Trane 7722TX Installation Instructions Manual

wm2-2&m
Wireless Zone Sensor
Model
7722TX
(TRANE
Part
No. X13790126060)
INSTALLATIQN INSTRUCVONS
INTRODUCTION
This wireless
zane
sensor is designed for use in a
temperature control system, operating
in conjunction with a centrally located Spread Spectrum Receiver (Model 7712RX). Zone sensors are installed in areas where temperature control is to be maintained. Ideally, the receiver should be equidistant from all its assigned zone sensors.
The zone sensor measures temperature and periodically transmits that information via RF stgnals to its assigned receiver. The sensor also transmits occupant set point temperature. Other information that can be transmitted includes special service requests, unique serial number of sensor, and status of the batteries in the unit.
RF signals from wireless zone sensors are received by a receiver, which will then send appropriate messages via
communication wires to specific
.heating
and air conditioning equipment assigned to it. This information is also sent to a central controller for system monitoring.
After mounting each wireless sensor, the Model 7712lT Installation Tool can be used to assign each sensor to a
necessary instructions for this are contained in the instructions accompanying the 7712lT Installation Tool.
INSTALLATION Location
Wireless sensors can be installed anywhere on common
walls and panitions. Operation will not be affected by metal framing in walls or partitions; however, mounting to solid metal walls or cabinets may reduce the operating distance between the zone sensor and the receiver. Typical line-ot- sight transmission range indoors for sensors is approximately
1OOOfeet
Mounting (Fig. 2)
A mounting plate is provided with the sensor. If attached to
the back of the sensor, release it by depressing the ‘locking tab’ at the bottom center of the mounting plate with the blade of a screwdriver, and then sliding the plate downward.
Mount the plate on the selected wall or partition with the VELCRO strips or screws provided. Hooks must point upward (the plate also has the word ‘TOP’ molded into the top side).
Position the sensor onto the mounting plate so that the mounting plate hooks enter the keyhole slots in the back of the sensor, then slide downward to lock the sensor in place.
Battery Installation (Fig. 3)
The sensor uses two 3-volt Lithium batteries (supplied). Remove the sensor cover by squeezing the cover at the top and bottom and then pulling the cover away.
Install one battery in each compartment in the sensor. THE SENSOR WILL NOT OPERATE WtTH ONLY ONE
BATTERY.
Note: Batteries will not seat properly in their compartments if installed incorrectly with regard to polarity. Make sure each battery is fully seated in the compartment and that proper
conted
is being made at each end of the battery.
WSHBlJl
SWrTC
i
n
0
ii
Figure 1.
Typkal
Wireless
Sensor
‘tiooks’
TON
SIES
LCCANG TAB
Fkf~ure 2. Mounting Plate
GREEN
LED’
a-w
a4oER
(For4
CONNECTION
OF
INSTALlATlOh
TOOL)
LOCKING TAB
(P!AE.SS IN-WAR0
TO RELEASE SENSOR FROM PLATQ
Figure
3. Wireless
tinsor,
Cover Removed
Removing A Sensor From Its Mounting Plate
To remove a sensor from its mounting plate after installation, press inward on the ‘locking tab’ at the bottom center
(just
to
the left of the
&pin
header), and slide the sensor up and
off
the mounting plate. See Figure 3 for location of the locking tab.
FUNCTIONAL ELECTRICAL TEST
This
check should be performed after a zone sensor has
been mounted and the batleries installed. The cover must be
Otf.
If
the
sensor is equipped with a temperature control, set the
control dial with
‘70’
in
the 9 o’clock
position.
Press either one d the two pushbutton
switches on
.the
upper
left
side of
the sensor. The green LED near the bottom of the
circuit board should flash each time the pushbutton is
pressed. If it does not,
check that both batteries are good and
are
property seated in the holders.
In normal use, the green LED will Hash each time the zone
sensor transmits a message,
usually several minutes apart.
SET-UP PROCEDURE Rater to the
sensor set-up procedures In
the
instructions
8ccompanylng the Model 771211
installation
Tool.
SPECIFICATIONS
Dlmenslonr: Height:
4-l/16’ Wiih: 5’ Depth: l-5416’ (not
incfuding
mounting plate).
(103mmH
x
127mmW x 33mmD)
Range:
Nominal
1OOO
feet fine-of-sight, indoors.
Batledes:
Two
3vdl&‘3A
Lithium Batteries.
Use only Trane No.
X1377001
7010, Panasonic
CR123A,
Duracell 1234 or Sanyo
CR123A
for
replacement.
Risk of fire, explosion and
bur’ns.
Do not
or inctnerate. Dispose of used batteries
USER NOTE
CHANGES OR MOOIFICATIONS MAOE TO THIS EOUIPMENT WHICH ARE NOT EXPRESSLY APPROVED BY THE AGENT FOR THE
TRANE
COMPANY RESPONSIBLE FOR COMPLIANCE WITH FEDERAL REGULATIONS COULD
VOID THE USER’S AUTHORITY TO OPERATE THIS EQUIPMENT.
THE
TFIANE
COMPANY,
Commercial Systems Group
3600
Pammel
Creek Road,
Lacrosse, WI 54602
Copyright
0
1994
Loading...