Trane Tracer MP503, 4950 0490, 4950 0590 User Manual

®
Installing the Tracer™ MP503 Input/Output Module
Ordering number: 4950 0490, 4950 0590
Product overview
The Tracer MP503 is available in two different versions: frame-mount (4950 0490) and metal enclosure (4950 0590) (see Figure 1 and Figure 2 on page 2).
The frame-mount package contains:
A Tracer MP503 circuit board fastened to a metal back plate
A removable molded resin cover
The metal-enclosure package contains:
A Tracer MP503 circuit board fastened to the back plate of the metal enclosure
A removable metal cover
Shipment
Operating environment
Make sure that the operating environment conforms to the specifications listed in Table 1. Dimensions and clearances are illustrated in Figure 1 and Figure 2 on page 2.
Table 1. Operating environment specifications
Te m p e r a t u r e From -40°F to 158°F (-40°C to 70°C)
Humidity 5–95%, noncondensing
20–30 Vac (24 Vac nominal), 50–60 Hz
Power
Mounting weight (frame­mount)
Mounting weight (metal enclosure)
Altitude 6,500 ft (2,000 m) maximum
Installation Category 3
10 VA per I/O module plus a maximum of 12 VA per binary output used
Mounting surface must be able to support 4 lb (2 kg)
Mounting surface must be able to support 16 lb (7.5 kg)
Visually inspect all parts for obvious defects or
Pollution Degree 2
damage. All components are thoroughly inspected before leaving the factory. Any claims for damage incurred in shipping should be filed with the carrier.
Location
Trane recommends locating the Tracer
Storage environment
The storage environment must meet the following requirements:
MP503 I/O module:
In an indoor environment for protection from the elements
Where public access is restricted to minimize the
Temperature: -40°F to 185°F (-40°C to 85°C)
Relative humidity: 5
95%, noncondensing
possibility of tampering or vandalism
Near the controlled equipment to reduce wiring costs
Where it is easily accessible for service personnel
Tr an e A Business of American Standard Companies www.trane.com © 2004 American Standard Inc. All rights reserved. 3270 3332 C
Figure 1. Dimensions and clearances for the frame-mount I/O module
1 in.
(25 mm)
6.313 in. (160 mm)
4 in.
(102 mm)
24V
GND
1 GND 2 GND 3 GND 4 GND
AC POWER
BINARY OUTPUTS
STATUS
LED
4 in.
(102 mm)
4 in.
(102 mm)
5.375 in. (137 mm)
UNIVERSALINPUTS
DC OUT
SERVICE
PIN
1 GND
24V 24V
LED
2 GND 3 GND 4 GND
COMM5
BAAB
COMM5
LED
5.625 in. (143 mm)
1 in.
Clearances
(25 mm)
Dimensions
Figure 2. Dimensions and clearances for the metal-enclosure version I/O module
2 in. (51 mm)
6.875 in.
(175 mm)
(229 mm)
2 in.
51mm)
24 in.
(610 mm)
9 in.
10.37 in.
(263 mm)
width with cover
1 in.
(25 mm)
1 in.
(25 mm)
Clearances
Dimensions
2 in. (51 mm)
(25 mm)
2.25 in. (58 mm)
7 in.
(178 mm)
1 in.
1.875 in. (48 mm)
6.5 in.
(165 mm)
9 in.
(229 mm)
10.25 in.
(260 mm)
width without cover
3270 3332 C 2
Mounting the frame-mount I/O module
Mounting the metal-enclosure I/O module
IMPORTANT
Mount the Tracer MP503 with the cover on to avoid damaging the circuit board during installation.
To mount the frame-mount I/O module:
1. Using the module as a template, mark the location of the two mounting holes on the mounting surface (Figure 3).
2. Set the module aside and drill holes for the screws at the marked locations.
Drill holes for #10 (5 mm) screws or #10 wall anchors. Use wall anchors if the mounting surface is dry wall or masonry.
3. Insert wall anchors if needed.
4. Secure the module to the mounting surface with #10 (5 mm) screws (not included).
Attach the frame-mount module securely so that it can withstand the vibrations of associated heating, ventilating, and air-conditioning (HVAC) equipment.
Figure 3. Mounting the Tracer MP503
To mount the metal-enclosure I/O module:
1. Remove the two cover screws and then the cover.
2. Using the enclosure as a template, mark the location of the four mounting holes on the mounting surface (Figure 4).
3. Set the enclosure aside and drill holes for the screws at the marked locations.
Drill holes for #10 (5 mm) screws or #10 wall anchors. Use wall anchors if the mounting surface is dry wall or masonry.
4. Insert wall anchors if needed.
5. Secure the enclosure to the mounting surface with #10 (5 mm) screws (not included).
Figure 4. Mounting the metal-enclosure Tracer MP503
Agency listings/compliance
CE marked
UL and C-UL listed: Energy Management Equipment—PAZX (UL 916)
UL 94-5V (UL flammability rating for plenum use)
FCC Part 15, Subpart B, Class B
3 3270 3332 C