Trane MS-SVN003-EN, ADAMO MCW 5097BA00, ADAMO MCW 5127BA00, ADAMO MCW 5187BA00, ADAMO MCW 5247BA00 Installation Manual

Page 1
ADAMO
Installation Manual
Split System Wall Type MCW Series 50 Hz
MS-SVN003-EN
January 2003
Page 2
2
MS-SVN003-EN© American Standard Inc. 2003
General Information
General Information
This Installation Manual is given as a guide to good practice in the installation by the installer of MCW mini-split system. Installation procedures should be performed in the sequence that they appear in this manual.
For installing the unit to operate properly and reliably, it must be installed in accordance with these instructions. Also, the services of a qualified service technician should be employed, through the maintenance contract with a reputable service company.
Read this Installation Manual completely before installing the air conditioning system.
About This Manual
Cautions appear at appropriate places in this Installation Manual. Your personal safety and the proper operation of this machine require that you follow them carefully. The Trane Company assumes no liability for installations or servicing performed by unqualified personnel. All phases of the installation of this air conditioning system must conform to all national, provincial, state and local codes.
About The Unit
These MCW units are assembled, pressure tested, dehydrated, charged and run tested before shipment. The information contained in this manual applies to MCW units are designed to operate in cooling mode only.
Trane MCW series offer wall mounted installation to leave the floor space uncluttered, and equipped with LCD wireless remote control.
Reception
On arrival, inspect the unit before signing the delivery note. Specify any damage of the unit on the delivery note, and send a registered letter of protest to the last carrier of the goods within 72 hours of delivery. Notify the dealer at the same time.
The unit should be totally inspected within 7 days of delivery. If any concealed damage is discovered, send a registered letter of protest to the carrier within 7 days of delivery and notify the dealer.
Warning
Warnings are provided at appropriate places in this manual to indicate to installers, operators and service personnel of potentially hazardous situations which, if not avoided, COULD result in death or serious injury.
Caution
Cautions are provided at appropriate places in this manual to indicate to installers, operators, and service personnel of potentially hazardous situations which, if not avoided, MAY result in minor or moderate injury or malfunction of the unit.
Your personal safety and the proper operation of this unit require that you follow them carefully. The Trane Company assumes no liability for installations or servicing performed by unqualified personnel.
Warranty
Warranty is based on the general terms and conditions by country. The warranty is void if the equipment is modified or repaired without the written approval of The Trane Company, if the operating limits are exceeded or if the control system or the electrical wiring is modified.
Damage due to inappropriate installation, lack of knowledge or failure to comply with the manufacturer’s instructions, is not covered by the warranty obligation. If the installation does not conform to the rules described in Installation Manual, it may entail cancellation of warranty and liabilities by The Trane Company.
Important
This document is customer property and is to remain with unit. Please place in service information pack upon completion of work. These instructions do not cover all variations in systems, nor do they provide for every possible contingency to be met in connection with installation. Should further information be desired or should particular problems arise which are not covered sufficiently in this manual, the matter should be referred to your authorized Trane dealer.
Page 3
MS-SVN003-EN
3
Contents
General Information 2
Typical Installation 4
Location and Preparation of Unit 5
Unit Installation 6
Wiring Diagram 12
Dimensional Data 13
Notes 14
Page 4
4
MS-SVN003-EN
Typical Installation
Figure 1
Insulation
Tube
Tapping Screw
Remote Control Holder
Vinyl Tape
Two AAA batteries are used in this remote control unit
Wireless Remote Control
Air Filter
Water
Condensated
Drain Tube
Installation Items
The following items are supplied with the indoor unit to provide proper system installation: 1Wall Bracket : For indoor unit
installation
4Tapping Screw (Large) : For wall
bracket installation
2Tapping Screw (Small) : For remote
control mounting bracket installation
1 Remote Control Holder : For remote
control unit holder
O N
O
F F
Page 5
MS-SVN003-EN
5
Location and Preparation of Unit
Figure 2
100 mm.
50 mm.
100 mm.
500 mm.
Figure 3
25 cm. or more
60 cm. or more
25 cm. or more
120 cm. or more
30 cm. or more
Selecting the Mounting Locations
Determine the mounting location with the customer as follows:
Indoor Unit
• Install the indoor unit level on a strong wall which is not subject to vibration.
• The inlet and outlet ports should not be obstructed. The air should be able to blow throughout the room.
• Install the indoor unit where connection to the outdoor unit can be made easily.
• Install the unit where the drain pipe can be easily installed.
•Take servicing into consideration and leave the spacing shown in Figure 2. Also, install the unit where the filter can be easily removed.
• Do not install the unit near a source of heat, steam, or flammable gas.
• Do not install the unit where it will be exposed to direct sunlight.
Outdoor Unit
• Leave the spacing shown in Figure 3 for required air flow.
• If possible, do not install the unit where it will be exposed to direct sunlight.
• Do not install the unit near a source of heat, steam, or flammable gas.
• Do not install the unit where a strong wind consistently blows or where it is extremely dusty.
• Do not install the unit where people pass in front of the fan discharge grille.
General Instructions
• All phases of the installation of this air conditioning system must conform to all national, provincial, state and local codes.
• Read these instructions carefully and completely before attempting to install the air conditioning system.
• For the air conditioning system to operate properly and reliably, it must be installed in accordance with these instructions.
• The maximum length of the piping is to10 meters. If the units are further apart than this, correct operation can not be guaranteed.
Page 6
6
MS-SVN003-EN
Unit Installation
Figure 4
2.Left rear outlet
3.Left
outlet
4.Right outlet
(Rear)
1.Rear outlet
5.Bottom outlet
Figure 6
Figure 5
Counter Weight
Type A Screw
Marking-off Line
Indoor Unit Installation
The piping can be connected in the five directions indicated by 1, 2, 3, 4 and 5 in Figure 4. When the piping is connected in direction 3, 4 or 5 cut along the piping groove in the side or bottom of the front cover with a saw.
1. Installing the Wall Bracket
1. Install the wall bracket so that it is level from side to side. If the wall bracket is tilted, condensate water will drip to the floor.
2. Install the wall bracket so that it is strong enough to withstand a weight of 50 kilograms or more.
3. Fasten the wall bracket to the wall with 6 or more screws through the holes near the outer edge of the bracket.
4. Check to insure that there is no rattle of the wall bracket against the wall.
Caution
• Always cut the wall hole uniformly and straight when the wall pipe is not used. If the hold center is not aligned, condensate leakage can occur.
• If the wall pipe is not used, the wiring cable connecting the indoor and outdoor units may become frayed and cause electric current leakage to earth.
3. Forming the Indoor Drain Hose and Refrigerant Pipes
1. For 3 Left piping. 4 Right piping,
5 Bottom piping: Perform. “Indoor Unit Wiring” before performing the following steps
3.2 through 3.6.
2. Wrap the pipes of the indoor unit
that are visible from the inside with decorative tape (Figure 7).
3. Insert the indoor unit piping into
the wall hole and bind the drain hose and pipe together with vinyl tape (Figure 8).
2. Cutting the Hole in the Wall for the Connecting Piping
1. Cut a 65 mm. diameter hole in
the wall at the desired position shown in Figure 6.
2. Cut the hole so that the outside
end is lower (5-10 mm.) than the inside end.
3. Cut the wall pipe length to match
the wall thickness, insert it into an accessory wall cap, fasten the cap with vinyl tape, and insert the pipe through the wall hole. (Wall pipe and wall cap are procured at the site).
4. For 3 left piping and 4 right piping, cut the hole sligthly lower so that the condensate water will flow freely.
Installation Plate
Thread
MCW509-512
MCW518-524
Page 7
MS-SVN003-EN
7
Figure 10
Drain hose
Wall hole
pipe
Pipe
Connection
cable
Figure 7
Connection
cable
Drain hose
Decorative tape
Left piping
Left rear piping
Bottom piping
Right piping
Cut the piping groove with a hacksaw
Cut the piping groove with a hacksaw
(Rear)
Indoor unit
piping
For left outlet, house the connection cord and piping at the position shown in the above figure with the drain hose at the bottom.
Figure 11
4. Install the piping so that the drain hose is at the bottom (Figure 7).
Caution
•To prevent breaking of the pipe, avoid sharp bends. Bend the pipe with a radius of curveture of 100 mm. or more.
• If the pipe is bent repeatedly at the same place, it will break.
• Do not remove the flare nuts from the indoor unit pipe until immediately before connecting the outdoor connection piping.
5. After passing the indoor piping and drain hose through the wall hole, hang the indoor unit on the hooks at the top and bottom of the wall bracket.
6. Check to insure that: (Ref. Figure 10).
• The top and bottom hooks are hooked firmly and the indoor unit does not move to the front and rear or left and right.
• The indoor unit is accurately positioned horizontally and vertically.
• The drain hose is at the bottom of the wall hole pipe.
Indoor Unit Wiring
Both of the cable wires should be connect from the terminal block of indoor unit (Figure 11).
• The appliance shall be installed in accordance with national wiring regulation.
• Means for disconnection from the supply having a contact separation of at least 3 mm. in all poles must be incorporated in the field wiring.
Figure 9
After hooking the indoor unit to the top hook, hook the fitting of the indoor unit to the two bottom hooks while lowering the unit and pushing it against the wall.
Wall hook
bracket
Indoor unit
(Rear)
(Fitting)
Bottom hooks
To p
hooks
Figure 8
Drain hose
(bottom)
Bind with vinyl tape
Pipe (top)
(Rear)
Page 8
8
MS-SVN003-EN
A good flare should have the following characteristics:
- Inside surface is glossy and smooth.
- Edge is smooth.
-Tapered sides are of uniform length.
Bending
5. When bending the tube, be careful not to crush it. To prevent crushing of the tube, bend it gently and do not bend the tube at a radius curvature of less than 100 mm.
3. Remove the flare nut from the unit and be sure to mount it on the copper tube.
4. Make a flare at the end of copper tube with a flare tool (Figure 14,15).
Outdoor Unit Installation
1. Install the unit mounting pads (4 places) into the bottom channels by tapping gently with a plastic or rubber tipped hammer.
2. Set the unit on a strong surface such as one made of concrete to minimize shock and vibration and to locate the unit securely.
3. Do not set the unit directly on the
ground.
Connecting the Unit with Flaring Procedure.
Flaring (If piping is procured or cut at the site).
1. Cut the copper tube to the
required length with a tube cutter. It is recommended to cut approx. 30-50 cm. longer than the tubing length you estimate.
2. Hold each pipe downward when
cutting and remove burrs at the end of the copper tube with a tube reamer or file. This process is important and should be done carefully to make a good flare (Figure 12 and Figure 13).
Flare nut
Copper tubing
Flare tool
Figure 14
Figure 15
L
Check if (L) is flared uniform and is not cracked or scratched. L Dimension:
1.4 to 1.7 mm (6.35 mm dia)
1.8 to 2.0 mm (9.53 mm dia)
1.9 to 2.2 mm (12.7 mm dia)
2.1 to 2.4 mm (15.88 mm dia)
Figure 12
Copper
tubing
Reamer
Figure 13
Deburring
Before After
6. If the copper tube is bent or pulled too often, it will become stiff. Do not bend the pipe more than three times at one place.
Cautions before Connecting Tubes Tightly
7. Be sure to apply a sealing cap or water-proof tape to prevent dust or water from getting into the tubes before they are used.
8. Be sure to apply refrigerant lubricant to the matching surfaces of the flare and union before connecting them together. This is effective for reducing gas leaks (Figure 16).
Figure 16
Apply refrigerant lubricant here
Figure 17
Union Flare nut
Connection
9. For proper connection, align the union tube and flare tube straight with each other, then screw in the flare nut lightly at first to obtain a smooth match (Figure 17).
When reaming, hold the tube end downward and be sure that no copper scraps fall into the tube.
10. Tighten the flare nut to the specified tightening torque with torque wrench and adjustable wrench (Figure 18).
11. Repeat the process above for the remaining line.
Page 9
MS-SVN003-EN
9
Indoor unit pipe
To rque wrench
Flare nut
Connection pipe
Wrench
(adjustable).
Figure 18
Flare Nut Tightening Torque
Flare nut/Piping size Tightening torque
kgf, - cm lbf-in
6.35 mm (1/4”) dia. 150~200 130~170
9.53 mm (3/8”) dia. 350~400 300~340
12.7 mm (1/2”) dia. 500~550 430~470
15.88 mm (5/8”) dia. 600~650 520~570
Remote Control Installation
Locate and attach the wireless remote control as follows:
1. Do not place the control and the remote control near heat sources or expose to the direct rays of the sun.
2. Do not expose the control to the indoor unit’s supply air stream.
3. Do not place in a confined space.
4. Attach the remote control holder as shown in Figure 19.
Evacuation and Refrigerant Charge
1. Air Evacuation and Charging
1. Remove the cap and connect the gauge manifold and the vacuum pump to the charging port using the service hoses (Figure 20).
2. Pump the indoor unit and the connecting pipes until the pressure in them lowers to below
1.5 mmHg of vacuum.
3. Stop the vacuum pump and close the gauge manifold valve.
4. Remove the blanking caps and fully open the service valves with a hexagon wrench (Torque: 70 to 90 kgf - cm).
Remote
Control
Unit
ON OFF
Remote Control Holder
Tapping Screw
(small)
Wireless Remote Control
Figure 19
Page 10
10
MS-SVN003-EN
Figure 22
Pipe length 16ft 23ft 33ft
(5m) (7m) (10m)
Additional refrigerant None 1.1 oz 2.8 oz (R22) (32g) (80g)
5. Reinstall the blanking caps of the service valves.
6. Disconnect the service hoses and reinstall the cap on the charging port. (Tightening torque: 70 to 90 kgf - cm).
2. Additional Charge
Refrigerant suitable for a piping length of 3.5 to 5.0 meters is charged in the outdoor unit from the factory. When the piping is longer than 5 m, additional charging is necessary. For the additional amount, see table below.
Outdoor Unit
Figure 20
Refrigerant pipe
Blank cap
Charging port
Cap
Service hose
with valve core
Service valve
Gauge manifold
Vacuum
pump
Service hose
Between 5 m and 10 m, when using connection pipe lengths other than that in the table, charge additional refrigerant with 0.56 oz (16g)/3.3ft.
Caution
• FREON GAS “R22” ONLY
• Always evacuate air from the piping before adding refrigerant.
• Add refrigerant through the charging valve after the completion of removing the blanking caps and fully open the service valves.
Gas Leakage Inspection
After charging with refrigerant, check the joints for gas leakage with gas leak detector or a soap bubble solution.
Figure 21
Outdoor Unit Wiring
1. Remove the outdoor unit terminal cover (Figure 21).
2. Route the connection cable through the cable entry brushing and up to the terminal block.
3. Insert the end of the cable wires into the terminal block connectors as shown on the unit wiring diagram (Figure 11).
4. Tighten the terminal block connector screws. (Torque: 7-12 kgf-cm).
• The appliance shall be installed in accordance with national wiring regulation.
Caution
• The connector cable wires must be connected such that terminal numbers on the indoor unit match those on the terminal block of the outdoor unit (Figure 11).
• Insert the connection cable wires into the terminal block firmly. Incorrect insertion may cause a safety problem.
5. Replace the outdoor unit terminal cover.
Drain hose
Page 11
MS-SVN003-EN
11
Figure 23
Pipe
Clamp
Wall
Outside wall cap sealer
(Outdoor)
End in water
Figure 24
Check the following:
Drain hose
Clamp
Lifted up
Wave
Finishing
1. Securely wrap the connection cable along the refrigerant pipes with vinyl tape. (Starting at the lowest end of the pipes, each wrap should be about 1/3 of the tape width so that water does not enter).(Figure 22)
2. Fasten the cable/piping to the outside wall with clamps, etc.
3. Fill the gap between the outside wall cap and the pipe with sealer so that rain water and wind cannot blow in.
4. Fasten the drain hose to the outside wall, etc (Figure 23 & Figure 24).
Run Test
1. Start the system and check items 1 through 7 below.
2. For the system start procedure, refer to the Owner Manual.
Indoor Unit
1. Is operation of the on and off button and fan button normal?
2. Does each indicator on the remote control display panel light normally?
3. Does the air deflection louver operate normally?
4. Is the condensate drain normal and freely flowing water?
Outdoor Unit
5. Is there any abnormal noise and vibration during operation?
6. Will noise, air flow, or drain water from the unit disturb the neighbors?
7. Is there any refrigerant gas leakage?
Customer Guidance
Explain the following to the customer in accordance with the Owner Manual.
1. Starting and stopping procedures, mode switching, temperature adjustment, timer and air flow adjustment, and other remote control operations.
2. Filter removal and cleaning and how to use the air louvers.
3. Give the operating and installation manuals to the customer.
Front Panel Assemble Removal and Replacement
1. Removal
Side out the plastic screw cap (3 pieces as shown in the picture.) Remove the front panel screws (3 pieces.) Remove the horizontal vane to the position as shown in the picture. Open the front panel by lifting the lower side of the panel carefully
2. Replacement
After securing the front panel tabs into the holes in the body, fasten the bottom of the front panel with the three screws removed in step 1.
Front panel
Mounting screw
Horizontal vane
Figure 25
Page 12
12
MS-SVN003-EN
Wiring Diagram
Page 13
MS-SVN003-EN
13
Dimensional Data
MODEL DIMENSIONS (MM.) CLEARANCE (MM.) WEIGHT (KG.)
ABCDEF
MCW 5097BA00 900.00 180.00 265.00 10.00
MCW 5127BA00 900.00 180.00 265.00 100.00 50.00 500.00 10.00
MCW 5187BA00 1,165.00 180.00 310.00 14.00
MCW 5247BA00 1,165.00 180.00 310.00 14.00
A
D
F
D
B
C
E
Page 14
14
MS-SVN003-EN
Notes
Page 15
MS-SVN003-EN
15
Notes
Page 16
Since The Trane Company has a policy of continuous product and product data improvement, it reserves the right to change design and specifications without notice.
Literature Order Number: MS-SVN003-EN 0103
Supersedes: MS-SVN003-EN 1200
Stocking Location: Bangkok, Thailand
Trane Thailand
7th Floor, Ploenchit Center Building 2 Sukhumvit Road, Klongtoey Bangkok 10110
Amair Limited
35 Mu 8, Poochaosamingprai Road Samrong Tai, Samutprakarn 10130
http://www.trane.com An American Standard Company
∫√‘…—∑ ·Õ¡·Õ√å ®”°—¥ 35 À¡Ÿà 8 ∂.ªŸÉ‡®â“¡‘ßæ√“¬ µ.”‚√ß„µâ Õ.æ√–ª√–·¥ß ®.¡ÿ∑√ª√“°“√ 10130
Loading...