The following safety practices and precautions must be
followed during the installation, servicing, and operation of this furnace.
1. Use only with the type of gas approved for this furnace. Refer to the furnace rating plate.
2. Install this furnace only in a location and position as
specified in “Location and Clearances” (page 4), of
these instructions.
3. Provide adequate combustion and ventilation air to
the furnace space as specified in “Air for Combustion and Ventilation” (pages 8-9), of these instructions.
4. Combustion products must be discharged outdoors.
Connect this furnace to an approved vent system
only, as specified in the “Venting” section (pages 16-
26), of these instructions.
5. Never test for gas leaks with an open flame. Use a
commercially available soap solution made specifically for the detection of leaks to check all connections, as specified in “Gas Piping” (page 32), of these
instructions.
6. Always install the furnace to operate within the
furnace’s intended temperature-rise range with a
duct system which has an external static pressure
within the allowable range, as specified on the unit
rating plate. Airflow with temperature rise for cfm
versus static is shown in the Service Facts accompanying this furnace.
7. When a furnace is installed so that supply ducts
carry air circulated by the furnace to areas outside
the space containing the furnace, the return air
shall also be handled by a duct(s) sealed to the furnace casing and terminating outside the space containing the furnace.
8. A gas-fired furnace for installation in a residential
garage must be installed as specified in “Location
and Clearances” section (page 4), of these instructions.
9. The furnace may be used for temporary heating of
buildings or structures under construction only
when the following conditions have been met:
a.The furnace venting system must be complete
and installed per manufacturers instructions.
b.The furnace is controlled only by a room ther-
mostat (no field jumpers).
c.The furnace return air duct must be complete
and sealed to the furnace and clean air filters
are in place.
d.The furnace input rate and temperature rise
must be verified to be within nameplate marking.
e.100% of the furnace combustion air require-
ment must come from outside the structure.
f.The furnace return air temperature range is
between 55 and 80 degrees Fahrenheit.
g.Clean the furnace, duct work, and components
upon substantial completion of the construction
process, and verify furnace operating conditions
including ignition, input rate, temperature rise
and venting, according to the manufacturer's
instructions.
10. This product must be gas piped by a Licensed
Plumber or Gas Fitter in the Commonwealth of Massachusetts.
Safety signal words are used to designate a degree or
level of seriousness associated with a particular hazard.
The signal words for safety markings are DANGER,WARNING, and CAUTION.
a. DANGER indicates an imminently hazardous situa-
tion which, if not avoided, will result in death or serious injury. This signal word is limited to the most extreme situations.
b. WARNING indicates a potentially hazardous situation
which, if not avoided, could result in death or serious
injury.
c. CAUTION indicates a potentially hazardous situation
which, if not avoided, may result in minor or moderate injury. It is also used to alert against unsafe practices and hazards involving only property damage.
!
WARNING
CARBON MONOXIDE POISONING HAZARD
Failure to follow the steps outlined below for each appliance connected to the venting system being placed into
operation could result in carbon monoxide poisoning or
death.
The following steps shall be followed for each appliance
connected to the venting system being placed into operation, while all other appliances connected to the venting system are not in operation:
1. Seal any unused openings in the venting system.
2. Inspect the venting system for proper size and horizontal pitch, as required in the National Fuel Gas
Code, ANSI Z223.1/ NFPA 54 or the CAN/ CGA B149
Installation Codes and these instructions. Determine
that there is no blockage or restriction, leakage, corrosion and other deficiencies which could cause an
unsafe condition.
3. As far as practical, close all building doors and windows and all doors between the space in which the
appliance(s) connected to the venting system are located and other deficiencies which could cause an
unsafe condition.
4. Close fireplace dampers.
5. Turn on clothes dryers and any appliance not connected to the venting system. Turn on any exhaust
fans, such as range hoods and bathroom exhausts,
so they are operating at maximum speed. Do not operate a summer exhaust fan.
6. Follow the lighting instructions. Place the appliance
being inspected into operation. Adjust the thermostat so appliance is operating continuously.
7. If improper venting is observed during any of the
above tests, the venting system must be corrected
in accordance with the National Fuel Gas Code,
ANSI Z221.1/ NFPA 54 and/ or CAN/ CGA B149 Installation Codes.
8. After it has been determined that each appliance
connected to the venting system properly vents
where tested as outlined above, return doors, windows, exhaust fans, fireplace dampers and any
other gas-fired burning appliance to their previous
conditions of use.
!
WARNING
FIRE OR EXPLOSION HAZARD
Failure to follow the safety warnings exactly could result in serious injury, death or property damage.
Improper servicing could result in dangerous operation, serious injury, death, or property damage.
GENERAL INSTALLATION INSTRUCTIONS
The manufacturer assumes no responsibility for equipment installed in violation of any code or regulation.
It is recommended that Manual J of the Air Conditioning Contractors Association (ACCA) or A.R.I. 230 be followed in estimating heating requirements. When estimating heating requirements for installation at altitudes above 2000 ft., remember the gas input may need
to be reduced (See High Altitude Installation).
Material in this shipment has been inspected at
the factory and released to the transportation
agency without known damage. Inspect exterior
of carton for evidence of rough handling in shipment. Unpack carefully after moving equipment
to approximate location. If damage to contents is
found, report the damage immediately to the delivering agency.
Codes and local utility requirements governing the
installation of gas fired equipment, wiring, plumbing,
and flue connections must be adhered to. In the absence of local codes, the installation must conform with
latest edition of the National Fuel Gas Code ANSI
Z223.1 • National Installation Code, CAN/CGA B149.1.
The latest code may be obtained from the American Gas
Association Laboratories, 400 N. Capitol St. NW,
Washington D.C. 20001.
1-800-699-9277 or www.aga.org
These furnaces have been classified as CATEGORY IV
furnaces in accordance with latest edition of ANSI
Z21.47 • CAN/ CGA 2.3 standards.
Category IV furnaces operate with positive vent static
pressure and with a flue loss less than 17 percent.
These conditions require special venting systems, which
must be gas tight and water tight. These Category IV
Direct Vent furnaces are approved for installation in
Manufactured/ Mobile housing when used with
BAYMFGH100A.
Contents
INSTALLATION INSTRUCTIONS
General Installation Instructions3
Location and Clearances4
Outline Drawings5
Upflow Installation7
Downflow Installation7
Horizontal Installation7
Air For Combustion and Ventilation8
Duct Connections10
Return Air Filters11
General Venting Instructions16
Venting Material16
Venting Tables18
Horizontal Venting21
Venting Through The Wall21
Venting Through The Roof25
Downward Venting25
Venting Through a Masonry Chimney26
Condensate Drain Instructions27
Electrical Connections29
Field Wiring Diagrams29
Gas Piping32
Combustion Input Checks33
Start Up and Adjustment35
Preliminary Inspections35
Lighting Instructions36
Sequence Of Operation36
Control And Safety Switch Adjustments36
Airflow Adjustment37
Abnormal Conditions37
IFC Error Flash Code39
!
CAUTION
To prevent shortening its service life, the furnace
should not be used as a “Construction Heater” during
the finishing phases of construction until the requirements listed in item 9, a-g of the safety section of this
publication have been met. Condensate in the presence of chlorides and fluorides from paint, varnish,
stains, adhesives, cleaning compounds, and cement
create a corrosive condition which may cause rapid deterioration of the heat exchanger.
!
CAUTION
Do NOT install the furnace in a corrosive or contaminated atmosphere.
18-CD19D5-253
Page 4
Installer’s Guide
LOCATION AND CLEARANCES
The location of the furnace is normally selected by the
architect, the builder, or the installer. However, before
the furnace is moved into place, be sure to consider the
following requirements:
1. Is the location selected as near the vent and as centralized for heat distribution as practical?
2. Do all clearances between the furnace and enclosure equal or exceed the minimums shown in the
Table 1.
3. Is there sufficient space for servicing the furnace
and other equipment? A minimum of 24 inches
front accessibility to the furnace must be provided.
Any access door or panel must permit removal of
the largest component.
4. Are there at least 3 inches of clearance between the
furnace front panel and any closed panel or door
provided?
5. Are the vent pipe and combustion air inlet pipe
within vent table lengths? Will the pipes remain unobstructed?
6. Allow sufficient height in supply plenum above or
below the furnace to provide for cooling coil installation if the cooling coil is not installed at the time of
this furnace installation.
7. A furnace shall be installed so electrical components
are protected from water.
8. If the furnace is installed in a residential garage,
it must be installed so that the burners and the ignition source are located not less than 18 inches (46
cm) above the floor and the furnace must be located
or protected to avoid physical damage from vehicles.
IMPORTANT:
The furnace must be installed level. The only allowable
variation would be slightly to the left and/or forward in upflow installations or slightly toward the front in horizontal installations. This is necessary for proper condensate drainage.
418-CD19D5-25
Page 5
18-CD19D5-255
Installer’s Guide
*UC1 OUTLINE DRAWING
(ALL DIMENSIONS ARE IN INCHES)
Page 6
618-CD19D5-25
Installer’s Guide
*DC1 DOWNFLOW/ HORIZONTAL OUTLINE DRAWING
(ALL DIMENSIONS ARE IN INCHES)
Page 7
Installer’s Guide
▲
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
UPFLOW INSTALLATION
Standoffs and screws (See Figure 1) are included with
the cased coils for attachment to the furnace. There are
clearance alignment holes near the bottom of the coil
wrapper. Drill screws are used to engage the furnace
top flanges. The standoff is inserted into the cabinet
alignment hole. The drill screws are inserted through
the standoffs then screwed into the furnace flange.
The coil is always placed downstream of the furnace airflow.
1
CASED
UPFLOW
FURNACE
STANDOFFS (4)
COIL
STANDOFFS
(BOTH SIDES)
DRILL SCREWS (4)
FOR VERTICAL
INSTALLATIONS:
SCREWS
(BOTH SIDES)
TABLE 1
CABINET
WIDTH
RETURN
DUCT WIDTH
17-1/2"16-1/4"16-5/8"20-1/8"15-5/8"19-3/8"
21"19-3/4"20-1/8"20-1/8"19-1/8"19-3/8"
24-1/2"23-1/4"23-5/8"20-1/8"22-5/8"19-3/8"
FLOOR OPENING PLENUM OPENING
"A""B""C""D"
HORIZONTAL INSTALLATION
The coil and furnace must be fully supported when used
in the horizontal position. It is always recommended
that an auxiliary drain pan be installed under a horizontally installed evaporator coil or 90% gas furnace. Connect the auxiliary drain line to a separate drain line (no
trap is needed in this line).
Three brackets (with screws) are included with downflow furnaces for installation to stabilize and secure the
furnace and 2/4TXC cased coil in the horizontal posi-tion. See Figure 3.
IMPORTANT:
The 2/4TXC cased coil must be placed downstream of the
furnace. In horizontal installations, the apex of the coil
may point either toward or away from the furnace. See
the 2/4TXC coil Installer's Guide for more details.
4
CASED COIL CONNECTION
BRACKET FOR DOWNFLOW
FURNACE IN HORIZONTAL
DOWNFLOW ONLY
DOWNFLOW INSTALLATIONS
!
WARNING
Do NOT install the furnace directly on carpeting, tile or
other combustible material other than wood flooring.
For vertical downflow application, subbase (BAYBASE-
205) must be used between the furnace and combustible flooring. When the downflow furnace is installed
vertically with a cased coil, a subbase is not required.
Required floor opening:
2
SUBBASE CROSS SECTION
2345678901234567890123456789012123456789012345
2345678901234567890123456789012123456789012345
2345678901234567890123456789012123456789012345
2345678901234567890123456789012123456789012345
3
2345678901234567890123456789012123456789012345
2345678901234567890123456789012123456789012345
2345678901234567890123456789012123456789012345
2345678901234567890123456789012123456789012345
2345678901234567890123456789012123456789012345
FURNACE
2345678901234567890123456789012123456789012345
2345678901234567890123456789012123456789012345
2345678901234567890123456789012123456789012345
2345678901234567890123456789012123456789012345
2345678901234567890123456789012123456789012345
2345678901234567890123456789012123456789012345
2345678901234567890123456789012123456789012345
2345678901234567890123456789012123456789012345
2345678901234567890123456789012123456789012345
FRONT
18-CD19D5-257
A (width)
B (depth)
The cased coil is secured to the furnace and both the
furnace and the cased coil must be properly supported.
The brackets mount using the rear screws on the coil
case and use the screws provided to secure the bracket
to the furnace. The remaining bracket is placed as close
to center as possible (horizontally) between the coil case
front and the furnace bottom channel (for downflow/
horizontal furnace). Use four of the screws provided to
secure the bracket. The upflow furnace, converted to
horizontal, aligns and attaches the TXC coil as in Figure 1. However, the coil requires additional support.
The furnace may be installed in an attic or crawl space
in the horizontal position by placing the furnace on theleft side (as viewed from the front in the vertical position). The horizontal furnace installation in an attic
should be on a service platform large enough to allow
for proper clearances on all sides and service access to
the front of the furnace (See Figure 5 & Clearance
Table). Line contact is only permissible between lines
formed by intersections of the top and two sides of the
furnace casing and building joists, studs, or framing.
D
C
The furnace may be placed horizontally in a crawl space
on a pad or other noncombustible material which will
raise the unit for sufficient protection from moisture.
Page 8
Installer’s Guide
5
UPFLOW/
HORIZONTAL
SHOWN
The furnace must be supported at both ends and
the middle when installed horizontally.
The furnace must also be elevated a minimum of 6
inches to allow clearance for the condensate drain
to exit the cabinet in the horizontal position.
The horizontal furnace may also be suspended from the
joists using 3/8" all-thread rods with pieces of angle iron
underneath the furnace to form a hanging rack at both
ends and the midpoint. The rods need to be of sufficient
length to allow for proper clearances from combustible
materials. The angle iron needs to be at least 32" in
length to allow for access to service panels.
AIR FOR COMBUSTION AND VENTILATION
If these furnaces are installed in a nondirect vent capacity
then the adequate flow of combustion and ventilating
air must not be obstructed from reaching the furnace.
Air openings provided for combustion air must be kept
free of obstructions which restrict the flow of air. Airflow restrictions affect the efficiency and safe operation
of the furnace. Keep this in mind should you choose to
remodel or change the area which contains your furnace. Furnaces must have a free flow of air for proper
performance.
6
50 CU. FT. OR MORE
PER 1000 BTU/ HR. INPUT
ALL EQUIP. INSTALLED
UNCONFINED
Provisions for combustion and ventilation air shall be
made in accordance with latest edition of Section 5.3,
Air for Combustion and Ventilation, of the National
Fuel Gas Code, ANSI Z223.1 — CAN/ CGA B149.1 or applicable provisions of the local building codes. Special
conditions created by mechanical exhausting of air and
fireplaces must be considered to avoid unsatisfactory
furnace operation.
OUTSIDE AIR IS RECOMMENDED
The use of indoor air for most applications is acceptable,
unless there is the presence of corrosive chemicals
or contamination. Certain types of installation will
require the use of outside air for combustion.
The following types of installations will require use of
OUTDOOR AIR for combustion, due to chemical exposures:
* Commercial buildings
* Buildings with indoor pools
* Furnaces installed in “confined” laundry rooms
* Furnaces installed in “confined” hobby or craft rooms
* Furnaces installed near chemical storage areas.
Exposure to the following substances in the combustion
air supply will also require OUTDOOR AIR for combustion:
* Permanent wave solutions
* Chlorinated waxes and cleaners
* Chlorine based swimming pool chemicals
* Water softening chemicals
* Deicing salts or chemicals
* Carbon Tetrachloride
* Halogen type refrigerants
* Cleaning solvents (such as perchloroethylene)
* Printing inks, paint removers, varnish, etc.
* Hydrochloric acid
* Cements and glues
* Antistatic fabric softeners for clothes dryers
* Masonry acid washing materials
Furnace locations may be in a “confined space” or an
“unconfined space”.
Unconfined space is defined in Figure 6. These spaces
may have adequate air by infiltration to provide air for
combustion and ventilation. Buildings with tight
construction (for example, weather stripping, heavily
insulated, caulked, vapor barrier, etc.), may need additional air to be provided as described for confined space.
Confined spaces are installations with less than 50 cu.
ft. of space per 1000 BTU/hr input from all equipment
installed. Air for combustion and ventilation requirements can be supplied from inside the building as in
Figure 8 or from the outdoors, as in Figure 9.
818-CD19D5-25
Page 9
Installer’s Guide
TABLE 2
MINIMUM AREA IN SQUARE FEET
FOR UNCONFINED SPACE INSTALLATIONS
FURNACE
MAXIMUM BTUH
INPUT RATING
60,000
80,000
100,000
120,000
MINIMUM AREA IN SQUARE FEET
WITH 8 FT. CEILING
OF UNCONFINED SPACE
375
500
625
875
7
CONFINED
SPACE
1. All air from inside the building as in Figure 8: The
confined space shall be provided with two permanent openings communicating directly with an additional room(s) of sufficient volume so that the combined volume of all spaces meets the criteria for an
unconfined space. The total input of all gas utilization equipment installed in the combined space
shall be considered in making this determination.
Refer to Table 2 for minimum open areas requirements.
2.
All air from outdoors as in Figure 9: The confined
space shall be provided with two permanent openings, one commencing within 12 inches of the top
and one commencing within 12 inches of the bottom of the enclosure. The openings shall communicate directly, or by ducts, with the outdoors or
spaces (crawl or attic) that freely communicate with
the outdoors. Refer to Table 3, for minimum open
areas requirements.
TABLE 3
MINIMUM FREE AREA IN SQUARE INCHES
EACH OPENING (FURNACE ONLY)
8
9
Furnace
Maximum
BTUH/INPUT
Rating
60,000
80,000
100,000
120,000
18-CD19D5-259
Air
From
Inside
100
100
100
120
Vertical
Duct
Air From Outside
Horizontal
15
20
25
30
Duct
30
40
50
60
Page 10
Installer’s Guide
▲
▲
DUCT CONNECTIONS
Air duct systems should be installed in accordance with
standards for air conditioning systems, National Fire
Protection Association Pamphlet No.90. They should be
sized in accordance with ACCA Manual D or whichever
is applicable.
Central furnaces, when used in connection with cooling
units, shall be installed in parallel or on the upstream
side of the cooling coil to avoid condensation in the heat
exchanger. With a parallel flow arrangement, the dampers or other means used to control flow of air shall be
adequate to prevent chilled air from entering the furnace, and if manually operated, must be equipped with
means to prevent operation of either unit unless the
damper is in full heat or cool position.
On any job, flexible connections of nonflammable material may be used for return air and discharge connections
to prevent transmission of vibration. Though these units
have been specifically designed for quiet, vibration free
operation, air ducts can act as sounding boards and could,
if poorly installed, amplify the slightest vibration to the
annoyance level.
When the furnace is located in a utility room adjacent
to the living area, the system should be carefully designed with returns to minimize noise transmission
through the return air grille. Although these furnaces
are designed with large blowers operating at moderate
speeds, any blower moving a high volume of air will
produce audible noise which could be objectionable
when the unit is located very close to a living area. It is
often advisable to route the return air ducts under the
floor or through the attic. Such design permits the installation of air return remote from the living area
(i.e. central hall).
When the furnace is installed so that the supply ducts
carry air circulated by the furnace to areas outside the
space containing the furnace, the return air shall also
be handled by a duct(s) sealed to the furnace and terminating outside the space containing the furnace.
RETURN AIR DUCT CONNECTION
NOTE:
On upflow 5 or 6 ton airflow models where the
airflow requirement exceeds 1800 CFM - Models will
require return air openings and filters on: (1) both
sides; or (2) one side and the bottom; or (3) just the
bottom.
All return air duct systems should provide for installation of return air filters.
1. Determine the appropriate position to set the
furnace in order to connect to the existing supply
and return ductwork.
2. For side return installations on upflow models,
remove the insulation around the opening in the
blower compartment.
1018-CD19D5-25
3. The side panels on upflow furnaces include locating
notches which may be used as guides for cutting an
opening for return air. Refer to Figure 11 and the
outline drawing on page 5 for duct connection
dimensions for various furnaces.
4. If a 3/4" flange is to be used for attaching the air
inlet duct, add to cut where indicated by dashed
lines in Figure 11. Cut corners diagonally and bend
outward to form flange.
5. If flanges are not required, and a filter frame is
installed, cut along knockout guidelines.
6. Upflow Furnaces: Use the optional filter rack on
either side or on the bottom if the filter is to be
used within the furnace cabinet.
When the upflow furnace is installed in the horizontal right or left application and a return duct is
attached to the top side as shown in Figure 10,
install the filter in a remote location.
!
WARNING
Do not install the filter in the return duct directly above the
furnace in horizontal applications. Install the filter remotely.
Installing the filter directly above the furnace in horizontal
applications may cause property damage, serious injury or
death.
!
WARNING
TO PREVENT INJURY OR DEATH DUE TO CONTACT
WITH MOVING PARTS, TURN THE POWER TO THE
FURNACE OFF BEFORE SERVICING FILTERS.
Do not install the filter in the return duct directly
above the furnace in horizontal applications.
When the upflow furnace is installed in the horizontal right or left application and a close coupled (less
than 36") return duct is attached to the bottom side
of the furnace as shown in Figure 10, securely
attach a 1/2" mesh metal hardware cloth protective
e screen to the inside bottom of the filter grill to
prevent personal injury from contacting
moving parts when reaching into the return
opening to replace the filter.
Close coupled (less than 36") return (filter directly
beneath bottom side return) is not recommended
due to noise considerations.
Downflow Furnaces: Brackets are factory
supplied to mount filters in the return air duct
work.
7. Connect the duct work to the furnace. See Outline
Drawing (pages 5&6) for supply and return duct size
and location. Flexible duct connectors are recommended to connect both supply and return air ducts
to the furnace.
Page 11
Installer’s Guide
REMOVE FILTER FROM UPFLOW
FURNACE WHEN RETURN DUCT IS
ATTACHED TO FURNACE TOP SIDE
(HORIZONTAL LEFT OR RIGHT
APPLICATIONS) AS SHOWN.
Close coupled (less than 36")
return (filter directly beneath bottom
side return) not recommended due to
noise considerations. If used, securely
attach 1/2" mesh metal hardware cloth
protective screen to the inside bottom of
filter grill.
If only the front of the furnace is accessible, it is
recommended that both supply and return air
plenums are removable.
8. When replacing a furnace, old duct work should be
cleaned out. Thin cloths should be placed over the
registers and the furnace fan should be run for
10 minutes. Don’t forget to remove the cloths
before you start the furnace.
FILTER
0
RETURN AIR FILTERS
(Filter and filter rack are not supplied with unit)
TYPICAL UPFLOW RETURN AIR FILTER INSTALLATIONS
These furnaces require high velocity type air filters.
The optional filters may be located within the furnace
blower compartment for UPFLOW furnaces in either a
BOTTOM or SIDE (left side or right side) return air
inlet. Some optional filters may need to be trimmed for
side or bottom filter use.
The furnace and the blower filter rack installation can
be seen in Figure 12 & 13.
The optional furnace filter in the bottom or side configuration can be removed by simply turning the two
latches on the blower door and tilting the door forward.
The filter rails are spring loaded for automatic adjustment to allow standard size, locally obtainable replacement filters. The filter rack itself slides to adjust to the
required width needed for bottom or side return.
TABLE 4
MODELS
NUMBERS
*UC1B040A9241A
*UC1B060A9361A
*UC1B080A9421A
*UC1C100A9481A21"1 - 20" X 25" X 1"
*UC1D100A9601A##
*UC1D120A9601A##
*DC1B040A9241A
*DC1B060A9361A
*DC1B080A9421A
*DC1C100A9481A21"2 - 16" X 20" X 1"
*DC1D120A9601A24-1/2"2 - 16" X 20" X 1"
## - Requires filters on 2 sides OR 1 side and bottom
filter or just the bottom
CABINET
WIDTH
17-1/2"1 - 17" X 25" X 1"
24-1/2"1 - 24" X 25" X 1"
17-1/2"2 - 14" X 20" X 1"
FILTER
QTY & SIZE
NOTE:
On upflow 5 or 6 ton airflow models where the
airflow requirement exceeds 1800 CFM - Models will
require return air openings and filters on: (1) both
sides; or (2) one side and the bottom; or (3) just the
bottom.
q
LOCATING
NOTCHES
PROVIDED
FOR SIDE
RETURN
CUTOUT
*
*
*
*
SEE OUTLINE DRAWING
*
18-CD19D5-2511
CUT OUT
FOR
SIDE
FILTER
FRONT
of Furnace
Page 12
Installer’s Guide
w
Airflow
NOTE: The narrow 14.5" width furnace cabinet prevents use
of the filter rack for right side return. Pre-drill clearance
holes and then attach filter clips with the screws provided.
The filter clip with the leaf spring mounts in the rear of the
cabinet
OPTIONAL FILTER RACK INSTALLATION FOR BOTTOM
RETURN
With the filter removed, the filter rack is compressed and
then inserted into the bottom of the furnace. The retaining
screw/pin on each side inserts into engagement holes at the
bottom of the furnace cabinet side. See Figures 13, 14 & 16.
NOTE: Remove the bottom front channel to install the filter
rack in the 14-1/2" width cabinet furnaces.
t
e
r
Airflow
BOTTOM FILTER RACK INSTALLATION
Blower Deck
Engagement
Hole
ENGAGEMENT
HOLE DETAIL
(Typical both sides
and blower deck)
y
Furnace
Cabinet
Side
VIEW
Filter
Rack
Optional Filter Rack Accessory Kit
BAYRACK960A
1218-CD19D5-25
Engagement Hole
For
Filter Rack
Installation With
Bottom Return
Filter Rack
Retaining
Screw/Pin
Page 13
Installer’s Guide
Airflow
Airflow
TABLE 5
Cabinet Width Left Side BottomRight Side
14.5X
17.5XXX
21XXX
24.5XXX
1. UD060C/R936K0 has 10x7 blower which requires use of alternate
filter clips for left side filter. "K1" and later use the filter rack.
2. Remove bottom front channel to install or reposition filter rack.
X - All Models
OPTIONAL FILTER RACK INSTALLATION FOR SIDE
RETURN AIR ON UPFLOW FURNACES (Left or Right)
If side air return is desired, the following instructions should
be used:
a. Open or remove the blower door.
b. Leave the bottom panel in place. (Some models
require field supplied bottom panels.)
c. After the side cutout is made following the directions
in the “Return Air Duct Connections” section on
pages 8 and 9; compress the filter rack and reinstall in
the side of the furnace. Confirm that the upper
retaining pin/screw locks into the engagement hole in
the blower deck and the lower pin/screw rests against
the side of the bottom panel. See Figures 14, 15, &
17-20.
d. Install the furnace filter on the side. See Figures 14,
15, & 17-20.
u
Furnace
Cabinet
Side
1
BOTTOM ENGAGEMENT
X2Use Alternate Filter Clips Only
Filter Rack
Retaining
Screw/Pin
Filter
Rack
o
Typical Upflow Left Side Return Filter Rack Installation
p
SIDE
CUTOUT
RETAINING
PIN
(Both Sides)
SPRINGS
Airflow
FILTER
RACK
RAILS
Airflow
BOTTOM
PANEL
INSTALLED
SIDE
CUTOUT
RETAINING
PIN
(Both Sides)
SPRINGS
Engagement Hole
For
Installation With
Bottom Return
i
BLOWER
DECK
Furnace
Cabinet
Side
Filter Rack
Engagement Hole
For
Filter Rack
Installation With
Side
Return
Filter Rack
Retaining
Screw/Pin
Bottom Panel
Furnace
Blower
Deck
Filter
Rack
Assembly
BOTTOM
PAN EL
INSTALLED
Typical Upflow Right Side Return Filter Rack Installation
FILTER
RACK
RAILS
a
Airflow
Optional door kit
BAYFLTR206
Typical Horizontal Filter Installation
18-CD19D5-2513
Page 14
Installer’s Guide
RETURN AIR FILTERS FOR UPFLOW FURNACE
IN HORIZONTAL CONFIGURATION
When the Upflow Furnace is installed in a horizontal configuration, the filter must never be installed inside or outside the
cabinet directly above the blower assembly. See Figure 10
(page 11). Remote filter grilles may be used for homeowner
convenience or the filters may be installed in the duct work
upstream of the furnace. See Figures 10 (page 11) and 21
(page 13).
1. Determine the location to be used. The furnace cabinet
has dimples for location of the alternate furnace clips
(Side return only). Pre-drill clearance holes with a
3/16" drill. Bottom return holes are pre-drilled.
2. Install the clips in front and rear of the desired location
using the screws provided. The filter clip with the leaf
spring mounts in the rear of the cabinet. See Figure 22.
s
REAR
SIDE
CUT-OUT
INSTALLING THE OPTIONAL FILTER
The filter may need to be cut to fit the unit depending on the
location of the return air filter.
A score line and the words “CUT HERE” are located on the
end of the filter. If your application requires cutting the filter,
do so as indicted by the score mark.
TABLE 6
UNIT
SIZE
RETURN AIR
BOTTOMSIDE
14-1/2"CUT ON LINE DO NOT CUT
17-1/2"DO NOT CUT DO NOT CUT
21"DO NOT CUT CUT ON LINE
24-1/2"DO NOT CUT CUT ON LINE
TYPICAL DOWNFLOW FURNACE
RETURN AIR FILTER INSTALLATIONS
d
ALTERNATE FILTER
CLIPS LOCATION
Optional horizontal filter conversion kits are BAYFLTR203
for 17 1/2" width cabinets, BAYFLTR204 for 21" width
cabinets, and BAYFLTR205 for 24" width cabinets. These
include filters and brackets necessary for horizontal filters.
In addition, optional door kit BAYFLTR206 is also available.
See Figures 21 and 24.
Airflow
f
Airflow
Optional door kit
BAYFLTR206
1418-CD19D5-25
Two high velocity type air filters are required for each downflow furnace. Downflow furnace filters must be located
outside the furnace cabinet. Typical installations are shown
in Figures 23 and 24. Tables 7 and 8 (page 13) provide
information for installation of the filter retaining brackets
shipped with downflow furnaces.
* Location dimension is from end of duct to the screw holes for the bracket.
FURNACE SURFACE
SIDES0"1"0"
BACK0"3"6"
TOP1"1"1"
FRONT3"3"18"
VENT0"0"0"
NOTE
: CLEARANCE REQUIRED AT TOP OF PLENUM IS 1"
FILTER
SIZE
TABLE 8
MINIMUM CLEARANCE FROM COMBUSTIBLE MATERIALS FOR
UPFLOW/HORIZONTAL AND DOWNFLOW/ HORIZONTAL FURNACES
FILTER BRACKET
LOCATION *
UNIT LOCATION
VERTICAL
CLOSET
HORIZONTAL
CLOSET
Installer’s Guide
HORIZONTAL
ALCOVE / ATTIC
18-CD19D5-2515
Page 16
Installer’s Guide
GENERAL VENTING
THIS FURNACE MUST BE VENTED TO THE OUTDOORS.
THESE FURNACES ARE INDUCED DRAFT VENTED
AND MUST NOT BE CONNECTED TO ANY VENT
SERVING ANOTHER APPLIANCE. PLEASE NOTE
THAT THESE FURNACES USE POSITIVE-PRES-SURE VENT SYSTEMS.
Proper venting is essential to obtain maximum efficiency from a condensing furnace. Proper installation of
the vent system is necessary to assure drainage of the
condensate and prevent deterioration of the vent
system.
American Gas Association has certified the design of
condensing furnaces for a minimum of 0" clearance
from combustible materials with a single wall plastic
vent pipe.
The recommended system is assembled from 2", 2-1/2",
or 3" plastic pipe and fittings (See Table 9, page 17).
Where the system is routed to the outdoors through an
existing masonry chimney containing flue products
from another gas appliance, or where required by local
codes, then 3" venting of Type 29-4C stainless steel
must be used in place of PVC material.
These furnaces have been classified as CATEGORY IV
furnaces in accordance with the latest edition of
ANSI Z21.47 • CAN/ CGA-2.3 Standards. Category IV
furnaces operate with positive vent pressure and with a
vent gas temperature less than 140°F above the
dewpoint. These conditions require special venting systems, which must be gas tight and water tight.
NOTE:
When an existing furnace is removed from a venting
system serving other gas appliances, the venting system is likely to be too large to properly vent
maining attached appliances.
The following steps shall be followed with each appliance remaining connected to the common venting system placed in operation, while the other appliances remaining connected to the common venting system are
not in operation.
1. Seal any unused openings in the common venting
system.
2. Visually inspect the venting system for proper size
and horizontal pitch and determine there is no
blockage or restriction, leakage, corrosion or other
deficiencies which could cause an unsafe condition.
the re-
3. Insofar as is practical, close all building doors and
windows and all doors between the space in which
the appliances remaining connected to the common
venting system are located and other spaces of the
building. Turn on clothes dryers and any appliances
not connected to the common venting system. Turn
on any exhaust fans, such as range hoods and bathroom exhausts, so they will operate at maximum
speed. Do not operate a summer exhaust fan, close
fireplace dampers.
4. Follow the lighting instructions. Place the appliance
being inspected in operation. Adjust thermostat so
appliance will operate continuously.
5. Test for spillage at the draft hood relief opening after 5 minutes of main burner operation. Use the
flame of a match or candle, or smoke from a cigarette, cigar, or pipe.
6. After it has been determined that each appliance remaining connected to the common venting system
properly vents when tested as outlined above, return door, windows, exhaust fans, fireplace dampers
and any other gas-burning appliance to their previous conditions of use.
If improper venting is observed during any of the above
tests, the remaining common venting system must be
corrected. Correction of the remaining common vent
system should be done by referring to the latest edition
of the National Fuel Gas Code (ANSI Z223.1) • CAN/
CGA B149.1 Installation Codes or “Exhibit J” of
ANSI Z21.47 • CAN/CGA-2.3 Standards. The following
are general steps to be used to correct or resize a remaining vent system when a furnace which may not be
common vented is removed from the system:
a. Determine the Btu per hour input of all remain-
ing appliances attached to the venting system.
b. Determine the diameter, rise, and lateral of the
existing venting system, as well as quantity and
type of bends.
c. Use the appropriate tables in the latest edition of
the National Fuel Gas Code (ANSI Z223.1 •
CAN/CGA B149.1 Installation Codes or “Exhibit
J” of ANSI Z21.47 • CAN/CGA-2.3 Standards. “Exhibit J” includes examples and drawings of typical
venting systems.
PVC VENT FITTING MATERIAL
These fittings are available from your Gas Furnace
Distributors.
Straight Pipe Sections, Couplings, 45° Elbows, 60° Elbows, 90° Elbows, Vent or Sanitary Tee, or other necessary fittings may be 2", 2½", 3", or 4" diameter. The allowable materials are shown in Table 9.
1618-CD19D5-25
NOTE:
Follow venting instructions carefully when using PVC
cement.
Page 17
Installer’s Guide
IMPORTANT:
These furnaces may be installed as Direct Vent (sealed
combustion) or as Nondirect vent (single pipe). The furnaces are shipped DIRECT VENT with sealed combustion.
For DIRECT VENT APPLICATION: The furnaces must be
vented to the exterior of the house and combustion air
MUST come through the inlet air pipe FROM OUTSIDE
AIR.
For NONDIRECT VENT APPLICATION: The furnace shall
be vented to the exterior of the house, but combustion air
may enter from the surrounding area as long as combustion air requirements are met. (See AIR FOR COMBUSTION AND VENTILATION)
VENT FITTING MATERIAL – PLASTIC
Gas and liquid tight single wall vent fittings, designed
for resistance to corrosive flue condensate, MUST be
used throughout.
Listed in Table 10 & 11 are 2", 2½", 3", and 4" size fittings
Procedure for Cementing Joints:
1. Cut pipe square, remove ragged edges and burrs.
Chamfer end of pipe, then clean fitting socket and
pipe joint area of all dirt, grease, moisture or chips.
2. After checking pipe and socket for proper fit, wipe
socket and pipe with cleaner-primer. Apply a liberal
coat of primer to inside surface of socket and outside of pipe.
DO NOT ALLOW PRIMER TO DRY BEFORE APPLYING CEMENT.
3. Apply a thin coat of cement evenly in the socket.
Quickly apply a heavy coat of cement to the pipe
end and insert pipe into fitting with a slight twisting
movement until it bottoms out.
4. Hold the pipe in the fitting for 30 seconds to pre-
vent tapered socket from pushing the pipe out of
the fitting.
that meet these requirements. The materials listed are
various grades of PVC and ABS plastic.
* - Allowable temperatures based on classifications covered in ASTM D4396 [Deflection Temps Under Load (264 PSI)]
** - Allowable temperatures based on classifications covered in ASTM D1784 [Deflection Temps Under Load (264 PSI)]
*** - Allowable temperatures based on classifications covered in ASTM D3965 [Deflection Temps Under Load (264 PSI)]
PIPE JOINTS: All joints must be fastened and sealed to
prevent escape of combustion products into the building.
NOTE:
It is recommended that the first joints from the furnace
be connected and sealed with high temperature RTV.
This will enable the pipes to be removed later without
cutting.
Be sure to properly support these joints.
BONDING OF PVC
Commercially available solvent cement must be used
to join the pipe and fittings. Follow instructions on the
container carefully.
18-CD19D5-2517
5. Wipe all excess cement from the joint with a rag.
Allow 15 minutes before handling. Cure time varies
according to fit, temperature and humidity.
Important:
Products installed in Canada must use vent systems
that are certified to the Standard for Type BH Gas
Venting Systems (ULC S636) for Class II-A venting
systems (up to 65 degrees C). Components of the vent
system must not be interchanged with other vent systems or unlisted pipe or fittings. Plastic components,
specified primers, and glues must be from a single
system manufacturer and not intermixed with other
system manufacturer’s vent system parts. In addition,
the first three feet of the vent pipe must be visible for
inspection.
Page 18
Installer’s Guide
NONDIRECT VENT (1 PIPE SYSTEM) -MAXIMUM TOTAL
g
VENT AND INLET AIR CONNECTIONS
Seal VENT PIPE
with RTV sealant
Front of Furnace
Seal INLET AIR PIPE
with RTV sealant
IMPORTANT:
All joints must be water tight. Flue condensate is somewhat acidic, and leaks can cause equipment damage.
Connection of the pipe and collar of the combustion
air inlet should just be a friction fit. It is recommended
that the inlet air joint be sealed with RTV type sealant
to allow the joint to be separated for possible future service. The inlet and vent pipes must be properly supported throughout the entire length.
Connection of the vent pipe to the vent collar should
also be accomplished using RTV type sealant. This type
sealant provides a connection which remains flexible
and can be separated in the future if service needs require the removal of the vent pipe for service or clearance.
NOTE:
To ensure proper operation at the vent lengths indicated, the combustion air inlet and vent terminals
should be in the same pressure zone. Terminating the
vent and inlet in different pressure zones will change
the maximum vent lengths and may cause nuisance
tripping of the pressure switch(es). The amount of
change can not be predicted. The selection of the inlet
and outlet terminal locations are the responsibility of
the designer/ installer. If the installer chooses separate
pressure zones for the terminals, the combustion air
inlet termination must be in the higher (more positive)
pressure zone.
UPFLOW/ HORIZONTAL VENTING TABLE
TABLE 10
MAXIMUM VENT LENGTH:
DIRECT VENT (2 PIPE SYSTEM) -
MAXIMUM TOTAL EQUIVALENT FEET FOR
VENT AND INLET AIR PIPES (See Notes)
2" PIPE
MODEL
*UC1B040A9241A
*UC1B060A9361A
*UC1B080A9421A
*UC1C080A9601A
*UC1C100A9481A
*UC1D100A9601A
*UC1D120A9601A
NOTES: * - First letter may be "A" or "T"
1. The INLET AIR of one pipe systems require the installation of a 90° elbow (to prevent dust and debris from falling straight into thefurnace) and a 2 foot
horizontal or vertical straight pipe section connected before or after the elbow.
2. DO NOT MIX PIPE DIAMETERS IN THE SAME LENGTH OF PIPE OUTSIDE THE FURNACE CABINET (Except adapters at the top of the furnace).
If different inlet and vent pipe sizes are used, the vent pipe must adhere to the maximum length limit shown in the table above (See Note 7 below for exception).
The inlet pipe can be of a larger diameter, but never smaller than the vent pipe.
3. MAXIMUM PIPE LENGTHS MUST NOT BE EXCEEDED! THE LENGTH SHOWN IS NOT A COMBINED TOTAL, IT IS THE MAXIMUM LENGTH OF EACH
(Vent or Inlet air pipes in two pipe systems).
4. One standard radius 90° elbow is equivalent to 12' of 4" pipe; one SHORT radius 90° elbow is equivalent to 10' of 3" pipe and one LONG radius elbow is
equivalent to 6' of 3" pipe. One SHORT/LONG radius 90° elbow is equivalent to 7½' of 2½" pipe, & 5' of 2" pipe. Two 45° elbows equal one 90°elbow.
5. The termination tee or bend must be included in the total number of elbows. If the BAYVENT100 termination kit is used, the equivalent length of pipe is 5 feet.
There is zero equivalent length for the BAYVENT200.
6. Pipe adapters are field supplied.
7. 4" pipe may be reduced to 3" for termination with BAYAIR30AVENTA or BAYVENT200 without additional length restriction.
& FITTINGS
6080100130508080130
6080100130508080130
5080100130408080130
5080100130408080130
NOT ALLOWED40100130NOT ALLOWED4080130
NOT ALLOWED40100130NOT ALLOWED4080130
NOT ALLOWED1560130NOT ALLOWED2570130
2-1/2" PIPE
& FITTINGS
3" PIPE
& FITTINGS
4" PIPE
& FITTINGS
2" PIPE
& FITTINGS
EQUIVALENT FEET FOR
VENT PIPE ONLY (See Notes)
2-1/2" PIPE
& FITTINGS
3" PIPE
& FITTINGS
4" PIPE
& FITTINGS
1818-CD19D5-25
Page 19
Installer’s Guide
DOWNFLOW/ HORIZONTAL VENTING TABLE
TABLE 11
MAXIMUM VENT LENGTH:
DIRECT VENT (2 PIPE SYSTEM) -
MAXIMUM TOTAL EQUIVALENT FEET FOR
VENT AND INLET AIR PIPES (See Notes)
MODEL
*DC1B040A9241A
*DC1B060A9361A
*DC1B080A9421A
*DC1C100A9481A
*DC1D120A9601A
NOTES: * - First letter may be "A" or "T"
1. The INLET AIR of one pipe systems require the installation of a 90° elbow (to prevent dust and debris from falling straight into the furnace) and a 2 foot
horizontal or vertical straight pipe section connected before or after the elbow.
2. DO NOT MIX PIPE DIAMETERS IN THE SAME LENGTH OF PIPE OUTSIDE THE FURNACE CABINET (Except adapters at the top of the furnace).
If different inlet and vent pipe sizes are used, the vent pipe must adhere to the maximum length limit shown in the table above (See Note 7 below for exception).
The inlet pipe can be of a larger diameter, but never smaller than the vent pipe.
3. MAXIMUM PIPE LENGTHS MUST NOT BE EXCEEDED! THE LENGTH SHOWN IS NOT A COMBINED TOTAL, IT IS THE MAXIMUM LENGTH OF EACH
(Vent or Inlet air pipes in two pipe systems).
4. One standard radius 90° elbow is equivalent to 12' of 4" pipe; one SHORT radius 90° elbow is equivalent to 10' of 3" pipe and one LONG radius elbow is
equivalent to 6' of 3" pipe. One SHORT/LONG radius 90° elbow is equivalent to 7½' of 2½" pipe, & 5' of 2" pipe. Two 45° elbows equal one 90°elbow.
5. The termination tee or bend must be included in the total number of elbows. If the BAYVENT100 termination kit is used, the equivalent length of pipe is 5 feet.
There is zero equivalent length for the BAYVENT200.
6. Pipe adapters are field supplied.
7. 4" pipe may be reduced to 3" for termination with BAYAIR30AVENTA or BAYVENT200 without additional length restriction.
2" PIPE
& FITTINGS
6080100130508080130
5080100130508080130
4580100130408080130
NOT ALLOWED80100130NOT ALLOWED8080130
NOT ALLOWED1560130NOT ALLOWED2570130
2-1/2" PIPE
& FITTINGS
3" PIPE
& FITTINGS
4" PIPE
& FITTINGS
& FITTINGS
SINGLE PIPE VENTING
UPFLOW FURNACE
A (0-2') or greater
B (0-2') or greater
A+B = 2' minimum
Vertical clearance to ventilated soffit located above the
D=
terminal within a horizontal distance of 2 feet (61 cm)
from the center line of the terminal
E= Clearance to unventilated soffit**
F= Clearance to outside corner**
G-
Clearance to inside corner**
=
Clearance to each side of center line extended above
H=
meter/regulator assembly
I= Clearance to service regulator vent outlet3 feet (91 cm)*
Clearance to nonmechanical air supply inlet to building
J=
or the combustion air inlet to any other appliance
K= Clearance to a mechanical air supply inlet6 feet (1.83m)3 feet (91 cm) above if within 10 feet (3m) horizontally
Clearance above a paved sidewalk or paved driveway
L=
located on public property
M-
Clearance under veranda, porch, deck, or balcony`12 inches (30 cm) ‡*
=
Notes:
1. In accordance with the current CSA B149.1 Natural Gas and Propane Installation Code.
2. In accordance with the current ANSI Z223.1/NFPA 54 National Fuel Gas Code.
†. A vent shall not terminate directly above a sidewalk or paved driveway that is located between two single family dwelling and serves both dwellings.
‡. Pemitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the floor.
* Clearance in accordance with local installation codes and the requirements of the gas supplier and the manufacturer's Installation Instructions.
inches (30 cm) for appliances > 10,000 Btuh (3 kw) and =/<
100,000 Btuh (30 kw), 36 inches (91 cm) for appliances >
100,000 Btuh (30 kw)
3 feet (91 cm) with a height 15 feet (4.5 m) above the
6 inches (15 cm) for appliances =/< 10,000 Btuh (3 kw), 12
inches (30 cm) for appliances > 10,000 Btuh (3 kw) and =/<
100,000 Btuh (30 kw), 36 inches (91 cm) for appliances >
100,000 Btuh (30 kw)
12 inches (30 cm)12 inches (30 cm)
6 inches (15 cm) for appliances =/< 10,000 Btuh (3 kw), 9
inches (23 cm) for appliances > 10,000 Btuh (3 kw) and =/<
50,000 Btuh (15 kw), 12 inches (30 cm) for appliances > 50,000
Btuh (15 kw)
**
meter/regulator assembly
6 inches (15 cm) for appliances =/< 10,000 Btuh (3 kw), 9
inches (23 cm) for appliances > 10,000 Btuh (3 kw) and =/<
50,000 Btuh (15 kw), 12 inches (30 cm) for appliances > 50,000
Btuh (15 kw)
Vertical clearance to ventilated soffit located above the
D=
terminal within a horizontal distance of 2 feet (61 cm)
from the center line of the terminal
E= Clearance to unventilated soffit**
F= Clearance to outsid e corner**
G= Clearance to inside corner**
Clearance to each side of center line extended above
H=
meter/regulator assembly
I=Clearance to servic e regulator vent outlet3 feet (91 cm)*
Clearance to nonmechanical air supply inlet to building
J=
or the combustion air inlet to any other appliance
K= Clearance to a mechanical air supply inlet6 feet (1.83m)3 feet (91 cm) above if within 10 feet (3m) horizontally
Clearance above a paved sidewalk or paved driveway
L=
located on public property
M= Clearance under veranda, porch, deck, or balcony`12 inches (30 cm) ‡*
Notes:
1. In accordance with the current CSA B149.1 Natural Gas and Propane Install ation Code.
2. In accordance with the current ANSI Z223.1/NFPA 54 National Fuel Gas Code.
†. A vent shall not terminate directly above a sidewalk or paved driveway that is located between two single family dwelling and serves both dwellings.
‡. Pemitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the floor.
* Clearance in accordance with local installation cod es and the requirements of the gas supplier and the manufacturer's Installation Instr uctions.
inches (30 cm) for appliances > 10,000 Btuh (3 kw) and =/<
100,000 Btuh (30 kw), 36 inches (91 cm) for appliances >
100,000 Btuh (30 kw)
3 feet (91 cm) with a height 15 feet (4.5 m) above the
6 inches (15 cm) for appliances =/< 10,000 Btuh (3 kw), 12
inches (30 cm) for appliances > 10,000 Btuh (3 kw) and =/<
100,000 Btuh (30 kw), 36 inches (91 cm) for appliances >
100,000 Btuh (30 kw)
12 inches (30 cm)12 inches (30 cm)
4 feet (1.2m) below or to the side of opening; 1 foot (0.3m)
above opening.
**
meter/regulator assembl y
4 feet (1.2 m) below or to side of opening; 1 foot (300 m) above
opening
7 feet (2.13 m) †7 feet (2.13 m)
*
2018-CD19D5-25
Page 21
▲
k
VENT
COMBUSTION
AIR
VENT
VENT
PLATE
VENT
CAP
12" MINIMUM
TO OVERHANG
MAINTAIN 12" (18" FOR CANADA) MINIMUM
CLEARANCE ABOVE HIGHEST ANTICIPATED
SNOW LEVEL OR GRADE WHICHEVER IS GREATER
SCREWS
(4 req.)
ANCHORS
(4 req.)
7.2"
3.2"
Installer’s Guide
ELBOW AND TEE MUST BE
AS CLOSE TOGETHER
AS POSSIBLE
POSSIBLE CONFIGURATIONS FOR TWO PIPE VENTING SYSTEMS
HORIZONTAL VENTING
NOTE:
Vent termination kit BAYAIR30AVENTA* or
Location of the vent/ wind terminal should be chosen to
meet the requirements of Figure 27 for either direct or
non-direct vent applications.
BAYVENT200B may be used instead of the horizontal
and vertical termination options shown in the following figures.
l
!
CAUTION
When the vent pipe is exposed to temperatures below
freezing, i.e., when it passes through unheated spaces,
etc., the pipe must be insulated with 1/2 inch (22.7 mm)
thick Armaflex-type insulation or equal. If the space is
heated sufficiently to prevent freezing, then the insulation would not be required. If domestic water pipes are
not protected from freezing then it is assumed the
space meets the condition of a heated space.
HORIZONTAL VENTING THROUGH WALL
These furnaces may be installed as direct vent (as
shipped) or as nondirect vent. Installation must
conform to national, state, and local codes.
The vent & inlet terminals must be located at least 12"
minimum above normally expected snow accumulation
level.
Avoid areas where staining or condensate drippage may
be a problem.
18-CD19D5-2521
BAYVENT200B
Page 22
Installer’s Guide
PITCH – Venting through the wall must maintain 1/4"
per foot pitched upward to insure that condensate
drains back to the furnace.
FLUE GAS DEGRADATION – The moisture content
of the flue gas may have a detrimental effect on some
building materials. This can be avoided by using the
roof or chimney venting option. When wall venting is
used on any surface that can be affected by this moisture, it is recommended that a corrosion resistant
shield (24 inches square) be used behind the vent terminal. This shield can be wood, plastic, sheet metal, etc.
Also, silicone caulk all cracks, seams and joints within 3
feet of the vent terminal.
;
12" MIN TO
OVERHANG
1
"
2
1"
COMBUSTION
AIR
VENT
x
c
SUPPORT HORIZONTAL PIPE EVERY 3'
0" WITH THE FIRST SUPPORT AS CLOSE
TO THE FURNACE AS POSSIBLE.
INDUCED DRAFT BLOWER, HOUSING,
AND FURNACE MUST NOT SUPPORT
THE WEIGHT OF THE FLUE PIPE.
BAYAIR30AVENTA
(Sidewall)
z
MAINTAIN 12 IN
(18 IN. FOR CANADA)
MINIMUM CLEARANCE
ABOVE HIGHEST
ANTICIPATED SNOW
LEVEL OR GRADE
COMBUSTIBLE MATERIAL WALL
A minimum clearance of 1" to combustible materials
must be maintained when using single wall stainless
steel venting. See Figure 32.
Shield material to be a minimum of 24 gauge stainless
or aluminized sheet metal. Minimum dimensions are
12"x12". Shield must be fastened to both inside and outside of wall. Use screws or anchor type fasteners suited
to the outside or inside wall surfaces.
NONCOMBUSTIBLE MATERIAL WALL
The hole through the wall must be large enough to
maintain pitch of vent and properly seal.
Use cement mortar seal on inside and outside of wall.
See Figure 33.
2218-CD19D5-25
Page 23
Installer’s Guide
IMPORTANT:
The Commonwealth of Massachusetts requires compliance
with regulation 248 CMR 4.00 and 5.00 for installation of
through – the – wall vented gas appliances as follows:
For all side wall horizontally vented gas fueled equipment
installed in every dwelling, building or structure used in
whole or in part for residential purposes, including those
owned or operated by the Commonwealth and where the
side wall exhaust vent termination is less than seven (7)
feet above finished grade in the area of the venting,
including but not limited to decks and porches, the
following requirements shall be satisfied:
1.INSTALLATION OF CARBON MONOXIDE
DETECTORS. At the time of installation of the side wall
horizontal vented gas fueled equipment, the installing
plumber or gasfitter shall observe that a hard wired
carbon monoxide detector with an alarm and battery backup is installed on the floor level where the gas equipment
is to be installed. In addition, the installing plumber or
gasfitter shall observe that a battery operated or hard
wired carbon monoxide detector with an alarm is installed
on each additional level of the dwelling, building or
structure served by the side wall horizontal vented gas
fueled equipment. It shall be the responsibility of the
property owner to secure the services of qualified licensed
professionals for the installation of hard wired carbon
monoxide detectors
a.In the event that the side wall horizontally vented
gas fueled equipment is installed in a crawl space or an
attic, the hard wired carbon monoxide detector with alarm
and battery back-up may be installed on the next adjacent
floor level.
b.In the event that the requirements of this
subdivision can not be met at the time of completion of
installation, the owner shall have a period of thirty (30)
days to comply with the above requirements; provided,
however, that during said thirty (30) day period, a battery
operated carbon monoxide detector with an alarm shall be
installed.
2.APPROVED CARBON MONOXIDE
DETECTORS. Each carbon monoxide detector as required
in accordance with the above provisions shall comply with
NFPA 720 and be ANSI/UL 2034 listed and IAS certified.
3.SIGNAGE. A metal or plastic identification plate
shall be permanently mounted to the exterior of the
building at a minimum height of eight (8) feet above grade
directly in line with the exhaust vent terminal for the
horizontally vented gas fueled heating appliance or
equipment. The sign shall read, in print size no less than
one-half (1/2) inch in size, “GAS VENT DIRECTLY
BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS”.
4.INSPECTION. The state or local gas inspector of
the side wall horizontally vented gas fueled equipment
shall not approve the installation unless, upon inspection,
the inspector observes carbon monoxide detectors and
signage installed in accordance with the provisions of 248
CMR 5.08(2)(a)1 through 4.
This appliance requires a special venting system. If
BAYAIR30AVENTA or BAYVENT200B are used, a copy of
the installation instructions for the kit shall remain with
the appliance or equipment at the completion of
installation. The venting system installation instructions
can be obtained from the manufacturer by writing to the
following address:
American Standard, Inc.
6200 Troup Highway
Tyler, TX 75707
Attention: Manager of Field Operations Excellence
18-CD19D5-2523
Page 24
Installer’s Guide
4
N
3" PIPING
2", 2-1/2"
or 3" PIPING
REDUCING
COUPLING,
FIELD SUPPLIED
IF NEEDED
SEAL ALL
WALL CAVITIES
v
COMBUSTION
AIR INLET
0" UPFLOW OR
DOWNFLOW MODELS
SEE VENTING TABLE
STRAPS OR OTHER SUITABLE SUPPORTS
AT MAXIMUM OF 3'-0" INTERVALS
UPWARD PITCH -- 1/4" PER FOOT
FIRST SUPPORT SHOULD BE AS
CLOSE TO FURNACE CONNECTION
AS POSSIBLE.
NOTE: ANY FITTINGS PASSING
THROUGH AN UNHEATED SPACE
MUST BE INSULATED.
USE ONLY
APPROVED
TERMINATIO
OUTSIDE
WALL
NOTE: VENT AND INLET MUST BE SUPPORTED
AT A MAXIMUM OF 3' INTERVALS
TEE
BAYAIR30AVENTA
VENT
COMBUSTION AIR
STRAP
(FIELD SUPPLIED)
ELBOW
(FIELD
SUPPLIED)
COMBUSTION
AIR
RAIN CAP
VENT
1" + 1/2"
BAYVENT200B
2418-CD19D5-25
Page 25
Installer’s Guide
MAINTAIN 12 IN.
(18 IN. FOR CANADA)
MINIMUM CLEARANCE
ABOVE HIGHEST
ANTICIPATED SNOW
LEVEL. MAXIMUM OF
24 IN. ABOVE ROOF.
VENT
COMBUSTION
AIR
DOWNWARD VENTING
Furnace may be in vertical or horizontal configuration.
DOWNWARD VENT
LENGTH IS LIMITED
TO A MAXIMUM OF 15
EQUIVALENT FEET.
Upflow or
Downflow
Slope 1/4" per ft.
Slope 1/4" per ft.
6" Min.
b
40 Inch
Furnace
All horizontal pipes must be supported
at a maximum of 3 foot intervals
NOTES:
A) Condensate trap for vent pipe must be a mini-
mum of 6 inches in height.
B) Condensate trap for vent and inlet pipe must be
connected into a condensate drain pump; an
open or vented drain; or it can be connected to
the outlet hose of the furnace's condensate trap.
Outdoor draining of the furnace and coil condensate is permissible if allowed by local codes. Caution should be taken to prevent drains from freezing or causing slippery conditions that could lead
to personal injury. Excessive draining of condensate may cause saturated ground conditions that
may result in damage to plants.
C) The condensate trap should be primed at initial
start up prior to heating season operation.
NOTE:
No vent cap as shown in Figure 36 is the preferred
method for vertical vent termination in extremely cold
climates.
In extreme climate conditions, insulate the exposed
pipe above the roof line with Armaflex type insulation.
n
m
VENTING THROUGH THE ROOF
When penetrating roof with a 2" PVC vent pipe, a 2"
electrical conduit flashing may be used for a weather
tight seal. Lubricate flexible seal on flashing before PVC
pipe is pushed through the seal. (Field Supplied)
18-CD19D5-2525
BAYAIR30AVENTA
,
REMOVE RIBS
FROM CAP
COMBUSTION
AIR
ROOF FLASHING BOOT
(FIELD SUPPLIED)
VENT
VENT
MAINTAIN 12 IN.
(18 IN. FOR CANADA)
MINIMUM CLEARANCE
ABOVE HIGHEST
ANTICIPATED SNOW
LEVEL. MAXIMUM OF
24 IN. ABOVE ROOF
SUPPORT
(FIELD SUPPLIED)
ELBOW
(FIELD SUPPLIED)
COMBUSTION
AIR
Page 26
Installer’s Guide
L
N
T
STAINLESS
▲
E
S
SS
▲
VENTING ROUTED THROUGH A MASONRY CHIMNEY
VENT FITTING MATERIAL – STAINLESS STEEL
Gas and liquid tight single wall metal vent fitting, designed for resistance to corrosive flue condensate such
.
/
TYPE 29-4C STAINLESS STEEL VENTING -
USED THROUGH CHIMNEY THAT VENTS
ANOTHER GAS APPLIANCE
STAINLESS STEEL
STEEL
VENT CAP
VENT CAP
(OPTIONAL)
E CAUTION
6 IN. MIN.
!
SEAL BETWEEN FLANGE, PIPE,
COUPLING AND METAL PANEL
WITH HI TEMP RTV SILICONE SEALANT
FLUE PIPE
COUPLING
SUPPORT
FLANGE
GALVANIZED FIRESTOP SHOULD
BE FABRICATED WITH 3-7/8" DIA.
HOLE FOR SUPPORT FLANGE
(12" x 12" PANEL OR 12" DIA MIN.)
CLEARANCE ( 0" ACCEPTABLE FOR PVC VENT PIPE )
( 1" ACCEPTABLE FOR TYPE 29-4C STAINLESS STEEL VENT PIPE )
VENTING THROUGH CEILING
PVC PLASTIC VENTING - ONLY
@
FLUE PIPE
THROUGH UNUSED CHIMNEY
STAINLESS STEEL
TAINLE
VENT CAP
STEEL
(OPTIONAL)
VENT CAP
SEE CAUTION
6 IN. MIN.
CEILING
SUPPORT THE SINGLE WA
STAINLESS STEEL GAS
VENTING AND CENTER IT I
THE CHIMNEY OPENING WI
ANGLES AS SHOWN OR
ANOTHER EQUIVALENT
MANNER.
NOTE:
HORIZONTAL VENTING
TO VERTICAL VENTING
!
CAUTION
Do not run vent through chimney for wood burning or oil
furnaces or incinerators.
If remaining free area between single wall flue pipe and
masonry chimney is to be used for another gas appliance venting area must be sufficient to vent that appliance and that appliance must be connected to chimney
with
separate entry openings.
IMPORTANT –
The single wall flue pipe joints must be sealed.
The 90° elbow connection to vertical pipe must be sealed to
prevent condensate leakage to base of masonry chimney.
UPLING TO SUPPORT
PE FROM ANGLES
OTHER SUITABLE
PPORT METHOD
FLUE PIPE
!
CAUTION
NOTE:
HORIZONTAL VENTING
TO VERTICAL VENTING
SUPPORT THE SINGL
WALL FLUE PIPE AND
CENTER IT IN THE
CHIMNEY OPENING WI
ANGLES AS SHOWN O
ANOTHER EQUIVALEN
MANNER.
COUPLING
AS REQUIRED
Do not run vent through chimney for wood burning or oil
furnaces or incinerators or any other gas appliance.
IMPORTANT –
The single wall flue pipe joints must be sealed.
The 90° elbow connection to vertical pipe must be sealed to
prevent condensate leakage to base of masonry chimney.
as Type 29-4C MUST be used throughout.
These fittings and fitting accessories are to be supplied
locally.
2618-CD19D5-25
Page 27
Installer’s Guide
▲
When the factory supplied “off-set” (2X3 reducing coupling) is used for 3” vent pipe installation, make sure
the marking “Top” is located on the top side of the pipe.
The straight side must be on bottom for proper condensate drainage. This coupling is factory supplied only with
the following models: UC120 & DC120, UX120 & UY120,
UX100 & UY100, UX808C960, and All DX & DY models.
WHEN THE FACTORY SUPPLIED "OFF-SET" (2X3
REDUCING COUPLING) IS USED FOR 3" VENT PIPE
INSTALLATION, MAKE SURE THE MARKING "TOP" IS
LOCATED ON THE TOP SIDE OF THE PIPE.
LABEL
#
STRAIGHT SIDE MUST BE
ON BOTTOM FOR PROPER
CONDENSATE DRAINAGE.
SAYS
"TOP"
CONDENSATE DRAIN INSTRUCTIONS
!
CAUTION
▲
IT IS RECOMMENDED THAT A DRAIN PAN BE INSTALLED
UNDER THE FURNACE TO PREVENT PROPERTY DAMAGE,
PERSONAL INJURY OR DEATH FROM LEAKING CONDENSATE.
VERTICAL APPLICATIONS
Upflow furnace - The connection tubing for left and
right side drainage is shipped in the blower compartment. Install the connection tubing from the trap to the
side of the unit and trim all excess tubing to avoid
kinks.
Downflow furnace - The furnace is shipped with the
left side drainage setup. To change the right side drain,
remove the drain lines from the trap, rotate the trap
180° so it exits to the right, reconnect the lines, and run
a 1/2" CPVC pipe from the trap out through the right
side knock-out. Use RTV silicone sealant to connect the
CPVC pipe to the trap for ease of removing to clean the
trap.
2" TO 3" COUPLING
$
FACTORY SUPPLIED ONLY WITH
THE FOLLOWING MODELS:
UC120 & DC120
UX120 & UY120
UX100 & UY100
UX080C960
ALL DX & DY MODLES
FURNACE
VENT
OUTLET
DIRECTION OF STAINLESS STEEL FITTING
All stainless steel fitting must be installed with male
end towards the furnace.
All horizontal stainless steel sections must be positioned with the seam on top.
All long horizontal sections must be supported to prevent sagging.
All pipe joints must be fastened and sealed to prevent
escape of combustion products into the building.
%
Right side
UPFLOW (VERTICAL)
^
NOTE:
Both venting methods shown in Figure 40 & 42 must
also have the combustion air inlet installed - meeting
dimension requirements of Figure 36.
18-CD19D5-2527
Left side
UPFLOW (VERTICAL)
Page 28
Installer’s Guide
&
Right
Use CPVC tubing from Trap outlet,
over burner box to cabinet exit
DOWNFLOW (VERTICAL)
HORIZONTAL APPLICATIONS
Upflow and Downflow furnaces - All horizontal applications are left side only. It is always recommended
that the auxiliary drain pan be installed under a horizontally installed evaporator and/or 90% gas furnace.
Connect the axillary drain pan to a separate drain line
(no trap is needed in this line).
The trap must be repositioned to the exterior of the
cabinet. Remove the trap from its present location and
reposition the trap outside of the unit, through the long
circular hole, next to the secondary recuperative cell.
Remove the larger drain line (from the secondary cell)
and trim to fit between the secondary cell and the new
trap location. On upflow units, plug the hole in the
blower deck where the tube went through.
Remove the hose from the induced blower and reposition into the other drain tap of the inducer, which is located 90° clockwise around the inducer. Move the cap
from that drain tap to the unused drain tap. On upflow
units, plug the hole in the blower deck where the tube
went through. This tube on downflow units will need to
be cut to fit between the inducer and the trap. On upflow units, this tube may need to be extended, using the
tubing shipped with the furnace.
Connections must be made to an OPEN/ VENTEDDRAIN. Outdoor draining of the furnace and coil condensate is permissible if allowed by local codes. Caution
should be taken to prevent drains from freezing or causing slippery conditions that could lead to personal injury. Excessive draining of condensate may cause saturated ground conditions that may result in damage to
plants.
NOTE:
Use 1/2" or larger PVC or CPVC pipe and fittings as required for drain connections (fittings, pipe and solvent
cement not provided).
NOTE:
A corrosion resistant condensate pump must be used
if a pump is required for a specific drain system.
*
UPFLOW HORIZONTAL 17" UNITS
(Left side only)
IMPORTANT:
The condensate drain should be installed with provisions to
prevent winter freeze-up of the condensate drain line. Frozen condensate will block drains, resulting in furnace shutdown. If the drain line cannot be installed in a conditioned
space, then UL listed heat tape should be applied as required to prevent freezing (per manufacturer’s instructions).
The heat tape should be rated at 5 or 6 watts per foot at
120 volts. Self-regulating (preferred) or thermostatically
controlled heat tape is required.
Evaporator and furnace condensate drain piping may
be manifolded together. A primary drain vent stack
must be installed and terminated below the outlet of
the secondary heat exchanger drain connection to prevent water from damaging furnace controls if the primary drain outlet plugs up. Where the furnace is installed above a finished ceiling, the primary drain vent
stack must be installed such that overflow from the
vent stack opening will flow into an auxiliary drain pan
in order to prevent water damage to the finished ceiling
below.
Use Inducer Drain
hose without
extension
(
Use
extension
hose here
UPFLOW HORIZONTAL 21" & 24" UNITS
(Left side only)
2818-CD19D5-25
Page 29
)
If upflow furnace is installed
over a finished ceiling, overflow
from the primary drain vent
stack must flow into an auxillary
drain pan to prevent damage to
the finished ceiling below.
Make wiring connections to the unit as indicated on enclosed wiring diagram. As with all gas appliances using
electrical power, this furnace shall be connected into a
permanently live electric circuit. It is recommended
that furnace be provided with a separate “circuit protection device” in the electric circuit. The furnace must be
electrically grounded in accordance with local codes or
in the absence of local codes with the National Electrical Code, ANSI/NFPA 70 or CSA C22.1 Electrical Code,
if an external electrical source is utilized.
The integrated furnace control is polarity sensitive. The hot leg of the 120V power supply must be con-
nected to the black power lead as indicated on the wiring diagram. Provision for hooking up an electronic air
cleaner and or humidifier is provided on the integrated
control.
Refer to the SERVICE FACTS literature and unit wiring
diagram attached to furnace diagram attached to furnace.
B/C
FIELD WIRING DIAGRAM FOR 1 STAGE FURNACE
1 STAGE HEATING
USING A 1 STAGE HEATING THERMOSTAT
NO COOLING
FURNACE
SEE
NOTE 6
B/C
TO 115 V 1 PH.,
60 HZ., POWER
SUPPLY PER
LOCAL CODES
18-CD19D5-2529
HUM SEE
NOTE 5
EAC SEE
NOTE 5
From drawing B341437 Rv 1
Page 30
Installer’s Guide
FIELD WIRING DIAGRAM FOR 1 STAGE FURNACE
USING A 1 STAGE HEATING, 1 STAGE COOLING THERMOSTAT
(OUTDOOR SECTION WITHOUT TRANSFORMER)
OUTDOOR UNIT
(NO TRANSFORMER)
SEE
NOTE 6
SEE
B/C
NOTE 8
1 STAGE HEATING, 1 STAGE COOLING
FURNACE
B/C
TO 115 V 1 PH.,
60 HZ., POWER
SUPPLY PER
LOCAL CODES
HUM SEE
NOTE 5
EAC SEE
NOTE 5
From drawing B340388 Rv 2
3018-CD19D5-25
Page 31
▲
!
WARNING
EXPLOSION HAZARD!
PROPANE GAS IS HEAVIER THAN AIR AND MAY
COLLECT IN ANY LOW AREAS OR CONFINED
SPACES. IN ADDITION, ODORANT FADE MAY MAKE
THE GAS UNDETECTABLE EXCEPT WITH A WARNING DEVICE. IF THE GAS FURNACE IS INSTALLED
IN A BASEMENT, AN EXCAVATED AREA OR A
CONFINED SPACE, IT IS STRONGLY RECOMMENDED TO CONTACT A GAS SUPPLIER TO INSTALL A GAS DETECTING WARNING DEVICE IN
CASE OF A GAS LEAK.
NOTE: The manufacturer of your furnace does NOT test
any detectors and makes no representations regarding
any brand or type of detector.
Installer’s Guide
TWINNING FURNACES
These furnaces may be twinned. Twinning requires that
two furnaces with the same configuration, capacity, and
airflow must be used. They shall have common returns
with equal pressure drops or ducts with equivalent
lengths and sizes. Twinning of this furnace requires the
use of twinning kit BAYTWIN400A.
18-CD19D5-2531
Page 32
Installer’s Guide
▲
GAS PIPING
The upflow/ horizontal furnace is shipped standard for
left side installation of gas piping. A knock-out is provided on the right side for an alternate gas piping arrangement. See Figure 51.
The installation of piping shall be in accordance with
piping codes and the regulations of the local gas company. Pipe joint compound must be resistant to the
chemical reaction with liquefied petroleum gases.
Refer to piping Table 10, for delivery sizes. Connect gas
supply to the unit, using a ground joint union and a
manual shut-off valve as shown in Figures 51-53.
National codes require a condensation drip leg to be installed ahead of the controls as shown in Figures 51-53.
The furnace and its individual shut-off valve must be
disconnected from the gas supply piping system during
any pressure testing of that system at test pressures in
excess of 1/2 psig (3.5 kPa).
Q
MAIN MANUAL
SHUTOFF VALVE
GROUND
UNION
JOINT
AUTOMATIC GAS VALVE
WITH MANUAL SHUTOFF
The furnace must be isolated from the gas supply piping
by closing its individual manual shut-off valve during
any pressure testing of the gas supply piping system at
test pressures equal to or less than 1/2 psig (3.5 kPa).
NOTE:
Maximum pressure to the gas valve for natural gas is
13.8" W.C. Minimum pressure is 5.0" W.C. Maximum
pressure to the gas valve for propane is 13.8" W.C.
Minimum pressure is 11.0" W.C.
All gas fittings must be checked for leaks using a
soapy solution before lighting the furnace.
CHECK WITH AN OPEN FLAME!
!
CAUTION
Use a backup wrench on the gas valve when installing
gas piping to prevent damage to the gas valve and
manifold assembly.
AUTOMATIC GAS VALVE
WITH MANUAL SHUTOFF
MAIN MANUAL
SHUTOFF VALVE
GROUND
UNION
JOINT
DO NOT
DRIP
LEG
DRIP
LEG
UPFLOW – LEFT HAND GAS PIPINGUPFLOW – RIGHT HAND GAS PIPING
W
THE DOWNFLOW (VERTICAL) MAY BE INSTALLED LEFT OR RIGHT SIDE GAS PIPING
3218-CD19D5-25
Page 33
Installer’s Guide
E
AUTOMATIC GAS VALVE
WITH MANUAL SHUTOFF
MAIN MANUAL
SHUTOFF VALVE
GROUND
UNION JOINT
DRIP
LEG
HORIZONTAL FURNACE GAS PIPING MAY BE FROM EITHER SIDE (UPFLOW SHOWN)
TABLE 13
NATURAL GAS ONLY
TABLE OF CUBIC FEET PER HOUR OF GAS
FOR VARIOUS PIPE SIZES AND LENGTHS
PIPE
SIZE
1/2132927363565046
3/427819015213011510596
1-1/41050730590520440400370
This table is based on pressure drop of 0.3 inch W.C. and 0.6 SP.GR. gas
10203040506070
1520350285245215195180
LENGTH OF PIPE
TABLE 14
ORIFICE SIZES
INPUT
RATING
BTUH
40,000
60,000
80,000
100,000
120,000
NUMBER
OF
BURNERS
2
3
4
5
6
MAIN BURNER ORIFICE
DRILL SIZE
NAT. GASLP GAS
45
45
45
45
45
56
56
56
56
56
COMBUSTION AND INPUT CHECK
1. Make sure all gas appliances are off except the furnace.
2. Clock the gas meter with the furnace operating (determine the dial rating of the meter) for one revolution.
3. Match the “Sec” column in the gas flow (in cfh)
Table 16 with the time clocked.
4. Read the “Flow” column opposite the number of seconds clocked.
5. Use the following factors
if necessary:
For 1 Cu. Ft. Dial Gas Flow CFH =
Chart Flow Reading ÷2
For 1/2 Cu Ft. Dial Gas Flow CFH =
Chart Flow Reading ÷4
For 5 Cu. Ft. Dial Gas Flow CFH =
10X Chart Flow Reading ÷4
MAIN MANUAL
SHUTOFF VALVE
AUTOMATIC GAS VALVE
WITH MANUAL SHUTOFF
GROUND UNION JOINT
DRIP
LEG
6. Multiply the final figure by the heating value of the
gas obtained from the utility company and compare
to the nameplate rating. This must not exceed the
nameplate rating.
Gas Valve Adjustment
Changes can be made by adjusting the manifold pres-
sure (See Table 15), or changing orifices (orifice
change may not always be required). To adjust the
manifold pressure:
1. Turn off all electrical power to the system.
2. Attach a manifold pressure gauge with flexible
tubing to the outlet pressure boss marked “OUT P”
on White-Rodgers gas valve model 36G or 36J. See
Figure 57 for White-Rodgers gas valve model 36J.
See Figure 56 for White-Rodgers gas valve model
36G.
3. Loosen (Do Not remove) the pressure tap test set
screw one turn with 3/32" hex wrench.
a. The pressure tap adjustment kit (KIT07611)
contains a 3/32" hex wrence, a 5/16" hose and a
connector and can be ordered through Global
Parts.
4. Turn on system power and energize valve.
5. Adjust gas heat by removing the adjustment
regulator cover screw.
a. To increase outlet pressure, turn the regulator
adjust screw clockwise.
b. To decrease outlet pressure, turn the regulator
adjust screw counterclockwise.
c. Adjust regulator until pressure shown on mano-
meter matches the pressure specified in Table
15.
1. The input of no more than nameplate rating
and no less than 93% of the nameplate rating,
unless the unit is derated for high altitude.
18-CD19D5-2533
Page 34
Installer’s Guide
▲
▲
d. Replace and tighten the regulator cover screw
securely.
6. Cycle the valve several times to verify regulator
setting.
a. Repeat steps 5-6 if needed.
7. Turn off all electrical power to the system.
8. Remove the manometer and flexible tubing and
tighten the pressure tap screw.
R
TABLE 15
FINAL MANIFOLD PRESSURE
SETTINGS (inches w.c.)
FUELPRESSURE
NATURAL GAS3.5" W.C.
LP GAS10.5" W.C.
IMPORTANT:
Reinstall the propane orifices to the same depth as the
orifices supplied with the equipment.
9. Using a leak detection solution or soap suds, check
for leaks at the pressure outlet boss and pressure
tap test screw.
10. Turn on system power and check operation of the
unit.
!
CAUTION
Replace and/or tighten all plugs removed or loosened
when adjusting gas pressure. Leak check the fittings
before placing the furnace into regular service. Failure
to follow this warning could result in fire, explosion, or
property damage.
NOTE:
The manifold pressure must be referenced to the
burner box. The burner box pressure tap equalizes the
gas valve pressure regulator. Manifold pressure is
checked by installing a tee (field supplied) in the tubing, between the tee coming from the burner box tube
and the gas valve,
pressure tap on the outlet
ure 49.
Replace manifold pressure tap threaded plug and leak
check after checking/ adjusting manifold gas pressure.
Table 14 lists the main burner orifices used with the
furnace. If a change of orifices is required to correct the
furnace input rating refer to Table 17.
3418-CD19D5-25
in addition to the regular gas valve
side of the gas valve. See Fig-
!
CAUTION
HIGH ALTITUDE DERATE
Input ratings (BTUH) of these furnaces are based on
sea level operation and should not be changed at elevations up to 2,000 ft.
If the installation is 2,000 ft. or above, the furnace input
rate (BTUH) shall be reduced 4% for each 1,000 ft.
above sea level. The furnace input rate shall be checked
by clocking the gas flow rate (CFH) and multiplying by
the heating value obtained from the local utility supplier for the gas being delivered at the installed altitude.
Input rate changes can be made by adjusting the manifold pressure (min 3.0 - max 3.7 in. W.C. - Natural Gas)
or changing orifices (orifice change may not always be
required). If the desired input rate can not be achieved
with a change in manifold pressure, then the orifices
must be changed. LP installations will require an orifice
change.
Installation of this furnace at altitudes above 2,000 ft.
(610m) shall be in accordance with local codes, or in the
absence of local codes, the National Fuel Gas Code,
ANSI Z223.1/ NFPA 54 or National Standard of
Canada, Natural Gas and Propane Installation Code,
CSA B149.1. Installation of this furnace at altitudes
above 2,000 ft (610m) shall be made in accordance with
the listed high Altitude Conversion Kit available with
this furnace.
INSERT THE TOP
FLANGE OF THE FRONT
COVER UNDER THE LIP
INSIDE THE BOX
ALL SIDE FLANGES
MUST BE OUTSIDE OF
THE BOX
ROTATE THE FRONT
COVER INWARD
MAKING SURE THAT
ALL SIDE FLANGES
ARE OUTSIDE OF THE
BOX.
IMPORTANT:
Reinstall the propane orifices to the same depth as the
orifices supplied with the equipment.
See Table 18 for help in selecting orifices if orifice
change is required. Furnace input rate and temperature rise should be checked again after changing orifices to confirm the proper rate for the altitude.
Installations above 4,000 feet may require a pressure
switch change. If required, use the BAYHALT*** Kit
(High Altitude Accessory Kit) listed in PRODUCT DATA.
Figure 55 shows the correct way to reinstall the burner
box cover if adjustment or replacement of the flame
sensor, hot surface igniter, or main burner orifices have
required removal of the cover.
TABLE 17
Orifice
Twist Drill
Size If
Installed
At Sea
Level
42
43
44
45
46
47
54
55
56
57
58
2000 3000 4000 5000 6000 7000 8000 9000 10000
42
44
45
46
47
48
54
55
56
58
59
From National Fuel Gas Code - Table F-4
ALTITUDE ABOVE SEA LEVEL
and Orifice Required At Other Elevations
43
43
43
44
44
45
44
44
45
45
47
47
47
47
48
49
55
55
55
55
56
57
59
59
60
60
!
WARNING
45
46
47
48
49
55
56
57
60
61
45
47
48
48
49
55
56
57
60
62
46
47
48
49
50
55
56
58
61
62
47
48
49
49
50
56
56
59
62
63
46
47
48
49
50
51
56
56
59
63
63
47
48
50
50
51
52
56
57
60
63
64
CARBON MONOXIDE POISONING HAZARD
Failure to follow the installation instructions for the
venting system being placed into operation could
result in carbon monoxide poisoning or death.
START UP AND ADJUSTMENT
PRELIMINARY INSPECTIONS
With gas and electrical power “OFF”
1. Duct connections are properly sealed
2. Filters are in place
3. Venting is properly assembled
4. Blower door is in place
Flip the switch on main gas valve within the unit to the
“OFF” position. Turn the external gas valve to “ON”.
Purge the air from the gas lines. After purging, Check
all gas connections for leaks with a soapy solution —
DO NOT CHECK WITH AN OPEN FLAME.
Allow 5 minutes for any gas that might have escaped to
dissipate. LP Gas being heavier than air may require
forced ventilation. Flip the switch on the gas valve in
the unit to the “ON” position.
18-CD19D5-2535
Page 36
Installer’s Guide
▲
▲
Outlet Pressure Boss
On/Offff
Switchch
In
let Pressure
Boss (opt.).)
Regulula
tor
Adj
ust
LIGHTING INSTRUCTIONS
!
WARNING
DO NOT attempt to manually light the burner.
Failure to follow this warning could result in property
damage, personal injury or death.
Lighting instructions appear on each unit. Each installation must be checked out at the time of initial start up
to insure proper operation of all components. Check out
should include putting the unit through one complete
cycle as outlined below.
Turn on the main electrical supply and set the thermostat above the indicated temperature. The ignitor will
automatically heat, then the gas valve is energized to
permit the flow of gas to the burners. After ignition and
flame is established, the flame control module monitors
the flame and supplies power to the gas valve until the
thermostat is satisfied.
To shut off.
For complete shut-down: Flip the switch on the main
gas valve to the “OFF” position, (See Figure 56 & 57).
Disconnect the electrical supply to the unit.
Y
let Pressure
Boss
U
Outlet Pressure Boss
Swi
White-Rodgers 36G gas valve
Outlet Pressure Boss
Adj
Regulator
Adjustment
ust
tor
!
CAUTION
If this is done during the cold weather months, provisions must be taken to prevent freeze-up of all water
pipes and water receptacles. Failure to follow this
warning could result in property damage.
Whenever your house is to be vacant, arrange to
have someone inspect your house for proper temperature. This is very important during freezing
weather. If for any reason your furnace should
fail to operate damage could result, such as frozen water pipes.
SEQUENCE OF OPERATION
Thermostat call for heat
R and W thermostat contacts close signaling the control
module to run its self-check routine. After the control
module has verified that the pressure switch contacts
are open and the limit switch(es) contacts are closed,
the draft blower will be energized.
As the induced draft blower comes up to speed, the
pressure switch contacts will close and the ignitor warm
up period will begin. The ignitor will heat for approximately 20 seconds, then the gas valve is energized to
permit gas flow to the burners. The flame sensor confirms that ignition has been achieved.
After the flame sensor confirms within a 4 second trial
period that ignition has been achieved, the delay to fan
ON period begins timing. After approximately 45 seconds the indoor blower motor will be energized and continue to run during the heating cycle.
When the thermostat is satisfied, R and W thermostat
contacts open, the gas valve will close, the flames will
extinguish, and the induced draft blower will be de-energized. The indoor blower motor will continue to run
for the fan off period (Field selectable at 60, 100, 140 or
180 seconds), then be de-energized by the control module.
CONTROL AND SAFETY SWITCH ADJUSTMENTS
LIMIT SWITCH CHECK OUT
The limit switch is a safety device designed to close the
gas valve should the furnace become overheated. Since
proper operation of this switch is important to the
safety of the unit, it must be checked out on initialstart up by the installer.
Inlet Pressure
Boss (opt.)
White-Rodgers 36J gas valve
3618-CD19D5-25
On/Off Switch
Page 37
Installer’s Guide
▲
To check for proper operation of the limit switches, set
the thermostat to a temperature higher than the indicated temperature to bring on the gas valve. Restrict
the airflow by blocking the return air (disconnecting the
indoor blower may trip the inducer limit). When the
furnace reaches the maximum outlet temperature as
shown on the rating plate, the burners must shut off. If
they do not shut off after a reasonable time and overheating is evident, a faulty limit switch is probable and
the limit switch must be replaced. After checking the
operation of the limit control, be sure to remove the paper or cardboard from the return air inlet. Refer to Service Facts for additional instructions.
NOTE TO INSTALLER
Review the following warnings with the owner. Review
contents of USER’S INFORMATION MANUAL with the
owner.
AIRFLOW ADJUSTMENT
Check inlet and outlet air temperatures to make sure
they are within the ranges specified on the furnace rating nameplate. If the airflow needs to be increased or
decreased, see the wiring diagram for information on
changing the speed of the blower motor.
!
WARNING
Disconnect power to the unit before removing the
blower door.
Failure to follow this warning could result in property
damage, personal injury or death.
This unit is equipped with a blower door switch which
cuts power to the blower and gas valve causing shutdown when the door is removed. Operation with the
door removed or ajar can permit the escape of dangerous fumes. All panels must be securely closed at all
times for safe operation of the furnace.
INDOOR BLOWER TIMING
Heating: The integrated furnace control module controls the indoor blower. The blower start is fixed at 45
seconds after ignition. The FAN-OFF period is field selectable by dip switches at 60, 100, 140, or 180 seconds.
The factory setting is 100 seconds (See wiring diagram).
Cooling: The fan delay off period is factory set at 0 seconds. The option for 80 second delay off is field selectable (See wiring diagram).
ROOM AIR THERMOSTAT
HEAT ANTICIPATOR ADJUSTMENT
Set the thermostat heat anticipator according to the
current flow measured, or the settings found in the
notes on the furnace wiring diagram (found in the SERVICE FACTS or inside the furnace casing).
INSTRUCTIONS TO THE OWNERS
In the event that electrical, fuel, or mechanical
failures occur, the owner should immediately
turn the gas supply off at the manual gas valve,
located in the burner compartment. Also turn off
electrical power to the furnace and contact the
service agency designated by your dealer.
BURNER BOX TEMPERATURE LIMIT DEVICE
All models are equipped with a manual reset temperature limit located on the burner box. In case of excessive temperature, the limit will open and cause the circuit to open which shuts off all flow of gas.
ABNORMAL CONDITIONS
1. EXCESSIVE COMBUSTION PRESSURE (WIND IN
EXCESS OF 40 M.P.H.) VENT OR FLUE BLOCKAGE
If pressure against induced draft blower outlet becomes excessive, the pressure switch will open and
shut off the gas valve until acceptable combustion
pressure is again available.
2. LOSS OF FLAME
If loss of flame occurs during a heating cycle, or
flame is not present at the sensor, the flame control
module will close the gas valve. The flame control
module will then recycle the ignition sequence,
then if ignition is not achieved, it will shut off the
gas valve and lock out the system.
3. POWER FAILURE
If there is a power failure during a heating cycle,
the system will restart the ignition sequence automatically when power is restored if the thermostat
still calls for heat.
4. GAS SUPPLY FAILURE
If loss of flame occurs during a heating cycle, the
system integrated control module will recycle the
ignition sequence, then if ignition is not achieved,
the integrated control module will shut off the gas
valve and lock out the system.
5. INDUCED DRAFT BLOWER FAILURE
If pressure is not sensed by the pressure switch, the
contacts will remain open and not allow the gas
valve to open, therefore the unit will not start. If
failure occurs during a running cycle, the pressure
switch contacts will open and the gas valve will
close to shut the unit down.
6. CONDENSATE DRAIN BLOCKAGE
If the condensate drain is blocked, either by debris,
improper draining, or by freezing condensate, the
pressure switch will sense the accumulation of condensate in the furnace drain pan. The pressure
switch contacts will open and remain open, not allowing unit operation. The unit will not operate until the condensate drain has been cleared, and the
condensate flows freely.
18-CD19D5-2537
Page 38
Installer’s Guide
7. RESET AFTER LOCKOUT
When the integrated control module has shut the
system down and gone into lockout, the system
must be manually reset before the unit will restart.
To reset, turn the system power off, then on, then
off and then on again within 30 seconds. This may
be done at the unit’s power source or at the thermostat. The system will not reset unless the proce-
dure off-on-off-on is completed within 30 seconds.
8. RESET AFTER BURNER BOX LIMIT SHUTDOWN
If the furnace shuts down, one thing that can be
checked is the burner box temperature limit switch.
It is located on the bottom of the burner box. The
vent and combustion air inlet terminations should
be checked for blockage. If blockage exists, clear
the problem and then the reset button may be depressed. If there is no blockage of the termina-
tions, the limit switch must be reset by a
qualified servicer.
Carbon monoxide, fire or smoke can cause serious
bodily injury, death, and/or property damage.
A variety of potential sources of carbon monoxide can be
found in a building or dwelling such as gas-fired clothes
dryers, gas cooking stoves, water heaters, furnaces and
fireplaces. The U.S. Consumer Product Safety Commission recommends that users of gas-burning appliances
install carbon monoxide detectors as well as fire and
smoke detectors per the manufacturers installation instructions to help alert dwelling occupants of the presence of fire, smoke or unsafe levels of carbon monoxide.
These devises should be listed by Underwriters Laboratories, Inc. Standards for Single and Multiple StationCarbon Monoxide Alarms, UL 2034 or CSA International Standard, Residential Carbon Monoxide AlarmingDevices, CSA 6.19
The following warning complies with State of California law, Proposition 65.
▲
WARNING:
fiberglass wool insulation! Fiberglass dust and ceram-
ic fibers are believed by the State of California to cause
cancer through inhalation. Glasswool fibers may also
cause respiratory, skin, or eye irritation.
PRECAUTIONARY MEASURES
●
Avoid breathing fiberglass dust.
●
Use a NIOSH approved dust/mist respirator.
●
Avoid contact with the skin or eyes. Wear long sleeved, loose-fitting clothing, gloves, and eye
protection.
●
Wash clothes separately from other clothing: rinse
washer thoroughly.
●
Operations such as sawing, blowing, tear-out, and
spraying may generate fiber concentrations requiring
additional respiratory protection. Use the appropriate
NIOSH approved respirator in these situations.
FIRST AID MEASURES
Eye Contact - Flush eyes with water to remove
dust. If symptoms persist, seek med ical attention.
Skin Contact - Wash affected areas gently with
soap and warm water after handling.
This product contains
NOTE:
The manufacturer of your furnace does not test any detectors and makes no representations regarding any
brand or type of detector.
3818-CD19D5-25
Page 39
Installer’s Guide
INTEGRATED FURNACE CONTROL ERROR FLASH CODES
Flashing Slow ---Normal - No call for Heat
Flashing Fast ---Normal - Call for Heat
Continuous ON ---Replace IFC
Continuous OFF ---Check Power
2 Flashes ---System Lockout (Retries or Recycles exceeded)
Draft Pressure Error - Possible problems:
3 Flashes ---
4 Flashes ---Open Temperature Limit Circuit
5 Flashes ---Flame sensed when no flame should be present
6 Flashes ---115 volt AC power reversed, poor grounding or system voltage too low
7 Flashes ---Gas valve circuit error
8 Flashes ---Low flame sense signal
9 Flashes ---
a) Venting problem
b) Pressure switch problem
c) Inducer problem
Check Ignitor Circuit and Line "N" to 24VAC "Common" voltage (≤ 2 volts)
[possible grounding problem]
18-CD19D5-2539
Page 40
Trane
6200 Troup Highway
Tyler, TX 75707
Literature Order Number 18-CD19D5-25
File Number18-CD19D5-25
Supersedes18-CD19D5-24
For more information
contact your local dealer.
The manufacturer has a policy of continuous product and product data improvement, it reserves the right
to change design and specifications without notice.
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.