Trane 4YCY4060A, 4YCY4024A User Manual

Product Data
4YCY4024A through 4YCY4060A
Single Packaged Convertible Gas/Electric 14 SEER 2 - 5 Ton, 40 - 120 KBTU
R-410A
© 2008 Trane
Pub. No. 22-1797-03
It's Hard to Stop a Trane.
Single Packaged Convertible Gas/Electric System
Trane offers a complete family of packaged gas/electric heating and cooling sys­tems, designed to give you the unbeatable combination of energy efficiency and lower operating costs. In warm weather, the packaged gas/electric system functions as an all-electric, high efficiency air conditioner. In cold weather, it operates as a natural gas or propane gas furnace, offering you the best of both energy worlds.
Introducing the new TRANE Single Packaged Convertible Gas/Electric System.
Single Packaged Convertible Gas/ Electric Systems are easy and versa­tile to install. Because cooling and
heating functions are all contained in a single cabinet, a Trane single packaged convertible gas/electric system is easy to install and service. It can be flush mounted beside your home at ground level or placed on the roof for horizontal or downflow installation. When connected to an optional Trane thermostat control, and air distribution ducts, you have a highly efficient, total home comfort system.
Single Packaged Convertible Gas/ Electric Systems are unmatched in quality and reliability. All major
components on these products, including the compressor, have been designed and manufactured for maximum service. Every Climatuff compressor is designed and manufac­tured to exacting specifications. Each design is life tested in extreme environ­ments to ensure reliable and long lasting operation in normal applications. Each compressor has internal motor protection for added reliability.
2
®
Contents
Optional Equipment Listing 4
General Data 5
Performance Data
Cooling 9 Indoor Fan 11
Typical Wiring 15
Optional Equipment 18
Dimensional Data 23
Mechanical Specifications 29
3
Optional Equipment Listing
OPTIONAL EQUIPMENT FOR PACKAGED UNITS (check mark [
Hinged Filter Access Door (4YCY4024-036) 8 ................................................................ BAYACCDOR1A[ ]
Hinged Filter Access Door (4YCY4042-060) 8 ................................................................ BAYACCDOR2A[ ]
Roof Curb Full Perimeter (4YCY4024-36A) 3 ................................................................... BAYCURB050A[ ]
Roof Curb Full Perimeter (4YCY4042-60A) 3 ................................................................... BAYCURB051A[ ]
Roof Curb Utility Extension Kit (BAYCURB050A) ................................................................. BAYUTIL101B[ ]
Roof Curb Utility Extension Kit (BAYCURB051A) ................................................................. BAYUTIL102B[ ]
0-25% Manual Fresh Air Damper (4YCY4024-36A) 1. ...................................................... BAYOSAH001A[ ]
0-25% Manual Fresh Air Damper (4YCY4042-60A) 1. ...................................................... BAYOSAH002A[ ]
Motorized Fresh Air Damper (4YCY4024-36A) 1............................................................. BAYDMPR101A[ ]
Motorized Fresh Air Damper (4YCY4042-60A) 1. ............................................................. BAYDMPR102A[ ]
16" Round Duct Adapter (2 per box) (4YCY4024-36A) 6 ................................................. BAYSQRD001A[ ]
18" Round Duct Adapter (2 per box) (4YCY4024-60A) 6 ................................................. BAYSQRD002A[ ]
0-100% Mod Economizer w/Baro. Relief (4YCY4024-36A) 124 .................................... BAYECON101B[ ]
0-100% Mod. Economizer w/Baro. Relief (4YCY4042-60A) 124. .................................. BAYECON102B[ ]
0-100% Horizontal Economizer (4YCY4024-36A) 12 . .................................................... BAYECON200A[ ]
0-100% Horizontal Economizer (4YCY4042-60A) 12 . .................................................... BAYECON201A[ ]
Enthalpy Control for Economizer (solid state). .................................................................... BAYENTH001A[ ]
Remote Potentiometer (All-BAYECON***A) ............................................................................ BAYSTAT023[ ]
1"-2" Filter Frame (4YCY4024-36A) (20 x 25 filter not included) 1. .................................... BAYFLTR101B[ ]
1"-2" Filter Frame (4YCY4042-60A) (20 x 20 & 20 x 18 filter not included) 1. ................... BAYFLTR201B[ ]
LP Conversion Kit (All 40K, 120K Models) ........................................................................... BAYLPKT100A[ ]
LP Conversion Kit (All 64K, 96K Models) ............................................................................. BAYLPKT101A[ ]
LP Conversion Kit (All 75K Models) ..................................................................................... BAYLPKT102A[]
Head Pressure Control (Low Ambient Cool) (208/240v) Kit 5. ......................................... BAYLOAM105A[ ]
Quick Start Kit (4YCY4-A1) .................................................................................................. BAYQSKT301A[ ]
Crankcase Heater Recip (4YCY4024A1 (230v) 5. .............................................................BAYCCHT101A[ ]
Crankcase Heater Scroll (4YCY4036-060A1/3)(230v) 5. .................................................. BAYCCHT102A[ ]
Adapter Curb 4YCY4024-036A to BAYCURB030,38 ........................................................ BAYADAP050A[ ]
Adapter Curb 4YCY4024-036A to BAYCURB033 ............................................................. BAYADAP051A[ ]
Adapter Curb 4YCY4042-060A to BAYCURB030,38 ........................................................ BAYADAP052A[ ]
Adapter Curb 4YCY4042-060A to BAYCURB033 ............................................................. BAYADAP053A[ ]
Adapter Curb 4YCY4042-060A to BAYCURB034 ............................................................. BAYADAP054A[ ]
12" Duct Shroud Covers Horizontal 4YCY4024-060A7. ................................................... BAYCOVR112A[ ]
18" Duct Shroud Covers Horizontal 4YCY4024-060A 7. .................................................. BAYCOVR118A[ ]
Extreme Condition Mounting Kit - All BAYCURB & BAYADAP ......................................... BAYEXMK001A[ ]
Extreme Condition Mounting Kit - All BAYUTIL .................................................................. BAYEXMK002B[ ]
Extreme Condition Mounting Kit - All Slab Mounts ............................................................. BAYEXMK003A[ ]
Lifting Lug Kit .......................................................................................................................... BAYLlFT002B[ ]
✓✓
] indicates accessories included)
✓✓
NOTES: 1 Must use filter frame when economizer/fresh air kit is used.
2 Dry bulb control standard with economizer. 3 Ships knocked down. 4 Downflow only. 5 Low Ambient cooling requires crankcase heater (BAYCCHT----A). 6 It is the responsibility of the installing dealer to properly size the ductwork for each specific application. 7 BAYCOVR112,118A will not cover BAYSQRD002A applications 8 BAYACCDOR1A requires BAYFLTR101B & BAYACCDOR2A requires BAYFLTR201B. They are not
backward compatible to BAYFLTR101/201A.
4
MODEL RATED Volts/PH/Hz Performance Cooling BTUHj
Indoor Airflow (CFM) Power Input (KW) EER/SEER(BTU/Watt-Hr.)n
Sound Power Rating [dB(A)]8
Performance Heatingk
Input BTUH - 1st Stage (Natural Gas)p Input BTUH - 2nd Stage (Natural Gas)p AFUE Temp. Rise — Min/Max (°F) Orifice Qty / Drill Size (Natural Gas)l
POWER CONN.—V/PH/HZ
Min. Brch. Cir. Ampacitym Fuse Size — Max. (amps) Fuse Size — Recmd. (amps)
COMPRESSOR
Volts/Ph/Hz R.L. Amps — L.R. Amps
OUTDOOR COIL — TYPE
Rows/F.P.I. Face Area (sq.ft.) Tube Size (in.)
INDOOR COIL — TYPE
Rows/F.P.I. Face Area (sq.ft.) Tube Size (in.) Refrigerant Control Drain Conn. Size (in.)
OUTDOOR FAN — TYPE
Dia. (in.) Drive/No. Speeds Motor — HP/R.P.M. Volts/Ph/Hz F.L. Amps/L.R. Amps
INDOOR FAN — TYPE
Dia x Width (in.) Drive/No. Speeds CFM @ 0.0 in. w.g.n
SEE FAN PERF TABLE Motor — HP/R.P.M. Volts/Ph/Hz F.L. Amps/L.R. Amps
COMBUSTION FAN — TYPE
Drive/No. Speeds Motor — HP/R.P.M. Volts/Ph/Hz FLA
FILTER / FURNISHED
Type Recommended Recmd. Face Area (sq. ft.)o
REFRIGERANT
Charge (lbs.)m
GAS PIPE SIZE (in.) DIMENSIONS
Crated (in.)
WEIGHT
Shipping (lbs.) / Net (lbs.)
4YCY4024A1064A
208-230/1/60
23400
790
2.162
11.6 / 14.0 68
48000 64000
79.0 35 / 65 2 / #37
208-230/1/60
16.5
25 25
RECIPROCATING
208-230/1/60
8.3 / 57.8
SPINE-FIN
2 / 24
13.32 3/8
PLATE FIN
3 / 15
3.54 3/8
EXPANSION VALVE
3/4 FEMALE NPT
PROPELLER
23.4
DIRECT / 1
1/12 / 810
208-230/1/60
0.54 / 0.95
CENTRIFUGAL
10 X 10
DIRECT / VARIABLE
1/2 / VARIABLE
200-230/1/60
4.3 / 4.3
CENTRIFUGAL
DIRECT / 2
1/45 / 2800/1500
208-230/1/60
0.34 NO
THROWAWAY
4.0
R410A
5.8 1/2
H X W X L
45.86 / 44.5 / 52.03
481 / 385
General Data
4YCY4030A1075A
208-230/1/60
30000
900
2.5
12.0 / 14.0 71
56250 75000
79.5 30 / 60 2 / #33
208-230/1/60
19.2
30 30
RECIPROCATING
200-230/1/60
11.1 / 63
SPINE-FIN
2 / 24
15.49 3/8
PLATE FIN
3 / 15
3.54 3/8
EXPANSION VALVE
3/4 FEMALE NPT
PROPELLER
23.4
DIRECT / 1
1/6 / 830
208-230/1/60
1.0 / 1.7
CENTRIFUGAL
10 X 10
DIRECT / VARIABLE
SEE FAN PERF TABLE
1/2 / VARIABLE
208-230/1/60
4.3 / 4.3
CENTRIFUGAL
DIRECT / 2
1/45 / 2800/1500
208-230/1/60
0.34 NO
THROWAWAY
4.0
R410A
6.0625 1/2
H X W X L
45.86 / 44.5 / 52.03
481 / 385
4YCY4036A1075A
208-230/1/60
36000
1210
3.284
11.6 / 14.2 69
56250 75000
79.5 30 / 60 2 / #33
208-230/1/60
24.6
40 40
SCROLL
208-230/1/60
15.4 / 83
SPINE-FIN
2 / 24
15.49 3/8
PLATE FIN
4 / 15
3.54 3/8
EXPANSION VALVE
3/4 FEMALE NPT
PROPELLER
23.4
DIRECT / 1
1/5 / 830
208-230/1/60
1.1 / 1.9
CENTRIFUGAL
10 X 10
DIRECT / VARIABLE
SEE FAN PERF TABLE
1/2 / VARIABLE
200-230/1/60
4.3 / 4.3
CENTRIFUGAL
DIRECT / 2
1/45 / 2800/1500
208-230/1/60
0.34 NO
THROWAWAY
4.0
R410A
6.75 1/2
H X W X L
47.86 / 44.5 / 52.03
488 / 392
4YCY4036A1096A
208-230/1/60
36000
1210
3.284
11.6 / 14.2 69
72000 96000
80.0 40 / 70 3 / #37
208-230/1/60
24.6
40 40
SCROLL
208-230/1/60
15.4 / 83
SPINE-FIN
2 / 24
15.49 3/8
PLATE FIN
4 / 15
3.54 3/8
EXPANSION VALVE
3/4 FEMALE NPT
PROPELLER
23.4
DIRECT / 1
1/5 / 830
208-230/1/60
1.1 / 1.9
CENTRIFUGAL
10 X 10
DIRECT / VARIABLE
SEE FAN PERF TABLE
1/2 / VARIABLE
200-230/1/60
4.3 / 4.3
CENTRIFUGAL
DIRECT / 2
1/45 / 2800/1500
208-230/1/60
0.34 NO
THROWAWAY
4.0
R410A
6.75 1/2
H X W X L
47.86 / 44.5 / 52.03
493 / 397
11
1 Certified in accordance with the Unitary Air-Conditioner Equipment certification program, which is based on ARI Standard 210/240. Noise calculated in accordance with A.R.I.
11
Standard 270.
22
2 All models are U L Listed. Ratings shown are for elevations up to 2000 ft. For higher elevations reduce ratings at a rate of 4% per 1000 ft. elevation.
22 33
3 Convertible to LPG.
33 44
4 This value is approximate. For more precise value, see Unit Nameplate.
44 55
5 Based on U.S. Government Standard Tests.
55 66
6 Filters must be installed in return air stream. Square footages listed are based on 300 f.p.m. face velocity. If permanent filters are used size per manufacturer's recommendation
66
with a clean resistance of 0.05" W.C.
77
7 Unit is shipped on high input, unit is convertible to low input with a Low Fire accessory kit.
77 88
8 Sound Power values are not adjusted for ARI 270-95 tonal corrections.
88
5
MODEL RATED Volts/PH/Hz Performance Cooling BTUHj
Indoor Airflow (CFM) Power Input (KW) EER/SEER(BTU/Watt-Hr.)n
Sound Power Rating [dB(A)]8
Performance Heatingk
Input BTUH - 1st Stage (Natural Gas)p Input BTUH - 2nd Stage (Natural Gas)p AFUE Temp. Rise — Min/Max (°F) Orifice Qty / Drill Size (Natural Gas)l
POWER CONN.—V/PH/HZ
Min. Brch. Cir. Ampacitym Fuse Size — Max. (amps) Fuse Size — Recmd. (amps)
COMPRESSOR
Volts/Ph/Hz R.L. Amps — L.R. Amps
OUTDOOR COIL — TYPE
Rows/F.P.I. Face Area (sq.ft.) Tube Size (in.)
INDOOR COIL — TYPE
Rows/F.P.I. Face Area (sq.ft.) Tube Size (in.) Refrigerant Control Drain Conn. Size (in.)
OUTDOOR FAN — TYPE
Dia. (in.) Drive/No. Speeds Motor — HP/R.P.M. Volts/Ph/Hz F.L. Amps/L.R. Amps
INDOOR FAN — TYPE
Dia x Width (in.) Drive/No. Speeds CFM @ 0.0 in. w.g.n Motor — HP/R.P.M. Volts/Ph/Hz F.L. Amps/L.R. Amps
COMBUSTION FAN — TYPE
Drive/No. Speeds Motor — HP/R.P.M. Volts/Ph/Hz FLA
FILTER / FURNISHED
Type Recommended Recmd. Face Area (sq. ft.)o
REFRIGERANT
Charge (lbs.)m
GAS PIPE SIZE (in.) DIMENSIONS
Crated (in.)
WEIGHT
Shipping (lbs.) / Net (lbs.)
General Data
4YCY4036A3075A
208-230/3/60
36000
1210
3.284
11.6 / 14.2 69
56250 75000
80.0 30 / 60 2 / #33
208-230/3/60
19.8
30 30
SCROLL
208-230/3/60
11.5 / 77
SPINE-FIN
2 / 24
15.49 3/8
PLATE FIN
4 / 15
3.54 3/8
EXPANSION VALVE
3/4 FEMALE NPT
PROPELLER
23.4
DIRECT / 1
1/5 / 830
208-230/1/60
1.1 / 1.9
CENTRIFUGAL
10 X 10
DIRECT / VARIABLE
SEE FAN PERF TABLE
1/2 / VARIABLE
200-230/1/60
4.3 / 4.3
CENTRIFUGAL
DIRECT / 2
1/45 / 2800/1500
208-230/1/60
0.34 NO
THROWAWAY
4.0
R410A
6.75 1/2
H X W X L
47.86 / 44.5 / 52.03
488 / 392
4YCY4036A3096A
208-230/3/60
36000
1210
3.284
11.6 / 14.2 69
72000 96000
80.0 40 / 70 3 / #37
208-230/3/60
19.8
30 30
SCROLL
208-230/3/60
11.5 / 77
SPINE-FIN
2 / 24
15.49 3/8
PLATE FIN
4 / 15
3.54 3/8
EXPANSION VALVE
3/4 FEMALE NPT
PROPELLER
23.4
DIRECT / 1
1/5 / 830
208-230/1/60
1.1 / 1.9
CENTRIFUGAL
10 X 10
DIRECT / VARIABLE
SEE FAN PERF TABLE
1/2 / VARIABLE
200-230/1/60
4.3 / 4.3
CENTRIFUGAL
DIRECT / 2
1/45 / 2800/1500
208-230/1/60
0.34 NO
THROWAWAY
4.0
R410A
6.75 1/2
H X W X L
47.86 / 44.5 / 52.03
493 / 397
4YCY4042A1096A
208-230/1/60
42000
1350
3.5
12.0 / 14.25 74
72000 96000
80
30 / 60 3 / #37
208-230/1/60
31.5 50 50
SCROLL
208-230/1/60
18.6 / 105 SPINE-FIN
2 / 24
23.57 3/8
PLATE FIN
3 / 15
5
3/8
EXPANSION VALVE
3/4 FEMALE NPT
PROPELLER
28.2
DIRECT / 1
1/4 / 825
208-230/1/60
1.5 / 3.4
CENTRIFUGAL
11 X 10
DIRECT / VARIABLE
SEE FAN PERF TABLE
3/4 / VARIABLE
208-230/1/60
6.8 / 6.8
CENTRIFUGAL
DIRECT / 2
1/45 / 2800/1500
208-230/1/60
0.34 NO
THROWAWAY
5.3
R410A
6.8125 1/2
H X W X L
47.86 / 47.4 / 61.75
653 / 525
11
1 Certified in accordance with the Unitary Air-Conditioner Equipment certification program, which is based on ARI Standard 210/240. Noise calculated in accordance with A.R.I.
11
Standard 270.
22
2 All models are U L Listed. Ratings shown are for elevations up to 2000 ft. For higher elevations reduce ratings at a rate of 4% per 1000 ft. elevation.
22 33
3 Convertible to LPG.
33 44
4 This value is approximate. For more precise value, see Unit Nameplate.
44 55
5 Based on U.S. Government Standard Tests.
55 66
6 Filters must be installed in return air stream. Square footages listed are based on 300 f.p.m. face velocity. If permanent filters are used size per manufacturer's recommendation
66
with a clean resistance of 0.05" W.C.
77
7 Unit is shipped on high input, unit is convertible to low input with a Low Fire accessory kit.
77 88
8 Sound Power values are not adjusted for ARI 270-95 tonal corrections.
88
6
MODEL RATED Volts/PH/Hz Performance Cooling BTUHj
Indoor Airflow (CFM) Power Input (KW) EER/SEER(BTU/Watt-Hr.)n
Sound Power Rating [dB(A)]8
Performance Heatingk
Input BTUH - 1st Stage (Natural Gas)p Input BTUH - 2nd Stage (Natural Gas)p AFUE Temp. Rise — Min/Max (°F) Orifice Qty / Drill Size (Natural Gas)l
POWER CONN.—V/PH/HZ
Min. Brch. Cir. Ampacitym Fuse Size — Max. (amps) Fuse Size — Recmd. (amps)
COMPRESSOR
Volts/Ph/Hz R.L. Amps — L.R. Amps
OUTDOOR COIL — TYPE
Rows/F.P.I. Face Area (sq.ft.) Tube Size (in.)
INDOOR COIL — TYPE
Rows/F.P.I. Face Area (sq.ft.) Tube Size (in.) Refrigerant Control Drain Conn. Size (in.)
OUTDOOR FAN — TYPE
Dia. (in.) Drive/No. Speeds Motor — HP/R.P.M. Volts/Ph/Hz F.L. Amps/L.R. Amps
INDOOR FAN — TYPE
Dia x Width (in.) Drive/No. Speeds CFM @ 0.0 in. w.g.n Motor — HP/R.P.M. Volts/Ph/Hz F.L. Amps/L.R. Amps
COMBUSTION FAN — TYPE
Drive/No. Speeds Motor — HP/R.P.M. Volts/Ph/Hz FLA
FILTER / FURNISHED
Type Recommended Recmd. Face Area (sq. ft.)o
REFRIGERANT
Charge (lbs.)m
GAS PIPE SIZE (in.) DIMENSIONS
Crated (in.)
WEIGHT
Shipping (lbs.) / Net (lbs.)
General Data
4YCY4048A1096A
208-230/1/60
48000
1605
4.034
11.9 / 14.2 73
72000 96000
80.0 30 / 60 3 / #37
208-230/1/60
33.8
50 50
SCROLL
208-230/1/60
20.5 / 109 SPINE-FIN
2 / 24
18.01 3/8
PLATE FIN
3 / 15
5.0 3/8
EXPANSION VALVE
3/4 FEMALE NPT
PROPELLER
28.2
DIRECT / 1
1/4 / 825
208-230/1/60
1.4 / 3.5
CENTRIFUGAL
11 X 10
DIRECT / VARIABLE
SEE FAN PERF TABLE
3/4 / VARIABLE
200-230/1/60
6.8 / 6.8
CENTRIFUGAL
DIRECT / 2
1/45 / 2800/1500
208-230/1/60
0.34 NO
THROWAWAY
5.3
R410A
8.2 1/2
H X W X L
47.86 / 47.4 / 61.75
653 / 525
4YCY4048A1120A
208-230/1/60
48000
1605
4.034
11.9 / 14.2 73
90000
120000
80.0 40 / 70 3 / #32
208-230/1/60
33.8
50 50
SCROLL
208-230/1/60
20.5 / 109 SPINE-FIN
2 / 24
18.01 3/8
PLATE FIN
3 / 15
5.0 3/8
EXPANSION VALVE
3/4 FEMALE NPT
PROPELLER
28.2
DIRECT / 1
1/4 / 825
208-230/1/60
1.4 / 3.37
CENTRIFUGAL
11 X 10
DIRECT / VARIABLE
SEE FAN PERF TABLE
3/4 / VARIABLE
200-230/1/60
6.8 / 6.8
CENTRIFUGAL
DIRECT / 2
1/45 / 2800/1500
208-230/1/60
0.34 NO
THROWAWAY
5.3
R410A
8.2 1/2
H X W X L
47.86 / 47.4 / 61.75
659 / 531
4YCY4048A3096A
208-230/3/60
48000
1605
4.034
11.9 / 14.2 73
72000 96000
80.0 30 / 60 3 / #37
208-230/3/60
26.4
40 40
SCROLL
208-230/3/60
14.6 / 91
SPINE-FIN
2 / 24
18.01 3/8
PLATE FIN
3 / 15
5.0 3/8
EXPANSION VALVE
3/4 FEMALE NPT
PROPELLER
28.2
DIRECT / 1
1/4 / 825
208-230/1/60
1.4 / 3.5
CENTRIFUGAL
11 X 10
DIRECT / VARIABLE
SEE FAN PERF TABLE
3/4 / VARIABLE
200-230/1/60
6.8 / 6.8
CENTRIFUGAL
DIRECT / 2
1/45 / 2800/1500
208-230/1/60
0.34 NO
THROWAWAY
5.3
R410A
8.2 1/2
H X W X L
47.86 / 47.4 / 61.75
653 / 525
11
1 Certified in accordance with the Unitary Air-Conditioner Equipment certification program, which is based on ARI Standard 210/240. Noise calculated in accordance with A.R.I.
11
Standard 270.
22
2 All models are U L Listed. Ratings shown are for elevations up to 2000 ft. For higher elevations reduce ratings at a rate of 4% per 1000 ft. elevation.
22 33
3 Convertible to LPG.
33 44
4 This value is approximate. For more precise value, see Unit Nameplate.
44 55
5 Based on U.S. Government Standard Tests.
55 66
6 Filters must be installed in return air stream. Square footages listed are based on 300 f.p.m. face velocity. If permanent filters are used size per manufacturer's recommendation
66
with a clean resistance of 0.05" W.C.
77
7 Unit is shipped on high input, unit is convertible to low input with a Low Fire accessory kit.
77 88
8 Sound Power values are not adjusted for ARI 270-95 tonal corrections.
88
7
MODEL RATED Volts/PH/Hz Performance Cooling BTUHj
Indoor Airflow (CFM) Power Input (KW) EER/SEER(BTU/Watt-Hr.)n
Sound Power Rating [dB(A)]8
Performance Heatingk
Input BTUH - 1st Stage (Natural Gas)p Input BTUH - 2nd Stage (Natural Gas)p AFUE Temp. Rise — Min/Max (°F) Orifice Qty / Drill Size (Natural Gas)l
POWER CONN.—V/PH/HZ
Min. Brch. Cir. Ampacitym Fuse Size — Max. (amps) Fuse Size — Recmd. (amps)
COMPRESSOR
Volts/Ph/Hz R.L. Amps — L.R. Amps
OUTDOOR COIL — TYPE
Rows/F.P.I. Face Area (sq.ft.) Tube Size (in.)
INDOOR COIL — TYPE
Rows/F.P.I. Face Area (sq.ft.) Tube Size (in.) Refrigerant Control Drain Conn. Size (in.)
OUTDOOR FAN — TYPE
Dia. (in.) Drive/No. Speeds Motor — HP/R.P.M. Volts/Ph/Hz F.L. Amps/L.R. Amps
INDOOR FAN — TYPE
Dia x Width (in.) Drive/No. Speeds CFM @ 0.0 in. w.g.n Motor — HP/R.P.M. Volts/Ph/Hz F.L. Amps/L.R. Amps
COMBUSTION FAN — TYPE
Drive/No. Speeds Motor — HP/R.P.M. Volts/Ph/Hz FLA
FILTER / FURNISHED
Type Recommended Recmd. Face Area (sq. ft.)o
REFRIGERANT
Charge (lbs.)m
GAS PIPE SIZE (in.) DIMENSIONS
Crated (in.)
WEIGHT
Shipping (lbs.) / Net (lbs.)
General Data
4YCY4048A3120A
208-230/3/60
48000
1605
4.034
11.9 / 14.2 73
90000
120000
80.0 40 / 70 3 / #32
208-230/3/60
26.4
40 40
SCROLL
208-230/3/60
14.6 / 91
SPINE-FIN
2 / 24
18.01 3/8
PLATE FIN
3 / 15
5.0
3/8
EXPANSION VALVE
3/4 FEMALE NPT
PROPELLER
28.2
DIRECT / 1
1/4 / 825
208-230/1/60
1.4 / 3.37
CENTRIFUGAL
11 X 10
DIRECT / VARIABLE
SEE FAN PERF TABLE
3/4 / VARIABLE
200-230/1/60
6.8 / 6.8
CENTRIFUGAL
DIRECT / 2
1/45 / 2800/1500
208-230/1/60
0.34 NO
THROWAWAY
5.3
R410A
8.2
1/2
H X W X L
47.86 / 47.4 / 61.75
659 / 531
4YCY4060A1120A
208-230/1/60
58500
1800
5.478
11.9 / 14.0 76
90000
120000
80.0 30 / 60 3 / #32
208-230/1/60
42.3
60 60
SCROLL
208-230/1/60
26.9 / 145
SPINE-FIN
2 / 24
23.07 3/8
PLATE FIN
4 / 15
5.0 3/8
EXPANSION VALVE
3/4 FEMALE NPT
PROPELLER
28.2
DIRECT / 1
1/3 / 830
208-230/1/60
1.7 / 3.5
CENTRIFUGAL
11 X 10
DIRECT / VARIABLE
SEE FAN PERF TABLE
1 / VARIABLE
208-230/1/60
6.9 / 6.9
CENTRIFUGAL
DIRECT / 2
1/45 / 2800/1500
208-230/1/60
0.34 NO
THROWAWAY
5.3
R410A
9.75 1/2
H X W X L
51.86 / 47.4 / 61.75
676 / 548
4YCY4060A3120A
208-230/3/60
58500
1800
5.478
11.9 / 14.0 76
90000
120000
80.0 30 / 60 3 / #32
208-230/3/60
30.6
45 45
SCROLL
208-230/3/60
17.6 / 123 SPINE-FIN
2 / 24
23.07 3/8
PLATE FIN
4 / 15
5.0 3/8
EXPANSION VALVE
3/4 FEMALE NPT
PROPELLER
28.2
DIRECT / 1
1/3 / 830
208-230/1/60
1.7 / 3.5
CENTRIFUGAL
11 X 10
DIRECT / VARIABLE
SEE FAN PERF TABLE
1 / VARIABLE 208-230/1/60
6.9 / 6.9
CENTRIFUGAL
DIRECT / 2
1/45 / 2800/1500
208-230/1/60
0.34 NO
THROWAWAY
5.3
R410A
9.75 1/2
H X W X L
51.86 / 47.4 / 61.75
676 / 548
11
1 Certified in accordance with the Unitary Air-Conditioner Equipment certification program, which is based on ARI Standard 210/240. Noise calculated in accordance with A.R.I.
11
Standard 270.
22
2 All models are U L Listed. Ratings shown are for elevations up to 2000 ft. For higher elevations reduce ratings at a rate of 4% per 1000 ft. elevation.
22 33
3 Convertible to LPG.
33 44
4 This value is approximate. For more precise value, see Unit Nameplate.
44 55
5 Based on U.S. Government Standard Tests.
55 66
6 Filters must be installed in return air stream. Square footages listed are based on 300 f.p.m. face velocity. If permanent filters are used size per manufacturer's recommendation
66
with a clean resistance of 0.05" W.C.
77
7 Unit is shipped on high input, unit is convertible to low input with a Low Fire accessory kit.
77 88
8 Sound Power values are not adjusted for ARI 270-95 tonal corrections.
88
8
Performance Data Cooling
4YCY4030A1 AT 1000 NOM CFM (COOLING PERFORMANCE AT INDOOR DRY BULB TEMPERATURES)
OD ID TOT SENS CAP AT ENTERING DB TEMP TOTAL
AMB WB CAP 72 75 78 80 KW
59 29.8 24.1 26.9 29.2 28.9 2.3 63 31.0 19.7 22.6 25.5 27.4 2.3
85
67 33.4 15.8 18.6 21.5 23.4 2.3 71 36.1 11.8 14.6 17.5 19.4 2.3
59 27.3 23.0 25.8 27.3 27.3 2.5 63 28.5 18.7 21.5 24.4 26.3 2.5
95
67 30.7 14.7 17.6 20.4 22.3 2.5 71 33.1 10.7 13.6 16.5 18.4 2.5
59 24.8 21.9 24.7 24.8 24.8 2.7 63 25.9 17.6 20.5 23.3 25.2 2.7
105
67 27.9 13.7 16.5 19.4 21.3 2.7 71 30.1 9.7 12.6 15.4 17.4 2.7
59 22.4 20.8 22.4 22.4 22.4 2.9 63 23.3 16.6 19.5 22.3 23.3 2.9
115
67 25.1 12.7 15.5 18.4 20.3 2.9 71 27.1 8.7 11.6 14.4 16.4 2.9
USE THE FOLLOWING FACTORS TO COMPENSATE FOR DIFFERENT AIR FLOW
LOW 875 0.97 0.98 HIGH 1125 1.03 1.02
CFM CAPACITY (A) TEST SEER EER
890 30000 14.00 12.00
ARI STANDARD 210/240 RA TING CONDITIONS — (A) Cooling 80°F DB, 67°F WB air entering indoor coil, 95°F DB air entering outdoor coil. (B) High Temperature Heating 47°F DB, 43°F WB air entering outdoor coil, 70°F DB air entering indoor coil. (C) Low Temperature Heating 17°F DB, 15°F WB air entering outdoor coil, 70°F DB air entering indoor coil. (D) Rated indoor airflow for heating is the same as for cooling.
AIR FLOW CAPACITY TOTAL POWER
RATE, CFM MULTIPLIER MULTIPLIER
ARI RATING FOR COOLING
ARI Standard Capacity Rating Conditions
4YCY4024A1 AT 800 NOM CFM (COOLING PERFORMANCE AT INDOOR DRY BULB TEMPERATURES)
OD ID TOT SENS CAP AT ENTERING DB TEMP TOTAL
AMB WB CAP 72 75 78 80 KW
59 22.9 19.1 21.4 22.9 22.9 1.8 63 23.9 15.6 17.9 20.2 21.8 1.8
85
67 25.8 12.3 14.7 17.0 18.6 1.9 71 27.8 9.1 11.5 13.8 15.3 1.9
59 20.9 18.2 20.5 20.9 20.9 2.0 63 21.8 14.7 17.0 19.3 20.9 2.0
95
67 23.5 11.5 13.8 16.1 17.7 2.0 71 25.3 8.3 10.6 12.9 14.5 2.0
59 18.8 17.3 18.8 18.8 18.8 2.1 63 19.6 13.8 16.1 18.5 19.6 2.1
105
67 21.1 10.6 12.9 15.3 16.8 2.2 71 22.8 7.4 9.7 12.1 13.6 2.2
59 16.7 16.4 16.7 16.7 16.7 2.3 63 17.5 13.0 15.3 17.5 17.5 2.3
115
67 18.8 9.8 12.1 14.4 16.0 2.3 71 20.3 6.6 8.9 11.2 12.8 2.3
USE THE FOLLOWING FACTORS TO COMPENSATE FOR DIFFERENT AIR FLOW
LOW 700 0.97 0.98
HIGH 900 1.03 1.02
CFM CAPACITY (A) TEST SEER EER
790 23400 14.00 11.60
ARI STANDARD 210/240 RA TING CONDITIONS — (A) Cooling 80°F DB, 67°F WB air entering indoor coil, 95°F DB air entering outdoor coil. (B) High Temperature Heating 47°F DB, 43°F WB air entering outdoor coil, 70°F DB air entering indoor coil. (C) Low Temperature Heating 17°F DB, 15°F WB air entering outdoor coil, 70°F DB air entering indoor coil. (D) Rated indoor airflow for heating is the same as for cooling.
AIR FLOW CAPACITY TOTAL POWER
RATE, CFM MULTIPLIER MULTIPLIER
ARI RATING FOR COOLING
ARI Standard Capacity Rating Conditions
4YCY4036A1/3 AT 1200 NOM CFM (COOLING PERFORMANCE AT INDOOR DRY BULB TEMPERATURES)
OD ID TOT SENS CAP AT ENTERING DB TEMP TOTAL
AMB WB CAP 72 75 78 80 KW
59 34.5 28.8 32.4 34.5 34.5 2.7 63 36.0 23.4 27.0 30.5 32.9 2.7
85
67 38.8 18.5 22.0 25.6 27.9 2.8 71 41.9 13.5 17.1 20.6 23.0 2.8
59 32.0 27.6 31.2 32.0 32.0 3.0 63 33.4 22.3 25.9 29.4 31.8 3.1
95
67 35.9 17.4 20.9 24.5 26.9 3.1 71 38.8 12.4 16.0 19.6 21.9 3.1
59 29.5 26.5 29.5 29.5 29.5 3.3 63 30.7 21.2 24.8 28.4 30.7 3.4
105
67 33.1 16.3 19.9 23.4 25.8 3.4 71 35.7 11.4 15.0 18.5 20.9 3.4
59 26.9 25.4 26.9 26.9 26.9 3.6 63 28.1 20.2 23.7 27.3 28.1 3.7
115
67 30.2 15.3 18.8 22.4 24.8 3.7 71 32.7 10.4 13.9 17.5 19.9 3.7
USE THE FOLLOWING FACTORS TO COMPENSATE FOR DIFFERENT AIR FLOW
LOW 1050 0.97 0.98 HIGH 1350 1.03 1.02
CFM CAPACITY (A) TEST SEER EER
1210 36000 14.20 11.60
ARI STANDARD 210/240 RA TING CONDITIONS — (A) Cooling 80°F DB, 67°F WB air entering indoor coil, 95°F DB air entering outdoor coil. (B) High Temperature Heating 47°F DB, 43°F WB air entering outdoor coil, 70°F DB air entering indoor coil. (C) Low Temperature Heating 17°F DB, 15°F WB air entering outdoor coil, 70°F DB air entering indoor coil. (D) Rated indoor airflow for heating is the same as for cooling.
AIR FLOW CAPACITY TOTAL POWER
RATE, CFM MULTIPLIER MULTIPLIER
ARI RATING FOR COOLING
ARI Standard Capacity Rating Conditions
9