Trane 7CONT624AS42DA, Nexia TCONT624AS42DA User's Manual And Installation Instructions

11-HD12D1-2
For HVAC related
issues, contact your
servicing dealer
Touchscreen Comfort Control
Model 7CONT624AS42DA
User Guide and Installation Instructions
Î NOTE: A 24 Volt common and hot wire MUST be
connected to the 7CONT624A for operation.
Contents User Guide
Features .......................................................................................................................................................................... 2
Operation .........................................................................................................................................................................3
User Settings ...................................................................................................................................................................4
Scheduling .......................................................................................................................................................................5
Enrolling into “Z-Wave” Network ........................................................................................8
About ...............................................................................................................................................................................9
Clean Screen ..................................................................................................................................................................9
Installer’s Guide
Product Specications ..................................................................................................................................................10
Installation and Wiring ................................................................................................................................................... 10
Physical Location ..........................................................................................................................................................10
Field Wiring Diagrams ................................................................................................................................................... 12
Optional Remote Temperature Sensors Installation .....................................................................................................29
Installer’s Setup .............................................................................................................................................................30
Test Mode ......................................................................................................................................................................33
Restore Defaults ............................................................................................................................................................33
Troubleshooting .............................................................................................................................................................34
Limited Warranty ............................................................................................................................................................36
FCC/IC Notice ................................................................................................................................................................38
1
User Guide
Features
TCONT624AS42DA Features
• 24v,Z-Wavecomfortcontrol
• Remoteaccessviasmartphone,tablet,orP.C.(requiresH0RQLWRUTMPRELOH$SS).
• Interactive4.3”black&whitetouchscreen
•
7Dayprogrammable,4schedules/day
• BuiltinhumiditysensorwithRHdisplay
• Filter,maintenance,humidierservicereminders
• Remotetemperaturesensingoption(1indoor/1outdoor)
• Auxiliary&compressorheatlockouts
• Dehumidication(overcooling)
• Enhanceddehumidication(cooling)
• Adjustablevariablespeedfansettings(pwm)
• EnergySavingsMode(ESM)
• Screenlockandguestlock
• Upgradablermware
• Servicetestmodes
2
User Guide
Operation
The model TCONT624AS42DAA Comfort Control provides typical operation of a forced air heating and cooling HVAC system. The TCONT624 comfort control also features a Z-Wave™ module for remote control.
:
PM
F
Cooling
Auto
Fan
Menu
Hold
Sched Mode
Cool
Normally, the Comfort Control displays the Home Screen as shown above.
Item Description Notes
Clock Display The current time is displayed in the upper left corner
of the main screen. The time will blink when the clock
See TIME/DATE for more information. The clock will be updated by the eMonitor.
has not been set.
Dynamic Labels and Func­tion Control Buttons
The buttons are dened by the dynamic labels in each
button. As you navigate through menus, the labels for the buttons will change.
Setpoint Display and Set­point Up/Down Buttons
The current heat or cool setpoint is displayed. These setpoints may be set at https://emonitor.us or by pressing the Set- point Up/Down buttons.
The setpoints will push each other if they are adjusted to within the minimum heat/cool separation setting.
This is normally 3 degrees. Pressing the setpoint button changes the setpoint screen. The current mode is display at the top of the screen. Adjust the setpoint by pressing the up or down arrows. To change setpoint mode, press the MODE button.
Temperature Display The Comfort Control displays the current temperature
as sensed by the internal temperature sensor.
The internal temperature sensor can be adjusted as
necessary.
Menu Button Button used to access other Comfort Control menus Other Comfort Control menus can be accessed by
pressing the MENU button.
System Mode Button Button used to change the system mode Off: System off
Heating: Heating only
Cooling: Cooling only
Auto: Heating/Cooling as necessary
EM Heat: Indoor Heat only
Fan Mode Button Button used to change the fan mode: Auto: Fan on when cooling/heating is necessary
On: Fan constantly on
Circ: Fan on for a user-selected number of minutes
per hour.
Schedule Mode Button Button used to change the schedule mode: Hold: System maintains the current temperature set-
points. Schedules are disregarded.
Run: Run the system schedule
Energy Saving Mode (ESM): Temperature setpoints in
ESM Setpoints are maintained.
3
User Guide
User Settings
User Settings allow the user to customize various settings on the 624 control. To access User Settings simply press the Menu button once and “User Settings” will be displayed. To enter the User Settings menu, press the Select button, then use the Next button to navigate through the options below. The default setting will be shown in brackets. After each selection press the Done button to save changes.
Thermostat
Setting Range Description
Temperature Scale [Fahrenheit], Celsius Select the temperature display scale
Cooling RH Setpoint 30% - 60% [50%] Select the desired indoor relative humidity during cooling mode. Dehu-
midication must be enabled in the Installer Settings for this option to be
available.
Smart Continuous Fan Yes, [No] If yes is selected, continuous fan mode is disabled when indoor humidity
exceeds the Cooling RH Setpoint
Continuous Fan Airow 35% - 100% [50%] Select the desired fan speed when the Fan Mode selected is Continuous
(variable speed blower required)
Fan Circulate On Time 1 - 59 minutes, [Off] Select the desired amount of time the fan will cycle per hour when the Fan
Mode selected is Circ
Local Schedule Enable [Yes], No Select whether scheduling will be enabled or disabled
Max Heat Setpoint 55 - [90] Degrees Select the highest heating setpoint allowed
Min Cooling Setpoint [60] - 99 Degrees Select the lowest cooling setpoint allowed
H/C Delta [3] - 15 Degrees Select the minimum deadband between Heating and Cooling setpoints
Once all selections have been made, press the Done button to exit and return to Menu. Press Next to navigate to the next setting.
Energy Savings Mode
Setting Range Description
ESM Heat Setpoint 55 - 90 degrees [62] Select the desired Heating Setpoint when ESM (Energy Savings Mode) is
selected
ESM Cooling Setpoint 60 - 99 Degrees [85] Select the desired Cooling Setpoint when ESM (Energy Savings Mode) is
selected
Once all selections have been made, press the Done button to exit and return to Menu. Press Next to navigate to the next setting.
Display
Setting Range Description
Screen Timeout [0] - 90 Seconds Select how long after the last button press before the screen timeouts to a
minimized screen
Backlight Timeout 0 - 90 Seconds [20] Select how long after the last button press before the backlight dims
Backlight On Percent 0 - [100] Percent Select the screen brightness when the backlight is lit
Backlight Off Percent [0] - 100 Percent Select the screen brightness when the backlight timeout expires
Buzzer Enable [Yes], No Select whether button presses are audible
Security [Unlocked], Display Lock, Guest
Access
Once all selections have been made, press the Done button to exit and return to Menu. Press Next to navigate to the next setting.
Select security level
• Unlocked - Enables selection of all menus and settings
• Display Lock - Disables selection of all menus and settings
• Guest Access - Disables selection of all menus and settings except the
following: Raise or lower heating or cooling setpoint +/- 5 degrees and change system mode Note: When Display Lock or Guest Lock is selected a lock icon will appear next to the up arrow. Note: To disable Display Lock or Guest Access, press and hold the up and down arrows until the lock icon disappears.
4
User Guide
User Settings Continued
User Settings allow the user to customize various settings on the 624 control. To access User Settings simply press the Menu button once and “User Settings” will be displayed. To enter the User Settings menu, press the Select button, then use the Next button to navigate through the options below. The default setting will be shown in brackets. After each selection press the Done button to save changes.
Time/Date
Setting Range Description
Hour 1 - 12 am, 1 - 12 pm Select the current hour of day
Minutes 0 - 59 Select current minute of day
Day of Week Sun - Sat Select current day of week
Year 2013 - 2113 Select current year
Month Jan - Dec Select current month of year
Date 1 - 31 Select current day of month
Once all selections have been made, press the Done button to exit and return to Menu. Press Next to navigate to the next setting.
Reminders
Setting Range Description
Filtration Enable Yes, [No] Selecting yes, enables the Filter Reminder feature
Filter Period [Monthly], Quarterly, Semi-Annu-
ally, Annually
Filter Start Month [Jan] - Dec Select the Filter Reminder start month
System Maint Enable Yes, [No] Selecting yes, enables the System Maintenance Reminder feature
First Maint Month Jan - Dec Select the rst System Maintenance month
Second Maint Month Jan - Dec Select the second System Maintenance month
Once all selections have been made, press the Done button to exit and return to Menu. Press Next to navigate to the next setting.
Select how often the reminder will be displayed
Scheduling
Schedule Setup Procedure
The 624 comfort control is preset at the factory with a 7 Day energy savings schedule. Each day of the week is pre-programmed with the following schedule:
Scheduling
Time Schedule Name Heat Temperature Setting Cool Temperature Setting
6:00 AM Wake 70 F 78 F
8:00 AM Day 62 F 85 F
6:00 PM Evening 70 F 78 F
10:00 PM Night 62 F 78 F
The schedule may be changed locally at the control with the Edit Schedule menu. You can also schedule the Thermostat at
https://emonitor.us With the eMonitor you can establish your own time period names (they will not display locally) and more than 4 time periods. The eMonitor will override this default schedule.
5
User Guide
Scheduling
Edit Schedule (Local)
Press the following button sequence to edit or create an entirely new daily schedule.
Edit Schedule
Button Press Menu Displayed What Needs to Be Done?
Press Menu from Home screen
Press Next SCHEDULE
Press Select EDIT SCHEDULE
Press Select SELECT DAY Continue to press “Next” until the day of week to edit is displayed.
Press Select SET TIME Set the start time for each of four periods for the day displayed. Use the Up/Down
Press Next HEAT SETPOINT Use the Up/Down arrows to set the Heat set point for the period displayed
Press Next COOL SETPOINT Use the Up/Down arrows to set the Heat set point for the period displayed
Press Next Continue pressing Next and using up/down arrows until all Heat & Cool set points
After Pressing Done Copy Schedule is dis-
Press Yes to Copy COPY “_ _ _” To is
Press Done** EDIT SCHEDULE
Press Done** Home Screen is displayed
The schedule may be changed locally at the control with the Edit Schedule menu. You can also make temporary changes at
https://emonitor.us or with the eMonitor mobile apps.
USER SETTINGS
played at the top of the screen. Yes and No buttons are dis­played on the right side of the screen.
displayed at the top of the screen. Yes and No buttons are displayed on the right side of the screen.
menu is displayed
buttons to set the start time for the period displayed. Wake is the default period. Pressing the “Next” button three times cycles through the period displayed (Wake, Day, Evening and Night).*
are set for the day displayed. After editing a start time or editing the set point temperature for one or more periods press “Done” to save edits. If “Done” is not pressed edits will not be saved.
Press yes to copy or no to return to Edit Schedule menu.
Pressing Yes will copy the day displayed to the next day in the week. If Yes is
pressed ve more times the scheduled will be copied to the remaining 5 days in
the week. To skip over a day and avoid copying the schedule to that day press No.
To return to the Home Screen press “Done” one more time.
6
User Guide
Scheduling
Copying Schedules
Press the following button sequence to access “Copying Schedules” from the Home Screen.
Copying Schedules
Button Press Menu Displayed What Needs to Be Done?
Menu
Next USER SETTINGS screen
Select EDIT SCHEDULE screen
Next COPY SCHEDULE screen
Select COPY FROM screen (Mon) Defaults to Monday
Next Advances to next day
Back Goes back to previous day
Select Copy To screen Select the day to copy to by pressing on Yes or No buttons until the copy to day
is selected.
Press Done COPY SCHEDULE Continue copying one days schedule at a time to another or Press Done until
the Home Screen Appears
Press Done SCHEDULE
Press Done HOME SCREEN is dis-
played
The schedule may be changed locally at the control with the Edit Schedule menu. You can also make temporary schedule changes at
https://emonitor.us or with the eMonitor mobile apps.
7
User Guide
Enroll Comfort Control into existing Z-Wave Network
1RWH7KHH0RQLWRU*DWHZD\QHHGVWREHRSHUDWLRQDOLQRUGHUWRVHWXSWKH=:DYHQHWZRUN
6WHSLVJHWWLQJWKHH0RQLWRU*DWHZD\LQWR,QFOXVLRQPRGH
1
2
Enroll the Comfort Control into the QHWZRUN. (Inclusion)
a. 3UHVVWKH0(18EXWWRQRQWKH&RPIRUW&RQWURO b Press WKH1(;7EXWWRQWRDGYDQFHWRWKH=:$9(PHQX. c. 3UHVV6(/(&7
d. 3UHVV<(6WR,QFOXGHLQWKH1HWZRUN
3
Verify enrollment of the Comfort Control.
a. Press Menu Button on the main Comfort Control screen.
b. Press the Next Button to advance to the About screen and press the Select Button.
c. Press the Next Button to advance through the menu options to Node ID
If the number listed there is anything other than “00”, the Comfort Control has been successfully enrolled.
If the number listed there is “00”, the Comfort Control has NOT been successfully enrolled. In this case, repeat stepV and
verify again.
8
About
About
Setting Range
Version Current rmware version loaded on the control
ZWAVE Ver Current version of the ZWAVE rmware
Node - ID ZWAVE identication for this device
Home - ID ZWAVE identication for the connected ZWAVE network
Out - Type Identies the type of outdoor unit installed
C/O - Type Indicates whether the switchover valve (SOV) is energized in cooling or heating mode
In - Type Identies the type of indoor unit installed
Once all selections have been made, press the Done button to exit and return to Menu. Press Next to navigate to the next setting.
Clean Screen
Clean Screen
Setting Range Description
Clean Screen Yes, No Selecting yes allows the user to clean the screen without activating any
of the onscreen touch points. Use only water and a soft cloth, no harmful chemicals.
Once all selections have been made, press the Done button to exit and return to Menu. Press Next to navigate to the next setting.
Installer’s Guide
Product Specications
Specication Description
Product Model: TCONT624AS42DAA
Product: HVAC System comfort control. Z-Wave™ RF communications enabled
Size: 5.75” wide x 3.5” height x 1” depth
Display: Fixed Segment LCD, 4” x 2.25”, with 17 character alpha numeric display
Touchscreen: Yes.
Backlight: Yes, White, Controllable, on, off, timeout
Power: 24VAC from HVAC System
HVAC System Type: Standard (gas/electric), Heat Pump, or Dual Fuel
Heat/Cool Stages: Up to four stages of heat/two stages cool
PWM Output (BK) Proprietary Variable speed motor control
Heat Pump Switchover valve: Selectable change over with cool or with heat
Auxiliary Contact Ventilation or dehumidier control
Communications: Z-Wave™ RF
Memory: Non-volatile
Date/Time: 24 hour super capacitor backup
Time is automatically updated if the control is connected toWKHH0RQLWRU
Installation and Wiring
MERCURY NOTICE
When this Comfort Control is replacing an old thermostat that contains mercury in a sealed tube, do not dispose of your old thermostat in the trash. Dispose of properly. Contact your local waste management authority for instructions regarding recycling and proper disposal of the old thermostat.
A listing of heating, ventilating and air conditioning wholesalers that participate in the Thermostat Recycling Corporation’s recycling program are available at www.thermostat-recyle.org.
Physical Location
Temperature Sensing Considerations
The624Controlisdesignedforinstallationinclimatecontrolledlivingspaces.Itisrecommendedtoplacetheunitincentral locationswithgoodcirculation.Avoidexteriorwallsandareasnearwindows,doors,ventsorconcealedpipesorchimneys.
Correct
Correct Placement
Placement of the 950
of the 624
2 FEET
Optimum Zone
5 FEET
Natural heat dissapation from the 924 Touch Screen
Onboard Thermistor
Incorrect Placement of the 624
Heat from the 624 screen may be
trapped within the body of the 624
control by an external top-down airflow
source, such as a ceiling fan.
The onboard thermistor may be
biased by this heat causing the
displayed indoor temperature to be
Ceiling Fan
elevated.
:
PM
F
Menu
H
Co
o ld
oling
Sched
C o
ol
Mode
Auto
Fa
n
10
AUX/C
J2 AUX NC
C
R W1 W2 O/B
G
BK
J2
J1
RS RS ODT ODT
AUX NO
Y1 Y2 J1
AUX/C
J2 AUX NC
C
R W1 W2 O/B
G
BK
J2
J1
RS
RS ODT ODT
AUX NO
Y1 Y2 J1
AUX/C
J2 AUX NC
C R W1 W2
O/B
G
BK
J2
J1
RS RS ODT ODT
AUX NO
Y1 Y2 J1
Installer’s Guide
AUX/C
J2 AUX NC
C
R
W1
W2
O/B
G
BK
J2
J1
RS
RS ODT ODT AUX NO
Y1 Y2 J1
1
CAUTION: Before proceeding with installation, verify system power has been removed.
Separate the face of the new Comfort Control from the wall plate.
Apply pressure at two tabs on top of wall plate to release it.
2
Mark two mounting holes using new wall plate.
Pull wires through hole in center of wall plate.
Locate the new wall plate over existing opening.
Mark two holes with pencil.
Use a level to verify that the two hole locations are level.
Correct hole locations as needed.
3
Install new wall plate.
Pull wires through hole in center of wall plate.
Locate the new wall plate over existing opening.
Attach wall plate to wall using two screws provided. Do not overtighten.
CAUTION: ELECTRICAL HAZARD
Î NOTE: It is not recommended that this Z-waveTM Comfort Control be mounted onto metal structures.
Metal may adversely affect the radio frequency (RF) communication between the Comfort Control and the Z-wave
TM
bridge.
4
Attach all wires securely to the new Comfort Control.
(See the Field Wiring Diagrams on the following pages.)
Note: A wire must be connected to “C” to power the Comfort Control.
Use the information from the Field Wiring Diagrams to match the wires to the correct terminals.
Use 1/8” blade screwdriver to secure wires in terminals.
CAUTION: EQUIPMENT DAMAGE HAZARD
Improper wiring can lead to equipment damage. Use the eld wiring diagrams to ensure the Comfort
Control is wired properly. After wires are secure, bare wires MUST NOT touch each other. See the Field Connection Wiring Diagrams on
the following pages for specic system applications.
5
Attach the Comfort Control face to the wall plate.
a. Carefully align the face plate to the wall plate while aligning pins into wire terminals. b. Once Comfort Control face is properly aligned, apply pressure at top and bottom of Comfort
Control face until it is secure.
6
Turn power to heating and cooling system back on.
The Comfort Control display should turn on and begin displaying information. Proceed to Installer’s Setup to congure system
J1
C R W1
W2 O/B
G
Y1 Y2 J1
BK
J2 RS RS
ODT ODT AUX NO AUX/C
J2 AUX NC
settings.
11
Field Wiring Diagrams
Heat/Cool Diagram 1: 1 or 2 Stage Cooling w/TAM7 Model Variable Speed Air Handler
G
W1
YI (In)
R
B/C
Y2
BK
W2
Y1
R
B
Y2
Notes:
1. Cut/remove the factory installed “BK” jumper at the indoor unit
2. “Y2” & “R” connections at outdoor are only required for two stage units
3. Jumper “W2” to “W3” if three stages of indoor heat is available
4. “YI” and “YO” connections must be made as shown for freeze protection and internally mounted condensate overflow circuits to work properly
5. If third party condenstate overflow switched are installed, they should be wired between “Y1” of the thermostat and “YI” of the airflow control board
Sensor Options in the Installer Settings/Sensor Settings menu Remote Sensor (connect to the RS terminals)
- None
- Replaces internal sensor
- Average with internal sensor Outdoor Temp Sensor (connect to the ODT terminals)
- None
- Outdoor Caution: Do not run sensor wires in the same bundle with HVAC wires. Keep away from high voltage wiring to avoid interference.
Remote Tempurature Sensor Connections and Operation:
Aux relay outputs
RS
C
RS
R
ODT
W1
W2
BK
ODT
NO
C
Y1
NC
Y2
O/B
G
Thermostat Connection
Outdoor
Sensor
Remote
Sensor
W3
YO
VS Air Handler &
Electric Heat
One or Two Stage
Cooling Only
(Note 1)
(Note 2)
(Note 2)
(Note 3)
(Note 5)
(Note 4)
Heat/Cool Diagram 2: 1 Stage Cooling w/“GAM5A” & “TAM4” Model Air Handler
G
W1
YI (In)
R
B/C
W2
B
Y
Notes:
1. Jumper “W2” to “W3” if three stages of indoor heat is available
2. “YI” and “YO” connections must be made as shown for freeze protection and internally mounted condensate overflow circuits to work properly
3. If third party condenstate overflow switched are installed, they should be wired between “Y” of the thermostat and “YI” of the airflow control board
Sensor Options in the Installer Settings/Sensor Settings menu Remote Sensor (connect to the RS terminals)
- None
- Replaces internal sensor
- Average with internal sensor Outdoor Temp Sensor (connect to the ODT terminals)
- None
- Outdoor Caution: Do not run sensor wires in the same bundle with HVAC wires. Keep away from high voltage wiring to avoid interference.
Remote Tempurature Sensor Connections and Operation:
Aux relay outputs
RS
C
RS
R
ODT
W1
W2
BK
ODT
NO
C
Y1
NC
Y2
O/B
G
Thermostat Connection
Outdoor
Sensor
Remote
Sensor
W3
YO
Non-VS
Air Handler &
Electric Heat
One Stage
Cooling Only
(Note 1)
(Note 2)
O
Heat/Cool Wiring Diagrams
Installer’s Guide
12
Loading...
+ 25 hidden pages