
flue gases. Buildings with tight construction (for example,
weather stripping, heavily insulated, caulked, vapor barrier, etc.), may need additional air provided as described for
confined space.
Confined spaces are installations with less than 50 cu. ft. of
space per 1000 BTU/hr input from all equipment installed.
Air for combustion and ventilation requirements can be
supplied from inside the building as in Figure 8 or from the
outdoors, as in Figure 9.
1. All air from inside the building as in Figure 8: The confined space shall be provided with two permanent openings communicating directly with an additional room(s)
of sufficient volume so that the combined volume of all
spaces meets the criteria for an unconfined space. The
Installer’s Guide
7
8
2. All air from outdoors as in Figure 9: The confined space
The openings shall communicate directly, or by ducts,
3. The following types of installations will require use
* Commercial buildings
* Buildings with indoor pools
* Furnaces installed in commercial laundry rooms
* Furnaces installed in hobby or craft rooms
* Furnaces installed near chemical storage areas.
Exposure to the following substances in the combustion
* Permanent wave solutions
* Chlorinated waxes and cleaners
* Chlorine based swimming pool chemicals
* Water softening chemicals
* Deicing salts or chemicals
* Carbon Tetrachloride
* Halogen type refrigerants
* Cleaning solvents (such as perchloroethylene)
* Printing inks, paint removers, varnish, etc.
* Hydrochloric acid
* Cements and glues
* Antistatic fabric softeners for clothes dryers
* Masonry acid washing materials
UNCONFINED
50 CU. FT. OR MORE
PER 1000 BTU/HR. INPUT
ALL EQUIP. INSTALLED
CONFINED
LESS THAN 50 CU. FT.
PER 1000 BTU/HR. INPUT
ALL EQUIP INSTALLED
total input of all gas utilization equipment installed in
the combined space shall be considered in making this
determination. Refer to Table 3, for minimum open
areas required.
shall be provided with two permanent openings, one
commencing within 12 inches of the top and one commencing within 12 inches of the bottom of the enclosure.
with the outdoors or spaces (crawl or attic) that freely
communicate with the outdoors. Refer to Table 3, for
minimum open areas required.
of OUTDOOR AIR for combustion, due to chemical
exposures:
air supply will also require OUTDOOR AIR for combustion:
TABLE 2
MINIMUM AREA IN SQUARE FEET
FOR UNCONFINED SPACE INSTALLATIONS
FURNACE
MAXIMUM BTUH
INPUT RATING
60,000
80,000
100,000
120,000
140,000
WITH 8 FT. CEILING
MINIMUM AREA IN SQUARE
FEET OF UNCONFINED SPACE
375
500
625
750
875
18-CD31D1-5 7
Installer’s Guide
TABLE 3
MINIMUM FREE AREA IN SQUARE INCHES
EACH OPENING (FURNACE ONLY)
Furnace
Maximum
BTUH/INPUT
Rating
60,000
80,000
100,000
120,000
140,000
Air
From
Inside
100
100
100
120
140
Air From Outside
Vertical
Duct
15
20
25
30
35
9
0
Horizontal
Duct
30
40
50
60
70
DUCT CONNECTIONS
Air duct systems should be installed in accordance with
standards for air conditioning systems, National Fire Protection Association Pamphlet No. 90. They should be sized
in accordance with ACCA Manual D or whichever is applicable. Check on controls to make certain they are correct
for the electrical supply.
Central furnaces, when used in connection with cooling
units, shall be installed in parallel or on the upstream side
of the cooling units to avoid condensation in the heating
element, unless the furnace has been specifically approved
for downstream installation. With a parallel flow arrangement, the dampers or other means used to control flow of
air shall be adequate to prevent chilled air from entering
the furnace, and if manually operated, must be equipped
with means to prevent operation of either unit unless the
damper is in full heat or cool position.
On any job, flexible connections of nonflammable material may be used for return air and discharge connections
to prevent transmission of vibration. Though these units
have been specifically designed for quiet, vibration free
operation, air ducts can act as sounding boards and could,
if poorly installed, amplify the slightest vibration to the
annoyance level.
When the furnace is located in a utility room adjacent to
the living area, the system should be carefully designed
with returns which minimize noise transmission through
the return air grille. Although these winter air conditioners are designed with large blowers operating at moderate
speeds, any blower moving a high volume of air will produce audible noise which could be objectionable when the
unit is located very close to a living area. It is often advisable to route the return air ducts under the floor or through
the attic. Such design permits the installation of air return
remote from the living area (i.e. central hall).
When the furnace is installed so that the supply ducts carry
air circulated by the furnace to areas outside the space
containing the furnace, the return air shall also be handled
by a duct(s) sealed to the furnace and terminating outside
the space containing the furnace.
Minimum return air/“air entering” temperature for
the furnace is 55° F.
Where there is no complete return duct system, the return
connection must be run full size from the furnace to a
location outside the utility room, basement, attic, or crawl
space.
DO NOT install return air through the back of the
furnace cabinet.
RETURN AIR DUCT CONNECTION
NOTE:
On upflow 5 or 6 ton airflow models, if the airflow requirement exceeds 1800 CFM, these models will require return
air openings and filters on both sides; OR 1 side and the
bottom; OR just the bottom.
All return air duct systems should provide for installation
of return air filters.
PREPARATION FOR UPFLOW BOTTOM AND SIDE RETURN AIR FILTER INSTALLATION
All return air duct systems should provide for installation
of return air filters.
1. Determine the appropriate position to set the furnace
in order to connect to existing supply and return ductwork.
8 18-CD31D1-5
Loading...
+ 16 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.