Trane ADAPTIVE CONTROL UCM-CLD Installation And Maintenance Manual

Page 1
Installation Operation Maintenance
UCM-CLD Operating and control principles
UUCCMM--CCLLDD OOppeerraattiinngg aanndd ccoonnttrrooll pprriinncciipplleess ooff tthhee eelleeccttrroonniicc mmoodduullee TTRRAANNEE AADDAAPPTTIIVVEE CCOONNTTRROOLL CCHHHHNN aanndd CCHHHHBB ccoommpprreessssoorrss..
L80 IM 025 E
usseedd oonn hheelliiccaall--rroottaarryy uunniittss eeqquuiippppeedd wwiitthh
u
Page 2
FFoorreewwoorrdd
These Installation, Operation, and Maintenance instructions are given as a guide to good practice in the installation, start-up, operation, and periodic maintenance by the user of UCM-CLD modules.
WWaarrrraannttyy
Warranty is based on the general terms and conditions of the manufacturer. The warranty is void if the equipment is modified or repaired without the written approval of the constructor, if the operating limits are exceeded, or if either the control system or the electrical wiring is modified.
RReecceeppttiioonn
On arrival, inspect the unit before signing the delivery note. Specify any damage on the delivery note, and send a registered letter of protest to the last carrier of the goods within 72 hours of delivery. Notify the local sales office at the same time. The unit should be totally inspected within 7 days of delivery. If any concealed damage is discovered, send a
They do not contain the full service procedures necessary for the continued successful operation of this equipment. The services of a qualified service technician should be employed, through the medium of a maintenance contract with a reputable service company.
Damage due to misuse, lack of maintenance, or failure to comply with the manufacturer's instructions, is not covered by the warranty obligation.
registered letter of protest to the carrier within 7 days of delivery and notify the local sales office. Units are shipped with the refrigerant operating or holding charge, and should be examined with an electronic leak detector to determine the hermetic integrity of the unit. The refrigerant charge is not included in the standard Warranty Cover.
GGeenneerraall iinnffoorrmmaattiioonn
About this manual
Cautions appear at appropriate places in this instruction manual. Your personal safety and the proper operation of this machine require that you follow them carefully.
The manufacturer assumes no liability for installations or servicing performed by unqualified personnel.
© American Standard Inc. 2000
2
Page 3
IInnddeexx
Foreword . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
Reception . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
General information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
Principles of operation of the UCM-CLD module
General information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Operator’s interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Description of the operation
Chiller report . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Refrigerant report . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
Compressor report . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
Operator’s settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
Service settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
Service tests . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
Diagnostics
Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
Default description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20
Unit operating modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26
Compressor operating modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .27
Maintenance contract . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .28
Training . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .28
3
Page 4
Compressor
Report
Refrigerant
Report
Chiller Report
Custom
Report
Select Report Group
Diagnostics
Service
Tests
Service
Settings
Operator
Settings
Alarm
AutoEnterPrevious
StopCancelNext
Select Setting Group
ADAPTIVE CONTROL
Principles of operation of the module UCM-CLD
Figure 1: Operator’s interface
General information
This regulation assembly is composed of 6 electronic modules which have each their own 115V power supply and communicate with each other via a serial link. Each module has a set of functions which are associated to make the unit regulation. Each module has the following name linked to its functions.
- MCSP (Motor Compressor Start and Protection): safety, protection and control of the helical-rotary compressor as well as all associated components.
- CPM (Chiller Protection and Management): safety, protection, and control of the chiller.
- EXV (Electronic Expansion Valve): control of both electrical expansion valves.
- CSR (Communication and Setpoint Reset): control of the serial communication, unit external setpoints, and ice-making mode (optional module).
- Local CLD (Local Clear Language Display): operator’s interface located in the unit: front panel (software version and number displayed at power-up).
- Remote LCD (Remote Clear Language Display): operator’s interface located up to 1500 m from the unit at the operator’s, and which can communicate with up to four units of the same type (optional module).
- TCI IV, IPCB (Tracer Communication Interface 4, Inter-Processor Communication Buffer): protection of the unit internal communication bus from the external interferences existing in the unit (optional module, compulsory when using a remote CLD, and which must be factory-mounted).
4
Page 5
Figure 2: Control and regulation panel mounted on helical-rotary units equipped with UCM-CLD
Operator’s interface (Figure 1)
Digital display
The display of control regulation and operating parameters, as well as diagnostic and error messages, is made on a two-line 40-character liquid crystal display. When powering-up the system, the display is not lit and the message Self-test in progress is displayed in order to make sure the display operates properly. The screen allows to display:
- The error codes.
- The settings of the various setpoints.
- The specified temperature and pressure values.
- The status of operating parameters and various options.
Keyboard
A 16-key touch pad allows the operator to move within the various menus and to modify their parameters and setpoints. The keys are divided into two groups.
Menu keys
- Chiller Report menu
- Custom Report menu
- Refrigerant menu
- Compressor menu
- Operator settings menu
- Service settings menu
- Service test menu
- Diagnostics menu These 8 keys allow to access each of these menus.
Control keys
- + key
- - key
- Previous key
- Next key
- Enter key
- Cancel key
- Auto key
- Stop key These 8 keys allow the operator to move within the various menus and to modify their parameters.
Remark: All the menus and setpoints cannot be accessed by the chillers operator; Service Settings and Service Test menus are protected by a password and are reserved for Trane engineers.
5
Page 6
Description of the operation
The whole information is gathered in various menus according to the location of the sensor and/or the function performed.
Chiller report menu
This menu gathers the information relating to the liquid chiller (reading only). Active setpoints and their origins, chilled water, air temperature, current draws, are found in this menu.
Custom report menu
This menu is peculiar because originally it does not include any information at all. However, the operator can build his own menu which is comprised of read­only information, by simply pressing the + key when in other menus. To remove information from this menu, simply press the - key when displayed.
Refrigerant report menu
This menu gathers the information, read-only, relating to the refrigerant. Refrigerant pressures and temperatures at various points of the refrigerant circuit can be found in this menu.
Compressor report menu
This menu gathers the information, read-only, relating to the compressor. Voltages and amps, hour and start counters, as well as oil temperature (GP compressor only) can be found in this menu.
Operator settings menu
This menu comprises all the particular setpoints and operating modes existing in the unit and which are accessible by the usual operator of the chiller. In addition, the following can be programmed: chilled water pump operation, temperature resets, ice-making operation, and low ambient limit.
Service settings menu
This menu has three access levels. The first one contains information which can be adjusted by the customer such as the unit voltage, the validation of over/under voltage protection, the display language, and the programmable relay function of the units. The keyboard can also be locked if the relating function is validated. A second level contains the setpoints adjusted by the service engineer to adapt the operation of the unit to a particular site, such as the address of the serial link, the water and refrigerant limit parameters, and so forth. The third level contains the configuration and protection information: number of circuits, compressors and fans, compressor amps and expansion valve settings.
Service tests menu
This menu allows the operator to perform some tests when the unit is in operation or during the initial start­up of the unit: expansion valve test, circuit locking, or pump-out.
Previous key
Pressing the Previous key allows the operator to scroll up to the previous information in the current menu. All the display items are looped, so it is possible to scroll from the first item to the last one.
Next key
Pressing the Next key allows the operator to scroll down to the next information in the current menu. All the display items are looped, so it is possible to scroll from the last item to the first one.
+ key
If this information displayed is a read-only item, pressing the + key will add it to the operators menu. if the information can be modified, the value is increased by 1. Pressing the key for longer than 1 second will increase the value of 1 every .25 seconds. A logical stop prevents an adjustment higher than the maximum value; a message is displayed to indicate this status.
- key
If the information displayed is a read-only item, pressing the - key will remove it from the operator’s menu. If the information can be modified, the value is increased by 1. Pressing the key for longer than 1 second will increase the value of 1 every .25 seconds. A logical stop prevents an adjustment higher than the maximum value; a message is displayed to indicate this status.
Enter key
Pressing this key allows the validation of a value after it has been modified by pressing the + or - key.
Cancel key
Pressing this key allows the cancellation of a value after it has been modified by pressing the + or - key and to come back to the original value.
Auto key
Pressing this key (green) allows the unit to come back in auto mode if it was previously placed in stop mode with the stop key. The unit cannot be forced into auto mode if it has been stopped by an external contact or the serial link. When the unit is stopped by the remote interface (Remote CLD), the local auto mode order is prioritary.
Stop key
Pressing this key (red) allows the unit to go into stop mode. In every case, and wherever the origin (except a local stop), the stop order and stop status have priority over a run order. The stop generated is a soft stop, meaning the unit unloads before stopping.
Diagnostics menu
This menu contains all the information on the current faults or faults that occurred in the past. It allows the possibility to reset a manual reset fault or to erase the historic list of faults.
6
Page 7
Chiller report
[operating mode] will be one of
Reset Stopped by Local Display Stopped by Remote Display Stopped by Tracer Stopped by External Source Auto Waiting, Restart Inhibit Starting Running Running, Current Limit Running, Condenser Limit Running, Evaporator Limit Stopping Making ice ice-making complete Low ambient temperature lockout Electronic expansion valve test Manufacturing test Service pumpdown
Chiller
report
Chiller report: status, water temperatures and setpoints
Press (Next) (Previous) to continue
Next
Unit model
(service setting menu)
all others RTXA
Mode: [OPERATING MODE] Request setpoint source: [SETPOINT SOURCE]
Chiller Mode: [OPERATING MODE] Request setpoint source: [SETPOINT SOURCE]
Heat Mode: [OPERATING MODE] Request setpoint source: [SETPOINT SOURCE]
Next
Compressors on A, B, C, D, NONE Circuits locked out CIRCUIT 1, CIRCUIT 2, NONE
Next
[Operating mode] Making ice, ice-making complete All others
Next
Next
Active ice termination setpoint XXX C Evaporator entering water temperature XXX.X C
Active chilled water setpoint XXX C Evaporator leaving water temperature XXX.X C
Active hot water setpoint XXX C Leaving water temperature XXX.X C
Next
Evaporator entering water temperature XXX.X C Evaporator leaving water temperature XXX.X C
Next
Fan control
(Service Setting Menu)
Disable Enable
Condenser entering water temperature XXX.X C Condenser leaving water temperature XXX.X C
Water heat recovery entering water temperature XXX.X C Water heat recovery leaving water temperature XXX.X C
Next
* Dashes will be displayed if the sensor is open
or shorted and neither outdoor air reset or low ambient lockout is enabled.
** Dashes will be displayed if the zone
temperature sensor is open or shorted or zone reset is disabled.
Active current limit setpoint XXX % Chiller % Rated load amps XXX %
Next
* Outdoor air temperature XXX.X C ** Zone temperature XXX.X C
Next
7
Page 8
Refrigerant report
The possible replacement to
Cooling Heating Defrosting Heat to Defrost Defrost to Heat Cool to Heat Heat to Cool
Refrigerant
report
Refrigerant temperature and pressure report
Press (Next) (Previous) to continue
Next
All others RTXA
Circuit 1 Circuit Mode: [Circuit mode]
Next
Circuit 1 evaporator refrigerant pressure XXX bar Circuit 1 condenser refrigerant pressure XXX bar
Next
Circuit 1 compressor suction refrigerant temperature XXX.X C Circuit 1 saturated evaporator refrigerant temperature XXX.X C
Next
Circuit 1 saturated condenser refrigerant temperature XXX.X C
Next
All others RTXA
Circuit 2 Circuit Mode: [Circuit mode]
Next
Circuit 2 evaporator refrigerant pressure XXX bar Circuit 2 condenser refrigerant pressure XXX bar
Next
Circuit 2 compressor suction refrigerant temperature XXX.X C Circuit 2 saturated evaporator refrigerant temperature XXX.X C
Next
Circuit 2 saturated condenser refrigerant temperature XXX.X C
Next
8
Page 9
Compressor report
* Display will change according to compressor
reviewing
Compressor A mode Compressor B mode Compressor C mode Compressor D mode
[MODE]
Stopped Locked out Waiting for restart inhibit time Starting Running Run-condenser limit Run-evaporator limit Run-current limit Stopping Service pumpdown
Compressor
report
Compressor report: Mode, Hours, Starts, Rated load amps
Press (Next) (Previous) to continue
Next
Compressors on A, B, C, D, NONE Circuits locked out Circuit 1, Circuit 2, NONE
Next
% line volts XXX %
Next
* Compressor A mode [MODE]
Next
Compressor A % Rated load amps, average XXX % Compressor A % Rated load amps, high phase XXX %
Next
Tonnage of unit
130-400 Tons 70-125 Tons
Compressor A entering oil temperature XXX C
Next
Compressor A starts XXXXX Compressor A running hours XXXXX
Next
After review of last compressor Compressor B, C, D
9
Page 10
Operator settings
[SOURCE] Local Tracer
Default = 6.7°C Select = - 17.8 to 18.3°C * If Limited by cutout setpoint, (+) to change is displayed, refer to the section on Leaving water temperature cutout and Low refrigerant temperature cutout.
Default = Disable
Default = 5.5 °C Select = -16 to +2°C This is difference between the entering and leaving chilled water temperature.
Operator
settings
Chiller operation settings and setpoints
Press (Next) (previous) to continue
Next
Setpoint source [SOURCE]
Press (+) (-) to change setting
Next
All others RTXA
Front panel chilled water setpoint XXX C
Press (+) (-) to change setting
Next
External chilled water setpoint [Disable/Enable]
Press (+) (-) to change setting
Next
Design delta temperature setpoint XXX C
Press (+) (-) to change setting
Front Panel Chilled Water Setpoint XXX C
Press (+) (-) to change setting
Default = 1.1°C Select = 16.6 to 1.1°C The temperature which is added the chilled water setpoint, at which the chiller will start.
Front Panel Hot Water Setpoint XXX C
Press (+) (-) to change setting
External Chilled Water Setpoint [Disable/Enable]
Press (+) (-) to change setting
External Hot Water Setpoint [Disable/Enable]
Press (+) (-) to change setting
Cooling Design Delta Temperature Setpoint XXX C
Press (+) (-) to change setting
Heating Design Delta Temperature Setpoint XXX C
Press (+) (-) to change setting
Differential to start setpoint XXX C
Press (+) (-) to change setting
Next
10
Page 11
Default = ON. Manual override of chilled water pump off delay AUTO = activates the Chilled water pump off delay
[MINUTES] Default = 10 minutes Select = 1 minute to 30 minutes The time period that the chilled water pump will run, once the stop signal is given to the chiller.
Default = 120% Select = 40% to 120%
Chilled water pump [ON, AUTO]
Press (+) (-) to change setting
Next
Chilled water pump off delay [MINUTES]
Press (+) (-) to change setting
Next
Front panel current limit setpoint XXX %
Press (+) (-) to change setting
Next
Default = Disable
Default = Disable
Default = -6.6°C Select: -28°C to 16°C
External current limit setpoint [Disable/Enable]
Press (+) (-) to change setting
Next
Low ambient lockout [Disable/Enable]
Press (+) (-) to change setting
Next
Low ambient lockout
(Operator settings menu)
Enable Disable
Low ambient lockout setpoint XXX C
Press (+) (-) to change setting
Next
11
Page 12
Default = Disable Select = Return water Zone Outdoor air
Chilled water reset type [TYPE]
Press (+) (-) to change setting
Next
Type of chilled water reset selected above
Return water Zone Outdoor air Disable
[TYPE] Return water
Default = 50% Range = 10% to 120%
Zone
Default = 100% Range = 50% to 300%
Outdoor
Default = 10% Range = -80% to 80%
[TYPE] Return:
Default = 2,7°C Range = 0° to 11°C
Zone
Default = 25°C Range = 10 to 55°C
Outdoor
Default = 32°C Range = 10 to 55°C
[TYPE] Return water
Default = 2,7°C Range = 0° to 11°C
Zone
Default = -15°C Range = 0° to 11°C
Outdoor
Default = 2,7°C Range = 0° to 11°C
Default = Disable
[TYPE] type, reset ratio XXX %
Press (+) (-) to change setting
Next
[TYPE] type, start reset setpoint XXX C
Press (+) (-) to change setting
Next
[TYPE] type, max reset setpoint Press (+) (-) to change setting
Next
Ice machine control [Disable/Enable]
Press (+) (-) to change setting
Default = -3°C Select = -7 to -1°C
Panel ice termination setpoint XXX F
Press (+) (-) to change setting
Next
12
Page 13
Service settings
Service settings
Service settings, enable and units
Press (Next) (Previous) to continue
Next
Status of keypad/display lock feature
(Service setting menu)
Enable Disable
Press (Enter) to lock display and keypad
password will be required to unlock
* If the keypad is locked and a diagnostic occurs,
the alarm light will flash if applicable but the diagnostic screen will not be displayed until the keypad is unlocked.
** Once the keypad is locked the PREVIOUS and
ENTER key need to be pressed simultaneously to unlock the keypad.
Default = Disable The optional under/over voltage transformer is needed for this feature.
Default = 460 Selections = 200, 220, 230, 346, 380, 415, 460, 500,
575.
Default = 120 seconds select = 30 to 120 seconds The time period between power-up or stop and the initiation of the compressor start sequence, when there is a call for cooling.
Default = Disable
Next
Depress either Enter or Next
Enter
*
***DISPLAY AND KEYPAD ARE LOCKED ***
*** ENTER PASSWORD TO UNLOCK ***
** Previous Enter
Display will return to
Chiller operating mode
under chiller report
Under/Over voltage protection [Disable/Enable]
Press (+) (-) to change setting
Next
Unit line voltage [VOLT] V
Press (+) (-) to change setting
Next
Restart inhibit time XXX SEC
Press (+) (-) to change setting
Next
Balanced compressor start and hours [Disable/Enable]
Press (+) (-) to change setting
Next
[UNITS] SI English
[LANGUAGE] English / Français / Espanol / Nippon / Italiano / Deutsch / Nederlands
Default = 1 Select = 1 to 12
Default = Disable
Next
Display units [UNITS]
Press (+) (-) to change setting
Next
Language [LANGUAGE]
Press (+) (-) to change setting
Next
** Programmable relay setup XX
Press (+) (-) to change setting
Next
External circuit lockout [Disable/Enable]
Press (+) (-) to change setting
Next
*** Password required for further access
Please enter password
Next
13
Page 14
Service tests
Service
tests
Service tests: pumpdown, electronic expansion valve,
compressor, lockout
Press (Next) (Previous) to continue
Next
Default = Disable Must be manually enabled by sevice personnel from the UCM. The unit must be in STOP/RESET and can be performed only once for every power­up of the UCM. Restart inhibit will be prepositioned and the compressor selected will start and run for one minute. Manual closing of the liquid line angle valve will be required.
Default = Disable
Default = Disable
Default = Disable
Service pumpdown, compressor A [Disable/Enable]
Press (+) (-) to change setting
Next
Is there a compressor B ?
Yes No
Service pumpdown, compressor B [Disable/Enable]
Press (+) (-) to change setting
Next
Is there a compressor C ?
Yes No
Service pumpdown, compressor C [Disable/Enable]
Press (+) (-) to change setting
Next
Is there a compressor D ?
Yes No
Service pumpdown, compressor D [Disable/Enable]
Press (+) (-) to change setting
Default = Disable Electronic expansion valve test will be initiated when the unit is in STOP/RESET and Electronic expansion valve test is set to enable. The mode will automatically be reset to disable upon completion of the test.
Default = Disable
Default = Disable Allows service personnel to override the lead/lag function and start the compressor of concern. After the compressor starts, the display will automatically return to D.
Default = Disable
Next
Electronic expansion valve test, circuit 1
Press (+) (-) to change setting
Next
Electronic expansion valve test, circuit 2
Press (+) (-) to change setting
Next
Compressor test, compressor A [Disable/Enable]
Press (+) (-) to change setting
Next
Is there a compressor B ?
Yes No
Compressor test, compressor B [Disable/Enable]
Press (+) (-) to change setting
Next
Is there a compressor C ?
Yes No
Default = Disable
Compressor test, compressor C [Disable/Enable]
Press (+) (-) to change setting
Next
14
Page 15
Is there a compressor D ?
Yes No
Default = Disable
Default = UNLOCK If the setting is changed to LOCKOUT, the circuit will become non-operational. The setting must be manually changed to UNLOCK to regain operation of the circuit.
Default = UNLOCK
Compressor test, compressor D [Disable/Enable]
Press (+) (-) to change setting
Next
Circuit lockout, circuit 1 [UNLOCK/LOCKOUT]
Press (+) (-) to change setting
Next
Circuit lockout, circuit 2 [UNLOCK/LOCKOUT]
Press (+) (-) to change setting
Next
15
Page 16
Diagnostics
If there are no diagnostic messages, the selected menu item will be displayed continuously. If the diagnostics key is pressed and there are no active diagnostics, the readout on the display will be:
NO ACTIVE DIAGNOSTICS PRESENT
When a system malfunction occurs, one of the following appropriate diagnostic messages will be displayed:
*** A machine shutdown has occurred ! ***
A machine shutdown occurred
but has cleared press (Next)
*** A circuit shutdown has occurred ! ***
A circuit shutdown occurred
but has cleared press (Next)
*** Informational warning ***
An informational warning occurred
but has cleared press (Next)
When a circuit shutdown - manual reset (CMR) or a machine shutdown - manual reset (MMR) occurs, the red LED to the right of the display will flash. Otherwise this alarm LED is de-energized.
If more than one diagnostic is present, only the highest priority active diagnostic will be explained in detail. For example, if the diagnostics occur in the following order before the operator returns - IFW, MMR, CMR - the display will read:
*** A machine shutdown has occurred ! ***
because the MMR has the highest priority. However, as the operator moves through the diagnostic menu to the Last diagnostic, the [Diagnostic description] will show the CMR diagnostic as well as the IFW. If the Next key is pressed, the display will show all the other active and historic diagnostics.
The active diagnostic priorities, listed from highest to lowest are:
Machine shutdown - manual reset (MMR)
Machine shutdown - automatic reset (MAR)
Circuit shutdown - manual reset (CMR)
Circuit shutdown - automatic reset (CAR)
Informational warning (IFW)
The following flowchart shows the display readouts found under the diagnostics menu. By following the steps shown in the flowchart, a brief description of the diagnostic can be viewed. Use the Next key to enter the main diagnostic menu, where the diagnostic can be cleared.
16
Page 17
Diagnostics
Note:
MMR: Machine shutdown manual reset. MAR: Machine shutdown automatic reset.
CMR: Circuit shutdown manual reset. CAR: Circuit shutdown automatic reset. IFW: Informational warning.
Diagnostics
Diagnostic present
Yes
Type of diagnostic
MMR/MAR Active
*** A machine shutdown has occurred ! ***
Press (Next) for diagnostic info
Next
Type of machine shutdown
MMR
[Diagnostic description]
Latched fault - manual reset required
Next
All others RTXA
Mode at fault: [OPERATING MODE] Compressors running at fault: [A, B, C, D]
No
Other
MAR
[Unit operating mode]
Cooling Mode Heating Mode Defrost Mode
[Unit operating mode] [Operating mode] Compressors running at fault: [A, B, C, D]
Next
Press (Enter) to reset control
and clear all active diagnostics
Enter
Next
Press Enter or Next
Enter
Machine will unload if loaded and display will automatically
return to MODE in the chiller report
[DIAGNOSTIC DESCRIPTION]
Active fault - May clear automatically
Next
All others RTXA
Mode at fault: [Operating mode] Compressors running at fault: [A, B, C, D]
[Unit operating mode] [Operating mode] Compressors running at fault: [A, B, C, D]
Type of diagnostic
MAR inactive
*** A circuit shutdown has occurred ! ***
Press (Next) for diagnostic information
17
Other
Next
Page 18
Note:
MMR: Machine shutdown manual reset. MAR: Machine shutdown automatic reset.
CMR: Circuit shutdown manual reset. CAR: Circuit shutdown automatic reset. IFW: Informational warning.
Type of diagnostic
CMR/ CAR active
Latched fault - manual reset required
Press (Next) for more
Type of circuit shutdown
Latched fault - manual reset required
Press (Next) for more
Did diagnostic occur
on Circuit 1 or Circuit 2?
Circuit 1
Press (Enter) to
reset circuit 1 diagnostics
Other
Next
CAR
CMR
Next
Circuit 2
Next
Next
Next
Next
Enter
Reset Circuit 1 diagnostic
Press (Enter) to
reset circuit 2 diagnostics
Enter
Reset Circuit 2 diagnostic
Active fault - can clear automatically
Press (Next) for more
Other
Type of diagnostic
CAR inactive
A circuit shutdown occurred
but has cleared Press (Next)
IFW inactive
Type of diagnostic
18
IFW active
*** Informational warning ***
Press (Next) for diagnostic info
Next
Page 19
Next
An informational warning occurred
but has cleared Press (Next)
No active diagnostics present
Press (Next) (Previous) to continue
Next
Are there diagnostics
in history ?
Diagnostic status report follows
Press (Next) (Previous) to continue
Next
Last diagnostic:
[DIAGNOSTIC DESCRIPTION]
No
Yes
Next
Next
Next
[DIAGNOSTIC DESCRIPTION]
[DIAGNOSTIC TYPE]
No historic diagnostics present
Press (Next) (Previous) to continue
Next
Press (Enter) to
clear diagnostic history
Next
Press (Enter) to
reset circuit 1 diagnostics
Next
Press (Enter) to
reset circuit 2 diagnostics
Next
Press (Enter) to reset control
and clear all active diagnostics
Next
Press Enter or Next
19
Enter
Machine will unload if loaded and
display will automatically return to
MODE in the chiller report.
Page 20
Defaults description
Fault 87 Check External Chilled Water Setpoint: IFW - Value out of range
Fault 89 Check External Current Limit Setpoint: IFW - Value out of range
Fault 8A Chilled Water Flow (Entering Water Temperature): MMR 1) Entering water temperature
< leaving water temperature
2) No water flow
3) Defective Evaporator sensor Fault 8E Evaporator Entering Water Temperature Sensor: MMR - Defective sensor
Fault 8F Condenser Refrigerant Temperature Sensor - Circuit 1: MMR - Defective sensor
Fault 90 Condenser Refrigerant Temperature Sensor - Circuit 2: MMR - Defective sensor
Fault 93 Evaporator Refrigerant Temperature Sensor - Circuit 1: MMR - Defective sensor
Fault 94 Evaporator Refrigerant Temperature Sensor - Circuit 2: MMR - Defective sensor
Fault 9A Condenser Entering Water Temperature Sensor: IFW - Defective sensor
Fault 9b Condenser Leaving Water Temperature Sensor: IFW - Defective sensor
Fault A0 Zone Temperature Sensor: IFW - Defective sensor
Fault A1 Outdoor Air Temperature Sensor: IFW - Defective sensor
Fault Ab Evaporator Leaving Water Temperature Sensor: MMR - Defective sensor
Fault b5 Low Pressure Cutout - Circuit 1: CMR - Low pressure switch open
Fault b6 Low Pressure Cutout - Circuit 2: CMR - Low pressure switch open
Fault bA Overload trip - Compressor A: CMR - Current exceeded
Fault bb Overload Trip - Compressor B: CMR - Current exceeded
Fault bC Overload trip - Compressor C: CMR - Current exceeded
Fault bd Overload trip - Compressor D: CMR - Current exceeded
Fault bE High Pressure Cutout - Compressor C: CMR - High pressure too high
Fault bF High Pressure Cutout - Compressor D: CMR - High pressure too high
20
Page 21
Fault C5 Low Chilled Water Temperature (Unit Off): IFW - Antifreeze protection
Fault C6 Low Chilled Water Temperature (Unit On): MAR - Antifreeze protection
Fault CA Contactor - Compressor A: MMR - Welded compressor contactor
Fault Cb Contactor - Compressor B: MMR - Welded compressor contactor
Fault CC Contactor - Compressor C: MMR - Welded compressor contactor
Fault Cd Contactor - Compressor D: MMR - Welded compressor contactor
Fault d7 Over Voltage: MAR - Voltage 10% > nominal
Fault d8 Under Voltage: MAR - Voltage 10% < nominal
Fault Ed Chilled Water Flow Interlock: MAR - Flow switch open more than 6 seconds
Fault F5 High Pressure Cutout - Compressor A: MMR - High pressure too high
Fault F6 High Pressure Cutout - Compressor B: MMR - High pressure too high
Fault Fd Emergency Stop Input: MMR - Emergency stop input open
Fault 180 Starter Transition - Compressor A: CMR 1) Transition proof signal not received
2) Proof input shunted
Fault 181 Starter Transition - Compressor B: CMR 1) Transition proof signal not received
2) Proof input shunted
Fault 182 Starter Transition - Compressor C: CMR 1) Transition proof signal not received
2) Proof input shunted
Fault 183 Starter Transition - Compressor D: CMR 1) Transition proof signal not received
2) Proof input shunted
Fault 184 Phase Reversal - Compressor A: CMR - Phase reversed
Fault 185: Phase reversal - Compressor B CMR - Phase reversed
Fault 186 Phase reversal - Compressor C: CMR - Phase reversed
Fault 187 Phase reversal - Compressor D: CMR - Phase reversed
Fault 190 Low Superheat - Circuit 1: CMR - Superheat < 1°C during more than
1333°C x seconds
21
Page 22
F
ault 191
Low Superheat - Circuit 2: CMR - Superheat < 1°C during more than 1333°C x seconds
Fault 194 Low Evaporator Refrigerant Temperature. - Circuit 1: CMR - Refrigerant temperature < setpoint during more than
30°C x seconds
Fault 195 Low Evaporator Refrigerant Temperature. - Circuit 2: CMR - Refrigerant temperature < setpoint during more than
30°C x seconds
Fault 198 Low Oil Flow - Compressor A: CMR - Oil flow switch open during more than 20 seconds
Fault 199 Low Oil Flow - Compressor B: CMR - Oil flow switch open during more than 20 seconds
Fault 19A low Oil Flow - Compressor C: CMR - Oil flow switch open during more than 20 seconds
Fault 19b Low Oil Flow - Compressor D: CMR - Oil flow switch open during more than 20 seconds
Fault 19C Phase Loss - Compressor A: CMR - Loss of 1 or more phases
Fault 19d Phase Loss - Compressor B: CMR - Loss of 1 or more phases
Fault 19E Phase Loss - Compressor C: CMR - Loss of 1 or more phases
Fault 19F Phase Loss - Compressor D: CMR - Loss of 1 or more phases
Fault 1A0 Power Loss - Compressor A: CAR - Loss of all three phases in operation
Fault 1A1 Power Loss - Compressor B: CAR - Loss of all three phases in operation
Fault 1A2 Power Loss - Compressor C: CAR - Loss of all three phases in operation
Fault 1A3 Power Loss - Compressor D: CAR - Loss of all three phases in operation
Fault 1A4 Tracer Communication Loss: IFW - Loss of external information
Fault 1A5 Oil Flow Control - Compressor A: CMR - Problem on oil circuit
Fault 1A6 Oil Flow Control - Compressor B: CMR - Problem on oil circuit
Fault 1A7 Oil Flow Control - Compressor C: CMR - Problem on oil circuit
Fault 1A8 Oil Flow Control - Compressor D: CMR - Problem on oil circuit
Fault 1A9 Electronic expansion valve Electric Drive Circuit
- Refrigerant Circuit 1: CMR 1) Electronic expansion valve wiring
2) Defective UCM
3) Defective Electronic expansion valve
4) Defective Electronic expansion valve relay
22
Page 23
Fault 1AA Electronic expansion valve Electric Drive Circuit
- Refrigerant Circuit 2: CMR 1) Electronic expansion valve wiring
2) Defective UCM
3) Defective Electronic expansion valve
4) Defective Electronic expansion valve relay Fault 1Ad Memory Error Type I: IFW - Non Volatile Random Access Memory [NOVRAM}
problem, unit is placed on default setting operating Fault 1AE Low Differential Pressure - Circuit 1: CMR - Delta P< 2,8bar during more than 2 minutes
Fault 1AF Low Differential Pressure - Circuit 2: CMR - Delta P< 2,8bar during more than 2 minutes
Fault 1b2 Severe Phase Unbalance - Compressor A: CMR - Phase imbalance >30%, check current transformer
and unit power supply
Fault 1b3 Severe Phase Unbalance - Compressor B: CMR - Phase imbalance >30%, check current transformer
and unit power supply
Fault 1b4 Severe Phase Unbalance - Compressor C: CMR - Phase imbalance >30%, check current transformer
and unit power supply
Fault 1b5 Severe Phase Unbalance - Compressor D: CMR - Phase imbalance >30%, check current transformer
and unit power supply
Fault 1b6 Compressor Overload Setting - Compressor A: IFW - Check setting of compressor overload
Fault 1b7 Compressor Overload Setting - Compressor B: IFW - Check setting of compressor overload
Fault 1b8 Compressor Overload Setting - Compressor C: IFW - Check setting of compressor overload
Fault 1b9 Compressor Overload Setting - Compressor D: IFW - Check setting of compressor overload
Fault 1bA Phase Unbalance - Compressor A: CMR - Phase imbalance >15%
Fault 1bb Phase Unbalance - Compressor B: CMR - Phase imbalance >15%
Fault 1bC Phase Unbalance - Compressor C: CMR - Phase imbalance >15%
Fault 1bd Phase Unbalance - Compressor D: CMR - Phase imbalance >15%
Fault 1bE Winding Temperature - Compressor A: CMR - Winding temperature > 105°C
Fault 1bF Winding Temperature - Compressor B: CMR - Winding temperature > 105°C
Fault 1C0 Winding Temperature - Compressor C: CMR - Winding temperature > 105°C
Fault 1C1 Winding Temperature - Compressor D: CMR - Winding temperature > 105°C
23
Page 24
Fault 1C6 High Differential Pressure - Circuit 1: CMR - LB/High pressure differential > 24,5 bar
Fault 1C7 High Differential Pressure - Circuit 2: CMR - LB/High pressure differential > 24,5 bar
Fault 1d1 Memory Error Type II: IFW - RAM error
Fault 1d2 Memory Error Type III: IFW - RAM error
Fault 1d3 Compressor Suction Temperature Sensor - Circuit 1:
CMR - Defective sensor
Fault 1d4 Compressor Suction Temperature Sensor - Circuit 2:
CMR - Defective sensor
Fault 1d7 Phase Reversal Protection Lost - Compressor A: CMR - Phase reversal protection not operative
Fault 1d8 Phase Reversal Protection Lost - Compressor B: CMR - Phase reversal protection not operative
Fault 1d9 Phase Reversal Protection Lost - Compressor C: CMR - Phase reversal protection not operative
Fault 1dA Phase Reversal Protection Lost - Compressor D: CMR - Phase reversal protection not operative
Fault 1db Slaved Electronic expansion valve Electronic Drive Circuit - Refrigerant Circuit 1: CMR - Electronic expansion valve electric drive defective
Fault 1dC Slaved Electronic expansion valve Electronic Drive Circuit - Refrigerant Circuit 2: CMR - Electronic expansion valve electric drive defective
Fault 1dd High Oil Temperature - Compressor A: CMR - Oil temperature > 77°C
Fault 1dE High Oil Temperature - Compressor B: CMR - Oil temperature > 77°C
Fault 1dF High Oil Temperature - Compressor C: CMR - Oil temperature > 77°C
Fault 1E0 High Oil Temperature - Compressor D: CMR - Oil temperature > 77°C
Fault 1E1 Oil System Fault - Compressor A: CMR - Oil temperature < condenser saturated temperature
during more than 30 minutes
Fault 1E2 Oil System Fault - Compressor B: CMR - Oil temperature < condenser saturated temperature
during more than 30 minutes
Fault 1E3 Oil System Fault - Compressor C: CMR - Oil temperature < condenser saturated temperature
during more than 30 minutes
Fault 1E4 Oil System Fault - Compressor D: CMR - Oil temperature < condenser saturated temperature
during more than 30 minutes
Fault 1E5 Entering Oil Temperature Sensor - Compressor A: CMR - Defective sensor
24
Page 25
Fault 1E6 Entering Oil Temperature Sensor - Compressor B: CMR - Defective sensor
Fault 1E7 Entering Oil Temperature Sensor - Compressor C: CMR - Defective sensor
Fault 1E8 Entering Oil Temperature Sensor - Compressor D: CMR - Defective sensor
Fault 2A1 Condenser Fan Variable Speed Drive Fault - Circuit 1: IFW - Defective fan speed controller after 5 attempts
Fault 2A2 Condenser Fan Variable Speed Drive Fault - Circuit 2: IFW - Defective fan speed controller after 5 attempts
Note:
MMR: Machine shutdown manual reset. MAR: Machine shutdown automatic reset.
CMR: Circuit shutdown manual reset. CAR: Circuit shutdown automatic reset. IFW: Informational warning.
Communication failures
Fault 410 Loss of Local Display Panel Communication
Fault 412 Chiller Module to Option Module Communication Failure
Fault 413 Chiller Module to Electronic expansion valve Module Communication Failure
Fault 414 Chiller Module to Compressor A Module Communication Failure
Fault 415 Chiller Module to Compressor B Module Communication Failure
Fault 416 Chiller Module Compressor C Module Communication Failure
Fault 417 Chiller Module to Compressor D Module Communication Failure
Fault 418 Chiller Module to Slaved Electronic expansion valve Module Communication Failure
Fault 431 Electronic expansion valve Module to Chiller Module Communication Failure
Fault 434 Electronic expansion valve Module to Compressor A Module Communication Failure
Fault 435 Electronic expansion valve Module to Compressor B Module Communication Failure
Fault 436 Electronic expansion valve Module to Compressor C Module Communication Failure
Fault 437 Electronic expansion valve Module to Compressor D Module Communication Failure
Fault 441 Compressor A Module to Chiller Module Communication Failure
Fault 443 Compressor A Module to Electronic expansion valve Module Communication Failure
25
Page 26
Fault 445 Compressor A Module to Compressor B Module Communication Failure
Fault 451 Compressor B Module to chiller Module Communication Failure
Fault 453 Compressor B Module to Electronic expansion valve Module Communication Failure
Fault 454 Compressor B Module to Compressor A Module Communication Failure
Fault 461 Compressor C Module to Chiller Module Communication Failure
Fault 463 Compressor C Module to Electronic expansion valve Module Communication Failure
Fault 467 Compressor C Module to Compressor D Module Communication Failure
Fault 471 Compressor D Module to Chiller Module Communication Failure
Fault 473 Compressor D Module to Electronic expansion valve Module Communication Failure
Fault 476 Compressor D Module to Compressor C Module Communication Failure
Fault 481 Slaved Electronic expansion valve Module to Chiller Module Communication Failure
Fault 483 Slaved Electronic expansion valve Module to Electronic expansion valve Module Communication Failure
Fault 484 Slaved Electronic expansion valve Module to Compressor A Module Communication Failure
Fault 485 Slaved Electronic expansion valve Module to Compressor B Module Communication Failure
Fault 486 Slaved Electronic expansion valve Module to Compressor C Module Communication Failure
Fault 487 Slaved Electronic expansion valve Module to Compressor D Module Communication Failure
Unit operating mode
Mode A00 Stopped
Mode A01, A02 Auto
Mode A17 Service Pump down
Mode A70 Waiting, Restart Inhibit
Mode A72 Starting
Mode A74 Running
26
Page 27
Mode A75 Running, Current Limit
Mode A76 Running, Condenser Limit
Mode A77 Running, Evaporator Limit
Mode A7E Stopping
Mode A88 Reset
Mode A100 Stopped by Source
Mode A101 Ice Making Complete
Mode A118 Electronic expansion valve Test
Mode A174 Making Ice
Mode A175 Making Ice, Condenser Limit
Mode A177 Making Ice, Evaporator Limit
Mode A200 Low Ambient Temperature Lockout
Mode A234 Manufacturing Test Stopped By Tracer Stopped By Remote Display
Compressor operating mode
Mode 00 Stopped
Mode 16 Locked Out
Mode 17 Service Pumpdown
Mode 70 Restart Inhibited
Mode 72 Starting
Mode 74 Running
Mode 75 Run - Current Limit
Mode 76 Run - Condenser Limit
Mode 77 Run - Evaporator Limit
Mode 7E Stopping
27
Page 28
MMaaiinntteennaannccee ccoonnttrraacctt
It is strongly recommended that you sign a maintenance contract with your local Service Agency. This contract provides regular maintenance of your intallation by a specialist in our equipment. Regular maintenance helps ensure that any malfunction is detected and corrected quickly and minimizes the
TTrraaiinniinngg
The equipment described in this manual is the result of many years of research and continuous development. To assist you in obtaining the best use of it, and maintaining it in perfect operating condition over a long period of time, the manufacturer has available a refrigeration and air conditioning service school. The principal aim of this is to give operators and
possibility that serious damage will occur. Finally, regular maintenance helps ensure the maximum operating life of your equipment. Failure to follow these installation and maintenance instructions may affect your warranty.
maintenance technicians a better knowledge of the equipment they are using, or that is under their charge. Emphasis is particularly given to the importance of periodic checks on the unit operating parameters as well as on preventive maintenance, which can reduce the cost of owning the unit by helping avoid serious and costly breakdown.
The Trane Company An American Standard Company www.trane.com
For more information contact Your local sales office or e-mail us at comfort@trane.com
This publication is a general guide to install, use and properly maintain our products. The information given may be different from the specification for a particular country or for a specific order. In this event, please refer to your nearest office.
All rights reserved. No part of this publication may be reproduced or transmitted in any form or by any means without the written authorization of the manufacturer.
Literature Order Number L80 IM 025 E
Date July 2000
Supersedes L80 IM 025 E - 1297
Stocking Location La Crosse
Since The Trane Company has a policy of continuous product improvement, it reserves the right to change design and specifications without notice.
Société Trane – Société Anonyme au capital de 41500 000 F – Siege Social: 1 rue des Amériques – 88190
Golbey – France – Siret 306 050 188-00011 – RSC Epinal B 306 050 188 Numéro d’identification taxe intracommunanutaire: FR 83 3060501888
Loading...