Trane offers a complete family of packaged gas/electric heating and cooling systems, designed to give you the unbeatable combination of energy efficiency and
lower operating costs. In warm weather, the packaged gas/electric system functions
as an all-electric, high efficiency air conditioner. In cold weather, it operates as a
natural gas or propane gas furnace, offering you the best of both energy worlds.
Introducing the new TRANE Single Packaged Convertible
Gas/Electric System.
Single Packaged Convertible Gas/
Electric Systems are easy and versatile to install. Because cooling and
heating functions are all contained in a
single cabinet, a Trane single packaged
convertible gas/electric system is easy to
install and service. It can be flush
mounted beside your home at ground
level or placed on the roof for horizontal
or downflow installation. When connected
to an optional Trane thermostat control,
and air distribution ducts, you have a
highly efficient, total home comfort
system.
Single Packaged Convertible Gas/
Electric Systems are unmatched in
quality and reliability. All major
components on these products,
including the compressor, have been
designed and manufactured for
maximum service. Every Climatuff
compressor is designed and manufactured to exacting specifications. Each
design is life tested in extreme environments to ensure reliable and long
lasting operation in normal applications.
Each compressor has internal motor
protection for added reliability.
2
®
Contents
Optional Equipment Listing4
General Data5
Performance Data
Cooling9
Indoor Fan11
Typical Wiring15
Optional Equipment18
Dimensional Data23
Mechanical Specifications29
3
Optional Equipment Listing
OPTIONAL EQUIPMENT FOR PACKAGED UNITS (check mark [
Hinged Filter Access Door (4YCY4024-036) 8 ................................................................ BAYACCDOR1A[ ]
Hinged Filter Access Door (4YCY4042-060) 8 ................................................................ BAYACCDOR2A[ ]
Roof Curb Full Perimeter (4YCY4024-36A) 3 ................................................................... BAYCURB050A[ ]
Roof Curb Full Perimeter (4YCY4042-60A) 3 ................................................................... BAYCURB051A[ ]
NOTES:1 Must use filter frame when economizer/fresh air kit is used.
2 Dry bulb control standard with economizer.
3 Ships knocked down.
4 Downflow only.
5 Low Ambient cooling requires crankcase heater (BAYCCHT----A).
6 It is the responsibility of the installing dealer to properly size the ductwork for each specific application.
7 BAYCOVR112,118A will not cover BAYSQRD002A applications
8 BAYACCDOR1A requires BAYFLTR101B & BAYACCDOR2A requires BAYFLTR201B. They are not
backward compatible to BAYFLTR101/201A.
4
MODEL
RATED Volts/PH/Hz
Performance Cooling BTUHj
Indoor Airflow (CFM)
Power Input (KW)
EER/SEER(BTU/Watt-Hr.)n
Dia x Width (in.)
Drive/No. Speeds
CFM @ 0.0 in. w.g.n
SEE FAN PERF TABLE
Motor — HP/R.P.M.
Volts/Ph/Hz
F.L. Amps/L.R. Amps
COMBUSTION FAN — TYPE
Drive/No. Speeds
Motor — HP/R.P.M.
Volts/Ph/Hz
FLA
FILTER / FURNISHED
Type Recommended
Recmd. Face Area (sq. ft.)o
REFRIGERANT
Charge (lbs.)m
GAS PIPE SIZE (in.)
DIMENSIONS
Crated (in.)
WEIGHT
Shipping (lbs.) / Net (lbs.)
4YCY4024A1064A
208-230/1/60
23400
790
2.162
11.6 / 14.0
68
48000
64000
79.0
35 / 65
2 / #37
208-230/1/60
16.5
25
25
RECIPROCATING
208-230/1/60
8.3 / 57.8
SPINE-FIN
2 / 24
13.32
3/8
PLATE FIN
3 / 15
3.54
3/8
EXPANSION VALVE
3/4 FEMALE NPT
PROPELLER
23.4
DIRECT / 1
1/12 / 810
208-230/1/60
0.54 / 0.95
CENTRIFUGAL
10 X 10
DIRECT / VARIABLE
1/2 / VARIABLE
200-230/1/60
4.3 / 4.3
CENTRIFUGAL
DIRECT / 2
1/45 / 2800/1500
208-230/1/60
0.34
NO
THROWAWAY
4.0
R410A
5.8
1/2
H X W X L
45.86 / 44.5 / 52.03
481 / 385
General Data
4YCY4030A1075A
208-230/1/60
30000
900
2.5
12.0 / 14.0
71
56250
75000
79.5
30 / 60
2 / #33
208-230/1/60
19.2
30
30
RECIPROCATING
200-230/1/60
11.1 / 63
SPINE-FIN
2 / 24
15.49
3/8
PLATE FIN
3 / 15
3.54
3/8
EXPANSION VALVE
3/4 FEMALE NPT
PROPELLER
23.4
DIRECT / 1
1/6 / 830
208-230/1/60
1.0 / 1.7
CENTRIFUGAL
10 X 10
DIRECT / VARIABLE
SEE FAN PERF TABLE
1/2 / VARIABLE
208-230/1/60
4.3 / 4.3
CENTRIFUGAL
DIRECT / 2
1/45 / 2800/1500
208-230/1/60
0.34
NO
THROWAWAY
4.0
R410A
6.0625
1/2
H X W X L
45.86 / 44.5 / 52.03
481 / 385
4YCY4036A1075A
208-230/1/60
36000
1210
3.284
11.6 / 14.2
69
56250
75000
79.5
30 / 60
2 / #33
208-230/1/60
24.6
40
40
SCROLL
208-230/1/60
15.4 / 83
SPINE-FIN
2 / 24
15.49
3/8
PLATE FIN
4 / 15
3.54
3/8
EXPANSION VALVE
3/4 FEMALE NPT
PROPELLER
23.4
DIRECT / 1
1/5 / 830
208-230/1/60
1.1 / 1.9
CENTRIFUGAL
10 X 10
DIRECT / VARIABLE
SEE FAN PERF TABLE
1/2 / VARIABLE
200-230/1/60
4.3 / 4.3
CENTRIFUGAL
DIRECT / 2
1/45 / 2800/1500
208-230/1/60
0.34
NO
THROWAWAY
4.0
R410A
6.75
1/2
H X W X L
47.86 / 44.5 / 52.03
488 / 392
4YCY4036A1096A
208-230/1/60
36000
1210
3.284
11.6 / 14.2
69
72000
96000
80.0
40 / 70
3 / #37
208-230/1/60
24.6
40
40
SCROLL
208-230/1/60
15.4 / 83
SPINE-FIN
2 / 24
15.49
3/8
PLATE FIN
4 / 15
3.54
3/8
EXPANSION VALVE
3/4 FEMALE NPT
PROPELLER
23.4
DIRECT / 1
1/5 / 830
208-230/1/60
1.1 / 1.9
CENTRIFUGAL
10 X 10
DIRECT / VARIABLE
SEE FAN PERF TABLE
1/2 / VARIABLE
200-230/1/60
4.3 / 4.3
CENTRIFUGAL
DIRECT / 2
1/45 / 2800/1500
208-230/1/60
0.34
NO
THROWAWAY
4.0
R410A
6.75
1/2
H X W X L
47.86 / 44.5 / 52.03
493 / 397
11
1 Certified in accordance with the Unitary Air-Conditioner Equipment certification program, which is based on ARI Standard 210/240. Noise calculated in accordance with A.R.I.
11
Standard 270.
22
2 All models are U L Listed. Ratings shown are for elevations up to 2000 ft. For higher elevations reduce ratings at a rate of 4% per 1000 ft. elevation.
22
33
3 Convertible to LPG.
33
44
4 This value is approximate. For more precise value, see Unit Nameplate.
44
55
5 Based on U.S. Government Standard Tests.
55
66
6 Filters must be installed in return air stream. Square footages listed are based on 300 f.p.m. face velocity. If permanent filters are used size per manufacturer's recommendation
66
with a clean resistance of 0.05" W.C.
77
7 Unit is shipped on high input, unit is convertible to low input with a Low Fire accessory kit.
77
88
8 Sound Power values are not adjusted for ARI 270-95 tonal corrections.
88
5
MODEL
RATED Volts/PH/Hz
Performance Cooling BTUHj
Indoor Airflow (CFM)
Power Input (KW)
EER/SEER(BTU/Watt-Hr.)n
Dia x Width (in.)
Drive/No. Speeds
CFM @ 0.0 in. w.g.n
Motor — HP/R.P.M.
Volts/Ph/Hz
F.L. Amps/L.R. Amps
COMBUSTION FAN — TYPE
Drive/No. Speeds
Motor — HP/R.P.M.
Volts/Ph/Hz
FLA
FILTER / FURNISHED
Type Recommended
Recmd. Face Area (sq. ft.)o
REFRIGERANT
Charge (lbs.)m
GAS PIPE SIZE (in.)
DIMENSIONS
Crated (in.)
WEIGHT
Shipping (lbs.) / Net (lbs.)
General Data
4YCY4036A3075A
208-230/3/60
36000
1210
3.284
11.6 / 14.2
69
56250
75000
80.0
30 / 60
2 / #33
208-230/3/60
19.8
30
30
SCROLL
208-230/3/60
11.5 / 77
SPINE-FIN
2 / 24
15.49
3/8
PLATE FIN
4 / 15
3.54
3/8
EXPANSION VALVE
3/4 FEMALE NPT
PROPELLER
23.4
DIRECT / 1
1/5 / 830
208-230/1/60
1.1 / 1.9
CENTRIFUGAL
10 X 10
DIRECT / VARIABLE
SEE FAN PERF TABLE
1/2 / VARIABLE
200-230/1/60
4.3 / 4.3
CENTRIFUGAL
DIRECT / 2
1/45 / 2800/1500
208-230/1/60
0.34
NO
THROWAWAY
4.0
R410A
6.75
1/2
H X W X L
47.86 / 44.5 / 52.03
488 / 392
4YCY4036A3096A
208-230/3/60
36000
1210
3.284
11.6 / 14.2
69
72000
96000
80.0
40 / 70
3 / #37
208-230/3/60
19.8
30
30
SCROLL
208-230/3/60
11.5 / 77
SPINE-FIN
2 / 24
15.49
3/8
PLATE FIN
4 / 15
3.54
3/8
EXPANSION VALVE
3/4 FEMALE NPT
PROPELLER
23.4
DIRECT / 1
1/5 / 830
208-230/1/60
1.1 / 1.9
CENTRIFUGAL
10 X 10
DIRECT / VARIABLE
SEE FAN PERF TABLE
1/2 / VARIABLE
200-230/1/60
4.3 / 4.3
CENTRIFUGAL
DIRECT / 2
1/45 / 2800/1500
208-230/1/60
0.34
NO
THROWAWAY
4.0
R410A
6.75
1/2
H X W X L
47.86 / 44.5 / 52.03
493 / 397
4YCY4042A1096A
208-230/1/60
42000
1350
3.5
12.0 / 14.25
74
72000
96000
80
30 / 60
3 / #37
208-230/1/60
31.5
50
50
SCROLL
208-230/1/60
18.6 / 105
SPINE-FIN
2 / 24
23.57
3/8
PLATE FIN
3 / 15
5
3/8
EXPANSION VALVE
3/4 FEMALE NPT
PROPELLER
28.2
DIRECT / 1
1/4 / 825
208-230/1/60
1.5 / 3.4
CENTRIFUGAL
11 X 10
DIRECT / VARIABLE
SEE FAN PERF TABLE
3/4 / VARIABLE
208-230/1/60
6.8 / 6.8
CENTRIFUGAL
DIRECT / 2
1/45 / 2800/1500
208-230/1/60
0.34
NO
THROWAWAY
5.3
R410A
6.8125
1/2
H X W X L
47.86 / 47.4 / 61.75
653 / 525
11
1 Certified in accordance with the Unitary Air-Conditioner Equipment certification program, which is based on ARI Standard 210/240. Noise calculated in accordance with A.R.I.
11
Standard 270.
22
2 All models are U L Listed. Ratings shown are for elevations up to 2000 ft. For higher elevations reduce ratings at a rate of 4% per 1000 ft. elevation.
22
33
3 Convertible to LPG.
33
44
4 This value is approximate. For more precise value, see Unit Nameplate.
44
55
5 Based on U.S. Government Standard Tests.
55
66
6 Filters must be installed in return air stream. Square footages listed are based on 300 f.p.m. face velocity. If permanent filters are used size per manufacturer's recommendation
66
with a clean resistance of 0.05" W.C.
77
7 Unit is shipped on high input, unit is convertible to low input with a Low Fire accessory kit.
77
88
8 Sound Power values are not adjusted for ARI 270-95 tonal corrections.
88
6
MODEL
RATED Volts/PH/Hz
Performance Cooling BTUHj
Indoor Airflow (CFM)
Power Input (KW)
EER/SEER(BTU/Watt-Hr.)n
Dia x Width (in.)
Drive/No. Speeds
CFM @ 0.0 in. w.g.n
Motor — HP/R.P.M.
Volts/Ph/Hz
F.L. Amps/L.R. Amps
COMBUSTION FAN — TYPE
Drive/No. Speeds
Motor — HP/R.P.M.
Volts/Ph/Hz
FLA
FILTER / FURNISHED
Type Recommended
Recmd. Face Area (sq. ft.)o
REFRIGERANT
Charge (lbs.)m
GAS PIPE SIZE (in.)
DIMENSIONS
Crated (in.)
WEIGHT
Shipping (lbs.) / Net (lbs.)
General Data
4YCY4048A1096A
208-230/1/60
48000
1605
4.034
11.9 / 14.2
73
72000
96000
80.0
30 / 60
3 / #37
208-230/1/60
33.8
50
50
SCROLL
208-230/1/60
20.5 / 109
SPINE-FIN
2 / 24
18.01
3/8
PLATE FIN
3 / 15
5.0
3/8
EXPANSION VALVE
3/4 FEMALE NPT
PROPELLER
28.2
DIRECT / 1
1/4 / 825
208-230/1/60
1.4 / 3.5
CENTRIFUGAL
11 X 10
DIRECT / VARIABLE
SEE FAN PERF TABLE
3/4 / VARIABLE
200-230/1/60
6.8 / 6.8
CENTRIFUGAL
DIRECT / 2
1/45 / 2800/1500
208-230/1/60
0.34
NO
THROWAWAY
5.3
R410A
8.2
1/2
H X W X L
47.86 / 47.4 / 61.75
653 / 525
4YCY4048A1120A
208-230/1/60
48000
1605
4.034
11.9 / 14.2
73
90000
120000
80.0
40 / 70
3 / #32
208-230/1/60
33.8
50
50
SCROLL
208-230/1/60
20.5 / 109
SPINE-FIN
2 / 24
18.01
3/8
PLATE FIN
3 / 15
5.0
3/8
EXPANSION VALVE
3/4 FEMALE NPT
PROPELLER
28.2
DIRECT / 1
1/4 / 825
208-230/1/60
1.4 / 3.37
CENTRIFUGAL
11 X 10
DIRECT / VARIABLE
SEE FAN PERF TABLE
3/4 / VARIABLE
200-230/1/60
6.8 / 6.8
CENTRIFUGAL
DIRECT / 2
1/45 / 2800/1500
208-230/1/60
0.34
NO
THROWAWAY
5.3
R410A
8.2
1/2
H X W X L
47.86 / 47.4 / 61.75
659 / 531
4YCY4048A3096A
208-230/3/60
48000
1605
4.034
11.9 / 14.2
73
72000
96000
80.0
30 / 60
3 / #37
208-230/3/60
26.4
40
40
SCROLL
208-230/3/60
14.6 / 91
SPINE-FIN
2 / 24
18.01
3/8
PLATE FIN
3 / 15
5.0
3/8
EXPANSION VALVE
3/4 FEMALE NPT
PROPELLER
28.2
DIRECT / 1
1/4 / 825
208-230/1/60
1.4 / 3.5
CENTRIFUGAL
11 X 10
DIRECT / VARIABLE
SEE FAN PERF TABLE
3/4 / VARIABLE
200-230/1/60
6.8 / 6.8
CENTRIFUGAL
DIRECT / 2
1/45 / 2800/1500
208-230/1/60
0.34
NO
THROWAWAY
5.3
R410A
8.2
1/2
H X W X L
47.86 / 47.4 / 61.75
653 / 525
11
1 Certified in accordance with the Unitary Air-Conditioner Equipment certification program, which is based on ARI Standard 210/240. Noise calculated in accordance with A.R.I.
11
Standard 270.
22
2 All models are U L Listed. Ratings shown are for elevations up to 2000 ft. For higher elevations reduce ratings at a rate of 4% per 1000 ft. elevation.
22
33
3 Convertible to LPG.
33
44
4 This value is approximate. For more precise value, see Unit Nameplate.
44
55
5 Based on U.S. Government Standard Tests.
55
66
6 Filters must be installed in return air stream. Square footages listed are based on 300 f.p.m. face velocity. If permanent filters are used size per manufacturer's recommendation
66
with a clean resistance of 0.05" W.C.
77
7 Unit is shipped on high input, unit is convertible to low input with a Low Fire accessory kit.
77
88
8 Sound Power values are not adjusted for ARI 270-95 tonal corrections.
88
7
MODEL
RATED Volts/PH/Hz
Performance Cooling BTUHj
Indoor Airflow (CFM)
Power Input (KW)
EER/SEER(BTU/Watt-Hr.)n
Dia x Width (in.)
Drive/No. Speeds
CFM @ 0.0 in. w.g.n
Motor — HP/R.P.M.
Volts/Ph/Hz
F.L. Amps/L.R. Amps
COMBUSTION FAN — TYPE
Drive/No. Speeds
Motor — HP/R.P.M.
Volts/Ph/Hz
FLA
FILTER / FURNISHED
Type Recommended
Recmd. Face Area (sq. ft.)o
REFRIGERANT
Charge (lbs.)m
GAS PIPE SIZE (in.)
DIMENSIONS
Crated (in.)
WEIGHT
Shipping (lbs.) / Net (lbs.)
General Data
4YCY4048A3120A
208-230/3/60
48000
1605
4.034
11.9 / 14.2
73
90000
120000
80.0
40 / 70
3 / #32
208-230/3/60
26.4
40
40
SCROLL
208-230/3/60
14.6 / 91
SPINE-FIN
2 / 24
18.01
3/8
PLATE FIN
3 / 15
5.0
3/8
EXPANSION VALVE
3/4 FEMALE NPT
PROPELLER
28.2
DIRECT / 1
1/4 / 825
208-230/1/60
1.4 / 3.37
CENTRIFUGAL
11 X 10
DIRECT / VARIABLE
SEE FAN PERF TABLE
3/4 / VARIABLE
200-230/1/60
6.8 / 6.8
CENTRIFUGAL
DIRECT / 2
1/45 / 2800/1500
208-230/1/60
0.34
NO
THROWAWAY
5.3
R410A
8.2
1/2
H X W X L
47.86 / 47.4 / 61.75
659 / 531
4YCY4060A1120A
208-230/1/60
58500
1800
5.478
11.9 / 14.0
76
90000
120000
80.0
30 / 60
3 / #32
208-230/1/60
42.3
60
60
SCROLL
208-230/1/60
26.9 / 145
SPINE-FIN
2 / 24
23.07
3/8
PLATE FIN
4 / 15
5.0
3/8
EXPANSION VALVE
3/4 FEMALE NPT
PROPELLER
28.2
DIRECT / 1
1/3 / 830
208-230/1/60
1.7 / 3.5
CENTRIFUGAL
11 X 10
DIRECT / VARIABLE
SEE FAN PERF TABLE
1 / VARIABLE
208-230/1/60
6.9 / 6.9
CENTRIFUGAL
DIRECT / 2
1/45 / 2800/1500
208-230/1/60
0.34
NO
THROWAWAY
5.3
R410A
9.75
1/2
H X W X L
51.86 / 47.4 / 61.75
676 / 548
4YCY4060A3120A
208-230/3/60
58500
1800
5.478
11.9 / 14.0
76
90000
120000
80.0
30 / 60
3 / #32
208-230/3/60
30.6
45
45
SCROLL
208-230/3/60
17.6 / 123
SPINE-FIN
2 / 24
23.07
3/8
PLATE FIN
4 / 15
5.0
3/8
EXPANSION VALVE
3/4 FEMALE NPT
PROPELLER
28.2
DIRECT / 1
1/3 / 830
208-230/1/60
1.7 / 3.5
CENTRIFUGAL
11 X 10
DIRECT / VARIABLE
SEE FAN PERF TABLE
1 / VARIABLE
208-230/1/60
6.9 / 6.9
CENTRIFUGAL
DIRECT / 2
1/45 / 2800/1500
208-230/1/60
0.34
NO
THROWAWAY
5.3
R410A
9.75
1/2
H X W X L
51.86 / 47.4 / 61.75
676 / 548
11
1 Certified in accordance with the Unitary Air-Conditioner Equipment certification program, which is based on ARI Standard 210/240. Noise calculated in accordance with A.R.I.
11
Standard 270.
22
2 All models are U L Listed. Ratings shown are for elevations up to 2000 ft. For higher elevations reduce ratings at a rate of 4% per 1000 ft. elevation.
22
33
3 Convertible to LPG.
33
44
4 This value is approximate. For more precise value, see Unit Nameplate.
44
55
5 Based on U.S. Government Standard Tests.
55
66
6 Filters must be installed in return air stream. Square footages listed are based on 300 f.p.m. face velocity. If permanent filters are used size per manufacturer's recommendation
66
with a clean resistance of 0.05" W.C.
77
7 Unit is shipped on high input, unit is convertible to low input with a Low Fire accessory kit.
77
88
8 Sound Power values are not adjusted for ARI 270-95 tonal corrections.
88
8
Performance Data Cooling
4YCY4030A1 AT 1000 NOM CFM (COOLING PERFORMANCE AT INDOOR DRY BULB TEMPERATURES)
USE THE FOLLOWING FACTORS TO COMPENSATE FOR DIFFERENT AIR FLOW
LOW8750.970.98
HIGH11251.031.02
CFMCAPACITY (A) TESTSEEREER
8903000014.0012.00
ARI STANDARD 210/240 RA TING CONDITIONS — (A) Cooling 80°F DB, 67°F
WB air entering indoor coil, 95°F DB air entering outdoor coil. (B) High
Temperature Heating 47°F DB, 43°F WB air entering outdoor coil, 70°F DB air
entering indoor coil. (C) Low Temperature Heating 17°F DB, 15°F WB air entering
outdoor coil, 70°F DB air entering indoor coil. (D) Rated indoor airflow for heating
is the same as for cooling.
AIR FLOWCAPACITYTOTAL POWER
RATE, CFMMULTIPLIERMULTIPLIER
ARI RATING FOR COOLING
ARI Standard Capacity Rating Conditions
4YCY4024A1 AT 800 NOM CFM (COOLING PERFORMANCE AT INDOOR DRY BULB TEMPERATURES)
USE THE FOLLOWING FACTORS TO COMPENSATE FOR DIFFERENT AIR FLOW
LOW7000.970.98
HIGH9001.031.02
CFMCAPACITY (A) TESTSEEREER
7902340014.0011.60
ARI STANDARD 210/240 RA TING CONDITIONS — (A) Cooling 80°F DB, 67°F
WB air entering indoor coil, 95°F DB air entering outdoor coil. (B) High
Temperature Heating 47°F DB, 43°F WB air entering outdoor coil, 70°F DB air
entering indoor coil. (C) Low Temperature Heating 17°F DB, 15°F WB air entering
outdoor coil, 70°F DB air entering indoor coil. (D) Rated indoor airflow for heating
is the same as for cooling.
AIR FLOWCAPACITYTOTAL POWER
RATE, CFMMULTIPLIERMULTIPLIER
ARI RATING FOR COOLING
ARI Standard Capacity Rating Conditions
4YCY4036A1/3 AT 1200 NOM CFM (COOLING PERFORMANCE AT INDOOR DRY BULB TEMPERATURES)
USE THE FOLLOWING FACTORS TO COMPENSATE FOR DIFFERENT AIR FLOW
LOW10500.970.98
HIGH13501.031.02
CFMCAPACITY (A) TESTSEEREER
12103600014.2011.60
ARI STANDARD 210/240 RA TING CONDITIONS — (A) Cooling 80°F DB, 67°F
WB air entering indoor coil, 95°F DB air entering outdoor coil. (B) High
Temperature Heating 47°F DB, 43°F WB air entering outdoor coil, 70°F DB air
entering indoor coil. (C) Low Temperature Heating 17°F DB, 15°F WB air entering
outdoor coil, 70°F DB air entering indoor coil. (D) Rated indoor airflow for heating
is the same as for cooling.
AIR FLOWCAPACITYTOTAL POWER
RATE, CFMMULTIPLIERMULTIPLIER
ARI RATING FOR COOLING
ARI Standard Capacity Rating Conditions