Trane CTA 7 Series, 090A***A – 60 HZ, 120A***A – 60 HZ, 120B***A – 60 HZ, 180B***A – 60 HZ Installation Owner Diagnostics

...
Installation Owner Diagnostics
Split System Cooling Condensers Model CTA 7 1/2 to 15 Tons
Models
090A***A 120A***A 120B***A 180B***A
“A” and later Design Sequence
60 HZ60 HZ60 HZ60 HZ
SS-SVN11A-EN
Notice
Overview of Manual
Note: One copy of this document ships inside each unit and is customer property. It must be retained by the unit’s maintenance personnel.
This booklet describes proper installa­tion, operation, and maintenance pro­cedures for air cooled systems. By carefully reviewing the information within this manual and following the instructions, the risk of improper operation and/or component damage will be minimized.
It is important that periodic mainte­nance be performed to help assure trouble free operation. A maintenance schedule is provided at the end of this manual. Should equipment failure occur, contact a qualified service organization with qualified, experi­enced HVAC technicians to properly diagnose and repair this equipment.
NOTICE:
Warnings and Cautions appear at appropriate sections throughout this manual. Read these carefully.
WARNING– Indicates a
potentially hazardous situation which, if not avoided, could result in death or serious injury.
CAUTION – Indicates a
potentially hazardous situation which, if not avoided, may result in minor or moderate injury. It may also be used to alert against unsafe practices.
CAUTION – Indicates a situa-
tion that may result in equipment or property-damage-only acci­dents.
IMPORTANT NOTE: All phases of this installation must comply with the NATIONAL, STATE & LOCAL CODES. In addition to local codes, the installa­tion must conform with National Elec­tric Code -ANSI/NFPA NO. 70 LATEST REVISION.
© 2004 American Standard Inc. All rights reserved. SS-SVN11A-EN
Note: Do Not release refrigerant to the atmosphere! If adding or
removing refrigerant is required, the service technician must comply with all federal, state, and local laws.
Contents
Installation/Startup/Commissioning
Model Number Description 4
Unit Dimensions
Electrical Data
Unit Inspection 9
Initial Leak Test
Lifting Recommendations
Clearances 10
Unit Mounting 10
Refrigerant Piping 10
Leak Check 12
System Evacuation 12
Refrigeration Charging 12
Electrical Wiring 13
Low Voltage Wiring 14
4
5
8
9
9
SS-SVN11A-EN 3
Refrigeration Schematic
Installation Checklist 21
Sequence of Operation
20
22
Maintenance 23
Warranty
25
Model Number Description
Model Number Description
All products are identified by a multi­ple-character model number that pre­cisely identifies a particular type of unit. An explanation of the alphanu­meric identification code is provided below. Its use will enable the owner/ operator, installing contractors, and service engineers to define the opera­tion, specific components, and other options for any specific unit.
When ordering replacement parts or requesting service, be sure to refer to the specific model number, serial number, and DL number (if applica­ble) stamped on the unit nameplate.
Split System Condensing Model Nomenclature
C T A 0 9 0 A 1 0 0 A A
1 2 3 4 5 6 7 8 9 10 11 12
Digits 1,2,3 - Product Type
CTA = Remote Air-Cooled Condenser
Digits 4,5,6 - Nominal Gross Cooling Capacity (MBh)
090 = 090 MBh-used with
3 & 5T SCRH
120 = 120 MBh - used with
7.5 & 10T SCRH
180 = 180 MBh - used with
12 & 15T SCRH)
Digits 7 - Major Development Sequence
A = 1 Refrig Cir.(3, 5, 7.5T SCRH) B = 2 Refrig Cir. (10, 12, 15T SCRH)
Digits 8 - Electrical Characteristics
1 = 208-230/60/1 2 = 460/60/1 8 = 575/60/1
Digits 9,10 - Factory Installed Options
00 = Packed Stock 0A = Coated Coil
Digits 11 - Minor Design Sequence
A = First
Digits 12 - Service Digit
A = First
4 SS-SVN11A-EN
Figure 1 CTA090A
Unit Dimensions
Figure 2 CTA120A
SS-SVN11A-EN 5
Figure 3 CTA120B
Unit Dimensions
6 SS-SVN11A-EN
Figure 4 CTA180B
Unit Dimensions
SS-SVN11A-EN 7
Electrical Data
Table 1: CTA Unit Electrical Data
Basic Unit Characteristics Outdoor Fan Motor
Model
Number
CTA090A1 208-230/60/1 187-254 15 15 1 1/2 3.1 8.1 CTA090A2 460/60/1 414-506 15 15 1 1/2 1.6 3.7 CTA090A8 575/60/1 518-632 15 15 1 1/2 1.2 3.0 CTA120A1 208-230/60/1 187-254 15 15 1 1 6.0 17.0 CTA120A2 460/60/1 414-506 15 15 1 1 2.7 7.0 CTA120A8 575/60/1 518-632 15 15 1 1 2.0 5.7 CTA120B1 208-230/60/1 187-254 15 15 1 1 6.0 17.0 CTA120B2 460/60/1 414-506 15 15 1 1 2.7 7.0 CTA120B8 575/60/1 518-632 15 15 1 1 2.0 5.7 CTA180B1 208-230/60/1 187-254 15 15 2 1/2 3.1 8.1 CTA180B2 460/60/1 414-506 15 15 2 1/2 1.6 3.7 CTA180B8 575/60/1 518-632 15 15 2 1/2 1.2 3.0
Electrical
Characteristics
Allowable
Voltage
Range
Minimum
Circuit
Ampacity
Maximum
Fuse
Size
Qty. HP
Amps
FLA
Amps
LRA
8 SS-SVN11A-EN
Loading...
+ 18 hidden pages