Trane ACONT900AC43UA, TCONT900AC43UA, Charge Assist Service Manual

Air Conditioning Procedures
Service Guide
Communicating Residential
Comfort Systems
A Comprehensive Reference for Service of Communicating
Residential Air Conditioning, Heat Pump & Gas Furnace Systems
First Edition
© 2010 Trane Inc. All rights reserved. No part of this book may be reproduced, in any form or by any means, without permission in writing from the publisher.
Produced and printed in the USA
1.0
We appreciate your feedback.....
We value your opinion. If you feel this service guide can be improved in some way, please give us your thoughts. Simply email your opinion to Loran.dailey@irco.com. You may also write in the space below , tear out this p age and mail it to:
Trane Company
Attn: Loran Dailey
6200 Troup Hwy.
Tyler , TX 75707
Comments
Air Conditioning Procedures
Name: Address: Email: Phone#
Pub# 034-3457-01
We appreciate your feedback.....
We value your opinion. If you feel this service guide can be improved in some way, please give us your thoughts. Simply email your opinion to Loran.dailey@irco.com. You may also write in the space below , tear out this p age and mail it to:
Trane Company
Attn: Loran Dailey
6200 Troup Hwy.
Tyler , TX 75707
Comments
Air Conditioning Procedures
Name: Address: Email: Phone#
Pub# 034-3457-01
WARNING
!
Cautions & Warnings
Throughout this manual there are procedures where voltage may be present and gas or refrigerant system checks may be required. Read all cautions and warnings on this page before proceeding.
W ARNING
!
SAFETY HAZARD
THIS INFORMATION IS INTENDED FOR USE BY INDIVIDUALS POSSESSING ADEQUA TE BACKGROUNDS OF ELECTRICAL AND MECHANICAL EXPERIENCE. ANY ATTEMPT T O REPAIR A CENTRAL AIR CONDITIONING PRODUCT MA Y RESUL T IN PERSONAL INJURY AND OR PROPERTY DAMAGE. THE MANUFACTURER OR SELLER CANNOT BE RESPONSIBLE FOR THE INTERPRET ATION OF THIS INFORMATION, NOR CAN IT ASSUME ANY LIABILITY IN CONNECTION WITH ITS USE.
W ARNING
!
FIRE OR EXPLOSION HAZARD
FAILURE TO FOLLOW THE SAFETY WARNINGS EXACTLY COULD RESUL T IN SERIOUS PERSONAL INJURY , PROPERTY DAMAGE, OR DEATH. IMPROPER SER VICING COULD RESULT IN DANGEROUS OPERA TION, SERIOUS PERSONAL INJURY , PROPERTY DAMAGE, OR DEA TH.
W ARNING
!
SERVICE PROCEDURES HAZARD
BODILY INJURY CAN RESULT FROM HIGH VOLTAGE ELECTRICAL COMPONENTS, FAST MOVING FANS, AND COMBUSTIBLE GAS. FOR PROTECTION FROM THESE INHERENT HAZARDS DURING INSTALLATION AND SERVICING, THE ELECTRICAL SUPPLY MUST BE DISCONNECTED AND THE MAIN GAS VALVE MUST BE TURNED OFF . IF OPERATING CHECKS MUST BE PERFORMED WITH THE UNIT OPERATING, IT IS THE TECHNICIAN’S RESPONSIBILITY TO RECOGNIZE THESE HAZARDS AND PROCEED SAFEL Y .
W ARNING
!
V oltage Hazard
Disconnect power to the unit before removing the blower door. Allow a minimum of 10 seconds for IFC power supply to discharge to 0 volts. Failure to follow this warning could result in property damage, personal
injury or death.
W ARNING
!
CARBON MONOXIDE POISONING HAZARD
FAILURE TO FOLLOW THE SER VICE AND/ OR PERIODIC MAINTENANCE INSTRUCTIONS FOR THE FURNACE AND VENTING SYSTEM, COULD RESUL T IN CARBON MONOXIDE POISONING OR DEATH.
W ARNING
!
FIRE OR EXPLOSION HAZARD
SHOULD OVERHEATING OCCUR, OR THE GAS SUPPL Y FAIL TO SHUT OFF, SHUT OFF THE GAS VALVE TO THE UNIT BEFORE SHUTTING OFF THE ELECTRICAL SUPPL Y . FAILURE TO FOLLOW THIS WARNING COULD RESUL T IN PROPERTY DAMAGE, PERSONAL INJURY , OR DEA TH.
CAUTION
!
Safety Hazard
Sharp Edge Hazard Be careful of sharp edges on equipment or any cuts made on sheet metal while installing or servicing. Personal injury may result.
Where there is no complete return duct system, the return connection must be run full size from the furnace to a location outside the utility room, basement, attic, or crawl space.
Do NOT install return air through the back of the furnace cabinet.
Do NOT install return air through the side of the furnace cabinet on horizontal applications.
NOTE: Minimum return air temperature is 55°F.
CAUTION
!
CONTAINS REFRIGERANT!
SYSTEM CONT AINS OIL AND REFRIGERANT UNDER HIGH PRESSURE. RECOVER REFRIGERANT TO RELIEVE PRESSURE BEFORE OPENING SYSTEM. Failure to follow proper procedures can result in personal illness or injury or severe equipment damage.
CAUTION
!
LABELING WIRES!
LABEL ALL WIRES PRIOR TO DISCONNECTION WHEN SERVICING CONTROLS. WIRING ERRORS CAN CAUSE IMPROPER AND DANGEROUS OPERA TION. VERIFY PROPER OPERATION AFTER SERVICING .
CAUTION
!
BURN HAZARD
DO NOT TOUCH IGNITER. IT IS EXTREMEL Y HOT .
A 1
Cautions & Warnings
A 2
Communicating Programmable 3-Wire Hookup
4 Heat/3 Cool/ Heat Pump
(A/T)CONT900AC43UA Installer Guide
Communicating Controller
Section A
Introduction........................................................................................................................................ 3
Product specifications ................................................................................................................... 3
Installation.......................................................................................................................................... 3
When installing this product .......................................................................................................... 3
Location......................................................................................................................................... 4
Selecting Comfort Control location ............................................................................................... 4
Sub-base installation ..................................................................................................................... 4
Wiring............................................................................................................................................ 5
Mounting Comfort Control on sub-base......................................................................................... 6
Initial power-up .................................................................................................................................. 6
Power-up sequence....................................................................................................................... 6
Discovery mode ............................................................................................................................ 6
Communicating indoor unit - Communicating outdoor unit ........................................................... 7
Communicating indoor unit - Single stage cooling unit ................................................................. 7
Adjusting real time clock .................................................................................................................. 7
Setting calendar and time ............................................................................................................. 7
Installer setup (ISU) ........................................................................................................................... 8
Entering installer setup.................................................................................................................. 8
Operation: Using the Comfort Control .......................................................................................... 18
System and fan settings .............................................................................................................. 18
Fan settings................................................................................................................................. 18
LED indication ............................................................................................................................. 18
Filter indication............................................................................................................................ 18
Pre-programmed ......................................................................................................................... 18
Alert code numbers ..................................................................................................................... 18
Equipment damage hazard. Minimum compressor off-time is bypassed during installer
System test ..................................................................................................................................19
System checkout ............................................................................................................................. 19
Installer system test..................................................................................................................... 19
Advanced features........................................................................................................................... 19
Adjustable continuous air flow..................................................................................................... 19
Control response rate .................................................................................................................. 20
Cycle rate .................................................................................................................................... 20
Auto changeover ......................................................................................................................... 20
C - A 1
(A/T)CONT900AC43UA Installer Guide
Communicating Programmable 3-Wire Hookup
4 Heat/3 Cool/ Heat Pump
Setpoint deadband ...................................................................................................................... 21
Backlit display ............................................................................................................................. 21
Filter reminders ........................................................................................................................... 21
Fan selections ............................................................................................................................. 21
Screen locked.............................................................................................................................. 21
Installer system tests................................................................................................................... 21
Default factory settings................................................................................................................ 21
Wait indicator .............................................................................................................................. 22
Calibrate indoor temperature....................................................................................................... 22
TCONT900AC43UA Installer’s Guide
Calibrate outdoor temperature .................................................................................................... 22
Outdoor temperature sensor ....................................................................................................... 22
Humidification.................................................................................................................................. 22
Indoor humidification control ....................................................................................................... 22
Frost control ................................................................................................................................ 22
Dehumidification ............................................................................................................................. 22
Integrated temperature and humidity control (ITHC)................................................................... 22
Droop ............................................................................................................................................23
Comfort-R™ delay .........................................................................................................................23
Dehumidification airflow .................................................................................................................23
Proprietary humidity control...........................................................................................................23
Special heat pump features ............................................................................................................ 23
Auxiliary heat lockout temperature..............................................................................................23
Compressor heat lockout temperature ........................................................................................ 23
Operation in heat mode............................................................................................................... 24
Defrost heater balance point control ........................................................................................... 24
Operation in emergency heat mode ............................................................................................ 24
Heat pump with fossil fuel heat (dual fuel) and outdoor temperature sensor .............................. 24
Troubleshooting guide ................................................................................................................... 25
C - A 2
Communicating Programmable 3-Wire Hookup
4 Heat/3 Cool/ Heat Pump
(A/T)CONT900AC43UA Installer Guide
Introduction
The (A/T)CONT900AC43UA is a communicating pro­grammable Comfort Control (See Table 1) that sup­ports single-stage or multi-stage heat/cool and heat pump applications. It is a wall mounted, low voltage (24V AC) communicating Comfort Control with backlit LCD and a touch screen display . Room temperature is maintained by controlling the operation of heating, cooling, heat pump, and dual fuel systems via digital, two-way communications. The Comfort Control will communicate with and identify all ComfortLink™ II com­ponents in the system. It is easily manually config­ured via the user friendly Installer Setup menu. The Comfort Control feature includes separate heating and cooling setpoints, selectable auto or manual changeover, menu driven 7-day programming, adjust­able filter reminders, and outdoor temperature sens­ing. Setup selections and diagnostics are stored in­definitely in the Comfort Control’s nonvolatile memory , eliminating the need for battery backup.
Product specifications
Power source: 18-30 VAC, Class II, 50/60 Hz Storage range: -30°F to 150°F, 5% to 90% RH non­condensing Operating temperature range: 0°F to 120°F, 5% to 90% RH non-condensing
System mode: Heat, Cool, Auto, Emergency Heat, and Off Fan mode: On, Auto and Circ Cooling setpoint temperature range: 60°F to 99°F, 1°F resolution Heating setpoint temperature range: 50°F to 90°F, 1°F resolution Indoor temperature display range: 40°F to 99°F , Outdoor temperature display range: -40°F to 127°F Indoor humidity display range: 0% to 99%, 1% reso­lution Minimum cycle off time delay: Compressor, 5 min­utes. Heat, 0 minutes.
The comfort control contains a Lithium battery which may contain Perchlorate material. Due to State Law in California, the following st atement is required:
Perchlorate Material-special handling may apply . See
www.dtsc.ca.gov/hazardouswaste/perchlorate
Installation
When installing this product
Step 1
Read these instructions carefully. Failure to follow these instructions may damage the product or cause a hazardous condition.
T able 1
C - A 3
(A/T)CONT900AC43UA Installer Guide
Communicating Programmable 3-Wire Hookup
4 Heat/3 Cool/ Heat Pump
Step 2
Check the ratings given in the instructions and on the product to make sure the product is suitable for your application.
Step 3
Installer must be a trained, experienced service tech­nician.
TCONT900AC43UA Installer’s Guide
Step 4
After completing installation, use these instructions to check out the product operation.
WARNING
Voltage Hazard. Can cause electrical shock or equipment damage. Disconnect power before beginning instructions.
Location
Install the Comfort Control about five feet (1.5m) above the floor in an area with good circulation at average temperature (See Figure 1.)
Figure 1
Selecting Comfort Control location
Do not install the Comfort Control where it can be affected by
• Drafts or dead spots behind doors and in corners.
• Hot or cold air from ducts.
• Radiant heat from sun or appliances.
• Concealed pipes and chimneys.
• Unheated (uncooled) areas such as an outside wall behind the Comfort Control.
Sub-base installation
The Comfort Control can be mounted horizontally on the wall or on a two inch by four inch wiring box. Position sub-base horizontally on the wall or on a two inch by four inch wiring box.
Step 1
Turn OFF all power to heating and cooling equip­ment.
Step 2
If an existing Comfort Control is being replaced:
a.)Remove existing Comfort Control from the wall. b.)Disconnect wires from existing control, one at
a time. Be careful not to allow wires to fall back into wall.
c.) As each wire is disconnected, record wire color
and terminal marking.
d.)Discard or recycle old Comfort Control.
C - A 4
Step 3
Separate the Comfort Control from the sub-base to expose mounting holes.
Step 4
Position and level the sub-base wallplate (for appear­ance only.) The Comfort Control functions properly even when not level.
Communicating Programmable 3-Wire Hookup
4 Heat/3 Cool/ Heat Pump
(A/T)CONT900AC43UA Installer Guide
Step 5
Use a pencil to mark the mounting holes.
Step 6
Remove the sub-base from the wall and drill two 3/ 16” holes in the wall (if drywall) as marked. For firmer material such as plaster, drill two 7/32” holes. Gently tap anchors (provided) into the drilled holes until flush with the wall.
Step 7
Position the sub-base over the holes, pulling the wires through the wiring opening.
Step 8
Insert the mounting screws in the holes and tighten.
Wiring
All wiring must comply with local electrical codes and ordinances. See Figures 2 and 3 wiring diagrams for specific equipment applications. Refer to Table 2 for terminal designations.
Figure 2
Figure 3
Field wiring diagram, Communicating indoor unit - Single stage cooling unit
T able 2
Field wiring diagram, Communicating indoor unit - Communicating outdoor unit
WARNING
Voltage Hazard. Can cause electrical shock or equipment damage. Disconnect power before beginning instructions.
Note:
The maximum cable length for the entire Comfort Control com­municating system is 500 feet 18 AWG. The maximum dis­tance of any single cable from a transformer is 250 feet 18 AWG.
C - A 5
(A/T)CONT900AC43UA Installer Guide
Step 1
Loosen the terminal screws on the sub-base. Insert wires into the terminal block next to the loosened screw (See Figure 4.)
Communicating Programmable 3-Wire Hookup
4 Heat/3 Cool/ Heat Pump
Step 2
Push the Comfort Control straight onto the wallplate (See Figure 4.)
Step 3
Perform installation of all other system equipment.
Figure 4
TCONT900AC43UA Installer’s Guide
Important: Use 18-gauge color-coded Comfort Control cable for proper wiring. Shielded cable is not typically required. Keep this wiring at least one foot away from large inductive loads such as Electronic Air Cleaners, motors, line starters, lighting ballasts, and large distribution panels. Failure to follow there wiring practices may introduce electrical interference (noise) which can cause erratic system operation. All unused Comfort Control wire to be grounded at indoor unit chassis ground only. Shielded cable may be required if the above wiring guidelines cannot be met. Ground the shield only to the system chassis.
Step 2
Securely tighten each terminal screw.
Step 3
Push excess wire back in the hole.
Step 4
Plug the hole in the wall with nonflammable insulation to help prevent drafts from adversely affecting Comfort Control operation.
Mounting Comfort Control on sub-base
Step 1
Align the terminal screw block with the pins on the back of the Comfort Control.
C - A 6
Step 4
Turn ON power to the heating and cooling equip­ment.
Initial power-up
Power-up sequence
The communicating Comfort Control will communicate and identify all communicating components in the sys­tem.
Discovery mode
Discovery mode begins when the communicating Com­fort Control is first installed and power is connected. For communicating equipment, the Comfort Control automatically configures the equipment type, number of stages, cycle rates for each stage and compressor stage ratios based on the information it received dur­ing Discovery mode.
While in Discovery mode, the LED indicator located in the upper right corner of the Comfort Control will be illuminated.
All discovered values will be saved into memory. If a communicating device goes missing (Err 89) or changes in value (Err 126) the error will be broad­cast to the Comfort Control screen (restoring com­munications will clear this error or see ISU 0706 to reset the system configuration.)
The communicating Comfort Control can be reset (ISU 0710) to factory default settings.
Note: ISU 0706 Will force a reinitialization without af­fecting presets. ISU 0710 will reset everything includ­ing custom programs and presets.
Communicating Programmable 3-Wire Hookup
4 Heat/3 Cool/ Heat Pump
If no equipment is connected during the Auto-Discov­ery process, the system mode will be stuck at “OFF” and no equipment will run.
T o change the default/discovery settings, enter the in­staller Setup menu (See Table 4, Pages 9-17) and select the desired item.
Only ISU settings with an “E” will be Auto-Discovered. Manually changing an ISU setting to an option other than “E” disables Discovery mode for that ISU setting.
See Table 3 for default cycle rate settings.
T able 3
(A/T)CONT900AC43UA Installer Guide
Adjusting real time clock
Setting calendar and time
Locate and remove the tab labeled “Remove” in the lower left corner of the Comfort Control back. The tab must be removed to activate the real time clock. (See Figure 5.)
Figure 5
Communicating indoor unit - Communicating outdoor unit
For a fully communicating system, the communicat­ing Comfort Control will automatically configure the indoor and outdoor equipment configuration and cycle rates for each stage (See Figure 2.)
Communicating indoor unit - Single stage cooling unit
For a partially communicating system, the commu­nicating Comfort Control will automatically config­ure the indoor equipment configuration and cycle rates for each stage (See Figure 3.)
The outdoor equipment configuration will default to a single stage cooling unit.
If the system is not powered, the real time clock bat­tery life is approximately 20 weeks.
The Comfort Control is designed to automatically keep the current time and day in memory for up to ten years under normal use once calendar is set. When the Comfort Control is powered, the display is ready for the calendar date to be entered (See Fig­ure 6, next page)
Note: Clock accuracy is +/- 1 minute per month
C - A 7
(A/T)CONT900AC43UA Installer Guide
Communicating Programmable 3-Wire Hookup
4 Heat/3 Cool/ Heat Pump
Figure 6
TCONT900AC43UA Installers Guide
Installer setup (ISU)
The Comfort Control works with many different sys­tem types. The installer can use the Installer Setup menu to change factory settings to customize instal­lations (See T able 4.)
Figure 7
Step 4
Release the two blank keys when the screen on the Comfort Control matches the screen in Figure 8 (See Figure 8.)
Figure 8
Entering installer setup
Follow these steps to enter the Installer Setup:
Step 1
Be sure the Comfort Control is powered. If neces­sary , press the Done key to return to the home screen.
Step 2
Press and release the system key.
Step 3
Press and hold the two blank keys on either side of the center key for approximately five seconds until screen changes (See Figure 7.)
C - A 8
Step 5
See Figure 8 to review how the Comfort Control keys are used during Installer Setup (See Table 4, Pages 9-17) for the Installer Setup numbers and settings.
Communicating Programmable 3-Wire Hookup
4 Heat/3 Cool/ Heat Pump
Step 6
Press the Done key to exit the Installer Setup.
Note:
Manually changing an ISU setting to an option other than “E” disables Discovery mode for that ISU setting. If power is lost, all custom settings are retained in the memory .
T able 4. Inst aller Setup Menu.
(A/T)CONT900AC43UA Installer Guide
C - A 9
(A/T)CONT900AC43UA Installer Guide
Table 4. Installer Setup Menu Continued.
TCONT900AC43UA Installers Guide
Communicating Programmable 3-Wire Hookup
No humidity option available if 3 is selected
4 Heat/3 Cool/ Heat Pump
Note: If single stage is configured, ODU will run Low Stage, but ID airflow ill be 100%. If 3-Three Stage is configured, there will be an Err 89 on stat but unit will run.
For 3 stage furnace: Option 1 = High stage heat only Option 2 = Medium and high stage heat only
For modulating furnace: Option 1 = High stage heat Option 2= Modulating Option 3 = 40% or 100% - No modulation
Note: If anything else is configured, other than “E1”, then the blower will not run in cooling with a furnace but continuous fan and heat will op­erate blower okay/
Note: Auto discovered low stage airflow for 20 SEER: 2 Ton = 50% 3 Ton = 55% 4 Ton = 50% 5 Ton = 65%
C - A 10
Communicating Programmable 3-Wire Hookup
4 Heat/3 Cool/ Heat Pump
Table 4. Installer Setup Menu Continued.
(A/T)CONT900AC43UA Installer Guide
Note: E1 = Auto discovered w/com ODU E0 = Auto discovered w/o com ODU
C - A 11
(A/T)CONT900AC43UA Installer Guide
Table 4. Installer Setup Menu Continued.
TCONT900AC43UA Installers Guide
HP with EH = 0 (no lockout) Dual Fuel = 40 degrees default (Range is 5 - 60)
Communicating Programmable 3-Wire Hookup
4 Heat/3 Cool/ Heat Pump
Note: Y2 counter only with Phase 2 product (serial date code 0904) if heat demand is satisfied by Y2 - reset timer
Note: “0” is not an option with Dual Fuel (must have a lockout temp configured)
C - A 12
Dual Fuel = 50 degrees default Must have option 2 selected in ISU0350. (Range is 45-65 with 40 degree de­fault is selected in ISU0350). (A 5 de­gree deadband is enforced between comp lockout and aux heat lockout)
Note: For phase 2 factory setting = 0 - disabled. (phase 2 = serial data code 0904)
Note: Watch for cool air complaints during de­frost if aux heat lockout is configured. Also be aware of ISU0361, 362 and 363.
Communicating Programmable 3-Wire Hookup
4 Heat/3 Cool/ Heat Pump
Table 4. Installer Setup Menu Continued.
Not shown if ODU is 2-stage HP and 3 stages of heat are present
(A/T)CONT900AC43UA Installer Guide
Note 1: RH gives 10-60% range selection on “MORE” screen Note 2: Dewpoint control gives 0-10 range selection on “MORE” screen. Either screen shows RH% on “MORE” screen
Option 1 = continuous fan speed (default = 50% cooling CFM Note: Fan runs for 2 minutes after humidifier demand ends
Phase 2 (serial date code 0904) makes this option available in USU
ISU0380 must = 1 for this ISU
If “0” is selected, RH% is no longer displayed on the “MORE” screen.
Deadband restricted to 5-9 degrees with ITHC enabled. See ISU0310
C - A 13
(A/T)CONT900AC43UA Installer Guide
Table 4. Installer Setup Menu Continued.
Communicating Programmable 3-Wire Hookup
4 Heat/3 Cool/ Heat Pump
Only shown if ISU0380 is set to 1 or 4
TCONT900AC43UA Installers Guide
C - A 14
Communicating Programmable 3-Wire Hookup
4 Heat/3 Cool/ Heat Pump
Table 4. Installer Setup Menu Continued.
(A/T)CONT900AC43UA Installer Guide
Phase 2 changes range from 50-90
C - A 15
(A/T)CONT900AC43UA Installer Guide
Table 4. Installer Setup Menu Continued.
Phase 1 = 120 seconds Phase 2 = 0 seconds
Phase 1 = 0 seconds Phase 2 = 90 seconds
Phase 1 = 0 - disabled Phase 2 = 5 - 1.5 min@100%
TCONT900AC43UA Installers Guide
Communicating Programmable 3-Wire Hookup
4 Heat/3 Cool/ Heat Pump
C - A 16
Communicating Programmable 3-Wire Hookup
4 Heat/3 Cool/ Heat Pump
Table 4. Installer Setup Menu Continued.
(A/T)CONT900AC43UA Installer Guide
C - A 17
(A/T)CONT900AC43UA Installer Guide
Communicating Programmable 3-Wire Hookup
4 Heat/3 Cool/ Heat Pump
Operation: Using the Comfort Control
System and fan settings
The system default setting is Heat, unless no Heat stage is discovered/configured. The fan default is Auto.
System settings
TCONT900AC43UA Installer’s Guide
Heat: Controls heating system. Off: Heating and cooling are off. Cool: Controls cooling system. Auto: Automatically changes between heating and cooling systems, depending on indoor temperature (See Installer Setup section.) Em. Heat: Compressor is locked out and auxiliary heat cycles to maintain temperature (used only for heat pump systems with backup heat.) Maximum allowable emergency heat stages is three.
Fan settings
Pressing the fan key selects whether the indoor fan motor runs in the On, Automatic, or Circulation mode. The fan setting can be programmed into the Com­fort Control schedule for each period (wake, leave, return, sleep.)
On: Fan runs continuously. Auto: Fan run is automatically following the fan sched­ule. Circ: Circulation control will provide a variable circu­lation determined by the Adaptive Intelligent Circu­lation (AIC) algorithm running the fan between 20% and 60% of the time.
It indicates that the Comfort Control is in Dis-
covery mode.
Filter indication
The Comfort Control can track up to two filter timers by total fan run time or calendar days. This feature can be used to tell the homeowner when to replace the furnace filter or clean the Air Cleaner cells:
Select filter timer reset time: Total fan run time: The number of run time days for
the filter timer to count down from: 0, 10, 30, 60, 90, 120, 180, 270, or 365 days (one run time day repre­sents 24 hours or continuous fan/system run time.)
Calendar days: The number of days for the filter timer to count down from: 0, 30, 60, 90, 120, 180, or 365 days. To activate this feature, select a value other than 0 (disabled.)
Pre-programmed
Table 5 shows the Energy Star default program set­tings. See owner’s guide for complete instructions on changing the program (See Table 5.)
T able 5
T able 5. Energy S tar Default Program Settings.
LED indication
An LED indicator is located in the upper right corner of the Comfort Control. It is only visible when illumi­nated.
It indicates that there is an Alert.
C - A 18
Alert code numbers
The Comfort Control can receive Alert codes from any communicating equipment’s buss. The Comfort Control will illuminate the Red “Service” LED and
Communicating Programmable 3-Wire Hookup
4 Heat/3 Cool/ Heat Pump
(A/T)CONT900AC43UA Installer Guide
toggle between the main screen and a screen show­ing the Alert code number . When multiple Alert codes exist simultaneously, the display will cycle through each code (showing a maximum of the five most re­cent Alert s) and return to the main screen.
Equipment damage hazard. Minimum compressor off-time is bypassed during Installer System T est.
Avoid cycling compressor quickly . Observe compres­sor protection period.
System checkout
Installer system test
The Installer System Test mode is used to test the Comfort Control operation with HVAC equipment (See Table 6, Pages 19-20.) System configuration determines which tests are available and the num­ber of stages shown. While in System Test mode, the minimum off time is bypassed.
The Installer Test is part of the Installer Setup op­tions. Enter Installer Setup screen and press the Down arrow key for quick access to the test selection(s).
• Changing tests will turn equipment off.
• Entering Installer Setup will turn equipment off.
• Charge Assist™ mode not available during Installer System Tests.
• Test modes times out after five minutes.
Advanced features
Adjustable continuous air flow
The Continuous Fan air flow is user adjustable from 25% to 100% in 5% increments either by entering the User Setup menu or the Installer Setup menu (See Table 4, ISU Number 0186, Page 10.)
Continuous fan mode during cooling operation may not be appropriate in humid climates. If the indoor air exceeds 60% relative humidity or sim­ply feels uncomfortably humid, it is
T able 6
T able 6. Inst aller System Tests.
C - A 19
(A/T)CONT900AC43UA Installer Guide
T able 6. Inst aller System T ests Continued.
TCONT900AC43UA Installers Guide
Communicating Programmable 3-Wire Hookup
4 Heat/3 Cool/ Heat Pump
recommended that the fan only be used in the AUTO mode.
Control response rate
A set of more/less aggressive Proportional-Integral control constants can be chosen to increase/decrease the responsiveness of the temperature control per­formance. Choosing a more aggressive rate may cause overshooting. Furthermore, selecting a less aggressive rate may result in undershooting.
Cycle rate
Cycle rate is the selected number of system cycles per hour at 50% load. If the cycle rate were set to 3,
C - A 20
each ON/OFF cycle would be 20 minutes long when operating at 50% load. The total ON and/or OFF times depends on the actual indoor space load. A shorter cycle rate may be desired for Heating mode to maintain tighter control to indoor setpoint. A longer cycle rate may be desired for Cooling mode to allow the system to remove moisture from the air and im­prove indoor comfort.
Auto changeover
When the system mode is set to Auto, the control automatically switches between heating and cooling modes to maintain the desired comfort level.
Communicating Programmable 3-Wire Hookup
4 Heat/3 Cool/ Heat Pump
(A/T)CONT900AC43UA Installer Guide
Setpoint deadband
The number of degrees separating Heating and Cool­ing setpoints is user adjustable from two to nine de­grees. When the control is set to Auto, and the cool­ing setpoint is changed to a cooler setpoint, the heat­ing setpoint will also change to maintain the selected deadband. The same action occurs when the Heat­ing setpoint is changed to a warmer temperature.
The deadband is restricted to a range of five to nine degrees if ISU 0380 is set to Integrated Temperature and Humidity Control (ITHC.)
Backlit display
When continuous backlight is disabled, the liquid crystal display will illuminate only when a touchscreen key is pressed to improve visibility. The backlight stays on for 45 seconds after the last touchscreen key press. When continuous backlight is enabled, the liquid crystal display will remain illuminated con­tinuously. The display will dim to half brightness 45 seconds after the last touchscreen key press.
Filter reminders
The Comfort Control can track up to two filter timers by total fan run time or calendar days. When the preset timer(s) has expired to remind the homeowner that it is time to change the filter(s), “Change” then “Filter” will automatically flash. To reset either filter timer, simply press the More key to access the filter timer value and then press the Reset key . Once the timer has been reset, the filter timer value can be viewed at any time by simply pressing the More key until the filter timer is displayed on the screen.
Both the filter timers are auto discoverable ISU set­tings. If no communicating filtering device has been discovered, the auto discovered value will default to zero. T o enable one or both timers, change ISU 0500 and/or ISU 0501 to a value other than zero.
Fan selections
Pressing the Fan key selects whether the indoor fan motor runs in the On, Automatic, or Circulation mode. In On mode, the fan motor runs continuously. The fan automatically follows the fan schedule in Auto­matic mode. Circulation control will provide a vari­able circulation determined by the Adaptive Intelli­gent Circulation (AIC) algorithm running the fan be­tween 20% and 60% of the time. Each scheduled period (wake, leave, return, sleep) can be pro­grammed with a specific fan setting (on, automatic, or circulation.)
Screen locked
Locking the control’s touchscreen keys can help pre­vent unwanted tampering with or changing of control settings. The Comfort Control can either be fully locked or partially locked. Both options continuously display “Screen Locked” on the screen. Changing ISU number 0670 to zero will unlock the keys and “Screen Locked” will disappear.
Installer system tests
The built-in Installer System Test mode allows the serviceperson to quickly and easily test the Comfort Control’s operation with HV AC equipment and makes diagnostic procedures a snap. System configura­tion determines which tests are available and the corresponding number of stages shown (See Table 6, Tests 1-6 for details.)
Default factory settings
The Comfort Control is shipped with a set of factory default settings. The factory default settings can be restored at any time using the Installer Setup menu (See Table 4, ISU number 0710, Page 17.)
Before you perform Auto-Discovery mode (ISU num­ber 0710), it is recommended that you record all your user settings. All user settings choices will be reset
C - A 21
(A/T)CONT900AC43UA Installer Guide
Communicating Programmable 3-Wire Hookup
4 Heat/3 Cool/ Heat Pump
to factory defaults in Auto-Discovery mode.
Wait indicator
“Wait” will be displayed when the setpoint is changed in the direction of calling for additional system ca­pacity or the outdoor unit is in Charge Assist™ mode. “Wait” indicates system time delays are being en­forced, and the control is adjusting to the new set-
TCONT900AC43UA Installer’s Guide
ting.
Calibrate indoor temperature
This option allows calibration of the room tempera­ture sensor. The selected number is number of de­grees, plus or minus, which will be added to the ac­tual temperature. The number can range between +3 and -3 degrees in one degree increments. Fac­tory default is zero. The adjusted value will be used as the temperature for both display and control ac­tion.
Calibrate indoor humidity
This option allows calibration of the indoor humidity sensor. The selected number is percent relative hu­midity , plus or minus, which can be added to the ac­tual indoor humidity . The number can range between +5 and -5% in one percent increments. Factory de­fault is zero. The adjusted value will be used as the humidity for both display and control action.
sor becomes unavailable, no outdoor value will be displayed. The Comfort Control will not send an Alert.
Humidification
Indoor humification control
This feature helps to control the indoor humidity to the user’s humidification setpoint using a humidifier. The humidification setpoint can range between 10% and 60% in 5% increments. When enabled, the default humidification setpoint is 50%.
Frost control
The Frost control requires an outdoor sensor and a humidifier. The Comfort Control calculates the pos­sibility of condensation or frost forming by using the outside temperature and inside temperature to de­termine the dewpoint. When the dewpoint could cause frost or condensation, the humidification re­quest will not be honored.
The Frost control can be accessed by pressing the More key until the Frost setting is displayed on the screen. It has a value range of zero to ten, with zero representing glass with poor insulation and ten rep­resenting glass with perfect insulation. If the factory setting results in too much condensation or frost on the windows, lower the setting. When the air seems too dry, raise the setting.
Outdoor temperature sensor
For accuracy, the initial reading of the outdoor tem­perature sensor requires five minutes to stabilize. See the Sensor Instructions for installation informa­tion.
If the device is using an outdoor sensor for control and the outdoor temperature sensor becomes un­available, the display will show dashes “--” and gen­erate an Alert. If the device is not using an outdoor sensor for control and the outdoor temperature sen-
C - A 22
Dehumidification
Integrated temperature and humidity control (ITHC)
The dehumidification control helps to control the in­door humidity to the user’s dehumidification setpoint by running the compressor. The dehumidification setpoint can be accessed by pressing the More key until the dehumidification setpoint is displayed on the screen. The setpoint can range between 40% and 80% in 5% increments. When enabled, the default
Loading...
+ 306 hidden pages