Trane 190, 260, 300, 350, 400 Installation & Operation Manual

...
RAU-SVX01F-E4
Installation Operation Maintenance
RAUL Air Cooled Condensing Unit Sizes 190 – 260 – 300 – 350 – 400 450 – 500 – 600 – 700 – 800
To be used
with the CH530 control
module manual
RAU-SVX01F-E4
General information
Foreword
These instructions are given as a guide to good practice in the installation, start-up, operation, and maintenance by the user, of Trane RAUL. They do not contain full service procedures necessary for the continued successful operation of this equipment. The services of a qualified technician should be employed through the medium of a maintenance contract with a reputable service company. Read this manual thoroughly before unit start-up. Units are assembled, pressure tested, dehydrated, charged and run tested before shipment.
Warnings and cautions
Warnings and Cautions appear at appropriate sections throughout this manual. Your personal safety and the proper operation of this machine require that you follow them carefully. The constructor assumes no liability for installations or servicing performed by unqualified personnel. WARNING! : Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury. CAUTION! : Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury. It may also be used to alert against unsafe practices or for equipment or property-damage-only accidents.
Safety recommendations
To avoid death, injury, equipment or property damage, the following recommendations should be observed during maintenance and service visits:
1. The maximum allowable pressures for system leak testing on low and high pressure side are given in the chapter «Installation». Always provide a pressure regulator.
2. Disconnect the main power supply before any servicing on the unit.
3. Service work on the refrigeration system and the electrical system should be carried out only by qualified and experienced personnel.
Reception
On arrival, inspect the unit before signing the delivery note.
Reception in France only:
In case of visible damage: The consignee (or the site representative) must specify any damage on the delivery note, legibly sign and date the delivery note, and the truck driver must countersign it. The consignee (or the site representative) must notify Trane Epinal Operations - Claims team and send a copy of the delivery note. The customer (or the site representative) should send a registered letter to the last carrier within 3 days of delivery. Note: for deliveries in France, even concealed damage must be looked for at delivery and immediately treated as visible damage.
Reception in all countries except France:
In case of concealed damage: The consignee (or the site representative) must send a registered letter to the last carrier within 7 days of delivery, claiming for the described damage. A copy of this letter must be sent to Trane Epinal Operations - Claims team.
Warranty
Warranty is based on the general terms and conditions of the manufacturer. The warranty is void if the equipment is repaired or modified without the written approval of the manufacturer, if the operating limits are exceeded or if the control system or the electrical wiring is modified. Damage due to misuse, lack of maintenance or failure to comply with the manufacturer’s instructions or recommendations is not covered by the warranty obligation. If the user does not conform to the rules of this manual, it may entail cancellation of warranty and liabilities by the manufacturer.
© 2012 Trane
RAU-SVX01F-E4
Contents
3
Refrigerant
The refrigerant provided by the manufacturer meets all the requirements of our units. When using recycled or reprocessed refrigerant, it is advisable to ensure its quality is equivalent to that of a new refrigerant. For this, it is necessary to have a precise analysis made by a specialized laboratory. If this condition is not respected, the manufacturer warranty could be cancelled.
Environmental Protection / Compliance with F-Gas regulation
This equipment contains a fluorinated gas covered by the Kyoto Protocol [or an ozone depleting substance covered by Montreal Protocol].The type and quantity of refrigerant per circuit is indicated on the product nameplate. The Global Warming Potential of the refrigerant implemented in Trane Air Conditioning and Refrigeration Equipment is presented in the table by type of refrigerant.
Refrigerant type GWP (1) value R134a 1 300 R407C 1 653
The operator (contractor or end user) must check local environmental regulations impacting installation, operation and disposal of the equipment; in particular need to recover environmentally harmful substances (refrigerant, oil, antifreeze agents, etc.) Do not vent into the atmosphere any refrigerant. The handling of refrigerant shall be fulfilled by a qualified service engineer.
(1) GWP = global warming potential
Maintenance contract
It is strongly recommended that you sign a maintenance contract with your local Service Agency. This contract provides regular maintenance of your installation by a specialist in our equipment. Regular maintenance ensures that any malfunction is detected and corrected in good time and minimizes the possibility that serious damage will occur. Finally, regular maintenance ensures the maximum operating life of your equipment. We would remind you that failure to respect these installation and maintenance instructions may result in immediate cancellation of the warranty.
Training
To assist you in obtaining the best use of it and maintaining it in perfect operating condition over a long period of time, the manufacturer has at your disposal a refrigeration and air conditioning service school. The principal aim of this is to give operators and technicians a better knowledge of the equipment they are using, or that is under their charge. Emphasis is particularly given to the importance of periodic checks on the unit operating parameters as well as on preventive maintenance, which reduces the cost of owning the unit by avoiding serious and costly breakdown.
4 RAU-SVX01F-E4
Contents
General information 2
Installation 5
Unit nameplate 5
Installation instructions 5
Handling 5
Refrigerant lines 6
Refrigerant charge 7
Oil charge 7
Electrical connections 10
Temperature sensor 10
Hot gas-bypass control (option) 10
Capacity control modes 11
General start-up 12
Start-up Preparation 12
Start-up 12
Operation 14
Control System 14
Unit operations 14
Week end shutdown 14
Seasonal shutdown 14
Seasonal start-up 14
Maintenance 15
Maintenance instructions 15
Installation checklist 16
Troubleshooting guide 17
Performance data 20
5RAU-SVX01F-E4
Installation
For minimum clearance, consult the certified submittals, which are available on request from your Trane Sales Office.
Unit nameplate
The unit nameplate gives the complete model reference numbers. The unit power rating is shown, and power supplies should not deviate by more than 5 % from the rated power. Compressor motor amperage is shown in box I.MAX. The customer’s electrical installation must be able to withstand this current.
Installation instructions
Foundations
No special foundations are required, provided the supporting surface is flat and level, and can withstand the weight or the unit.
Anti-vibration rubber pads
They are supplied as standard with the machine, and should be placed between the supporting floor and the unit to attenuate vibrations.
- 4 pads for the sizes 190 to 300
- 6 pads for the sizes 350 to 800
- Trane does not allow the installation of spring isolators.
Clearance
Respect recommended clearance around the unit to allow maintenance operation to take place without obstruction and recommended clearance around condenser.
CAUTION! Unit operation depends on the air temperature. Any recycling of the air fed out by the fans will increase the air intake temperature over the condenser fins and can result in high pressure cut-out. In this case the standard operating conditions are modified. Operation of the unit may be affected by an increase in air temperature on the condenser. When the units are positioned in a windy area, avoid all the risks of air­cooled recycling.
See submittals
Handling
Note: The plates welded at the end of the bases must not be used for handling.
Figure 1 - Handling
A
B
Table 1 - Dimensions of recommended slings and swing-bar:
190 260 300 350 400 450 500 600 700 800 A (mm) 1500 1500 1500 1500 1500 1500 2400 2400 2300 2300 B (mm) 1800 1800 1800 1800 1800 1800 1800 1800 2200 2200 Weight - crated (kg) 555 625 691 869 959 985 1123 1251 1695 1754
6 RAU-SVX01F-E4
Installation
Discharge lines
Discharge lines should be calculated to obtain the gas displacement speed in horizontal and vertical lines required to drive compressor oil. Determine diameter of discharge lines as per the following criteria.
1. Speed above 2.5 m/s horizontally. (Consider minimum speed at minimum load)
2. Speed above 5.0 m/s vertically (Vertical risers, consider speed at minimum load)
3. Maximum speed 20 m/s.
4. Horizontal pipe run must be pitched of 1cm/m in the same direction as the refrigerant circulation
5. An oil trap is necessary for vertical risers greater than 3m. For major elevations add an intermediate oil trap every 5m.
6. Maximum pressure drop between 20 to 50 kPa
7. Install a filter drier adapted to refrigerant capacity.
Insulation of refrigerant lines
Insulate refrigerant lines from building itself to avoid transmission to building structure of vibrations normally caused by pipework. Also avoid bypassing the unit’s damping system by fixing the refrigerant lines or the electrical ducts very rigidly.Vibrations may propagate into building structure through rigidly fixed refrigerant lines.
Refrigerant lines
Figure 2 - Refrigerant flow chart
1 = Compressor 2 = Condenser coil 3 = Subcooler coil 4 = Schraeder valve 5 = Coil header 6 = Relief valve 7 = High pressure switch 8 = Low pressure transducer 9 = High pressure transducer 10 = Stop valve
Calculating and fixing the capacity of refrigerant lines is necessary to assure the oil return to the compressor, avoid refrigerant phase changes and limit pressure drop.
Liquid lines
Calculate capacity of liquid line, as per the following criteria.
1. Maximum load operating conditions.
2. To avoid any evaporation risk:
- Consider the vertical risers
- Maximum pressure drop must not exceed 1 to 2°C
3. Liquid circulation speed in a 0.5 to 2m/s range.
Pressure tests. Leak detection
During operations, take the following precaution:
1. Neither oxygen nor acethylene should be used instead of refrigerant and nitrogen to detect leaks, otherwise a violent explosion may occur.
2. Always use valves and manometers to check the test pressure in system. Excessive pressure may either cause pipes to rupture, damage unit, or cause an explosion, causing possible physical injury.
Carry out liquid line and hot gas line pressure tests in accordance with current standards. The test pressures applied to the liquid line and the hot gas suction line must comply with the country’s standards.
Caution: Do not go more than 0.7 bar above the high pressure switch setpoint.
7RAU-SVX01F-E4
Installation
Introduce enough refrigerant into circuit in order to obtain a pressure of 85 to 100 kPa. Search for possible leaks using detector. This operation should be carried out with great care throughout the system. If leaks are detected, pump down the refrigerant, and repair defective component. Repeat test process, to check that the repair can withstand rated pressure.
Refrigerant charge (all split system types)
Units ship with a nitrogen holding charge and isolating valves.
After system pressure and vacuum testing, fill up unit with refrigerant. The refrigerant complement will be charged according to the diameter and the length of the refrigerant piping work up to obtain the correct superheat and subcooling temperatures.
Oil charge
The oil quantity necessary for the split system has also to be adjusted according to the diameter and the length of the refrigerant piping work.
Important note: These operations have to be performed by a specialist according to the rules of the art. The results have to be written on a start up record by the Trane engineer or the client’s specialist who has performed this start up. The quantity of refrigerant and oil added are at the client’s charges.
8 RAU-SVX01F-E4
Split
system
Split
system
Split
system
Split
system
Split
system
Split
system
Split
system
Split
system
Split
system
Split
system
Table 3 - R407C General data
RAU 190 RAU 260 RAU 300 RAU 350 RAU 400 RAU 450 RAU 500 RAU 600 RAU 700 RAU 800 R407C R407C R407C R407C R407C R407C R407C R407C R407C R407C
Performances (1)
Gross cooling capacity (1) (kW) 54.8 66.6 81.1 95.3 108.3 118.8 133.0 162.0 194.7 218.8 Power input in cooling (1) (kW) 16.7 23.6 28.2 31.0 36.1 43.2 48.7 57.9 61.8 74.6 Main Power supply 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 Sound Power Level (5) (dB(A)) 88 90 91 91 92 93 93 94 98 98
Units Amps
Nominal (4) (A) 41.3 50.1 59.0 70.3 79.1 88.0 99.3 117.0 150.4 168.1 Start-up Amps (A) 144 199 207 219 228 236 248 265 299 316 Max supply cable size (mm2) 35 35 35 50 50 95 95 95 150 150
Compressor
Number 2 2 2 3 3 3 4 4 6 6 Type Scroll Scroll Scroll Scroll Scroll Scroll Scroll Scroll Scroll Scroll Model 10T+10T 10T+15T 2x15T 10+10T- 15T 10T+15T - 15T 15T+15T - 15T 2x(10T+15T) 2 x (15T+15T) 2x(10T+10T+15T) 2x(10T+15T+15T) Number of speeds 1 1 1 1 1 1 1 1 1 1 Number of motors C1 / C2 2 2 2 2 / 1 2 / 1 2 / 1 2 / 2 2 / 2 3 / 3 3 / 3 Rated Amps (2)(4) (A) 17.7 17.7 / 26.6 26.6 17.7 / 26.6 17.7 / 26.6 26.6 17.7 / 26.6 26.6 17.7 / 26.6 17.7 / 26.6 Locked rotor Amps (2) (A) 120 120 / 175 175 120 / 175 120 / 175 175 120 / 175 175 120 / 175 120 / 175 Motor RPM (rpm) 2900 2900 2900 2900 2900 2900 2900 2900 2900 2900 Sump Heater (2) (W) 50W - 400V 50W - 400V 50W - 400V 50W - 400V 50W - 400V 50W - 400V 50W - 400V 50W - 400V 50W - 400V 50W - 400V
Liquid and Suction connection
Suction connection brazed 1»5/8 1»5/8 1»5/8 1»5/8 1»5/8 1»5/8 1»5/8 1»5/8 2»1/8 2»1/8 Liquid connection brazed 7/8» 7/8» 7/8» 7/8» 7/8» 7/8» 7/8» 7/8» 1»1/8 1»1/8
Coil
Type Plate Fin Plate Fin Plate Fin Plate Fin Plate Fin Plate Fin Plate Fin Plate Fin Plate Fin Plate Fin Tube size (mm) 9.52 9.52 9.52 9.52 9.52 9.52 9.52 9.52 9.52 9.52 Tube type Smooth Smooth Smooth Smooth Smooth Smooth Smooth Smooth Smooth Smooth Height (mm) 1219 1219 1219 1219 1219 1219 1219 1219 1219 1219 Length (mm) 2743 2743 2743 3455 4115 4115 5486 5486 5486 5486 Face Area (m
2
) 3.34 3.34 3.34 4.21 5.02 5.02 6.69 6.69 6.69 6.69 Rows # 2 2 3 3 3 3 2 3 3 3 Fins per foot (fpf) # 156.0 156.0 156.0 156.0 156.0 156.0 156.0 156.0 156.0 156.0
Fan
Type Propeller Propeller Propeller Propeller Propeller Propeller Propeller Propeller Propeller Propeller Number 2 2 2 3 3 3 4 4 6 6 Diameter (mm) 962 962 962 962 962 962 962 962 962 962 Drive type Direct Direct Direct Direct Direct Direct Direct Direct Direct Direct Number of speeds 1 1 1 1 1 1 1 1 1 1 Air flow (m
3
/h) 27000 27000 25300 35900 37900 37900 54000 50700 89100 89100 Number of motors 2 2 2 3 3 3 4 4 6 6 Motor HP (2) (kW) 0.85 0.85 0.85 0.85 0.85 0.85 0.85 0.85 1.72 1.72 Rated Amps (2) (A) 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 3.26 3.26 Locked rotor Amps (2) (A) 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 15.5 15.5 Motor RPM (rpm) 705 705 705 705 705 705 705 705 930 930
Dimensions
Height (mm) 1582 1582 1582 1582 1582 1582 1584 1584 1598 1598 Length (mm) 2061 2061 2061 2921 2921 2921 2225 2225 3090 3090 Width (mm) 995 995 995 995 995 995 1865 1865 1948 1948 Weight uncrated (kg) 514 584 650 810 900 926 1040 1168 1575 1634 Weight crated (kg) 555 625 691 869 959 985 1123 1251 1695 1754
System Data
Refrigerant circuit 1 1 1 2 2 2 2 2 2 2
System Data
Refrigerant circuit 1 1 1 2 2 2 2 2 2 2
Refrigerant Charge (3)
Circuit A & B (kg)
(1) at 7°C SST and 35°C ambiant (2) per motor (3) per circuit (4) 5°C sat suction temp. - 60°C sat discharge temp. (5) In accordance with ISO 3746
Installation
Loading...
+ 16 hidden pages