Trane 4TWX606OB, 4TWX6024B, 4TWX6048B, 4TWX6036B, 4TWX6 User Manual

18-BC55D1-2
Pumps
4TWX6
ALL phases of this installation must comply with NATIONAL, STATE AND LOCAL CODES
IMPORTANT -- This Document is customer property and is to remain with this unit. Please return to service information
pack upon completion of work.
These instructions do not cover all variations in systems nor provide for every possible contingency to
this installation must comply with NATIONAL, STATE
AND LOCAL CODES. Should further information be
desired or should particular problems arise which are not covered sufficiently for the purchaser's purposes, the matter should be referred to your installing dealer or local distributor.
A. GENERAL
The following instructions cover 4TWX6 Heat Pump Units.
NOTICE:
These outdoor units may be used with indoor units
equipped with Thermostatic Expansion Valve only.
UNiT CONTAINS R-410A REFRIGERANT!
R-410A OPERATING PRESSURE EXCEEDS THE
LiMiT OF R-22. PROPER SERVICE EQUIPMENT IS
REQUIRED. FAILURE TO USE PROPER SERVICE
TOOLS MAY RESULT IN EQUIPMENT DAMAGE OR
PERSONAL iNJURY.
SERVICE
USE ONLY R-410A REFRIGERANT AND
APPROVED POE COMPRESSOR OiL.
These units use R-410A refrigerant which operates at 50 to 70% higher pressures than R-22. Use only R-410A approved service equipment. Refrigerant cylinders are painted a "Rose" color to indicate the type of refrigerant and may contain a "dip" tube to allow for charging of liquid refrigerant into the system. All R-410A systems use a POE oil that readily absorbs moisture from the atmosphere. To limit this "hygroscopic" action, the system should remain sealed whenever pos- sible. Never break a vacuum with air and alwa_Ls change the driers when opening the system for component replacement.
Check for transportation damage after unit is uncrated. Report promptly, to the carrier, any damage found to the unit.
To determine the electrical power requirements of the unit, refer to the nameplate of the unit. The electrical power
available must agree with that listed on the nameplate. The Weathertron ®Heat Pump has been designed and
manufactured to withstand and operate in severe winter conditions. However, there are precautionary steps which
should be taken at the time of installation which will help assure the efficient operation of the unit. It is recom-
mended that these precautions be taken for units
being installed in areas where snow accumulation and
prolonged below freezing temperatures occur.
1,
Units should be elevated 3 to 12 inches above the pad or rooftop, depending on local weather. This additional height will allow better drainage of snow and ice (melted
during defrost cycle) prior to its refreezing. This should
prevent a build-up of ice around the unit which occurs
when unit is not elevated. Insure that drain holes in
©
2,
3,
5 FT. ABOVE UNIT=UNRESTRICTED
unit base pan are not obstructed preventing draining of defrost water.
If possible, avoid locations that are likely to accumulate snow drifts. If not possible, a snow drift barrier should be installed around the unit to prevent a build-up of snow
on the sides of the unit and should be of sufficient distance from the unit to prevent restriction of airflow to
and from the unit. Also allow for proper maintenance space. The barrier should be constructed of materials which will blend in with the building design.
Avoid locating the unit where condensation and freezing of defrost vapor may annoy the customer. For instance,
|nsta||er's Guide
@
installing the unit under a bedroom, kitchen, or picture window may be annoying to the customer since conden- sate and fog will occur during the defrost cycle.
4. Avoid locating the unit under the eaves or other over- head structures as sizeable icicles may form and the unit may be damaged by these falling icicles.
BASEPAN TAB REMOVAL
B. LOCATION AND PREPARATION
OF THE UNiT
1. When removing unit from the pallet, notice the tabs on the basepan. Remove tabs by cutting with a sharp tool as shown above in Figure 2, and slide unit off of pallet.
2. The unit should be set on a level support pad at least as large as the unit base pan, such as a concrete slab. If this is not the application used please refer to application
bulletin "Trane APB2001-02".
3. The support pad must NOT be in direct contact with any structure. Unit must be positioned a minimum of 12" from any wall or surrounding shrubbery to insure adequate airflow. Clearance must be provided in front of control box (access panels) and any other side requiring service access to meet National Electrical Code. Also, the unit location must be far enough away from any structure to prevent excess roof run-off water from pouring directly on the unit. Do not locate unit(s) close to bedroom(s).
5. When the outdoor unit is mounted on a roof, be sure the roof will support the unit's weight. Properly selected
isolation is recommended to prevent transmission to the building structure.
6. The maximum length of refrigerant lines from outdoor to indoor unit should NOT exceed eighty (80) feet.
7. If outdoor unit is mounted above the air handler, maxi- mum lift should not exceed twenty-five (25) feet (suction
line). If air handler is mounted above condensing unit, maximum lift should not exceed twenty-five (25) feet (liq-
uid line).
8. Locate and install indoor coil or air handler in accor- dance with instruction included with that unit.
The indoor end of the recommended refrigerant line sets may be straight or with a 90 degree bend, depending upon situation requirements. This should be thoroughly checked out before ordering refrigerant line sets.
The gas line must always be insulated.
in scroll compressor applications, dome temperatures may
be hot. Do not touch top of compressor, may cause minor to severe burning.
The units are factory charged with the system charge required when using fifteen (15) feet of connecting line. Unit
nameplate charge is the same. Final refrigerant charge adjustment is necessary. Use
the Charging Charts in the outdoor unit Service Facts.
1. Determine the most practical way to run the lines.
2. Consider types of bends to be made and space limitations.
NOTE: Large diameter tubing will be very difficult to rebend once it
has been shaped.
3. Determine the best starting point for routing the refrigerant tubing -- INSIDE OR OUTSIDE THE STRUCTURE.
4,
Provide a pull-thru hole of sufficient size to allow both liquid and gas lines.
5,
Be sure the tubing is of sufficient length.
6.
Uncoil the tubing -- do not Mnk or dent.
7.
Route the tubing making all required bends and properly secure the tubing before making connections.
8,
To prevent a noise within the building structure due to vibration transmission from the refrigerant lines, the following precautions should be taken:
a. When the refrigerant lines have to be fastened to floor
joists or other framing in a structure, use isolation
type hangers.
b. Isolation hangers should also be used when refriger-
ant lines are run in stud spaces or enclosed ceilings.
c. Where the refrigerant lines run through a wall or sill,
they should be insulated and isolated.
d. Isolate the lines from all ductwork.
®
UNITSIDEOF HEXHEADED
SERVICEVALVE STEM
LiQUiD LiNE SERVICE VALVE
ROLLED EDGE TO
CAPTIVATESTEM
CAP
C. iNSTALLiNG REFRIGERANT LINES
If using existing refrigerant lines make certain that all joints are brazed, not soldered.
Condensing units have provisions for braze connections. Pressure taps are provided on the service valves of outdoor
unit for compressor suction and liquid pressures.
© 2005 American Standard inc. All Rights Reserved 18-BC55D1-2
PORT "_ /
LIQUIDLINE CONNECTION
|nsta||er's Guide
©
GAS LiNE SERVICE VALVE
CAP _ _ 1/4 TURN ONLY
OF VALVE
COUNTERCLOCKWISE FOR FULL OPEN
I .... POSITION
........ F"_ STE"
PRESSURE TAP PORT J
GAS LINE CONNECTION
CAP_
D. SERVICE VALVE OPERATION
BRASS LIQUID LINE SERVICE VALVE
The Brass Liquid Line Service Valve is factory shipped in the seated position to hold factory charge. The pressure tap service port (when depressed) opens only to the field brazing side of the valve when the valve is in the seated position. The liquid line valve is not a back seating valve (see WARNING below).
Extreme caution should be exercised when opening the Liquid Line Service Valve. Turn valve stem counterclock-
wise only until the stem contacts the rolled edge. (See Figure 3) No torque is required.
BRASS GAS LiNE SERVICE VALVE
The Brass Gas Line Service Valve is shipped in the closed position to hold the factory refrigerant charge. The pressure
tap service port (when depressed) opens only to the field
brazing side when the valve is in the closed position.
The Gas Line Service Valve is full open with a 1/4 turn. See Figure 4.
BRAZING REFRIGERANT LINES
1. Remove lower access cover to access service valves.
2. Before brazing, remove plugs from external copper stub tubes. Clean internal and external surfaces of stub tubes
prior to brazing.
3. Cut and fit tubing, minimizing the use of sharp 90 °
bends.
4. Insulate the entire gas line and its fittings.
5. Do NOT allow uninsulated liquid line to come in direct contact with bare gas line.
6. Precautions should be taken to avoid heat damage to the pressure tap valve core during brazing. It is
recommended that the pressure tap port valve core be removed and a wet rag wrapped around the valve body.
NOTICE: Use care to make sure that no moisture enters pressure tap
port, while wet rag is being used.
NOTICE: Precautions should be taken to avoid heat damage to
basepan during brazing. It is recommended to keep the flame directly off of the basepan.
7. Use a Dry Nitrogen Purge and Brazing Alloy without flux when brazing the field line to the copper factory connection. Flow dry nitrogen into either valve pressure tap port, thru the tubing and out the other port while brazing.
8. Braze using accepted good brazing techniques.
LEAK CHECK
IMPORTANT:
Replace pressure tap port valve core before attaching hoses for
evacuation.
After the brazing operation of refrigerant lines to both the outdoor and indoor unit is completed, the field brazed connections must be checked for leaks. Pressurize through the service valve ports, the indoor unit and field refrigerant lines with dry nitrogen to 350-400 psi. Use soap bubbles or other leak-checking methods to see that all field joints are leak-free! If not, release pressure; then repair!
SYSTEM EVACUATION
NOTE: Since the outdoor unit has a refrigerant charge, the gas and
liquid line valves must remain closed.
1. Upon completion of leak check, evacuate the refrigerant lines and indoor coil before opening the gas and liquid
line valves.
2. Attach appropriate hoses from manifold gauge to gas and liquid line pressure taps.
NOTE:
Unnecessary switching of hoses can be avoided and com- plete evacuation of all lines leading to sealed system can be accomplished with manifold center hose and connect- ing branch hose to a cylinder of R-410A and vacuum pump.
3. Attach center hose of manifold gauges to vacuum pump.
4. Evacuate until the micron gauge reads no higher than 350 microns.
5,
Close off valve to vacuum pump and observe the micron gauge. If gauge pressure rises above 500 microns in one (1) minute, then evacuation is incomplete or system
has a leak.
6. If vacuum gauge does not rise above 500 microns in one (1) minute, the evacuation should be complete.
7. With vacuum pump and micron gauge blanked off; open valve on R-410A cylinder and charge refrigerant lines and indoor coil with vapor to tank pressure of R-410A supply.
NOTE: DO NOT VENT REFRIGERANT INTO THE ATMOSPHERE.
8. Close valve on R-410A supply cylinder. Close valves on manifold gauge set and remove refrigerant charging hoses from liquid and gas pressure tap ports.
NOTE: A 3/16" Allen wrench is required to open liquM line service
valve. A 1/4" Open End or Adjustable wrench is required to
open gas line valve. A 3/4" Open End wrench is required to
take off the valve stem cap.
9. The liquid line shut-offvalve can now be opened. Remove shut-offvalve cap. Fully insert hex wrench into the stem and backout counterclockwise until valve stem just touches rolled edge (approximately five [5] turns) observing WARNING statement on page 2. See Figure 3.
18-BC55D1-2
Loading...
+ 5 hidden pages