Trane 4TYK6524D1000AL Installation And Maintenance Manual

Page 1
Installation, Operation and Maintenance Manual
U - M a t c h D C I n v e r t e r S y s t e m Up To16 SEER
Outdoor Unit - Cooling Only and Heat Pump 24,000 to 60,000 BTU/h -
R-410A
60Hz
SAFETY WARNING
Only qualified personnel should install and service the equipment. The installation, start- up, and servicing of heating, ventilating and air-conditioning equipment can be hazardous and requires specific knowledge and training. Improperly installed, adjusted or altered equipment by an unqualified person could result in death or serious injury. When working on the equipment, observe all caution indications in the literature and on the tags, stickers and labels that are attached to the equipment.
May 2017
MS-SVN052E-EN
Page 2
Content
Identification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Unit Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Electrical Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
System Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
2 MS-SVN052E-EN
Page 3
Warnings, Cautions and Notices
Safety advisories appear throughout this manual as required. Your personal safety and the proper operation of this machine depend upon the strict observance of these precautions.
The three types of advisories are defined as follows:
Warnings, Cautions and Notices
WARNING
CAUTIONs
NOTICE
Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury..
Indicates a potentially hazardous situation which, if not avoided, could result in minor or moderate injury. It could also be used to alert against unsafe practices. Indicates a situation that could result in equipment or property-damage only accidents.
Important Environmental Concerns
Scientific research has shown that certain man-made chemicals can affect the earth’s naturally occurring stratospheric ozone layer when released to the atmosphere. In particular, several of the identified chemicals that may affect the ozone layer are refrigerants that contain Chlorine, Fluorine and Carbon (CFCs) and those containing Hydrogen, Chlorine, Fluorine and Carbon (HCFCs). Not all refrigerants containing these compounds have the same potential impact to the environment. Trane advocates the responsible handling of all refrigerants including industry replacements for CFCs and HCFCs such as saturated or unsaturated HFCs and HCFCs.
Important Responsible Refrigerant Practices
Trane believes that responsible refrigerant practices are important to the environment, our customers and the air conditioning industry. All technicians who handle refrigerants must be certified according to local rules. For the USA, the Federal Clean Air Act (Section 608) sets forth the requirements for handling, reclaiming, recovering and recycling of certain refrigerants and the equipment that is used in these service procedures. In addition, some states or municipalities may have additional requirements that must also be adhered to for responsible management of refrigerants. Know the applicable laws and follow them.
WARNIN G
Proper Field Wiring and Grounding Required
Failure to follow code could result in death or serious injury. All field wiring must be performed by qualified personnel. Improperly installed and grounded field wiring poses FIRE and ELECTROCUTION hazards. To avoid these hazards, you MUST follow requirements for field wiring installation and grounding as described in NEC and your local/state/national electrical codes.
WARNIN G
Use of Refrigerant!
Failure to follow recommendations in the use of service equipment or components classified for the use of R410A refrigerant, could give way to equipment or component explosion under R410A pressures and as a result lead to death or serious injury or equipment damage. R410A refrigerant works at a higher pressure than R22 refrigerant. Employ only service equipment or components classified for use with this unit. In case of specific doubts related with the use of refrigerant, consult your local Trane representative.
MS-SVN052E-EN 3
Page 4
Warnings, Cautions and Notices
Personal Protective Equipment (PPE) Required!
Failure to wear proper PPE for the job being undertaken could result in death or serious injury. Technicians, in order to protect themselves from potential electrical, mechanical and chemical hazards, MUST follow precautions in this manual and on the tags, stickers and labels, as well as the instructions below:
Before installing/servicing this unit, technicians MUST put on all PPE required for the work being undertaken (example; cut-resistant gloves/sleeves, butyl gloves, safety glasses, hard hat/bump cap, fall protection, electrical PPE and arc flash clothing). ALWAYS refer to appropriate Material Safety Data Sheets (MSDS)/Safety Data Sheets (SDS) and OSHA guidelines for proper PPE.
When working with or around hazardous chemicals, ALWAYS refer to the appropriate MSDS/ SDS and OSHA/GHS (Global Harmonized System of Classification and Labelling of Chemicals) guidelines for information on allowable personal exposure levels, proper respiratory protection and handling instructions.
If there is a risk of energized electrical contact, arc, or flash, technicians MUST put on all PPE in accordance with OSHA, NFPA 70E, or other country-specific requirements for arc flash protection, PRIOR to servicing the unit. NEVER PERFORM ANY SWITCHING, DISCONNECTING, OR VOLTAGE TESTING WITHOUT PROPER ELECTRICAL PPE AND ARC FLASH CLOTHING. ENSURE ELECTRICAL METERS AND EQUIPMENT ARE PROPERLY RATED FOR INTENDED VOLTAGE.
WARNIN G
4 MS-SVN052E-EN
Page 5
Identification
U-Match Inverter Unit (16 SEER) - R410A Refrigerant Voltage 220/230/1/60hz
Inspection
Upon arrival, the unit should be inspected in search of shipping damages. If these are detected, they should be indicated on the delivery document presented by the transportation company. Present the transportation entity a written request for inspection of damages. If further information should be required, be sure to consult with your local distributor.
Requirements for installation/service of equipment using R410A refrigerant:
Accessories such as pressure gauge, hoses, refrigerant containers and recovery system must be designed to handle POE or PVE oils.
Manifold gauge classification should be 800 PSIG on the high side and 250 PSIG on the low side with 550 PSIG for restart on the low side.
All hoses must be classified for 700 PSIG service pressure.
Leak detectors must be designed to detect R-410A refrigerant.
Recovery equipment (including containers for refrigerant recovery) must be designed specifically to handle R-410A refrigerant.
Do Not use a TXV for R-22.
Good refrigeration practice requires the installation of a field provided liquid line filter dryer. See Figure 1.
Ou tdoor Unit - Co o ling Only
Mode l Capa cit y
4TYK6524D1000AL 24 MBH - 16 SEER
4TYK6536D1000AL 36 MBH - 16 SEER
4TYK6548D1000AL 48 MBH - 16 SEER
4TYK6560D1000AL 60 MBH - 16 SEER
Ou tdoor U n i t - H ea t Pu m p
Mode l
4TXK6524D1000AL 24 MBH - 16 SEER
4TXK6536D1000AL 36 MBH - 16 SEER
4TXK6548D1000AL 48 MBH - 16 SEER
4TXK6560D1000AL 60 MBH - 16 SEER
Capa cit y
Identification
MS-SVN052E-EN 5
Page 6
Identification
It is better to open de service valve after the removal of the bottom access panel
Large service valve
Small service valve
Liquid line filter dryer . Field provided and installed
Figure 1. Filter Dryer Installation
Limitations
The unit should be installed in accordance with all national, state and local codes and in compliance with the following limitations:
1. All limitations shall be observed for the indoor unit as well as for the coil and appropriate accessories.
2. The outdoor unit shall not be installed with ductwork in the passage of air current. The outdoor fan is one of propeller type and is not designed to operate against any additional external static pressure.
3. Maximum and minimum operating conditions shall be observed in order to ascertain that the system offers maximum performance with minimum service.
4. This unit is not designed to operate with a low ambient kit. The control system shall not be modified to operate with any type of low ambient kit.
5. The maximum length of line allowed for this product is of 100 feet.
Outdoor units are designed to connect to an indoor coil with brazed connection lines. These units are shipped with factory charged refrigerant to be connected to a matched indoor coil and to 4.5m (15 ft) of field provided lines.
Indoor coils are provided with a thermostatic expansion valve or a calibrated expansion orifice. The size of the orifice and/or of refrigerant charge may require alterations in the case of some indoor­outdoor unit combinations, differences in lift or total lengths of line.
6 MS-SVN052E-EN
Page 7
Figure 2. Dimensional Data
DIMENSIONAL DATA
CONTROL WIRING
7/8” (22.2mm) KNOCKOUT 1-11/32” (34.5mm)
SERVICE CONNECTOR
POWER WIRING SEE DETAIL A
DETAIL A
ORIFICE 1-3/32” (27.8mm)
NOTE: GRILL APPEARANCE MAY VARY
DISCHARGE AIR: ALLOW 60” (1.5m)
MINIMUM CLEARANCE
INCOMING AIR
DAMPER WITH VENTS: ALLOW 18” (0.45m) MINIMUM CLEARANCE
W
SUCTION LINE CONNECTION
LIQUID LINE CONNECTION
SERVICE CONNECTOR
SERVICE ACCESS ALLOW 24” MINIMUM CLEARANCE
Identification
MS-SVN052E-EN 7
Mode l Size
Heig h t ( in ) ( mm ) W idt h ( in ) ( m m ) Liq u i d ( in ) Su ct ion ( in)
2 4 24-15/16 (633) 29-1/8 (740) 29-1/8 (740) 3/8 3/4
3 6 24-15/16 (633) 29-1/8 (740) 29-1/8 (740) 3/8 3/4
4 8 33-3/16 (843) 29-1/8 (740) 29-1/8 (740) 3/8 7/8
6 0 33-3/16 (843) 29-1/8 (740) 29-1/8 (740) 3/8 7/8
Dim e nsi o n ( in)
Re f r ige r a n t Con n e ct ion
Se r v ice Va lve Siz e
Page 8
Unit Installation
Unit Installation
Location
Prior to the installation, select and verify the adaptability of the location for both indoor and outdoor units. Take into consideration all limitations and clearance requirements. The outdoor unit must comprise sufficient clearance for incoming air into the condenser, for discharge air, and for service access. See Figure 2.
Important: In the case of multiple units installation, these must be spaced to contain a minimum
If the unit is to be installed on the roof with exposure to sun rays, or on a “blackened” surface, then the unit must be placed over a base with sufficient elevation that will prevent the accumulation of hot air being drawn into the outdoor unit.
Provide an appropriate structured support.
Installation on Outdoor Flat Surface
The unit may be installed on a solid flat surface which cannot shift or move in order to prevent stress over refrigerant lines or possible leaks. Clearances must be maintained as can be seen in Figure
2. Installation must be completely balanced.
Normal operation levels of noise may prove to be objectionable if the unit is installed directly below windows o close to bedrooms, studios, etc.
Important: Outdoor unit must not be installed in areas where accumulation of mud or ice may
Place the unit high enough to avoid blocking the entry of air due to ice/snow or in areas that are prone to accumulate ice/snow. Isolate the unit away from drains to avoid mud slides/landslides of the foundation.
separation of 36 inches (face-to-face coils).
cause personal injury or damages to the system.
Installation on the Roof
When installing the unit on the roof, the structure should be able to support the total weight of the unit, including mounting frame, rails, etc., which must be used to minimize the transmission of sound or vibrations to the conditioned space.
Installation of the unit
1. Provide a mounting base on the selected installation area.
2. Remove all packaging material and inspect the unit in search of possible damages.
3. Compressor fastening nuts must remain tightened.
4. Place the unit on the provided mounting base.
The outdoor unit must be connected to the indoor coil with the provided copper refrigerant piping. The installation must employ only the approved sizes of pipes for system combinations. Refrigerant charge shown on the unit’s nameplate refers to the lengths of standard size interconnecting liquid line up to 15 feet.
Note: The use of a larger size of line from original specifications could cause problems of oil
return. The use of a much smaller size of line could cause loss of capacity and other problems provoked by insufficient flow of refrigerant. Tilt the horizontal suction lines at least 1” every 20 feet towards the outdoor unit to aid in the appropriate return of oil.
8 MS-SVN052E-EN
Page 9
Unit Installation
Elevation above the snow line
Base pan (bottom view) Avoid obstruction of drain holes
Concrete base or other appropriate material
Mounting of the Unit
If the unit is to be installed on a roof surface or on a concrete base, observe the following guidelines:
1. The provided base pan rises the heating pump 2” above the installation base.
2. If the unit is to be raised over the roof surface, use 4” x 4” boards (or equivalent) placed in a manner that may allow weight to be evenly distributed and to prevent the transmission of noise and vibrations. See Figure 3.
Note: Avoid the blockage of drain openings as shown in Figure 3.
3. If the unit is to be raised to avoid seasonal snow/ice buildup, make sure the elevation support is sturdy enough to avoid unit’s falling or tilting.
Note: See Figure 4 for proper unit setting guidelines.
Figure 3. Recommended Rise Installation
Factory Recommendation for Mounting the Unit
1. Before installation, clean the mounting surface.
Important = The cement base must comply
with local codes and be thick enough to sustain the installation of fasteners.
2. Center and level the unit over the base or mounting surface.
3. Using the provided L-shaped bracket, mark the boring holes over the concrete and bore holes of at least 1/4” additional depth as compared to the bracket to be used.
Important = Drill
screws should not exceed 3/8” in length to avoid harming the coil.
4. Tighten brackets and drill screws following conventional practices for the installation of these supports. See Figure 4.
Note: Use one bracket at each side. For further stability, use 2 brackets at each side.
Note: Do not over-tighten brackets in order to avoid weakening the concrete material.
MS-SVN052E-EN 9
Page 10
Unit Installation
See Detail B
#7 X 3/8” drill screws
(Not to exceed 3/8” in length)
´ȋ´ZDVKHUDQGKH[VFUHZVIRUFRQFUHWH
(Pilot hole required 3/16”. Pilot hole should be 1/4” deeper than the space occupied by the bracket).
DETAIL B
Brackets:
´ZLGH´WKLFN
height as required.
$YDLODEOHIURPYHQGRU
RULQWKHILHOG
6HHGLPHQVLRQVLQ)LJ
IMPORTANT NOTE:
These instructions are intended to provide a method of installation of the unit to the concrete base in order to establish a protective procedure in cases of strong winds. It is recommended to verify local codes for the application of methods and protocols for secure setting of the unit.
Figure 4. Preferred Method for Unit Setting
Cautions to be Observed During Installation of Refrigerant Lines
1. Install lines with the least amount of curves possible. Avoid damaging line couplings or line curves. Use clean and hard drawn copper tubing at points where it will not be necessary to apply multiple curves around obstructions. When it is necessary to use soft copper, it should be carefully applied avoiding sharp curves that may provoke any type of restriction.
2. Install lines avoiding any obstructions to the coil, to the air handling components o to the filter.
3. Take special care in the application of insulation to refrigerant lines in order to minimize the transmission of sound to the structure.
4. When applying insulation material to the suction line, refrigerant lines should be supported as illustrated in Figure 5. DO NOT allow any friction contact between metal piping.
5. Use PVC piping as conduit in all underground installations. See Figure 6. Underground lines should be kept as short as possible in order to minimize the accumulation of liquid refrigerant in the suction line during extended system shutdown periods.
6. In an effort to reduce vibrations and to retain some degree of flexibility, place a type of sealant material like permagum or similar around refrigerant lines that must be directed through walls.
10 MS-SVN052E-EN
Page 11
Figure 5. Lines Support
Insulated liquid line
Insulation
optional
Wrong
Suggested
Sheet metal support
Insulated suction line
A serpentín interior
A unidad exterior
Tapa
Línea vapor aislada
Línea liquido
To indoor fan
To power supply
To
Coil
Disconnect switch
Seal openings with Permagum sealant or equivalent
2
4
V signal
NOTE:All outdoor wiring should be weather proof
Figure 6. Underground Installation
Unit Installation
Figure 7. Typical Installation
MS-SVN052E-EN 11
Page 12
Unit Installation
Wet cloth Service valve
Precautionary Measures During Line Brazing
All connections to indoor unit and to evaporator coil will be copper-to-copper. Brazing material should be done with the use of a copper-phosphorous alloy such as Silfos-5 or equivalent. DO NOT employ soft brazing alloy. Outdoor units contain service valves in both liquid and suction connections. Total system refrigerant charge is retained inside the outdoor unit during shipment and installation. Service valves are provided for evacuation and charging in accordance with these instructions.
The application of precautionary measures to ensure that system is clean and dry will aid in the avoidance of serious service problems.
¡CAUTION!
During line brazing always supply dry nitrogen through the lines due to the fact that temperature is sufficiently high to cause metal oxide of copper tubing, unless an inert atmosphere is provided. The flow of dry nitrogen must continue until the coupling/connection has cooled. Always use a pressure regulator and security valve to ascertain that only low pressure dry nitrogen is introduced into the line. Only a small amount of flow is required to move the air and prevent oxidation.
Precautionary Measures During Service Valve Brazing
Precautionary measures should be adopted to prevent heat damage to the service valve.Wrap a wet cloth around the valve as shown in Figure 8. During brazing action, protect all painted surfaces and insulation; also, be sure to remove the Schraeder core to protect it against high temperature in the area due to the welding process. Once brazing has ended, wrap the coupling with a wet cloth.
In order to open the valve, it is necessary to remove the top of the plunger/piston and insert a hex wrench over the valve stem to turn it counterclockwise until the valve stem reaches the angled retention wall.
Connect refrigerant lines as follows;
1. Remove the Schraeder core taps from both service ports of liquid and suction lines’ service valves on the outdoor unit. Connect low pressure nitrogen flow to the service port of the liquid line.
Figure 8. Protection against heat
12 MS-SVN052E-EN
2. Weld the liquid line to the liquid valve on the outdoor unit. Do not forget to wrap the body of the valve with a wet cloth. Continue to allow the flow of nitrogen.
3. Protect the suction valve with a wet cloth and braze the suction line connection to the outdoor unit. The flow of nitrogen should be leaving the system from the service port connection of the suction line. When this connection has cooled, remove the flow of nitrogen from the service port at the liquid coupling.
Page 13
Unit Installation
4. Replace the Schraeder core once more onto the liquid and suction valves.
5. Carry out leak tests on all refrigerant line connections, including tapered valves at the service port to ensure they are all leak-free. DO NOT OVERTIGHTEN (between 40 and 60 in.lbs
maximum).
6. Purge suction line, evaporator, and liquid line at 350 microns or less. Consult Data Sheet to learn the appropriate sizing of liquid line.
Table 1. Recommended Size for Liquid and Suction Lines (in.)
Mod e l Líq u id
2 4 3/8 7/8
3 6 3/8 7/8
4 8 3/8 7/8
6 0 3/8 7/8
7. Replace taps once more onto service ports. Do not remove tapered caps of service ports unless absolutely necessary for system service tasks.
8. Release the refrigerant charge inside the system. Open both liquid and suction valves; remove the plunger/piston cap and insert a hex wrench over the stem in order to turn it counterclockwise until said valve stem reaches the angled retention wall.
9. Replace the plunger/piston cap once more and tighten with your fingers; give it an additional 1-1/2 turn with your fingers. The cap should be placed in order to prevent leaking.
Su ct ion
¡WARNING!
Never try to repair soldered connections while the system is under low pressure. Such action could provoke personal injuries. Consult “System Charging” section to verify and
register system charge values.
Interconnecting Lines
Suction and Liquid Lines
Maintain all lines duly sealed until ready for interconnection tasks.
First, carry out connections on the indoor coil.
Consult line sizing information on Ta bl e 2 and Table 3 to verify the use of correct sizes and multipliers to determine the capacity for several diameter sizes of suction line and routing lengths. Losses due to exposure of lines under outdoor conditions are not included.
Factory refrigerant charge for outdoor unit is sufficient for 15 feet of standard size interconnecting liquid line.
Maximum Length for Lines
Maximum length for interconnecting lines is 160 feet.
MS-SVN052E-EN 13
Page 14
Unit Installation
Outdoor units
Indoor units
Rise
Rise
Figure 9. Piping Length Diagram #1
Always use the shortest length possible with a minimum amount of curves.
Note: Excessively long refrigerant lines produce capacity loss for the equipment.
Vertical Rise
14 MS-SVN052E-EN
Keep the vertical rise at a minimum. See the following guides for unit installation.
1. DO NOT exceed vertical rise as indicated in Ta b l e 3 .
2. It is recommended to use the smallest allowable size for liquid line in order to minimize system charge. This will maximize compressor reliability.
Tab l e 3 may be used to define dimensions for horizontal runs.
Page 15
Installation of TXV Valve
TXV KIT
Brazed
ĐŽŶŶĞĐƟŽŶ
Tapered
ĐŽŶŶĞĐƟŽŶ
TX
SETP 1
STEP 2
STEP 4
V
KIT
V
STEP 3
TXV Kit (thermostatic expansion valve) provided together with the equipment is for on-site mounting. Installation of this valve must be done with tapered threaded fitting.
Figure 10. Thermostatic Expansion Valve TXV
Figure 11. Steps for TXV Kit Installation
Unit Installation
Step 1 - Remove the fixed expansion device (calibrated orifice) mounted on the indoor unit. See images.
Step 2 - Connect liquid line and gas line piping to the outdoor unit (brazed fitting).
Step 3 - Connect the thermostatic expansion valve TXV to the liquid line and gas line connections
coming from the outdoor unit.
Step 4 - Connect the thermostatic expansion valve TXV to the liquid line and gas line piping of the indoor unit. Apply appropriate torque. Verify the absence of refrigerant leaks.
MS-SVN052E-EN 15
Page 16
Unit Installation
Evacuation
It is required to evacuate the system at 350 microns or less. If a leak is suspect, apply dry nitrogen to locate it. Repair the leak and repeat the leak test. To verify that the system reports no further leaks, close the valve that goes to the suction vacuum pump; this will isolate it and will allow you to sustain the system under a vacuum. Observe the gauge during several minutes. If reading indicates a stable and continuous increase, it will be indicative of a leak. If the gauge indicates an increase and after several minutes it stabilizes and remains constant, it will be indicative of a system free of leaks but still withholding humidity. This situation will require an additional evacuation in the event of a gauge reading above 350 microns.
Line Sizing
Table 2. Length/Dimension of Suction Line vs. Capacity Multiplier (R410A)
Mode l Si z e 2 Ton 3 To n 4 To n 5 T o n
Su ct ion Lin e Co n n e ct ion Si ze 3/8” Std. 3/8” Std. 3/8” Std. 3/8” Std.
Su ct ion Lin e r out ing ( i n f e et )
25’
50’
100’
Optional1.000.990.990.98
Standard 1.00 1.00 1.00 1.00
Optional0.990.980.980.97
Standard 0.99 0.99 0.99 0.99
Optional0.980.950.970.95
Standard 0.99 0.98 0.98 0.97
5/8 Opt 5/8 Opt. 3/4 Opt. 3/4 Opt.
3/4 Std. 3/4 Std. 7/8 Std. 7/8 Std.
Table 3. Dimension of Líquid Line (R410A)
Li n e Con ne ct ion
Mod e l Siz e
2 Ton 3/8”x Rotating
3 Ton 3/8”x Rotating
4 Ton 3/8”x Rotating
5 Ton 3/8”x Rotating
Siz e
( inch < O . D .)
Com pr esso r
Note:
1. x Standard line size
2. N/A (application not recommended
3. Charge multiplier for additional interconnection of refrigerant line length: Líquid 3/8” 0.6oz/ft
Ty p e
Con n e ctio n Size
and Li n e Si z e
( inc h O . D .)
3/4”x 25 50 45 40
5/8” 25 50 45 40
3/4”x 25 50 50 50
5/8” 25 50 50 50
7/8”x 25 50 50 40
3/4” 25 50 50 40
3/4” 25 50 50 40
7/8”x 25 50 50 40
1-1/8” 25 40 30 N/A
Ou t doo r U n it A bove o r Be l ow I ndo o r Coil
25 50 60 100
Ma x im um V e r t ica l Separat io n - Fe e t
Liq u i d Lin e S ize
To t a l Le ngth Eq u i va le nt - Fe e t
16 MS-SVN052E-EN
Page 17
Electrical Connections
CORNER
PANEL
HIGH VOLTAGE WIRING
LOW VOLTAGE WIRING
General Information and Grounding
Verify power supply to ensure compliance with data on the unit’s identification label and wiring tags.
The installer shall supply power wiring, control wiring (low voltage), disconnect switches and overcurrent protection. All cable wiring should comply with specific requirements.
CAUTION!
All field wiring shall be of ONLY COPPER CONDUCTORS and in compliance with local, national and electrical security codes.This unit must be grounded with a separate cable and in accordance with local, national and electrical security codes.
Wiring diagram and wiring schematics can be found on the inside surface of the service access panel as well as in the present manual.
Power Wiring of Field Connections
1. Install properly sized and weather proof disconnect switch outdoors and close to the unit.
2. Remove retaining screws on the side of the corner panel. Slide corner panel downwards to remove it. See
Figure 12.
3. Run power wiring from the disconnect switch to the unit
4. Direct cables from the disconnect point through the opening provided for power wiring and towards the interior of the unit’s main control box.
5. Install properly sized time delay fuses or circuit breaker, and conduct power supply connections.
6. To save time, energize the crankcase heater (if equipped) through the reheating of compressor oil while the remaining the remaining installation steps continue to proceed.
Note: When changing motor, first remove the top panel.
Electrical Connections
Figure 12. Typical Field Wiring
MS-SVN052E-EN 17
Page 18
Electrical Connections
1/2” nut
5/16” nuts
If fan nuts are removed before removal of top panel, it will harm the condensing unit.
NOTE:
Figure 13. Removal of top panel and motor
When it is necessary to change the motor, follow the steps indicated below:
Step 1: Open the electrical panel; disconnect all power to the motor.
Important:
Step 2: Remove top panel (be careful with motor wiring)
Step 3: Place top panel on the floor.
Important:
Step 4: Remove fan motor with the removal of all 5/16” nuts from the panel.
Step 5: Remove fan blades from motor fan with the removal of 1/2” nut and place fan on the floor.
Step 6: Invert the removal process when ready to reinstall fan and motor.
Important:
– Disconnect power supply to the unit. Failure to follow this recommendation could
provoke severe burns and electrical shock.
– Take care NOT to allow fan blades to rest on or touch the floor or against any
surface.
– When connecting wiring to the motor, verify the direction of the motor.
18 MS-SVN052E-EN
Page 19
System Operation
Control Logic Description
The variable speed system adopts the same 24VAC control as conventional heat pumps.
Compressor speed is controlled according to coil pressures monitored by the pressure transducer. In order to ensure stable and appropriate capacity, compressor speed is modulated in accordance with evaporator pressure during the cooling mode, and in accordance with condensing pressure during the heating mode. Nominal pressure can be adjusted automatically at the SW4 switch to reach optimized compressor operational capacity, as well as to satisfy higher dehumidifying and capacity demands.
SW4
ON
OFF 1234
SW 4- 1 Not U sed
SW 4- 2 N ot Used
SW 4 - 3
SW 4 - 4
ON
OFF
ON Accelerated cooling/heating
OFF Normal cooling/heating
Adaptive capacity output
disable
Adaptive capacity output
enable
System Operation
Sensor
T3 (Outdoor coil temperature) and T4 (indoor temperature heat pump only).
T5 (Compressor discharge temperature and Tf (IPM radiator temperature)
Pressure Transducer.
Sensor Description
T3 temperature sensor is used for:
T4 sensor is required (heat pump only) for:
T5 sensor is required for:
– Protection during system operation (high/low coil temperature)
– Outdoor fan control (cooling)
– Defrost (heat pump only)
– Forecasting environment temperature (cooling only)
– Enabling system operation according to outdoor temperature
– Indicating one of the conditions for enabling defrost cycle
– Outdoor fan control (heating mode heat pump only)
– Operational protection (high/low temperature)
– Control of outdoor electronic expansion valve (heat pump only)
MS-SVN052E-EN 19
Page 20
System Operation
Tf sensor is required for:
– Protection against module temperature (high temperature)
A pressure transducer (PT) is required for:
– Operating speed control
– Outdoor electronic expansion valve (heat pump only)
– High pressure protection (heating mode heat pump only)
– Low pressure protection (cooling mode)
Defrost Description (Heat Pump Only)
Defrost control (when ordered) measures coil temperature with the use of a sensor located on the heat pump coil. In order to measure outdoor ambient temperature, a second sensor is located on the outside of the outdoor coil.
Defrost cycle starts with the reading of various parameters, i.e., outdoor unit coil temperature (T3 temperature sensor), outdoor environment temperature (T4 temperature sensor), cummulative time of operation, coil temperature and high pressure (when high pressure is found to be lower than a specific value).
Defrost cycle starts under one of 3 conditions as follows:
1. When temperature differential (Delta T) between outdoor temperature (T4) and coil temperature (T3) reaches a duration of 5 minutes, that is:
T4 39ºF, Delta T = 18ºF
T4 30ºF, Delta T = 16ºF
T4 19ºF, Delta T = 14ºF
When T4 ˂ 19ºF, T3 ˂ 9ºF
2. When minimum time of operation (MRT) based on outdoor temperature is for example:
MRT - 4 hour duration when: T4 ˂ 23ºF
MRT - 2 hour duration when: 23ºF T4 ˂ 42ºF
3. When saturation temperature descends below 82ºF during a period of 20 minutes.
Defrost cycle ends under the following conditions:
1. When outdoor coil temperature (T3) reaches 64ºF during a period of 1 minute or when defrost period exceeds 8 minutes.
2. The adjustment of SW5 switch offers various defrost cycle options depending upon geographical conditions and/or outdoor area conditions.
20 MS-SVN052E-EN
Page 21
System Operation
SW5
ON
OFF 12
Defrost Opt ion s SW 5 -1 SW 5- 2 Re m ar k s
ON
OFF Normal Normal Default
Re m ar k s Enter defrost Cancel defrost
Operating time
is reduced by
10%
Defrost
extended by 60
seconds
Manual Defrost (Heat Pump Only)
1. Demand defrost can start when the system has been operating in heating mode during a period exceeding 8 minutes.
2. Press “Force” key during 6 seconds to initiate demand defrost.
3. Wait approximately 40 seconds to watch the initiation of the defrost cycle.
4. Once defrost cycle has started, the display will show “DF”.
5. Defrost test ends automatically and the display will show speed of operation.
6. If a second test is required, repeat Step 3 after 5 minutes has elapsed.
Compressor Crankcase Heater Description
The migration during the OFF cycle can result in a noisy startup. The use of a crankcase heater (CCH) minimizes refrigerant migration, reduces startup noise, and reduces the wearing out of bearings.
Crankcase heater must be located on the lower half of the compressor shell. Its purpose is to heat the compressor during the OFF cycle and avoid the return of refrigerant to the compressor.
At initial startup, or after extended periods of inactivity, the crankcase heater must be activated during a minimum of 12 hours prior to compressor operation, applying line tension to the system but with the controller in OFF mode.
Crankcase heater operation is initiated:
1. When the application of line tension for the first time and compressor discharge temperature is T5˂104ºF.
2. During the defrost process.
3. When compressor stops operating during a period of 4 hours and outdoor temperature is T4˂50ºF or T5˂104ºF.
Crankcase heater operation ends:
1. When compressor discharge temperature is T5 113ºF.
2. During heating mode and stops working during cooling mode.
MS-SVN052E-EN 21
Page 22
System Operation
Protection Functions
Outdoor coil protection function (T3)
Ambient temperature protection (T4)
Discharge temperature (DT) protection (T5)
High pressure protection (HPS) (mechanical switch opening/closing pressure)
Low pressure protection (LP)
Module (inverter) heating protection (TF)
Note: In an effort to improve our products, we reserve the right to make changes without previous notice.
– When T3 ˃ 143.6ºF, compressor stops working
– When T3 ˃ 129.2ºF, compressor starts working
– When 40ºF T4 ˂ 120ºF, the unit is able to operate in the cooling mode
– When 5ºF T4 ˂ 86ºF, the unit is able to operate in the heating mode
– When T4 ˂ 6.8ºF, the heat pump provides the indoor unit with 24V, which in turn
activates the electric heater (if installed)
–When DT ˃ 239ºF during cooling mode, the compressor shuts down
–When DT ˂ 194ºF during cooling mode, the compressor starts up again
–When DT ˃ 221ºF during heating mode, the compressor starts up again
– When HPS is P ˃ 580 PSIG, both the compressor and outdoor fan shut down
– When HPS is P ˂ 435 PSIG, both the compressor and outdoor fan start up again
–When LP ˂ 43.5 PSI during a period of 5 minutes in the cooling mode, both the compressor
and outdoor fan shut down. After a 6 minute lapse, the system tries to start up again
– When TF ˃ 176ºF, both the compressor and outdoor fan shut down
– When TF ˂ 145ºF, both the compressor and outdoor fan start up again
22 MS-SVN052E-EN
Page 23
Refrigerant Charge Review
Weigh-in Method (use of electronic scale)
Weigh-in method can be used the initial installation or anytime a system charge is being replaced. This method can also be used when power is not available at the site, or when operating conditions (indoor/outdoor temperature) are not in range to verify with the sub-cooling charging method.
AB C
Mode l Factory charge
All m ode ls (see data on nameplate)
Note: Factory charge in the outdoor unit is sufficient for 15 feet of standard size interconnecting
liquid line.
New installations - Calculation of additional charge for a line that is longer than 15 feet
1. Total line length (feet) = __________ (a)
2. Standard line (feet) = ____15______ (b)
3. (a) less (b) = _____________ (c)
4. Refrigerant multiplier = 0.6 or 0.4 oz/ft (d
5. Additional refrigerant (c*d) = ____________(e)*
*If the line is shorter than 15 feet, (e) = 0
System Operation
Charge multiplier for interconnecting
refrigerant tube length
Liquid 3/8” 0.6 oz/ft
Liquido 5/16” 0.4 oz/ft
)
Sealed system repairs - Charge calculation
1. Total line length (feet) = __________ (a)
2. Standard line (feet) = ____15______ (b)
3. (a) less (b) = _____________ (c)
4. Refrigerant multiplier = 0.6 or 0.4 oz/ft (d
)
5. Additional refrigerant (c*d) = ____________(e)*
6. Factory charge (unit nameplate) = ________(f)
7. Total system charge (e+f) =
*If the line is shorter than 15 feet, (e) = 0
Note: The only approved mode to validate the system charge during cooling mode, is employing
the weigh-in charge. Outdoor temperature must be established to be between 55ºF and 120ºF with indoor temperature to be between 70ºF and 80ºF.
MS-SVN052E-EN 23
Page 24
System Operation
Sub-cooling charge and refrigerant adjustment during cooling mode (above 55ºF outdoor temperature)
24 MS-SVN052E-EN
Page 25
System Operation
MS-SVN052E-EN 25
Page 26
System Operation
26 MS-SVN052E-EN
Page 27
Final Leak Test
Manintenance
System Operation
After evacuating and charging the unit, use a halogen detector to detect any leaking. All piping must be verified in the evaporator, in the condenser and in the interconnecting lines. If a leak is detected, all refrigerant must be recovered before any intent of repair is carried out. The Clear Air Act forbids any emission of refrigerant to the atmosphere.
1. Prevent the accumulation of dirt in the indoor unit or in the outdoor coils and in any other parts of the air-conditioning system circuit. Cleaning methods should be exercised frequently to maintain the unit under a clean state. Use appropriate brushes, vacuum cleaners or other adequate accessories.
2. Outdoor fan motor is permanently lubricated and does not require periodic oiling.
3. Refer to heater and air handler instructions for filter and fan motor maintenance.
4. Carry out regular inspections of the indoor coil and drain pan to ensure appropriate operation.
CAUTION!
Under the law, the emission of refrigerant to the atmosphere is not allowed during unit servicing, repairing, maintenance or unit discarding. Once the unit is operating appropriately and once the proprietor has received proper instructions regarding the unit, obtain the corresponding approval from the proprietor of the equipment.
MS-SVN052E-EN 27
Page 28
Wiring Diagrams
Wiring Diagrams
CAUTION!
These units must be wired and installed in compliance with all national, state and local security codes.
Figure 14. Outdoor Unit Wiring for A/C Systems (208/230V/1 Phase- 60Hz)
28 MS-SVN052E-EN
Page 29
Figure 15. Control Wiring Diagram for A/C Systems
(Indoor Unit)
(Outdoor Unit)
Post description
C1: Compressor
N1: Common 24 VAC
C: Common 24 VAC
Y: Compressor
Grounding
(ID Unit) (OD Unit)
Post description
C1: Compressor N1: Common 24 VAC V1: 4-way valve F1: Outdoor fan signal C: Common 24 VAC B: 4-way valve Y: Compressor W: Aux. elec. resistor N/A Grounding
Figure 16. Control Wiring Diagram for Heat Pump Systems
Wiring Diagrams
Table 4. Electrical Data
M odel
2 4 AC 17.7 30
3 6 AC 24.2 40
4 8 AC 31.9 50
6 0 AC 36.5 60
2 4 HP 17.7 30
3 6 HP 24.2 40
4 8 HP 31.9 50
6 0 HP 36.5 60
Minim um Cir cuit
Am picit y ( A)
AC: Air conditioning unit
HP: Heat Pump
Ma x i m um Cir cu i t
Pr ot e ct ion ( A)
MS-SVN052E-EN 29
Page 30
Troubleshooting
Troubleshooting
Table 5. Troubleshooting
30 MS-SVN052E-EN
Page 31
Table 6. Fault Codes
Troubleshooting
MS-SVN052E-EN 31
Page 32
Troubleshooting
Operational and Verification Procedures
Parameter Point Check Table
Press “Check” button to see system available parameters. When pressing for the first time, the display will show you a sequence and at the end of 1 minute, the parameter value will appear. When pressing a second time, the following sequence appears.
For normal status display, the last 2 digits appear under the following conditions:
i. Unit is not in operation (delay mode); “outdoor ambient temperature”.
ii. Unit is in operation; “compressor frequency of operation” will be displayed.
After a 20 second delay under the same parameter, the display returns to its normal state.
If a system protection is active, the first digit indicates “status code”.
32 MS-SVN052E-EN
Page 33
For model 24/36k
Troubleshooting
MS-SVN052E-EN 33
Page 34
Troubleshooting
For model 48/60k and board
Board
34 MS-SVN052E-EN
Page 35
Troubleshooting
MS-SVN052E-EN 35
Page 36
Ingersoll Rand (NYSE:IR) advances the quality of life by creating comfortable, sustainable and efficient environments. Our people and our family of brands—including Club Car®, Ingersoll Rand®, Thermo King® and Trane®—work together to enhance the quality and comfort of air in homes and buildings; transport and protect food and perishables; and increase industrial productivity and efficiency. We are a global business committed to a world of sustainable progress
and enduring results.
© 2017 Trane All Rights Reserved
MS-SVN052E-EN May 3, 2017
NEW
We are committed to using environmentally conscious printing practices.
Loading...