Trane AUD1B060A9H31B, TUD1A040A9H21B, TUD1B060A9H31B, AUD1B060G9H31A, TUD1B060G9H31A Installer's Manual

...
Page 1
18-CD21D1-12
Installer’s Guide
High Efficiency Single Stage Upflow/ Horizontal and Downflow/ Horizontal Gas-Fired Furnaces, “Fan Assisted Combustion System”
*UD1A040A9H21B *UD1A040G9H21A *UD1B060A9H31B *UD1B060G9H31A *UD1B080A9H31B *UD1B080G9H31A *UD1C080A9H41B *UD1C080G9H41A
*__First letter may be “A” or “T”
ALL phases of this installation must comply with NATIONAL, STATE AND LOCAL CODES
IMPORTANT — This Document is customer property and is to remain with this unit.
For VENT SIZING INFORMATION see:
USA
National Fuel Gas Code ................ ANSI Z223.1/NFPA 54 (latest version)
CANADA
Natural Gas Installation Code ..............CAN/CGA-B149.1 (latest version)
Propane Installation Code ....................CAN/CGA-B149.2 (latest version)
USA/CANADA ALTERNATE —
Category I Venting Guide ......................................Pub. No. 18-CH23D1-2
*UD1B100A9H31B *UD1B100G9H31A *UD1C100A9H51B *UD1C100G9H51A *UD1D120A9H51B *UD1D120G9H51A *UD1D140A9H51B *UD1D140G9H51A
*DD1B060A9H31B *DD1B080A9H31B *DD1C100A9H51B *DD1D120A9H51B
*UD1-H
Upflow/ Horizontal* Downflow/ Horizontal*
*Horizontal Conversion for these furnaces may be left or right side rotation.
*DD1-H
A341789P07
Page 2
Installer’s Guide
CARBON MONOXIDE POISONING HAZARD Failure to follow the steps outlined below for each
appliance connected to the venting system being placed into operation could result in carbon monoxide poisoning or death.
The following steps shall be followed for each appliance connected to the venting system being placed into operation, while all other appliances connected to the venting system are not in operation:
1. Seal any unused openings in the venting system.
2. Inspect the venting system for proper size and horizontal pitch, as required in the National Fuel Gas Code, ANSI Z223.1/NFPA 54 or the CAN/CGA B149 Installation Codes and these instructions. Determine that there is no blockage or restriction, leakage, corrosion and other deficiencies which could cause an unsafe condition.
3. As far as practical, close all building doors and windows and all doors between the space in which the appliance(s) connected to the venting system are located and other deficiencies which could cause an unsafe condition.
4. Close fireplace dampers.
5. Turn on clothes dryers and any appliance not connected to the venting system. Turn on any exhaust fans, such as range hoods and bathroom exhausts, so they are operating at maximum speed. Do not operate a summer exhaust fan.
6.
Follow the lighting instructions. Place the appliance be­ing inspected into operation. Adjust the thermostat so appliance is operating continuously.
7. If improper venting is observed during any of the above tests, the venting system must be corrected in accordance with the National Fuel Gas Code, ANSI Z221.1/NFPA 54 and/or CAN/CGA B149 Installation Codes.
8.
After it has been determined that each appliance connected to the venting system properly vents where tested as outlined above, return doors, windows, exhaust fans, fireplace dampers and any other gas -fired burning appliance to their previous conditions of use.
WARNING
!
SAFETY SECTION
The following safety practices and precautions must be followed during the installation, servicing, and opera­tion of this furnace.
1. Use only with the type of gas approved for this fur­nace. Refer to the furnace rating plate.
2. Install this furnace only in a location and position as specified in “Location and Clearances” (page 4), of these instructions.
3. Provide adequate combustion and ventilation air to the furnace space as specified in “Air for Combus­tion and Ventilation” (pages 8-9), of these instruc­tions.
4. Combustion products must be discharged outdoors. Connect this furnace to an approved vent system only, as specified in the “Venting” section (pages 13-15), of these instructions.
5. Never test for gas leaks with an open flame. Use a commercially available soap solution made specifi­cally for the detection of leaks to check all connec­tions, as specified in “Gas Piping” (page 618), of these instructions.
6. Always install the furnace to operate within the
7. When a furnace is installed so that supply ducts
8. A gas-fired furnace for installation in a residential
9. The furnace may be used for temporary heating
a. The furnace venting system must be complete
b. The furnace is controlled only by a room thermo-
c. The furnace return air duct must be complete
d. The furnace input rate and temperature rise
e. 100% of the furnace combustion air requirement
© 2013 Trane All Rights Reserved 18-CD21D1-12
furnace’s intended temperature-rise range with a duct system which has an external static pressure within the allowable range, as specified on the unit rating plate. Airflow with temperature rise for cfm versus static is shown in the Service Facts accom­panying this furnace.
carry air circulated by the furnace to areas out­side the space containing the furnace, the return air shall also be handled by a duct(s) sealed to the furnace casing and terminating outside the space containing the furnace.
garage must be installed as specified in “Location and Clearances” section (page 4), of these instruc­tions.
of buildings or structures under construction only when the following conditions have been met:
and installed per manufacturer’s instructions.
stat (no field jumpers).
and sealed to the furnace and clean air filters are in place.
must be verified to be within nameplate mark­ing.
must come from outside the structure.
f. The furnace return air temperature range is be-
tween 55 and 80 degrees Fahrenheit.
g. Clean the furnace, duct work, and components
upon substantial completion of the construction process, and verify furnace operating conditions including ignition, input rate, temperature rise and venting, according to the manufacturer’s in­structions.
10. This product must be gas piped by a Licensed Plumber or Gas Fitter in the Commonwealth of Massachusetts.
Page 3
Installer’s Guide
WARNING
!
CAUTION
!
WARNING
!
CAUTION
!
Safety signal words are used to designate a degree or level of seriousness associated with a particular hazard. The signal words for safety markings are WARNING, and CAUTION. a. WARNING indicates a potentially hazardous situa-
tion which, if not avoided, could result in death or serious injury.
b. CAUTION indicates a potentially hazardous situa-
tion which, if not avoided, may result in minor or moderate injury. It is also used to alert against un­safe practices and hazards involving only property damage.
FIRE OR EXPLOSION HAZARD Failure to follow the safety warnings exactly could result in serious injury, death or property damage. Improper servicing could result in dangerous opera­tion, serious injury, death, or property damage.
Contents
Installation Instructions 3
General Installation Instructions 4 Location and Clearances 4
Outline Drawing 5
Upflow Installation 7 Downflow Installation 7 Air For Combustion and Ventilation 8 Duct Connections 10 Return Air Filters 11 Typical Upflow Return Air Filter Installations 11 Alternate Upflow Filter Clip / Bracket Installation 13 Typical Downflow Furnace Return Air Filter Installations 13 General Venting Instructions 14 Venting Into a Masonry Chimney 15 Electrical Connections 16
Field Wiring Diagrams 17
Gas Piping 19 Sequence of Operation 19
Start Up and Adjustment 20
Preliminary Inspections 20 Combustion and Input Check 20 High Altitude Derate 21 Lighting Instructions 22 Control and Safety Switch Adjustment 23
Abnormal Conditions 23
IFC Error Flash Codes 24
To prevent shortening its service life, the furnace
should not be used as a “Construction Heater” during the finishing phases of construction until the require­ments listed in item 9, a-g of the safety section of this publication have been met. Condensate in the pres­ence of chlorides and fluorides from paint, varnish, stains, adhesives, cleaning compounds, and cement create a corrosive condition which may cause rapid de­terioration of the heat exchanger.
These furnaces are not approved or intended for instal­lation in manufactured (mobile) housing, trailers, or recreational vehicles. Failure to follow this warning could result in property damage, personal injury, or death.
18-CD21D1-12 3
Do NOT install the furnace in a corrosive or contami­nated atmosphere.
Page 4
Installer’s Guide
GENERAL INSTALLATION INSTRUCTIONS
The manufacturer assumes no responsibility for equip­ment installed in violation of any code or regulation. It is recommended that Manual J of the Air Condition­ing Contractors Association (ACCA) or A.R.I. 230 be followed in estimating heating requirements. When es­timating heating requirements for installation at Alti­tudes above 2000 ft., remember the gas input must be reduced (See GAS INPUT ADJUSTMENT).
Material in this shipment has been inspected at the factory and released to the transportation agency without known damage. Inspect exterior of carton for evidence of rough handling in ship­ment. Unpack carefully after moving equipment to approximate location. If damage to contents is found, report the damage immediately to the de­livering agency.
Codes and local utility requirements governing the installation of gas fired equipment, wiring, plumb­ing, and flue connections must be adhered to. In the absence of local codes, the installation must conform with latest edition of the National Fuel Gas Code ANSI
Z223.1 • National Installation Code, CAN/CGA B149.1.  
The latest code may be obtained from the American Gas Association Laboratories, 400 N. Capitol St. NW, Washington D.C. 20001. 1-800-699-9277 or www.aga.org These furnaces have been classified as Fan Assisted Combustion system CATEGORY I furnaces as re-
quired by ANSI  Z21.47  “latest edition”  and  CAN/CGA 
2.3. Therefore they do not require any special provi­sions for venting other than what is indicated in these instructions. (Category I defined on page 14).
These furnaces may be twinned. They shall have common returns with equal pressure drops or ducts with equivalent lengths and sizes. See Field Wiring Diagrams for Twinning on page 17 for proper hookup.
LOCATION AND CLEARANCES
The location of the furnace is normally selected by the architect, the builder, or the installer. However, before the furnace is moved into place, be sure to consider the following requirements:
1. Is the location selected as near the chimney or vent and as centralized for heat distribution as practi­cal?
2. Do all clearances between the furnace and en­closure equal or exceed the minimums stated in Clearance Table on the Outline Drawings.
3. Is there sufficient space for servicing the furnace and other equipment? A minimum of 24 inches front accessibility to the furnace must be provided. Any access door or panel must permit removal of the largest component.
4. Are there at least 3 inches of clearance between the furnace combustion air openings in the front panel and any closed panel or door provided?
5. Are the ventilation and combustion air openings large enough and will they remain unobstructed? If outside air is used, are the openings set above the highest snow accumulation level? (See the Air for Combustion and Ventilation section.)
6. Allow sufficient height in supply plenum above the furnace to provide for cooling coil installation, if the cooling coil is not installed at the time of this furnace installation.
7. A furnace shall be installed so electrical compo­nents are protected from water.
8. If the furnace is installed in a residential garage, it must be installed so that the burners, and the ignition source are located not less than 18 inches above the floor and the furnace must be located or protected to avoid physical damage from vehicles.
4 18-CD21D1-12
Page 5
Installer’s Guide
From Dwg. 21C341699 Sh. 1 Rev. 4
(ALL DIMENSIONS ARE IN INCHES)
*UD1-H OUTLINE DRAWING
MODEL DIM "A" DIM "B" DIM "C" DIM "D"
TUD1A040A9H21B, TUD1A040G9H21A 14-1/2" 9-5/8" 13-1/4" 13"
17-1/2" 9-5/8" 16-1/4" 16"
TUD1B060A9H31B, TUD1B060G9H31A
TUD1B080A9H31B, TUD1B080G9H31A
21" 13-1/16" 19-3/4" 19-1/2"
TUD1B100A9H31B, TUD1B100G9H31A
TUD1C080A9H41B, TUD1C080G9H41A
TUD1C100A9H51B, TUD1C100G9H51A
TUD1D120A9H51B, TUD1D120G9H51A
24-1/2" 15-5/16" 23-1/4" 23"
TUD1D140A9H51B, TUD1D140G9H51A
18-CD21D1-12
Page 6
Installer’s Guide
From Dwg. 21C341700 Sh. 1 Rev. 0
(ALL DIMENSIONS ARE IN INCHES)
*DD1-HF OUTLINE DRAWING
6 18-CD21D1-12
Page 7
Installer’s Guide
WARNING
!
UPFLOW
FURNACE
CASED
COIL
SCREWS
(BOTH SIDES)
STANDOFFS
(BOTH SIDES)
STANDOFFS (4)
DRILL SCREWS (4)
UPFLOW INSTALLATION
Standoffs and screws (See Figure 1 on page 6) are in­cluded with the cased coils for attachment to the fur­nace. There are clearance alignment holes near the bottom of the coil wrapper and drill screws are used to engage the furnace top flange. The standoff is inserted into the cabinet alignment hole. The drill screws are inserted through the standoffs then screwed into the furnace flange. The coil is always placed downstream of the furnace airflow. These instructions apply only if the coil is on top of an upflow furnace.
1
FOR VERTICAL
INSTALLATIONS:
REQUIRED FLOOR OPENING: (DOWNFLOW)
SEE FIGURE 3 AND TABLE 1
3
A (width)
FURNACE
FRONT
TABLE 1
CABINET
WIDTH
14-1/2" 13-1/4" 13-5/8" 20-1/8" 12-5/8" 19-3/8" 17-1/2" 16-1/4" 16-5/8" 20-1/8" 15-5/8" 19-3/8"
21" 19-3/4" 20-1/8" 20-1/8" 19-1/8" 19-3/8"
24-1/2" 23-1/4" 23-5/8" 20-1/8" 22-5/8" 19-3/8"
RETURN
DUCT WIDTH
FLOOR OPENING PLENUM OPENING
HORIZONTAL INSTALLATION
The coil and furnace must be fully supported when used in the horizontal position. Three brackets (with screws) are included with down­flow furnaces for installation to stabilize and secure the furnace and TXC cased coil in the horizontal posi- tion. See Figure 4.
IMPORTANT: The 2/4TXC cased coil must be placed downstream of the furnace. In horizontal installations, the apex of the coil may point either toward or away from the furnace. See the
2/4TXC coil Installer's Guide for more details.
The cased coil is secured to the furnace and both the furnace and the cased coil must be properly supported.
B (depth)
D
C
"A" "B" "C" "D"
DOWNFLOW INSTALLATION
Do NOT install the furnace directly on carpeting, tile or other combustible material other than wood floor­ing. For vertical downflow application, subbase (BAY­BASE205) must be used between the furnace and combustible flooring. When the downflow furnace is installed vertically with a cased coil, a subbase is not required.
2
18-CD21D1-12
4
CASED COIL CONNECTION
BRACKET FOR DOWNFLOW 
FURNACE IN HORIZONTAL
The brackets mount using the rear screws on the coil case and use the screws provided to secure the brack­et to the furnace. The remaining bracket is placed as close to center as possible (horizontally) between the coil case front and the furnace bottom channel (for
downow/  horizontal  furnace).  Use  four  of  the  screws 
provided to secure the bracket. This furnace may be installed in an attic or crawl space in the horizontal position by placing the furnace on the left or right side (as viewed from the front in the up­right position). The horizontal furnace installation in an attic should be on a service platform large enough to allow for proper clearances on all sides and service access to the front of the furnace (See Clearance Table on Outline Drawings and Figure 5). If the furnace is suspended using perforated steel strap (plumber’s strap), it must be supported at all four cor­ners and in the middle at the front of the furnace. The
Page 8
Installer’s Guide
forward most screw on the side of the furnace may be used to connect the strapping (See Figure 6). Line con­tact is only permissible between lines formed by the intersection of the top and two sides of the furnace cas­ing and the building joists, studs, or framing. A cutout is provided on both sides of the downflow fur­nace cabinet to allow a 90° elbow to be attached in­side the cabinet and the vent piping to connect there.
7
UNCONFINED
50 CU. FT. OR MORE
PER 1000 BTU/ HR.
INPUT ALL EQUIP-
MENT INSTALLED
5
TYPICAL ATTIC PLATFORM INSTALLATION
(UPFLOW/HORIZONTAL FURNACE SHOWN)
In horizontal, the downflow furnace may be vented through the top of the cabinet if needed. In vertical configuration, the downflow furnace may be vented us­ing the side cabinet cutouts. This venting configuration could be used if an electronic air cleaner is installed.
When the downflow furnace is vented through the left side of the furnace cabinet in horizontal or vertical configuration, Type B vent pipe must be used within the cabinet.
AIR FOR COMBUSTION AND VENTILATION
Adequate flow of combustion and ventilating air must not be obstructed from reaching the furnace. Air open­ings provided in the furnace casing must be kept free of obstructions which restrict the flow of air. Airflow restrictions affect the efficiency and safe operation of
the  furnace.    Keep  this  in  mind  should  you  choose  to 
remodel or change the area which contains your fur­nace. Furnaces must have a free flow of air for proper performance. Provisions for combustion and ventilation air shall be made in accordance with “latest edition” of Section 5.3, Air for Combustion and Ventilation, of the National Fuel Gas Code, ANSI Z223.1, or Sections 7.2, 7.3 or 7.4
of CAN/  CGA B149 Installation  Codes,  and applicable 
provisions of the local building codes. Special condi­tions created by mechanical exhausting of air and fire­places must be considered to avoid unsatisfactory fur­nace operation. Furnace locations may be in “confined space” or “uncon­fined space”. Unconfined space is defined in Table 2 and Figure 7. These spaces may have adequate air by infil­tration to provide air for combustion, ventilation, and dilution  of  ue  gases.    Buildings  with  tight  construc­tion (for example, weather stripping, heavily insulated, caulked, vapor barrier, etc.), may need additional air provided as described for confined space.
6
Typical Suspended Installation
(Upflow/Horizontal Furnace Shown)
8 18-CD21D1-12
8
Confined spaces are installations with less than 50 cu.
ft. of space per 1000 BTU/ hr input from all equipment 
installed. Air for combustion and ventilation require­ments can be supplied from inside the building as in Figure 9 or from the outdoors, as in Figure 10.
CONFINED
LESS THAN 50 CU. FT.
PER 1000 BTU/ HR.
INPUT ALL EQUIP-
MENT INSTALLED
Page 9
Installer’s Guide
1. All air from inside the building as in Figure 9: The confined space shall be provided with two perma­nent openings communicating directly with an additional room(s) of sufficient volume so that the combined volume of all spaces meets the criteria for an unconfined space. The total input of all gas utilization equipment installed in the combined space shall be considered in making this determi­nation. Refer to Table 3, for minimum open areas required.
2. All air from outdoors as in Figure 10: The confined space shall be provided with two permanent open­ings, one commencing within 12 inches of the top and one commencing within 12 inches of the bot­tom of the enclosure. The openings shall commu­nicate directly, or by ducts, with the outdoors or spaces (crawl or attic) that freely communicate with the outdoors. Refer to Table 3, for minimum open areas required.
3. The following types of installations will require use of OUT DOOR AIR for combustion, due to chemical exposures:
* Commercial buildings
* Buildings with indoor pools
* Furnaces installed in commercial laundry rooms * Furnaces installed in hobby or craft rooms * Furnaces installed near chemical storage areas. Exposure to the following substances in the combus-
tion air supply will also require OUTDOOR AIR for combustion:
* Permanent wave solutions * Chlorinated waxes and cleaners * Chlorine based swimming pool chemicals * Water softening chemicals * Deicing salts or chemicals * Carbon Tetrachloride * Halogen type refrigerants * Cleaning solvents (such as perchloroethylene) * Printing inks, paint removers, varnish, etc. * Hydrochloric acid * Cements and glues * Antistatic fabric softeners for clothes dryers * Masonry acid washing materials
TABLE 2
TABLE 3
MINIMUM FREE AREA IN SQUARE INCHES
EACH OPENING (FURNACE ONLY)
Furnace
Maximum
BTUH/INPUT
Rating
40,000 60,000
80,000 100,000 120,000 140,000
Air From
Insid
100 100 100 100 120 140
Vertical
Duct
9
0
Air From Outside
Horizontal
Duct
10 15 20 25 30 35
20 30 40 50 60 70
MINIMUM AREA IN SQUARE FEET FOR
UNCONFINED SPACE INSTALLATIONS
FURNACE MAXIMUM
BTUH / INPUT RAT-
ING
40,000 60,000
80,000 100,000 120,000 140,000
18-CD21D1-12
WITH 8 FOOT CEILING
MINIMUM AREA IN SQUARE FEET
OF UNCONFINED SPACE
250 375 500 625 750 875
Page 10
Installer’s Guide
WARNING
!
TO PREVENT INJURY OR DEATH DUE TO CONTACT WITH MOVING PARTS, TURN THE POWER TO THE FURNACE OFF BEFORE SERVICING FILTERS.
WARNING
!
Do NOT install the filter in the return duct directly above the furnace in horizontal applications. Install the filter remotely. Installing the filter directly above the furnace in horizontal applications may cause property damage, serious injury or death.
DUCT CONNECTIONS
Air duct systems should be installed in accordance with standards for air conditioning systems, National Fire Protection Association Pamphlet No. 90. They should be sized in accordance with ACCA Manual D or whichever is applicable. Check on controls to make certain they are correct for the electrical supply. Central furnaces, when used in connection with cool­ing units, shall be installed in parallel or on the up­stream side of the cooling units to avoid condensation in the heating element, unless the furnace has been specifically approved for downstream installation. With a parallel flow arrangement, the dampers or oth­er means used to control flow of air shall be adequate to prevent chilled air from entering the furnace, and if manually operated, must be equipped with means to prevent operation of either unit unless the damper is in full heat or cool position. On any job, flexible connections of nonflammable ma­terial may be used for return air and discharge con­nections to prevent transmission of vibration. Though these units have been specifically designed for quiet, vibration free operation, air ducts can act as sounding boards and could, if poorly installed, amplify the slight­est vibration to the annoyance level. When the furnace is located in a utility room adjacent to the living area, the system should be carefully de­signed with returns which minimize noise transmis­sion through the return air grille. Although these winter air conditioners are designed with large blow­ers operating at moderate speeds, any blower moving a high volume of air will produce audible noise which could be objectionable when the unit is located very close to a living area. It is often advisable to route the return air ducts under the floor or through the attic. Such design permits the installation of air return re­mote from the living area (i.e. central hall). When the furnace is installed so that the supply ducts carry air circulated by the furnace to areas outside the space containing the furnace, the return air shall also be handled by a duct(s) sealed to the furnace and ter­minating outside the space containing the furnace.
Minimum return air “entering temperature” for the furnace is 55° F.
Where there is no complete return duct system, the re­turn connection must be run full size from the furnace to a location outside the utility room, basement, attic, or crawl space.
NOTE: DO NOT install return air through the back of the furnace cabinet.
RETURN AIR DUCT CONNECTION
NOTE: On upflow 5 or 6 ton airflow models, if the airflow re­quirement exceeds 1800 CFM, these models will re-
quire return air openings and filters on both sides; OR 1 side and the bottom; OR just the bottom.
10 18-CD21D1-12
All return air duct systems should provide for installa­tion of return air filters.
PREPARATION FOR UPFLOW BOTTOM AND SIDE RETURN AIR FILTER INSTALLATION
All return air duct systems should provide for installa­tion of return air filters.
1. Determine the appropriate postion to set the fur­nace in order to connect to the supply and return ductwork.
2. The return air filter are shipped in either the bottom or side location. Remove the filter by first turning the two latches on the blower door and tilt­ing the door forward to remove. Remove the filter by sliding it out.
3. For upflow side return installations, remove the insulation around the opening in the blower com­partment.
4. The side panels of the upflow furnace include locating notches that are used as guides for cutting an opening for return air, refer to Figure 12 and the outline drawing on page 5 for duct connection dimensions for various furnaces.
  5. If  a  3/4"  ange  is  to  be  used for  attaching  the  air 
inlet duct, add to cut where indicated by solid lines in Figure 12. Cut corners diagonally and bend out­ward to form flange.
6. If flanges are not required, and a filter frame is installed, cut between the locating notches. See Figure 12.
7. Upflow Furnaces: Two clips are factory supplied for bottom or side return. Use the filter rack on ei­ther side or on the bottom if the filter is to be used within the furnace cabinet.
Page 11
Installer’s Guide
REMOVE FILTER FROM UPFLOW FURNACE WHEN RETURN DUCT IS ATTACHED TO FURNACE TOP SIDE (HORIZONTAL LEFT OR RIGHT AP­PLICATIONS) AS SHOWN.
Close coupled (less than 36") return (filter directly beneath bottom side return) not recommended due to noise considerations. If used, securely
attach 1/2" mesh metal hardware cloth 
protective screen to the inside bottom of filter grill.
When the upflow furnace is installed in the hori-
zontal right or left application and a return duct is attached to the top side as shown in Figure 11, remove the filter from the furnace and install in a remote location.
Do not install the filter in the return duct directly
above the furnace in horizontal applications.
When the upflow furnace is installed in the hori-
zontal right or left application and a close coupled (less  than  36")  return  duct  is  attached  to  the  bot­tom side of the furnace as shown in Figure 11, se-
curely  attach  a  1/2"  mesh  metal  hardware  cloth 
protective screen to the inside bottom of the filter grill to prevent personal injury from contact-
ing moving parts when reaching into the re­turn opening to replace the filter.
    Close  coupled (less than 36") return (lter directly 
beneath bottom side return) is not recommended due to noise considerations.
Downflow Furnaces:   Brackets  are  factory  sup-
plied to mount filters in the return air duct work.
8. Connect the duct work to the furnace. See Outline Drawing for supply and return duct size and loca­tion. Flexible duct connectors are recommended to connect both supply and return air ducts to the furnace.
If only the front of the furnace is accessible, it is
recommended that both supply and return air ple­nums are removable.
9. The horizontal installation of the upflow fur-
nace requires an external filter section. Do NOT use the bottom return filter within the furnace. Filter kits are available for horizon­tal applications.
10. When replacing a furnace, old duct work should be cleaned out. Thin cloths should be placed over the registers and the furnace fan should be run for 10 minutes. Don’t forget to remove the cloths be­fore you start the furnace.
18-CD21D1-12
FILTER
q
w
LOCATING NOTCHES PROVIDED FOR SIDE RETURN CUTOUT
*SEE OUTLINE DRAWING
*
*
*
*
CUT OUT
FOR
SIDE
FILTER
FRONT
of Furnace
e
Airflow
BOTTOM FILTER RACK INSTALLATION
11. The bottom panel of the upflow furnace must be removed for bottom return air. After removing the filter, lay the furnace on its back. Remove the two
5/16" hex screws securing the front of the bottom 
channel to the cabinet. Rotate the channel down­ward (or remove by lowering the front edge of the channel and pulling forward). Slide the bottom return air panel out of the cabinet. Rotate the front channel to its original position and reinstall
the two 5/16” screws.  
RETURN AIR FILTERS
TYPICAL UPFLOW RETURN AIR FILTER INSTALLATIONS
These furnaces require high velocity type air filters. The filters may be installed within the furnace blower compartment  for  UPFLOW  furnaces  in  either  a  BOT­TOM or SIDE (left side or right side) return air inlet. Some filters may need to be trimmed for side or bottom filter use.
NOTE: For upflow 5 ton airflow models where the airflow requirement exceeds 1800 CFM - Models will require return air openings and filters on: (1) both sides, or (2) one side and the bottom, or (3) just the bottom.
The furnace and the bottom lter rack, BAYRACK960,  
installation can be seen in Figure 13.
Page 12
Installer’s Guide
RETAINING
PIN
(Both Sides)
SPRINGS
SIDE
CUTOUT
FILTER
RACK
RAILS
BOTTOM
PANEL
INSTALLED
Airflow
RETAINING
PIN
(Both Sides)
SPRINGS
SIDE
CUTOUT
FILTER
RACK RAILS
BOTTOM
PANEL
INSTALLED
Airflow
TABLE 4
UPFLOW FURNACE RETURN AIR FILTERS
CABINET
WIDTH
14-1/2" 1 14" X 25" X 1" 17-1/2" X 25" X 1"
17-1/2" 1 17" X 25" X 1" 17-1/2" X 25" X 1"
21" 1 20" X 25" X 1" 17-1/2" X 25" X 1"
24-1/2" 1 24" X 25" X 1" 17-1/2" X 25" X 1"
**NOTE: For upflow 5 ton airflow models where the airflow requirement exceeds 1800 CFM - Models will require return air openings and filters on: (1) both sides, or (2) one side and the bottom, or (3) just on the bottom
QTY*
CABINET
BOTTOM FILTER
CABINET
SIDE FILTER
ALTERNATE FILTER RACK INSTALLATION FOR BOT­TOM RETURN - BAYRACK960
The following checklist should be used when installing a bottom return filter on an upflow furnace:
a. Remove the filter.
b. Remove the bottom panel.
c. With the filter removed, the filter rack is com-
pressed and then inserted into the bottom of the
furnace.  The retaining screw/pin on each side 
inserts into engagement holes at the bottom of the furnace cabinet side. See Figure 18.
d. Reinstall the furnace filter in the bottom position
by inserting the chamfer end first into the filter rack.
ALTERNATE FILTER RACK INSTALLATION FOR SIDE RETURN AIR ON UPFLOW FURNACES (LEFT OR RIGHT) ­BAYRACK960
The following checklist should be used when installing a right or left side return filter on an upflow furnace:
a. Remove the filter. b. Leave the bottom panel in place. c. Make side cutout by following the directions in
the “Return Air Duct Connections” section on page 10.
d. Compress the filter rack and reinstall in the side
position on the furnace. Confirm that the upper
retaining pin/screw locks into the engagement  hole in the blower deck and the lower pin/screw 
rests against the side of the bottom panel. See Figures 15-16, 19-20.
e. Reinstall the furnace filter in the side position
by inserting the chamfer end first into the filter rack.
Optional conversion kits for horizontal lters are BAY­FLTR203 for 17 1/2"  width cabinets, BAYFLTR204 for  21" width cabinets, and BAYFLTR205 for 24" width 
cabinets. These include filters and brackets necessary for horizontal filters. See Figure 17.
y
r
Airflow
t
Typical Upflow Left Side Return Filter Rack Installation
12 18-CD21D1-12
Typical Upflow Right Side Return Filter Rack Installation
u
Airflow
Accessory lter kit BAY­FLTR203, 204, 205 used for Upflow Horizontal furnaces.
Typical Horizontal Filter Installation
Page 13
Installer’s Guide
Bottom Panel
Filter Rack
Furnace
Cabinet
Side
Filter Rack Retaining Screw/Pin
Engagement Hole
For
Bottom Return
Filter Rack
Installation With
Filter Rack
Furnace
Cabinet
Side
Filter Rack Retaining Screw/Pin
Engagement Hole For
Bottom Return
Filter Rack
Installation With
Filter Rack Assembly
Furnace Blower Deck
Filter Rack Retaining Screw/Pin
Engagement Hole For
Return
Filter Rack Installation With Side
Furnace
Cabinet
Side
SIDE
CUT-OUT
ALTERNATE SIDE
FILTER CLIPS
LOCATIONS
ALTERNATE BOTTOM
FILTER CLIPS LOCATIONS
i
o
p
BLOWER DECK
a
s
Airflow
RETURN AIR FILTERS FOR UPFLOW FURNACE IN HORIZONTAL CONFIGURATION
When the Upflow Furnace is installed in the horizontal configuration, the return air filters must be installed exterior to the furnace cabinet. Remote filter grilles may be used for homeowner convenience or the filters may be installed in the duct work upstream of the fur­nace. See Figure 17.
UPFLOW FILTER CLIP/ BRACKET INSTALLATION
1. Determine the location to be used. The furnace cabinet has dimples for location of the alter­nate furnace clips (Side return only). Pre-drill
clearance holes with a 3/16" drill.  Bottom 
return holes are pre-drilled. See Figure 21. Attach clip to bottom channel and rear of unit with screws provided for bottom return.
2. Install the clips in front and rear of the desired location using the screws provided. The filter clip with the leaf spring mounts in the rear of the cabinet.
TYPICAL DOWNFLOW FURNACE RETURN AIR FIL­TER INSTALLATIONS
These furnaces require high velocity type air filters. Downflow furnace filters must be located outside the furnace cabinet. Typical installations are shown in Figure 22. Tables 5 and 6 provide information for in­stallation of the filter retaining brackets shipped with downflow furnaces.
18-CD21D1-12
Page 14
Installer’s Guide
CARBON MONOXIDE POISONING HAZARD
Failure to follow the steps outlined below for each appliance connected to the venting system being placed into operation could result in carbon monoxide poisoning or death.
The following steps shall be followed for each appliance connected to the venting system being placed into operation, while all other appliances connected to the venting system are not in operation:
1. Seal any unused openings in the venting system.
2. Inspect the venting system for proper size and horizontal pitch, as required in the National Fuel Gas Code, ANSI Z223.1/NFPA 54 or the CAN/CGA B149 Installation Codes and these instructions. Determine that there is no blockage or restriction, leakage, corrosion and other deficiencies which could cause an unsafe condition.
3. As far as practical, close all building doors and windows and all doors between the space in which the appliance(s) connected to the venting system are located and other spaces of the building.
4. Close fireplace dampers.
5. Turn on clothes dryers and any appliance not connected to the venting system. Turn on any exhaust fans, such as range hoods and bathroom exhausts, so they are operating at maximum speed. Do not operate a summer exhaust fan.
6. Follow the lighting instructions. Place the appliance being inspected into operation. Adjust the thermostat so appliance is operating continuously.
7. If improper venting is observed during any of the above tests, the venting system must be corrected in accordance with the National Fuel Gas Code, ANSI Z221.1/NFPA 54 and/or CAN/CGA B149 Installation Codes.
8. After it has been determined that each appliance connected to the venting system properly vents where tested as outlined above, return doors, windows, exhaust fans, fireplace dampers and any other gas-fired burning appliance to their previous conditions of use.
WARNING
!
TABLE 5
CABINET
WIDTH
14-1/2" 2 - 14X20X1 12-7/8" 17-1/2" 2 - 16X20X1 14-3/8"
21" 2 - 16X20X1 13-1/8"
24-1/2" 2 - 16X20X1 11-5/8"
* Location dimension is from end of duct to the screw holes for the bracket.
CABINET
WIDTH
14-1/2" 13-1/4" 12" 14" 17-1/2" 16-1/4" 15" 14"
21" 19-3/4" 19-1/2" 14"
24-1/2" 23-1/4" 22" 14"
14 18-CD21D1-12
RETURN
DUCT
WIDTH
FILTER
SIZE
TABLE 6
FILTER ACCESS
OPENING - DI-
MENSION "A"
FILTER BRACKET
GENERAL VENTING INSTRUCTIONS
LOCATION *
FILTER ACCESS
OPENING -
DIMENSION "B"
Page 15
Installer’s Guide
WARNING
!
WARNING
!
WARNING
!
VENT PIPING
These furnaces have been classified as Fan-Assisted Combustion System, Category I furnaces under the
“latest edition” provisions of ANSI Z21.47 and CAN/ 
CGA 2.3 standards. Category I furnaces operate with a non-positive vent static pressure and with a flue loss of not less than 17 percent.
NOTE: If desired, a side wall termination can be accomplished through the use of an “add-on” draft inducer. The in­ducer must be installed according to the inducer man­ufacturer’s instructions. Set the barometric pressure relief to achieve -0.02 inch water column.
NOTE: When the downflow furnace is vented through the left side of the furnace cabinet using the provided cutout, Type B vent piping must be used. The furnace shall be connected to a factory built chim­ney or vent complying with a recognized standard, or a masonry or concrete chimney lined with a lining mate­rial acceptable to the authority having jurisdiction.
Furnace venting into an unlined masonry chimney or concrete chimney is prohibited. Failure to follow this warning could result in property damage, personal injury, or death.
VENTING INTO A MASONRY CHIMNEY
If the chimney is oversized, the liner is inadequate, or flue-gas condensation is a problem in your area, con­sider using the chimney as a pathway or chase for type
“B” vent or exible vent liner. If exible liner material  is  used,  size  the  vent  using  the  “B”  vent  tables,  then 
reduce the maximum capacity by 20% (multiply 0.80
times  the  maximum   capacity).  Masonry  Chimney  Kit  BAYVENT800B may be used with these furnaces (Up-
flow model furnaces only) to allow venting into a
masonry chimney. Refer to the BAYVENT800B Install­er’s Guide for application requirements.
INTERNAL MASONRY CHIMNEYS
Venting of fan assisted appliances into a lined, inter­nal masonry chimney is allowed only if it is common vented with at least one natural draft appliance; OR,
if the  chimney is lined with type  “B”, double wall vent 
or suitable flexible liner material (See Table 7).
The chimney liner must be thoroughly inspected to insure no cracks or other potential areas for flue gas leaks are present in the liner. Liner leaks will result in early deterioration of the chimney. Failure to follow this warning could result in carbon monoxide poisoning or death.
TABLE 7
MASONRY CHIMNEY VENTING
Tile Lined Chimney Chimney Lining
Type Furnace
Internal External “B” Vent
Single Fan
Assist
Fan Assist
+
Fan Assist
Fan Assist
+
Natural
* Flexible chimney liner size is determined by using the type “B” vent size for the available BTUH input, then reducing the maximum capacity by 20% (multiply maximum capacity times 0.80). The minimum capacity is the same as shown in the “B” vent tables.
No No Ye s Yes*
No No Ye s Yes*
Ye s No Ye s Yes*
Flexible
Metal Liner
External Masonry Chimney
Venting of fan assisted appliances into external chim­neys (one or more walls exposed to outdoor tempera-
tures),  requires  the  chimney  be  lined  with  type  “B”, 
double wall vent or suitable flexible chimney liner material. This applies in all combinations of common venting as well as for fan assisted appliances vented alone.
CARBON MONOXIDE POISONING HAZARD Failure to follow the installation instructions for the venting system being placed into operation could re­sult in carbon monoxide poisoning or death.
The following installation practices are recommended to minimize corrosion caused by condensation of flue products in the furnace and flue gas system.
1. Avoid an excessive number of bends.
  2.  Horizontal  runs  should  pitch  upward  at  least  1/4" 
per foot.
3. Horizontal runs should be as short as possible.
4. All vent pipe or connectors should be securely sup­ported and must be inserted into, but not beyond the inside wall at the chimney vent.
5. When vent connections must pass through walls or partitions of combustible material, a thimble must be used and installed according to local codes.
6. Vent pipe through the roof should be extended to a height determined by National Fuel Gas Code or local codes. It should be capped properly to prevent rain water from entering the vent. Roof exit should be waterproofed.
  7. Use type “B” double wall vent when vent pipe is 
routed through cool spaces (below 60° F.).
NOTE: The following section does not apply if BAYVENT800B (Masonry Chimney Vent Kit) is used. All instructions with the kit must be followed.
18-CD21D1-12
Page 16
Installer’s Guide
WARNING
!
CAUTION
!
WARNING
!
TABLE 8
GAS VENT TERMINATION
ROOF PITCH MINIMUM HEIGHT
FLAT TO 7/12 OVER 7/12 TO 8/12 OVER 8/12 TO 9/12 OVER 9/12 TO 10/12 OVER 10/12 TO 11/12 OVER 11/12 TO 12/12 OVER 12/12 TO 14/12 OVER 14/12 TO 16/12 OVER 16/12 TO 18/12 OVER 18/12 TO 20/12 OVER 20/12 TO 22/12
* THIS REQUIREMENT COVERS MOST INSTALLATIONS
1.0 FEET *
1.5 FEET
2.0 FEET
2.5 FEET
3.25 FEET
4.0 FEET
5.0 FEET
6.0 FEET
7.0 FEET
7.5 FEET
8.0 FEET
d
8. Where long periods of airflow are desired for com-
fort, use long fan cycles instead of continuous air­flow.
9. Apply other good venting practices as stated in the venting section of the National Fuel Gas Code ANSI Z223.1 “latest edition”.
10. Vent connectors serving appliance vented by
natural draft or non-positive pressure shall not be connected into any portion of a mech­anized draft system operating under positive pressure.
11. Horizontal pipe runs must be supported by hang­ers, straps or other suitable material in intervals at a minimum of every 3 feet of pipe.
12. A furnace shall not be connected to a chimney or flue serving a separate appliance designed to burn solid fuel.
13. The flow area of the largest section of vertical vent or chimney shall not exceed 7 times the small­est listed appliance categorized vent area, flue col­lar area, or draft hood outlet area unless designed in accordance with approved engineering methods.
Maximum Vent or Tile Lined Chimney Flow Area
*Drafthood outlet diameter, flue collar diameter, or listed appliance cat­egorized vent diameter.
= X 7
π(D*)
4
2
ELECTRICAL CONNECTIONS
The cabinet must have an uninterrupted or unbroken ground according to National Electrical Code, ANSI/ NFPA 70 – “latest edition” and Canadian Electrical Code, CSA C22.1 or local codes to minimize personal injury if an electrical fault should occur. Failure to follow this warning could result in an electri­cal shock, fire, injury, or death.
The integrated furnace control is polarity sensitive. The hot leg of the 115 VAC power must be connected to the BLACK field lead.
To prevent injury or death due to electrical shock or contact with moving parts, lock unit disconnect switch in the open position before servicing the unit. Failure to follow this warning could result in electrical shock, personal injury, or death.
Make wiring connections to the unit as indicated on enclosed wiring diagram. As with all gas appliances using electrical power, this furnace shall be connected into a permanently live electric circuit. It is recom­mended that it be provided with a separate “circuit protection device” electric circuit. The furnace must be electrically grounded in accordance with local codes or in the absence of local codes with the National Electri-
cal  Code,  ANSI/NFPA 70  “latest  edition”  or  Canadian 
Electrical Code, CSA C22.1, if an external electrical source is utilized. All field supplied wiring must conform with the tem­perature limitation for Type T wire [63° F. (35° C)], when installed in accordance with these instructions and wiring diagrams supplied with the furnace. A dis­connecting means must be located within sight from, and readily accessible to, the furnace. Refer to the SERVICE FACTS literature for unit wir­ing diagrams in addition to the diagram inside the blower door.
16 18-CD21D1-12
Page 17
Installer’s Guide
SEE
NOTE 6
From Dwg. B341437 Rev. 1
FURNACE
TWIN
SEE
NOTE 7
B/C
B/C
TO 115 V 1 PH., 60 HZ., POWER SUPPLY PER LOCAL CODES
HUM SEE NOTE 5
EAC SEE NOTE 5
FIELD WIRING DIAGRAM FOR 1 STAGE FURNACE
1 STAGE HEATING
USING A 1 STAGE HEATING THERMOSTAT
NO COOLING
OUTDOOR UNIT
(NO TRANSFORMER)
SEE
NOTE 6
From Dwg. B341436 Rev. 1
SEE
NOTE 8
FURNACE
TWIN
SEE
NOTE 7
B/C
B/C
TO 115 V 1 PH., 60 HZ., POWER SUPPLY PER LOCAL CODES
HUM SEE NOTE 5
EAC SEE NOTE 5
FIELD WIRING DIAGRAM FOR 1 STAGE FURNACE
1 STAGE HEATING, 1 STAGE COOLING
USING A 1 STAGE HEATING, 1 STAGE COOLING THERMOSTAT
(OUTDOOR SECTION WITHOUT TRANSFORMER)
18-CD21D1-12
From Dwg. 21B341437 P01
From Dwg. 21B341436 P01
Page 18
Installer’s Guide
TWIN
TWIN
R1
R1
TWINNING CONNECTION DIAGRAM
FOR TWINNING 1 STAGE FURNACES WITH
SINGLE WIRE TWINNING FEATURE
1 STAGE HEATING ONLY THERMOSTAT
1 STAGE HEAT
ONLY
THERMOSTAT
(WITH FAN SWITCH) FURNACE NO. 1
FURNACE NO. 2
BLOWER OPERATION OF
UNIT NO. 2 IS SYNCRONIZED
WITH UNIT NO. 1 VIA SIGNALS
FROM TWIN CONNECTION.
SEE NOTE 4
SEE NOTE 3
ISOLATION RELAY (FIELD SUPPLIED)
SEE NOTE 4
ISOLATION RELAY
SEE NOTE 4
B/C
B/C
B/C
From Dwg. 21B341422 Rev. 3
TWIN
TWIN
R1
R1
TWINNING CONNECTION DIAGRAM
FOR TWINNING 1 STAGE FURNACES WITH
SINGLE WIRE TWINNING FEATURE
1 STAGE HEAT / 1 STAGE COOL THERMOSTAT
1 STAGE
HEATING / COOLING
THERMOSTAT FURNACE NO. 1
FURNACE NO. 2
BLOWER OPERATION OF
UNIT NO. 2 IS SYNCRONIZED
WITH UNIT NO. 1 VIA SIGNALS
FROM TWIN CONNECTION.
SEE NOTE 4
SEE NOTE 5
ISOLATION RELAY (FIELD SUPPLIED)
SEE NOTE 4
ISOLATION RELAY
SEE NOTE 4
OUTDOOR UNIT
(NO TRANSFORMER)
OUTDOOR UNIT
(WITH TRANSFORMER)
RC
ISOLATION RELAY (FIELD SUPPLIED)
SEE NOTE 3
B/C
B/C
B/C
From Dwg. 21B341423 Rev. 2
TWINNING
These furnaces may be twinned. Twinning requires that two furnaces with the same configuration, capac­ity, and airflow must be used. They shall have common returns with equal pressure drops or ducts with equiv­alent lengths and sizes. See Field Wiring Diagrams be­low for proper hookup.
18 18-CD21D1-12
Page 19
TOP VIEW
AUTOMATIC GAS VALV E WITH MANUAL SHUTOFF
WARNING
!
FIRE OR EXPLOSION HAZARD
WARNING
!
CAUTION
!
The following warning complies with State of California law, Proposition 65.
Hazardous Gases!
Exposure to fuel substances or by-products of incomplete fuel combustion is believed by the state of California to cause cancer, birth defects, or other reproductive harm.
WARNING
!
WARNING
!
DRIP LEG
DRIP LEG
Failure to follow the safety warnings exactly could re­sult in serious injury, death or property damage. Never test for gas leaks with an open flame. Use a commer­cially available soap solution made specifically for the detection of leaks to check all connections. A fire or ex­plosion may result causing property damage, personal injury, or loss of life.
IMPORTANT:
A sediment trap must be installed in the gas line before the furnace gas valve. The sediment trap must be located as close to the furnace cabinet as practical.
LEFT SIDE PIPING (STANDARD)
f
Installer’s Guide
GAS PIPING
FIRE - EXPLOSION HAZARD DO NOT RUN FLEXIBLE GAS LINE THROUGH THE FURNACE CABINET WALL. FAILURE TO FOLLOW THIS WARNING COULD RESULT IN PROPERTY DAMAGE,
SERIOUS PERSONAL INJURY, OR DEATH.
This unit is shipped standard for left side installation of gas piping. A piping knockout is also provided in the right side for an alternate piping arrangement. The installation of piping shall be in accordance with pip­ing codes and the regulations of the local gas company. Pipe joint compound must be resistant to the chemical reaction with liquefied petroleum gases. Refer to pip­ing Table 9 for delivery sizes.
NOTE: Refer to local codes and the National Fuel Gas Code, current edition, for gas pipe re­quirements.
The furnace and its individual shut-off valve must be disconnected from the gas supply piping system during any pressure testing of that system at test pressures in
excess of 1/2 psig.
The furnace must be isolated from the gas supply pip­ing by closing its individual manual shut-off valve dur­ing any pressure testing of the gas supply piping sys-
tem at test pressures equal to or less than 1/2 psig.
RIGHT SIDE PIPING (OPTIONAL)
TOP VIEW OF RIGHT SIDE PIPING
TO PREVENT AN EXPLOSION OR POSSIBLE INJURY, DEATH AND EQUIPMENT DAMAGE, DO NOT STORE COMBUSTIBLE MATERIALS, GASOLINE OR OTHER FLAMMABLE VAPORS OR LIQUIDS NEAR THE UNIT.
18-CD21D1-12
Use a backup wrench on the gas valve when install­ing gas piping to prevent damage to the gas valve and manifold assembly.NOTE:
Maximum pressure to the gas valve for natural gas is
13.8" W.C. Minimum pressure is 5.0" W.C. Maximum pressure to the gas valve for propane is 13.8" W.C. Minimum pressure is 11.0" W.C.
All gas fittings must be checked for leaks using a soapy solution before lighting the furnace.
DO NOT CHECK WITH AN OPEN FLAME!
SEQUENCE OF OPERATION THERMOSTAT CALL FOR HEAT
R and W thermostat contacts close signaling the con­trol module to run its self-check routine. After the control module has verified that the pressure switch contacts are open and the limit switch(es) contacts are closed, the draft blower will be energized.
Page 20
Installer’s Guide
WARNING
!
As the induced draft blower comes up to speed, the pressure switch contacts will close and the ignitor warm up period will begin. The ignitor will heat for approx. 20 seconds, then the gas valve is energized to permit gas flow to the burners. The flame sensor con­firms that ignition has been achieved within the 6 sec­ond ignition trial period. After the flame sensor confirms that ignition has been achieved, the delay fan ON period (fixed at 45 seconds) begins timing. After the delay of 45 seconds, the in­door blower motor will be energized and will continue to run during the heating cycle.
When the thermostat is satisfied, R and W thermostat contacts open, the gas valve will close, the flames will extinguish, and the induced draft blower will be de-en­ergized. The indoor blower motor will continue to run for the fan off period (fixed at 100 seconds), then will be de-energized by the control module.
FIRE OR EXPLOSION HAZARD Failure to follow the safety warnings exactly could re­sult in serious injury, death or property damage. Never test for gas leaks with an open flame. Use a commer­cially available soap solution made specifically for the detection of leaks to check all connections. A fire or ex­plosion may result causing property damage, personal injury, or loss of life.
START-UP AND ADJUSTMENT
PRELIMINARY INSPECTIONS
With gas and electrical power “OFF”
1. Duct connections are properly sealed
2. Filters are in place
3. Venting is properly assembled
  4. Blower door is in place
Turn knob on main gas valve within the unit to the “OFF” position. Turn the external gas valve to “ON”. Purge the air from the gas lines. After purging, check all gas connections for leaks with a soapy solution – DO NOT CHECK WITH AN OPEN FLAME. Allow 5 minutes for any gas that might have escaped to dis­sipate. LP Gas, being heavier than air, may require forced ventilation. Turn the knob on the gas valve in the unit to the “ON” position.
COMBUSTION AND INPUT CHECK
1. Make sure all gas appliances are off except the fur­nace.
2. Clock the gas meter with the furnace operating (determine the dial rating of the meter) for one revolution.
3. Match the “Sec” column in the gas flow (in cfh) Ta­ble 13 with the time clocked.
4. Read the “Flow” column opposite the number of seconds clocked.
5. Use the following factors if necessary: For 1 Cu. Ft. Dial Gas Flow CFH = Chart Flow Reading ÷ 2
For 1/2 Cu. Ft. Dial Gas Flow CFH =
Chart Flow Reading ÷ 4 For 5 Cu. Ft. Dial Gas Flow CFH = 10X Chart Flow Reading ÷ 4
6. Multiply the final figure by the heating value of the gas obtained from the utility company and compare to the nameplate rating. This must not exceed the nameplate rating.
Gas Valve Adjustment
Changes can be made by adjusting the manifold pres-
sure (See Table 12), or changing orifices (orifice change may not always be required). To adjust the manifold pressure:
1. Turn off all electrical power to the system.
2. Attach a manifold pressure gauge with flexible
tubing to the outlet pressure boss marked “OUT P” on White-Rodgers gas valve model 36G or 36J. See Figure 26 for White-Rodgers gas valve model 36J. See Figure 25 for White-Rodgers gas valve model 36G.
3. Loosen (Do Not remove) the pressure tap test set
screw one turn with 3/32" hex wrench.
a. The pressure tap adjustment kit (KIT07611) 
contains a 3/32" hex wrence, a 5/16" hose and 
a connector and can be ordered through Global Parts.
4. Turn on system power and energize valve.
5. Adjust gas heat by removing the adjustment regu-
lator cover screw.
a. To increase outlet pressure, turn the regulator
adjust screw clockwise.
b. To decrease outlet pressure, turn the regulator
adjust screw counterclockwise.
c. Adjust regulator until pressure shown on mano-
meter matches the pressure specified in Table
12.
1. The input of no more than nameplate rating and no less than 93% of the nameplate rating, unless the unit is derated for high altitude.
d. Replace and tighten the regulator cover screw
securely.
6. Cycle the valve several times to verify regulator setting.
a. Repeat steps 5-6 if needed.
7. Turn off all electrical power to the system.
8. Remove the manometer and flexible tubing and tighten the pressure tap screw.
20 18-CD21D1-12
Page 21
Installer’s Guide
CAUTION
!
WARNING
!
9. Using a leak detection solution or soap suds, check for leaks at the pressure outlet boss and pressure tap test screw.
10. Turn on system power and check operation of the unit.
Replace and/ or tighten all plugs removed or loosened when adjusting gas pressure. Leak check the fittings before placing the furnace into regular service. Failure to follow this warning could result in fire, explo­sion, or property damage.
Table 10 lists the main burner orifices shipped with the furnace. If a change of orifices is required to cor­rect the input rate, refer to Table 11.
TABLE 9
NATURAL GAS ONLY
TABLE OF CUBIC FEET PER HOUR OF GASFOR VARIOUS PIPE
PIPE-
SIZE
1/2 132 92 73 63 56 50 46
3/4 278 190 152 130 115 105 96
1-1/4 1050 730 590 520 440 400 370
This table is based on pressure drop of 0.3 inch W.C. and 0.6 SP.GR. gas
10 20 30 40 50 60 70
1 520 350 285 245 215 195 180
SIZES AND LENGTHS
LENGTH OF PIPE
TABLE 10
ORIFICE SIZES
INPUT
RATING
BTUH
40,000 60,000
80,000 100,000 120,000 140,000
NUMBER
OF
BURNERS
2 3 4 5 6 7
TABLE 11
MAIN BURNER ORIFICE
DRILL SIZE
NAT. GAS LP GAS
45 45 45 45 45 45
56 56 56 56 56 56
PART NUMBERS FOR REPLACEMENT ORIFICES
DRILL
SIZE
44 45 46 47 48 49 50
PART
NUMBER
ORF00501 ORF00644 ORF00909 ORF00910 ORF01099 ORF00503 ORF00493
TABLE 12
FINAL MANIFOLD PRESSURE SET-
TINGS (inches w.c.)
FUEL PRESSURE
NATURAL GAS 3.5" W.C.
LP GAS 10.5" W.C.
DRILL
SIZE
54 55 56 57 58 59
PART
NUMBER
ORF00555 ORF00693 ORF00907 ORF00908 ORF01338 ORF01339
HIGH ALTITUDE DERATE
Input  ratings  (BTUH)  of  these  furnaces  are  based  on 
sea level operation and should not be changed at eleva­tions up to 2,000 ft. If the installation is 2,000 ft. or above, the furnace in-
put  rate  (BTUH)  shall  be  reduced  4%  for  each  1,000 
ft. above sea level. The furnace input rate shall be checked by clocking the gas flow rate (CFH) and mul­tiplying by the heating value obtained from the local utility supplier for the gas being delivered at the in­stalled altitude. Input rate changes can be made by adjusting the manifold pressure (min 3.0 - max 3.7 in. W.C. - Natural Gas) or changing orifices (orifice change may not always be required). If the desired input rate cannot be achieved with a change in manifold pressure, then the orifices must be changed. LP installations will require an orifice change. Installation of this furnace at altitudes above 2,000 ft. (610m) shall be in accordance with local codes, the Na-
tional Fuel Gas Code, ANSI Z223.1/ NFPA 54 or Na­tional Standard of Canada, Natural Gas and Propane Installation Code, CSA B149.1. Installation of this fur-
nace at altitudes above 2,000 ft. (610m) shall be made in accordance with the listed high Altitude Conversion
Kit available with this furnace.
IMPORTANT: Re-install the propane orifices to the same depth as the orifices supplied with the equipment.
See Table 14 for help in selecting orifices if orifice change is required. Furnace input rate and tempera­ture rise should be checked again after changing ori­fices to confirm the proper rate for the altitude. Installations above 4,000 feet may require a pressure
switch change.    If required,  use  the  BAYHALT*** Kit  (High  Altitude  Accessory  Kit)  listed  in  PRODUCT 
DATA.
EXPLOSION HAZARD! PROPANE GAS IS HEAVIER THAN AIR AND MAY COLLECT IN ANY LOW AREAS OR CONFINED SPAC­ES. IN ADDITION, ODORANT FADE MAY MAKE THE GAS UNDETECTABLE EXCEPT WITH A WARNING DEVICE. IF THE GAS FURNACE IS INSTALLED IN A BASEMENT, AN EXCAVATED AREA OR A CONFINED SPACE, IT IS STRONGLY RECOMMENDED TO CON­TACT A GAS SUPPLIER TO INSTALL A GAS DETECT­ING WARNING DEVICE IN CASE OF A GAS LEAK.
NOTE: The manufacturer of your furnace does NOT test any detectors and makes no representations regarding any brand or type of detector.
18-CD21D1-12
Page 22
Installer’s Guide
WARNING
!
CAUTION
!
Outlet Pressure Boss
On/Off Switch
Inlet Pressure
Boss (opt.)
Regulator
Adjust
TABLE 13
GAS FLOW IN CUBIC FEET PER HOUR
2 CUBIC FOOT DIAL
SEC. FLOW SEC. FLOW SEC. FLOW SEC. FLOW
8 900 29 248 50 144 82 88
9 800 30 240 51 141 84 86 10 720 31 232 52 138 86 84 11 655 32 225 53 136 88 82 12 600 33 218 54 133 90 80 13 555 34 212 55 131 92 78 14 514 35 206 56 129 94 76 15 480 36 200 57 126 96 75 16 450 37 195 58 124 98 73 17 424 38 189 59 122 100 72 18 400 39 185 60 120 104 69 19 379 40 180 62 116 108 67 20 360 41 176 64 112 112 64 21 343 42 172 66 109 116 62 22 327 43 167 68 106 120 60 23 313 44 164 70 103 124 58 24 300 45 160 72 100 128 56 25 288 46 157 74 97 132 54 26 277 47 153 76 95 136 53 27 267 48 150 78 92 140 51 28 257 49 147 80 90 144 50
g
White-Rodgers 36G gas valve
h
Outlet Pressure Boss
Regulator Adjustment
TABLE 14
Orifice
Twist Drill
Size If
Installed
At Sea
Level
42 43 44 45 46 47
54 55 56 57 58
2000 3000 4000 5000 6000 7000 8000 9000 10000
42 44 45 46 47 48
54 55 56 58 59
From National Fuel Gas Code - Table F-4
ALTITUDE ABOVE SEA LEVEL
and Orifice Required At Other Elevations
43
43
43
44
44
45
46
44
44
45
45
46
47
47
45
45
46
47
47
48
48
47
47
47
48
48
49
49
47
47
48
48
49
49
50
48
49
49
49
50
50
51
55
55
55
55
55
56
56
55
55
56
56
56
56
56
56
57
57
57
58
59
59
59
59
60
60
61
62
63
60
60
61
62
62
63
63
47 48 50 50 51 52
56 57 60 63 64
LIGHTING INSTRUCTIONS
DO NOT attempt to manually light the burner. Failure to follow this warning could result in property damage, personal injury or death.
Lighting instructions appear on each unit. Each installation must be checked out at the time of initial start up to insure proper operation of all components. Check out should include putting the unit through one complete cycle as outlined below.
Turn on the main electrical supply and set the thermo­stat above the indicated temperature. The ignitor will automatically heat, then the gas valve is energized to permit the flow of gas to the burners. After ignition and flame is established, the flame control module monitors the flame and supplies power to the gas valve until the thermostat is satisfied.
TO SHUT OFF
For complete shutdown: Move the control switch on the main gas valve to the “OFF” position (See Figures 25 and 26). Disconnect the electrical supply to the unit.
Inlet Pressure Boss (opt.)
White-Rodgers 36J gas valve
22 18-CD21D1-12
On/Off Switch
If this is done during the cold weather months, provi­sions must be taken to prevent freeze-up of all water pipes and water receptacles. Failure to follow this warning could result in property damage.
Whenever your house is to be vacant, arrange to have someone inspect your house for proper temperature. This is very important in below freezing weather. If for any reason your furnace should fail to operate damage could result, such as frozen water pipes.
Page 23
Installer’s Guide
WARNING
!
WARNING
!
The following warning complies with State of California law, Proposition 65.
This product contains fiberglass wool insulation!
Fiberglass dust and ceramic fibers are believed by the State of California to cause cancer through inhalation. Glasswool fibers may also cause respiratory, skin, or eye irritation.
PRECAUTIONARY MEASURES
Avoid breathing fiberglass dust.
Use a NIOSH approved dust/ mist respirator.
Avoid contact with the skin or eyes. Wear long-
sleeved, loose-fitting clothing, gloves, and eye protection.
Wash clothes separately from other clothing: rinse washer thoroughly.
Operations such as sawing, blowing, tear-out, and spraying may generate fiber concentrations requiring additional respiratory protection. Use the appropriate NIOSH approved respirator in these situations.
FIRST AID MEASURES
Eye Contact – Flush eyes with water to remove dust. If
symptoms persist, seek medical attention.
Skin Contact – Wash affected areas gently with soap and warm water after handling.
WARNING
!
CONTROL AND SAFETY SWITCH ADJUSTMENT
LIMIT SWITCH CHECK OUT
The limit switch is a safety device designed to close the gas valve should the furnace become overheated. Since proper operation of this switch is important to the safety of the unit, it must be checked out on initial start up by the installer. To check for proper operation of the limit switches, set the thermostat to a temperature higher than the indi­cated temperature to bring on the gas valve. Restrict the airflow by blocking the return air or by disconnect­ing the blower. When the furnace reaches the maxi­mum outlet temperature as shown on the rating plate, the burners must shut off. If they do not shut off after a reasonable time and overheating is evident, a faulty limit switch is probable and the limit switch must be replaced. After checking the operation of the limit con­trol, be sure to remove the paper or cardboard from the return air inlet, or reconnect the blower.
AIRFLOW ADJUSTMENT
Check inlet and outlet air temperatures to make sure they are within the ranges specified on the furnace rat­ing nameplate. If the airflow needs to be increased or decreased, see the wiring diagram for information on changing the speed of the blower motor.
INSTRUCTIONS TO THE OWNERS
In the event that electrical, fuel, or mechanical failures occur, the owner should immediately turn the gas supply off at the manual gas valve, located in the burner compartment (See Figure
24). Also turn off electrical power to the furnace and contact the service agency designated by your dealer.
Should overheating occur, or the gas supply fail to shut off, shut off the gas valve to the unit before shutting off the electrical supply. Failure to follow this warning could result in property damage, personal injury or death.
Disconnect power to the unit before removing the blower door. Failure to follow this warning could result in property damage, personal injury or death.
This unit is equipped with a blower door switch which cuts power to the blower and gas valve causing shut­down when the door is removed. Operation with the door removed or ajar can permit the escape of danger­ous fumes. All panels must be securely closed at all times for safe operation of the furnace.
NOTE: Direct drive motors have bearings which are perma­nently lubricated and under normal use, lubrication is not recommended.
INDOOR BLOWER TIMING
The control module controls the indoor blower. The blower starts approximately 45 seconds after ignition. The FAN-OFF period is approximately 100 seconds from the interruption of gas flow.
ROOM AIR THERMOSTAT HEAT ANTICIPATOR ADJUSTMENT
Set the thermostat heat anticipator according to the current flow measured, or the settings found in the notes on the furnace wiring diagram (found inside the furnace casing).
18-CD21D1-12
OPERATING INFORMATION
FLAME ROLL-OUT DEVICE
All models are equipped with a thermal control device on the burner cover. In case of flame roll-out, the de­vice will cause the circuit to open which shuts off all flow of gas.
ABNORMAL CONDITIONS
  1. EXCESSIVE  COMBUSTION  VENT  PRESSURE  OR FLUE BLOCKAGE
If pressure against the induced draft blower outlet
becomes excessive, the pressure switch will shut off the gas valve until acceptable combustion pres­sure is again available.
Page 24
Installer’s Guide
Failure to follow safety warnings exactly, could result in a fire or explosion causing property damage, personal injury or loss of life.
— Do not store or use gasoline or other flammable
vapors and liquids in the vicinity of this or any other appliance.
— WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch;
do not use any phone in your building.
Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the fire department.
— Installation and service must be performed by
a qualified installer, service agency or the gas supplier.
WARNING
!
2. LOSS OF FLAME OR GAS SUPPLY FAILURE If loss of flame occurs during a heating cycle (when flame is not present at the sensor), the con­trol module will retry the ignition sequence up to two times after the sensor cools. If ignition is not achieved, it will lockout the furnace.
3. POWER FAILURE
If there is a power failure during a heating cycle,
the system will restart the ignition sequence auto­matically when power is restored, if the thermostat still calls for heat.
  4. INDUCED DRAFT BLOWER FAILURE
If pressure is not sensed by the pressure switch, it
will not allow the gas valve to open, therefore the unit will not start. If failure occurs during a run­ning cycle, the pressure switch will cause the gas valve to close and shut the unit down.
Carbon monoxide, fire or smoke can cause serious bodi-
ly injury, death, and/ or property damage. 
A variety of potential sources of carbon monoxide can be found in a building or dwelling such as gas-fired clothes dryers, gas cooking stoves, water heaters, fur­naces and fireplaces. The U.S. Consumer Product Safety Commission recommends that users of gas­burning appliances install carbon monoxide detectors as well as fire and smoke detectors per the manufac­turers installation instructions to help alert dwelling occupants of the presence of fire, smoke or unsafe lev-
els of carbon monoxide. These devises should be listed by Underwriters Laboratories, Inc. Standards for Sin-
gle and Multiple Station Carbon Monoxide Alarms, UL 2034 or CSA International Standard, Residential Car­bon Monoxide Alarming Devices, CSA 6.19.
NOTE: The manufacturer of your furnace does not test any de­tectors and makes no representations regarding any brand or type of detector.
INTEGRATED FURNACE CONTROL ERROR FLASH CODES
Flashing Slow --- Normal - No call for Heat
Flashing Fast --- Normal - Call for Heat
Continuous ON --- Replace IFC
Continuous OFF --- Check Power
2 Flashes --- System Lockout (Retries or Recycles exceeded)
Draft Pressure Error - Possible problems:
3 Flashes ---
4 Flashes --- Open Temperature Limit Circuit
5 Flashes --- Flame sensed when no flame should be present
6 Flashes --- 115 volt AC power reversed, poor grounding or system voltage too low
7 Flashes --- Gas valve circuit error
8 Flashes --- Low flame sense signal
9 Flashes --- Check Ignitor Circuit and Line "N" to 24VAC "Common" voltage (< 2 volts) [possible grounding problem]
Trane 6200 Troup Highway Tyler, TX 75707
For more information contact your local dealer (distributor)
24 18-CD21D1-12
a) Venting problem b) Pressure switch problem c) Inducer problem
File Number 18-CD21D1-12
Supersedes 18-CD21D1-11
Date 08/13
The manufacturer has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice.
Loading...