Split System Heat Pump
Units Designed With
Your Needs In Mind.
The Trane reputation for quality and
reliability in air conditioning is
apparent with Odyssey™ light
commercial split systems. These
Trane systems are designed to meet
your job requirements every
time...and at a competitive price.
Odyssey has Trane quality and
reliability built-in. Couple that with
outstanding efficiency, flexibility and
installation ease, and you have an
unbeatable combination for years of
worry-free service and operation.
Manufacturing Control
Trane’s exclusive control over the
design and manufacturing of all
major components is unique in the
industry. This approach assures total
control over both the quality and
reliability of these components and
allows us to custom match
components to deliver the best in
split system performance.
Standardized Cabinets
In addition, all cabinets have been
standardized. When you are
servicing an outdoor unit or an air
handler, all components are in the
same location from unit to unit.
Filters
The 5, 7½ and 10 ton air handlers are
supplied with 1" throwaway filters as
standard. The filter racks were
designed to easily convert for
installation of 2" filters. The 15 and
20 ton air handlers have 2" filters as
standard.
Figure 1.
Designing the Details
Careful attention was given to
designing the details — from control
wiring to the access panels. Odyssey
units feature time-saving colored
and numbered wiring and
removable panels which allow
complete access to all major
components and controls. All
outdoor units feature external high
and low pressure switches for easy
diagnosing and servicing of the unit.
Service valves with gauge ports are
provided on all units.
The 7½ and 10-ton single
compressor models feature single
refrigeration circuitry, lowering job
installation costs by requiring only
one set of refrigerant lines. These
units are ideal for low cost, new
construction, building renovation
and unit replacement jobs.
In addition, Odyssey includes 15 and
20-ton dual compressor units to give
true stand-by protection; if one
compressor fails, the second will
automatically start-up. Also, the first
compressor can be serviced without
shutting down the unit since the
refrigerant circuits are independent.
Dual compressors also provide high
energy savings. Most buildings are
designed for peak load requirements
even though the building typically
operates at less than peak load.
During light load conditions only one
compressor functions to maintain
the space comfort, reducing energy
use. For instance, the EER of the 15
ton unit at ARI conditions is 10.1 and
at part load conditions it is 11.6.
Trane split systems have been
specified in thousands of
applications. You’ll find Odyssey will
win you even more jobs with its
compact, manageable cabinet which
will save time and money for rigging
and installation and permit Trane to
replace almost any unit —
effortlessly.
Each heat pump unit can operate to
50°F as standard in the cooling
mode. An accessory Head Pressure
Control gives you the capability to
operate to 0°F. All heat pumps offer
these accessories:
•Head Pressure Control
•Coil Guard Kits
•Isolators - both Rubber-in-Shear
and Spring Type
•Anti-Short-Cycle Kit
•Time Delay Relay
Air Handlers Offer More
Flexibility
Flexibility is a key to meeting
changing market requirements.
Odyssey split systems offer not only
heat pumps, but also convertible air
handlers.
The air handlers can be installed
either vertically in a mechanical
room or horizontally above a ceiling
— and it doesn’t require any removal
of panels to make either airflow
application work.
Figure 2.
These air handlers have a double
sloped condensate drain pan that
allows for either airflow
configuration. The drain pan can
easily be removed for cleaning.
All the air handlers feature factoryinstalled belt drive and ball bearing
evaporator fans with adjustable
sheaves for maximum airflow
performance. In fact, the standard
motor on the 10-ton air handler will
deliver 4000 cfm at 1.4" ESP. Plus
oversized motors are available for
higher static applications.
4SSP-PRC001-EN
Features and Benefits
Odyssey’s air handler versatility is
further increased by a complete line
of accessories designed to match and
install smoothly:
•Discharge Plenum and Grille
•Return Grille
•Subbase
•Electric Heaters
•High Static Evaporator Motor
•Isolators both Rubber-in-Shear
and Spring Type
•A full line of Thermostats
•Outdoor Thermostat
Figure 3.
Odyssey — A Complete
Split System
Odyssey delivers the flexibility to
select a complete system that meets
your particular job requirements.
Air handlers are designed, tested and
rated with outdoor units to let you
select the proper match between
capacity and load. Also, these
matched systems can be quickly
engineered for specific applications
using Trane’s computerized selection
and load programs.
Odyssey Lowers Installation Costs
Your installation costs are reduced
with Odyssey Split. Both outdoor
units and air handlers are factory
packaged and assembled so jobsite
installation is quick and easy. You get
a complete system, with all the
components, controls and the
internal wiring, factory-installed for a
smooth jobsite start-up.
Unlike some competitive models the
following components are factoryinstalled in Trane air handlers:
•Single Point Power Entry
•Blower Wheel and Housing
•Evaporator Motor with Sheaves
and Pulleys
•Low Voltage Terminal Board
•Transformer
•Contactor
•Fan Relay
•DX Coil with complete
Refrigeration Circuitry
•Expansion Valve and Check
Valves
There’s no need to install
components and put together the air
handler on the job. This provides you
with less labor cost and fewer
chances for installation errors which
cause callbacks. All this means
saving you money both in
replacement and new construction
applications.
Figure 4.
SSP-PRC001-EN5
Application Considerations
Application of this product should be
within the catalogued airflow and
performance considerations.
Clearance Requirements
The recommended clearances
identified with unit dimensions
should be maintained to assure
adequate serviceability, maximum
capacity and peak operating
efficiency. Actual clearances which
appear inadequate should be
reviewed with a local Trane
Representative.
180° Blower Rotation
The 5, 7½ and 10 ton air handler
blower section can be rotated 180° to
change the discharge pattern. This
modification must be done in the
field and requires an additional kit.
See unit installer's guide.
Low Ambient Cooling
As manufactured, these units can
operate to 50°F in the cooling mode
of operation. An accessory head
pressure control will allow operation
to 0°F outdoor ambient. When using
these units with control systems
such as bypass changeover Variable
Air Volume, make sure you consider
the requirement for a head pressure
control to allow low ambient
cooling.
Figure 5.Typical Horizontal Air Handler Application
Figure 6.Typical Split System Application
6SSP-PRC001-EN
Application Considerations
Figure 7.Typical Vertical Air Handler Application
SSP-PRC001-EN7
Selection Procedure
Cooling Capacity
Step 1.
Calculate the building’s total and
sensible cooling loads at design
conditions.
Step 2.
Size the equipment using Tab l e 3 .
Match the cooling loads at design
conditions.
Example: The following are the
building cooling requirements:
TWE090A has a gross cooling
capacity of 91.1 MBh and 65.9 MBh
sensible capacity at 95°F DB ambient
and 3000 cfm with 80°F DB/67°F WB
air entering the evaporator.
To find the net cooling capacities, fan
motor heat must be subtracted.
Determine the total unit static
pressure:
External Static Duct System0.77 in.
Standard Filter 1 in.0.10 in.
Supplementary Electric Heat0.23 in.
Total Static Pressure1.10 in.
Note: The Evaporator Fan
Performance Table has
included the effect of a 1 in.
filter already. Therefore, the
actual Total Static Pressure is
1.10 - 0.10 = 1.0 0 in. Wit h
3000 cfm and 1.00 in.,
Ta b le 1 7 shows a 1.17 bhp.
Note: The formula below the table
can be used to calculate Fan
Motor Heat:
3.5 X bhp = MBh
3.5 X 1.17 = 4.09 MBh
Net Total Cooling Capacity =
91.1 MBh - 4.09 = 87.01 MBh
Net Sensible Cooling Capacity =
65.9 MBh - 4.09 = 61.81 MBh
Heating Capacity
Step 1.
Calculate the building heating load
using the Trane calculation form or
any other standard accepted
method.
Step 2.
Size the equipment using Tab le 11 to
match the heating loads at design
conditions. The following are
building heating requirements:
a. Total Heating Load: 95.0 MBh
b. Outdoor Ambient (Winter):
17°F DB
c. Indoor Return Temperature:
70°F DB
d. Airflow: 3000 cfm
Ta b le 11 indicates the mechanical
heating portion of the heat pump will
provide 54.8 MBh for the winter
design conditions.
Step 3.
Because 54.8 MBh is less than the
building’s required heating capacity,
a supplementary heater must be
selected. 95.0 - 54.8 = 40.2 MBh
minimum heater capacity.
From Table 32, the 14.96 kW heater
has a capacity of 51,058 Btu/h.
From Table 37, the 14.96 kW heater
at 460V indicates the heater model
number is BAYHTRL415A.
This heater will be adequate to cover
the residual heat capacity needed for
the application.
Air Delivery Selection
External static pressure drop
through the air distribution system
has been calculated to be 0.77 in. of
water gauge.
From Table 31 static pressure drop
through the electric heater is 0.12 in.
of water (0.77 + 0.12 = .89 in.)
Enter Tab l e 17 for TWE090A4 at 3000
cfm and .90 static pressure. The
standard motor at 790 RPM will give
the desired airflow.
Matched Air Handler10.110.19.99.3
Heat Pump Only11.511.110.910.3
Integrated Part Load Value
(v)
--11.010.5
System/Condensing Unit Power (kW)8.70/7.9511.91/11.0717.77/16.6224.99/23.20
Heating Performance
ARI Heating and Matched Air Handler
High Temperature Capacity87,000122,000168,000234,000
System kW/COP7.68/3.310.82/3.216.10/3.122.42/3.1
Low Temperature Capacity55,00080,000106,000154,000
System kW/COP6.73/2.49.62/2.414.16/2.219.54/2.30
No. Refrigerant Circuits1122
Suction Line (in.) OD1 3/81 3/81 3/81 3/8
Liquid Line (in.) OD1/21/21/21/2
Outdoor Coil - TypePlate FinPlate FinPlate FinPlate Fin
Tube Size (in.) OD.375.375.375.375
Face Area (sq ft)19.229.538.550.2
Rows/FPI2/182/182/182/18
Refrigerant ControlExpansion ValveExpansion ValveExpansion ValveExpansion Valve
Outdoor Fan - TypePropellerPropellerPropellerPropeller
No. Used/Diameter (in.)1/261/282/262/28
Drive Type/No. SpeedsDirect/1Direct/1Direct/1Direct1
CFM5890820011,78016,240
No. Motor/HP1/.501/1.002/.502/1.00
Motor RPM1100110011001100
Refrigerant Charge (Field Supplied)
(lbs of R-22)
(i)
(ii)
(iii)
(iv)
(v)
(vi)
(vii)
(viii)
(viii)
Cooling Performance is ra ted at 95°F ambient, 80°F enterin g dry bulb , 67°F ente ring wet bu lb. Gross c apacity doe s not inclu de t he effect of fan motor
heat. ARI capacity is net and includes the effect of fan motor heat. Certified in accordance with the Unitary Large Equipment certification program,
which is based on ARI Standard 340/360-00.
Condensing unit only gross cooling capacity rated at 45°F saturated suction temperature and at 95°F ambient.
ARI net cooling capacity is calculated with matched blower coil and 25 feet of 1 3/8" or 1/2" OD interconnecting tubing.
EER is rated at ARI conditions and in accordance with DOE test procedures.
Integrated part load value is based on ARI Standard 340/360-00. Units are rated at 80°F ambient, 80°F entering dry bulb (DB), and 67°F entering
wet bulb (WB) at ARI rated cfm.
Sound rating shown is tested in accordance with ARI Standard 270 or 370.
Refer to refrigerant piping applications manual for line sizing and line length.
Refrigerant (operating) charge is for c ondens ing uni t (all circui ts) wi th matchi ng bl ower co ils and 25 feet of inter connec ting refrigerant lines. All units
are supplied with a small nitrogen holding charge only.
18.0031.5036.0048.50
Single Compressor
TWA120A3,A4,AW
Dual Compressor
TWA180B3,B4,BW
Dual Compressor
TWA240B3,B4,BW
10SSP-PRC001-EN
General Data
Table 2. General Data - Air Handlers
5 Tons7½ Tons10 Tons
Single Circuit
TWE060A1
A3, A4, AW
Dual Circuit
(i)
,
TWE060B1, B3,
B4
System Data
No. Refrigerant Circuits121211
Suction Line (in.) OD1 1/83/41 3/81 1/81 3/81 3/8
Liquid Line (in.) OD3/85/161/23/81/21/2
Indoor Coil - TypePlate FinPlate FinPlate FinPlate FinPlate FinPlate Fin
Tube Size (in.).375.375.375.375.375.375
Face Area (sq. ft.)5.05.08.18.111.211.2
Rows/FPI3/123/123/123/124/124/12
Refrigerant ControlExpansion Valve Expansion Valve Expansion Valve Expansion Valve Expansion Valve Expansion Valve
Drain Connection Size (in.)1 PVC1 PVC1 PVC1 PVC1 PVC1 PVC
Indoor Fan - TypeCentrifugalCentrifugalCentrifugalCentrifugalCentrifugalCentrifugal
No. Used/Diameter x Width (in.)1/12 x 121/12 x 121/15 x 151/15 x 151/15 x 151/15 x 15
Drive Type/No. SpeedsBelt/Adjustable Belt/AdjustableBelt/AdjustableBelt/AdjustableBelt/Adjustable Belt/Adjustable
CFM200020003000300040004000
No. Motors111111
Motor HP - Standard/Oversized.75/1.00.75/1.001.50/2.001.50/2.002.002.00/3.00
Motor RPM172517251725172517251725
Motor Frame Size565656H56H56HZ56HZ
Filters - Type/FurnishedThrowaway/Yes Throwaway/Yes Throwaway/YesThrowaway/Yes Throwaway/Yes Throwaway/Yes
(No.)/Size Recommended(1) 16x20x1(1) 16x20x1(3) 16x25x1(3) 16x25x1(4) 16x25x1(4) 16x25x1
(1) 20x20x1(1) 20x20x1
10 Tons15 Tons20 Tons
Dual Circuit
Dual Circuit
TWE120B1
(iv)
TWE120B3
B4, BW
System Data
No. Refrigerant Circuits22222
Suction Line (in.) OD1 1/81 1/81 1/81 3/81 3/8
Liquid Line (in.) OD3/83/83/81/21/2
Indoor Coil - TypePlate FinPlate FinPlate FinPlate FinPlate Fin
Tube Size (in.).375.375.375.375.375
Face Area (sq. ft.)11.211.211.216.321.6
Rows/FPI4/124/124/123/123/12
Refrigerant ControlExpansion Valve Expansion Valve Expansion Valve Expansion Valve Expansion Valve
Drain Connection Size (in.)1 PVC1 PVC1 PVC1 PVC1 PVC
Indoor Fan - TypeCentrifugalCentrifugal-CentrifugalCentrifugal
No. Used/Diameter x Width (in.)1/15x151/15x15-2/15x152/15x15
Drive Type/No. SpeedsBelt/Adjustment Belt/Adjustment-Belt/Adjustment Belt/Adjustment
CFM40004000-60008000
No. Motors11-11
Motor HP - Standard/Oversized2.00/-2.00/3.00-3.00/5.005.00/7.50
Motor RPM17251725-1735/17501750/3470
Motor Frame Size56HZ56HZ-145T184T
Filters - Type/FurnishedThrowaway/Yes Throwaway/YesThrowaway/
TWE60A1 has motor RPM of 3450 for oversized motor.
(ii)
Ships wired for 208-230/60/3. Field convertible to 460/60/3.
(iii)
TWE120A1 does not have an oversized motor option.
(iv)
TWE120B1 does not have an oversized motor option.
(v)
Coil has filter rack as standard, but no filters. When us ing this coil as a duct coi l, use below s ize recommended. Filters for coil no t recommen ded when
using coil with upflow gas furnaces.
Single Circuit
TWE090A1,
(ii)
,
Dual Circuit
TXE120B500B
A3
(ii)
Yes
, AW
(v)
Dual Circuit
TWE090B1,
(ii)
B3
Dual Circuit
TWE180B3, B4,
BW
Single Circuit
TWE120A1
Dual Circuit
TWE240B3, B4,
BW, E3, E4, EW
Throwaway/Yes Throwaway/Yes
(4) 16x20x2
Single Circuit
TWE120A3
(iii)
(ii)
AW
,
SSP-PRC001-EN11
Performance Data
Table 3. Gross Cooling Capacities (MBh) 7½ Tons TWA090A Heat Pump with 7½ TWE090A Air Handler
1. Dry coil condition. Total gross capacity (MBh) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total capacity.
2. All temperatures are in °F.
3. All capacities shown are gross and have not considered indoor fan heat.
4. To obtain net cooling capacities, subtract indoor fan heat.
1. Dry coil condition. Total gross capacity (MBh) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total capacity.
2. All temperatures are in °F.
3. All capacities shown are gross and have not considered indoor fan heat.
4. To obtain net cooling capacities, subtract indoor fan heat.
1. Dry coil condition. Total gross capacity (MBh) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total capacity.
2. All temperatures are in °F.
3. All capacities shown are gross and have not considered indoor fan heat.
4. To obtain net cooling capacities, subtract indoor fan heat.
1. Dry coil condition. Total gross capacity (MBh) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total capacity.
2. All temperatures are in °F.
3. All capacities shown are gross and have not considered indoor fan heat.
4. To obtain net cooling capacities, subtract indoor fan heat.
1. Data includes pressure drop due to wet coil and 1" filter.
2. Fan motor heat (MBh) = 3.15 x BHP.
3. Trane’s factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and
continuously at all cataloged condit ions. Using the full horsepower range of our fan motors as shown in our tabular data will not r esult in nuisance
tripping or premature motor failure. Our product’s warranty will not be affected.
(i)
Field Supplied Low Static Drive (use Table 16)
(i)
.75 HP Standard Motor & Sheaves
Table 16. Low Static Fan Drive 5 Ton TWE060A, TWE060B Air Handler
Motor Sheave Turns OpenNominal RPM
0752
1708
2663
3619
4574
5530
(i)
Field supplied components required:
Blower Sheave: Fixed Pitch (7.8 inch Pitch Diameter)
Blower Sheave: 0.625 inch Bore, Single Groove, "A" Belt
Belt: A48
(i)
22SSP-PRC001-EN
Performance Data
Evaporator Fan Performance, Low Static Fan Drive, 7½ Tons
Table 17. Evaporator Fan Performance 7 1/2 Ton TWE090A, TWE090B - Air Handler
1. Data includes pressure drop due to wet coil and 1" filter.
2. Fan motor heat (MBh) = 3.15 x BHP.
3. Trane’s factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and
continuously at all cataloged condit ions. Using the full horsepower range of our fan motors as shown in our tabular data will not r esult in nuisance
tripping or premature motor failure. Our product’s warranty will not be affected.
(i)
Field Supplied Low Static Drive (use Table 18)
Low Static Drive
External Static Pressure (Inches of Water Gauge)
2 HP Oversized Motor & Sheaves
(i)
1.5 HP Standard Motor & Sheaves
1.5 HP Standard Motor & Low Static Drive Kit
1.5 HP Standard Motor &
Sheaves
Table 18. Low Static Fan Drive 7½ Tons TWE090A, B Air Handler
Field Supplied Low Static Fan Drive
7½ Tons TWE090A, B Air Handler
Field supplied components required:
Blower Sheave: Fixed Pitch (9.8 inch Pitch Diameter), Blower Sheave: 1.00 inch Bore,
Single Groove, "A" Belt. Belt: A55
Nominal
(i)
RPM
SSP-PRC001-EN23
Low Static Fan Drive Accessory Kit
7½ Tons TWE090A, B Air Handler
Motor Sheave
Turns Open
Nominal
RPM
Performance Data
Evaporator Fan Performance, Low Static Fan Drive, 10 Tons
Table 19. Evaporator Fan Performance 10 Tons TWE120A1, TWE120B1 - Air Handler
1. Data includes pressure drop due to wet coil and 1" filter.
2. Fan motor heat (MBh) = 3.15 x BHP.
3. Trane’s factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and
continuously at all cataloged condit ions. Using the full horsepower range of our fan motors as shown in our tabular data will not r esult in nuisance
tripping or premature motor failure. Our product’s warranty will not be affected.
(i)
Field Supplied Low Static Drive (use Table 2 0)
Low Static Drive
(i)
2 HP Standard Motor and Sheaves
Table 20. Low Static Fan Drive 10 Tons TWE120A1, TWE120B1 - Air Handler
Motor Sheave Turns OpenNominal RPM
0745
1706
2666
3627
4588
5549
(i)
Field supplied components required:
Blower Sheave: Fixed Pitch (8.8 inch Pitch Diameter)
Blower Sheave: 1.00 inch Bore, Single Groove, "A" Belt
Belt: A54
(i)
24SSP-PRC001-EN
Performance Data
10 Tons Evaporator Fan Performance
Table 21. Evaporator Fan Performance 10 Tons TWE120A3, AW; TWE120B3, BW - Air Handler
1. Data includes pressure drop due to wet coil and 1" filter.
2. Fan motor heat (MBh) = 3.15 x BHP.
3. Trane’s factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and
(i)
3 HP Oversized Motor & Sheaves
continuously at all cataloged condit ions. Using the full horsepower range of our fan motors as shown in our tabular data will not r esult in nuisance
tripping or premature motor failure. Our product’s warranty will not be affected.
Field Supplied Low Static Drive (use Table 2 2)
Low Static Drive
(i)
3 HP Oversized Motor & Sheaves
2 HP Standard Motor & Sheaves
s
Table 22. Low Static Fan Drive 10 Tons TWE120A3, AW; BE, BW Air Handler
Motor Sheave Turns OpenNominal RPM
0745
1706
2666
3627
4588
5549
(i)
Field supplied components required:
Blower Sheave: Fixed Pitch (8.8 inch Pitch Diameter)
Blower Sheave: 1.00 inch Bore, Single Groove, "A" Belt
Belt: A54
SSP-PRC001-EN25
(i)
Performance Data
Evaporator Fan Performance, Low Static Fan Drive, 15 Tons
Table 23. Evaporator Fan Performance 15 Tons TWE180B - Air Handler
1. Data includes pressure drop due to wet coil and 2" filter.
2. Fan motor heat (MBh) = 3.15 x BHP.
3. Trane’ s factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably
and continuously at all catalog ed con ditio ns. U sing t he ful l hor sepow er r an ge o f our fan mo tors as sho wn in ou r tabu lar d ata will not result
in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.
(i)
Field Supplied Low Static Drive (use Table 24)
Sheaves
5 HP Oversized Motor and Sheaves
(i)
3 HP Standard Motor and Sheaves
5 HP Oversized Motor and Sheaves
Table 24. Low Static Fan Drive 15 Ton TWE180B Air Handler
Motor Sheave Turns OpenNominal RPM
0776
1748
2720
3692
4663
5635
6607
(i)
Field supplied components required:
Motor Sheave: Variable Pitch (4.3-5.5 inch Pitch Diameter),
0.875 inch Bore, Single Groove, "B" Belt.
Blower Sheave: Fixed Pitch (12.4 inch Pitch Diameter),
1.4375 inch Bore, Single Groove, "B" Belt.
Belt: B67
26SSP-PRC001-EN
(i)
Performance Data
Evaporator Fan Performance, Low Static Fan Drive, 20 Tons
Table 25. Evaporator Fan Performance 20 Ton TWE240B - Air Handler
1. Data includes pressure drop due to wet coil and 2" filter.
2. Fan motor heat (MBh) = 3.15 x BHP.
3. Trane’s factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and
continuously at all cataloged condit ions. Using the full horsepower range of our fan motors as shown in our tabular data will not r esult in nuisance
tripping or premature motor failure. Our product’s warranty will not be affected.
(i)
Field Supplied Low Static Drive (use Table 2 6)
(i)
5 HP Standard Motor & Low Static Drive Kit
5 HP Standard Motor & Sheaves
Table 26. Low Static Fan Drive 20 Tons TWE240B/TWE240E Air Handler
Notes: Heaters are rated at 240V, 480V and 600V. For other than rated voltage capacity = (Voltage/Related Voltage)2 x Rated Capacity.
Total kWNo. of
5.0015.0017,065--5.0017,065
24.92214.9651,0589.9633,99324.9285,051
5.0015.0017,065--5.0017,065
19.92119.9267,987--19.9267,987
49.84229.92102,11719.9267,98749.84170,104
StageskW Input
BTUH
OutputkW Input
BTUH
OutputkW Input
BTUH
Output
30SSP-PRC001-EN
Controls
Thermostats
Two stage heating/cooling or one
stage heating/cooling thermostats
are available in either manual or
automatic changeover.
Programmable Electronic Night
Setback Thermostat
Heating setback and cooling setup
with 7-day, 5-1-1 programming
capability. Available in 2 heating/
cooling or 1 heating/cooling versions
with automatic changeover.
Digital Display Programmable
Thermostat (2H/2C)
Two Heat/Two Cool digital display
thermostat. 7-day programmable
stat with night setback shall be
available.
Figure 12.
Tue
Heat
System & Fan
Hold Until
Fan Auto
Override
More
Touchscreen Programmable
Thermostat (2H/2C)
Two Heat/Two Cool programmable
thermostat with touch screen digital
display. Menu-driven programming.
Effortless set-up. Program each day
separately with no need to copy
multiple days. All programming can
be done on one screen. Easy to read
and use. Large, clear backlit digital
display.
Figure 13.
WED THU FRI
TUE
MON
FAN
ON
AUTO
CIRC
CANCEL
SYSTEM
RESET
PERIOD
EM HEAT
HEAT
OFF
PM
COOL
AUTO
DONE WAKE LEAVE RETURN SLEEP EDIT CANCEL
SAT
DEHUMIDIFIER
SUN
HEAT
COOL
Digital Display Programmable
Thermostat with Built-In Relative
Humidity Sensing (3H/2C)
Three Heat/Two Cool digital display
thermostat with built-in humidity
control and display. This thermostat
combines both humidity and dry
bulb into one. Fully programmable
with night setback.
Figure 14.
Tue
Digital Display Thermostat
(3H/2C)
Three Heat/Two Cool digital display
thermostat. Easy access battery
replacement. Flip-out door for easy
battery replacement without
removing or disassembling the
thermostat.
Figure 15.
RA Remote Sensor
Return Air Remote Sensor which can
be mounted in the return air duct to
report return air temperature.
Room Remote Sensor
Space Remote Sensor which can be
mounted on the wall to report/
control from a remote location in the
space.
Outdoor Thermostat
Outdoor thermostat which can be
mounted outdoors to turn on the
units electric heater at a pre-selected
outdoor temperature.
SSP-PRC001-EN31
Electrical Data
Table 33. Unit Wiring - Heat Pumps
Maximum Fuse Size or
Maximum Circuit
Breaker
TonsUnit Model No.
TWA090A3187-25334.550
7½
10
15
20
(i)
HACR type circuit breaker per NEC.
TWA090A4414-50618.125
TWA090AW518-63214.520
TWA120A3187-25348.170
TWA120A4414-50623.335
TWA120AW518-63218.825
TWA180B3187-25362.780
TWA180B4414-50632.945
TWA180BW518-63226.335
TWA240B3187-25387.8100
TWA240B4414-50642.550
TWA240BW518-63234.245
Unit Operating Voltage
Range
Minimum Circuit
Ampacity
Table 34. Electrical Characteristics - Compressor and Condenser Fan Motors - 60 Cycle - Heat Pumps
kW ratings are at: 208/240V for 208-230V air handlers.
480V for 460V air handlers
600V for 575V air handlers
For other than rated voltage, capacity = (Voltage/Rated Voltage)2 x Rated Capacity.
(ii)
Any power supply and circuits must be wired and protected in accordance with local codes.
(iii)
The HACR circuit breaker is for U.S.A. installations only.
(iv)
Field wire must be rated at least 75 C.
(v)
Field wire must be rated at least 90 C.
(vi)
With motor field converted to 460V.
Table 38. Unit Wiring with Electric Heat (Single Point Connection) - 15 and 20 Ton Air Handlers
kW ratings are at: 208/240V for 208-230V air handlers.
480V for 460V air handlers
600V for 575V air handlers
For other than rated voltage, capacity = (Voltage/Rated Voltage)
(ii)
Any power supply and circuits must be wired and protected in accordance with local codes.
(iii)
The HACR circuit breaker is for U.S.A. installations only.
(iv)
Field wire must be rated at least 90 C.
SSP-PRC001-EN35
2
x Rated Capacity.
Jobsite Connections
Wiring shown with dashed lines is to
be furnished and installed by the
customer. All customer- supplied
wiring must be copper only and
must conform to NEC and local
electrical codes. Codes may require
line of sight between disconnect
switch and unit.
Note: When electric heater
accessory is used single
point power entry or dual
point power entry is field
optional. Single point power
entry option is through
electric heater only.
TWA060/TWE060A
Field Wiring:
A3 power wires. Line voltage for 3
phase; 2 wires for single phase.
B3 power wires. Line voltage for 3
phase; 2 wires for single phase
CHeat pump thermostat: 6 wires,
24 volts.
Electric heat: add 2 additional
wires, 24 volts.
D2 wires, 24 volts.
Outdoor thermostat: add 1
additional wire per ODT, 24 volts.
Electric heat: add 1 additional
wire, 24 volts.
Units shall be assembled on heavy
gauge steel mounting/lifting rails
and shall be weather proofed. Unit
shall include a hermetic scroll or
reciprocating compressor(s), plate
fin condenser coil, fans and motors,
controls and holding charge of
nitrogen. Operating Range shall be
between 115°F to 50°F in cooling as
standard from factory. Units shall be
UL 1995 listed and rated in
accordance with ARI Standard 340/
360.
Casing
Unit casing shall be constructed of
18 gauge zinc coated heavy gauge,
galvanized steel. Exterior surfaces
shall be cleaned, phosphatized and
finished with a weather-resistant
baked enamel finish. Units surface
shall be tested 500 hours in salt
spray test. Units shall have
removable end panels which allow
access to all major components and
controls.
Refrigeration System —
Single Compressor
TWA090A, TWA120A units shall
have a single refrigeration circuit.
Each refrigeration circuit has an
integral subcooling circuit. A
refrigeration filter drier, expansion
valve and check valves shall be
provided as standard.
The TWA090A, TWA120A units shall
have both a liquid line and suction
gas line service valve with gauge
port. TWA090A, TWA120A units shall
have one direct drive Trane hermetic
scroll compressor with centrifugal oil
pump providing positive lubrication
to moving parts.
Motor shall be suction gas-cooled
and shall have a voltage utilization
range of plus or minus 10 percent of
nameplate voltage. Crankcase
heater, internal temperature and
current-sensitive motor overloads
shall be included for maximum
protection. Scroll type compressor
shall provide inherently low
vibration and noise by having no
suction and discharge valves.
External high and low pressure
cutout devices shall be provided.
Evaporator defrost control provided
in indoor blower coil unit shall
prevent compressor slugging by
temporarily interrupting compressor
operation when low evaporator coil
temperatures are encountered.
Refrigeration System — Dual
Compressor
TWA180B, TWA240B units shall have
two separate and independent
refrigeration circuits. Each
refrigeration circuit shall have an
integral subcooling circuit. A
refrigeration filter drier shall be
provided as standard.
Units shall have both a liquid line
and suction gas line service valve
with gauge ports. TWA180B,
TWA240B units shall have two Trane
direct drive hermetic scroll
compressors with centrifugal oil
pump and provide positive
lubrication to all moving parts.
Motor shall be suction gas-cooled
and shall have a voltage utilization
range of plus or minus 10 percent of
nameplate voltage. Crankcase
heater, internal temperature and
current-sensitive motor overloads
shall be included for maximum
protection. Scroll type compressor
shall provide inherently low
vibration and noise by having no
suction and discharge valves.
External high and low pressure
cutout devices shall be provided.
Evaporator defrost control provided
in indoor blower coil shall prevent
compressor slugging by temporarily
interrupting compressor operation
when low evaporator coil
temperatures are encountered.
Condenser Coil
Coils shall be internally finned or
smooth bore 3/8" copper tubes
mechanically bonded to configured
aluminum plate fin as standard. Coil
shall be factory pressure and leak
tested to 420 psig air pressure. Metal
grilles with PVC coating for coil
protection is optional.
Condenser Fan and Motor(s)
Direct-drive, statically and
dynamically balanced 26 or 28 inch
propeller fan(s) with aluminum
blades and electro-coated steel hubs
shall be used in draw-through
vertical discharge position. Either
permanently lubricated totally
enclosed or open construction type
motors shall be provided and shall
have built in current and thermal
overload protection. Motor(s) shall
have either ball or sleeve bearing
type.
Controls
Heat pump units shall be completely
factory wired with necessary
controls and contactor pressure lugs
or terminal block for power wiring.
Control wiring shall be 24-volt
control circuit which includes fusing
and control transformer. Units shall
provide external location for
mounting a fused disconnect device.
Time delay timers to prevent
compressors in dual compressor
units from simultaneous start-up and
anti-recycle timers are available as
optional accessories.
Defrost Controls
Electronic timed initiated,
temperature terminated defrost
system with choice of 50, 70, or 90
minute cycle. Timed override limits
defrost cycle to 10 minutes.
Low Ambient Operation
Standard units shall start and
operate to approximately 50°F when
matched with Trane air handlers and
coils. Optional head pressure control
accessory permits operation to 0°F.
Accessories
Low Ambient Head Pressure
Control — Shall modulate the RPM
of unit outdoor fan motor in
response to outdoor ambient
temperatures and liquid line
temperature. Accessory provides
unit cooling operation to outdoor
temperatures of 0°F.
Vibration Isolation Packages —
Shall reduce transmission of noise
60SSP-PRC001-EN
Mechanical Specifications
and vibration to building structures,
equipment and adjacent spaces.
Packages shall be available in either
neoprene-in-shear or spring-flex
types.
Time Delay Relay — Shall prevent
compressors in dual compressor unit
from coming on line simultaneously.
Timer shall be 24-volt, 60 cycle, with
four minute timing period.
Anti-Short-Cycle Timer — Shall
prevent rapid on-off compressor
cycling in light load conditions by not
allowing compressor to operate for
5-7 minutes upon shutdown. Shall
consist of a solid state timing device,
24-volt, 60 cycle with either 5 or 7
minute fixed-off timing period.
Condenser Coil Guard — Metal
grille with PVC coating shall be
provided to alleviate coil damage.
Black Epoxy Coated Condenser
Coil — The black epoxy coils have a
thermoset vinyl coating that is
bonded to the aluminum fin stock
prior to the fin-stamping process.
The pre-coated coils are an
economical option for protection in
mildly corrosive environments.
Air Handlers
General
Air handler units shall be completely
factory assembled including coil,
condensate drain pan, fan motor(s),
filters and controls in an insulated
casing that can be applied in either
vertical or horizontal configuration.
Units shall be rated and tested in
accordance with ARI standard 340/
360. Units shall be UL listed and
labeled in accordance with UL 1995
for indoor blower coil units.
Casing
Unit casing shall be constructed of
zinc coated, heavy gauge, galvanized
steel. Exterior surfaces shall be
cleaned, phosphatized and finished
with a weather-resistant baked
enamel finish. Casing shall be
completely insulated with cleanable,
foil faced, fire-retardant, permanent,
odorless glass fiber material. All
insulation edges shall be either
captured or sealed. Knockouts shall
be provided for unit electrical power
and refrigerant piping connections.
Captive screws shall be standard on
all access panels.
Refrigeration System
The TWE060A, TWE090A, TWE120A
units shall have a single refrigeration
circuit and the TWE060B, TWE090B,
TWE120B, TWE180B, TWE240B units
shall have dual refrigeration circuits.
Each refrigeration circuit is controlled
by a factory installed thermal
expansion valve.
Evaporator Coil
Configured aluminum fin surface
shall be mechanically bonded to 3/8"
internally enhanced copper tubing
and factory pressure and leak tested
at 375 psig. Coil is arranged for drawthrough airflow and shall provide a
double sloped condensate drain pan
constructed of PVC plastic. The drain
pan shall be removable for cleaning.
The condensate drain pan can be
installed in any of four positions
allowing for vertical or horizontal
application and providing external
connections on either side of the
unit.
Evaporator Fan
Double inlet, double width, forward
curved, centrifugal-type fan(s) with
adjustable belt drive shall be
standard. Thermal overload
protection shall be standard on
motor. Fan and motor bearings shall
be permanently lubricated. Oversized
motors shall be available as an
option for high static application. All
indoor fan motors meet the U.S.
Energy Policy Act of 1992 (EPACT)
Controls
Magnetic evaporator fan contactor,
low voltage terminal strip, check
valve(s), and single point power
entry shall be included. All necessary
controls shall be factory-installed and
wired. Evaporator defrost control
shall be included to prevent
compressor slugging by temporarily
interrupting compressor operation
when low evaporator coil
temperatures are encountered.
Filters
One inch, throw-away filters shall be
standard on TWE060A, TWE090A,
TWE060B, TWE090B and TWE120B
model air handlers. Filters shall be
accessible from the side coil access
panel. Filter rack can be field
converted to two inch capability. Two
inch, throw-away filters shall be
standard on TWE180B and TWE240B
models.
Accessories
Electric Heaters — UL and CSA
approved electric heat modules shall
be available for installation directly
on fan discharge. Electric Heaters
shall be available in a wide range of
capacities with one or two stage
control, single-point electric power
connection and terminal strip
connections. Electric heater elements
shall be constructed of heavy-duty
nickel chromium elements internally
wye connected on 480/600 volt, three
phase and delta connected on 208/
240 volt, three phase. Each 208/240
volt heater shall have pilot duty with
secondary backup fuse links for
automatic reset of high limit controls.
Each 480/600 volt heater shall have
automatic line break high limit
controls.
Discharge Plenums and Grilles —
Accessory discharge plenums shall
be available for vertical, free
discharge applications. Plenums shall
be constructed of heavy-gauge, zinc
coated galvanized steel finished with
baked enamel to match the air
handler unit. Grilles shall be satin
finished aluminum and have fourway adjustable louvers.
Return Air Grilles — Accessory
return air grille shall be provided for
vertical front, free return
applications. Grilles shall be installed
in place of the front lower side panel.
Grille shall be satin finished
aluminum with non-adjustable
louvers.
Mounting Subbase — Available for
vertical floor mount configurations.
Subbase shall be constructed of
heavy gauge, zinc coated galvanized
steel with baked enamel finish to
match air handler unit. Subbase is
required in the vertical air flow
application for condensate drain
trapping and when isolators are
required.
Vibration Isolators — Shall reduce
transmission of noise and vibration
to building structures, equipment
and adjacent spaces. Packages shall
SSP-PRC001-EN61
be available in either neoprene-in
shear or spring-flex types in floor or
suspended mountings.
Oversized Motors — Field installed
oversized motors shall be available
for high static pressure applications.
Control Options
Standard Indoor Thermostats —
Two stage heating and cooling
operation or one stage heating and
cooling thermostats shall be
available in either manual or
automatic changeover.
Programmable Electronic Night
Setback Thermostat — Shall
provide heating setback and cooling
setup with 7-day programming
capability.
Outdoor Thermostat — Shall
provide staging control of electric
heaters based on a set outdoor
temperature.
Mechanical Specifications
62SSP-PRC001-EN
Tr a n e
A business of American Standard Companies
www.trane.com
For more information, contact your local Trane
office or e-mail us at comfort@trane.com
Literature Order NumberSSP-PRC001-EN
DateFebruary 2008
SupersedesSSP-PRC001-EN (July 2007)
Trane has a policy of continuous product and product data improvement and reserves the right to
change design and specifications without notice.
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.