Precedent is a flexible line of packaged
units that covers a wide variety of
applications.
Electromechanical controls are available
for simpler applications, and for the more
sophisticated, ReliaTel™ microprocessor
controls. In addition to controls,
Precedent offers many other outstanding
features and option choices.
TM
. . . The same Trane
With its sleek compact cabinet, rounded
corners and beveled top, it may just be
the most aesthetically pleasing packaged
unit on the planet. And, of course,
Precedent carries the Trane reputation for
excellence, quality and reliability.
From simple applications, to the most
complex, Precedent has the solution.
RT-PRC005-EN
Contents
Introduction
Features and Benefits
Application Considerations
Selection Procedure
Model Number Description
General Data
Performance Data
Cooling Performance
Fan Performance
Heat Performance
Controls
Electric Power
Dimension and Weights
2
4
10
11
13
14
18
18
31
56
59
61
76
Mechanical Specifications
85
3RT-PRC005-EN
Unit Cabinet
The compact cabinet with rounded
corners takes up less room and is less
costly to ship. The beveled and ribbed top
is not only aesthetically pleasing, it is
designed to prevent water from pooling.
Single Point Power
A single electrical connection powers the
unit.
Features and
Benefits
Easy Access Panels
Remove two screws for access to the
standardized internal components and
wiring.
Easy-Adjust Idler Arm
With the Easy-Adjust Idler Arm, the belt
and sheaves on belt drive units can be
quickly adjusted without moving the
mounted fan motor. The result is a major
savings in time and money.
Colored And Numbered Wiring
You save time and money tracing wires
and diagnosing the unit.
Patented Condenser Coil
Precedent boasts a patented 1+1+1
Hybrid coil, permanently gapped for easy
of cleaning.
Compressors
Precedent™ contains the best
compressor technology available to
achieve the highest possible
performance. Our compressor line
includes Trane built reciprocating and
scrolls.
Easy Access Panels
Easy access panels reduce the number of
possible water entry points.
Low Ambient Cooling
All Precedent microprocessor units have
cooling capabilities down to 0°F as
standard. Electromechanical models
have cooling capabilities to 40°F as built,
or to 0°F by adding the optional low
ambient control (frostat).
Convertible Units
• The units ship in a downflow
configuration. They can be easily
converted to horizontal by simply
moving two panels.
• Units come complete with horizontal
duct flanges so the contractor doesn’t
have to field fabricate them. These duct
flanges are a time and cost saver.
Unit Base
For added water integrity, Precedent has
a raised 1
downflow supply and return to prevent
water from blowing into the ductwork.
1
/8" lip around the unit’s
Sloped Drain Pans
Every Precedent unit has a noncorrosive, removable, double-sloped
drain pan that’s easy to clean and
reversible to allow installation of drain
trap on either side of the unit.
Through the Base Condensate
Every unit includes provisions for through
the base condensate drain connections.
This allows the drain to be connected
through the roof curb instead of a roof
penetration.
Foil-Faced Insulation
All panels in the Evaporator section of the
unit have cleanable foil-faced insulation.
All edges are either captured or sealed to
ensure no fibers get into the airstream.
4RT-PRC005-EN
Features and
Benefits
Standardized Components
• Components are placed in the same
location on all Precedent™ units.
Familiarize yourself with one Precedent
and you are familiar with every
Precedent.
Easy Access Low Voltage Terminal Board
Precedent’s Low Voltage Terminal Board
is external to the electrical control cabinet.
It is extremely easy to locate and attach
the thermostat wire. This is another cost
and time saving installation feature.
Flexible Applications
• Only two roof curbs for the 3-10 ton
Precedent line simplifies curb selection.
• Standard or High Efficiency Cooling
• Electromechanical or ReliaTel
microprocessor controls to meet either
the simple or the more complex
application.
• Airflow is outstanding. The Precedent
can replace an older machine with old
ductwork and, in many cases, improve
comfort through better air distribution.
• Belt or direct drive — standard or
oversized supply fan motors meet a
wide airflow range.
• Precedent offers ultimate flexibility.
Options and components are not prepackaged at the factory. Units are built
to order in our standard “shortest in the
industry” ship cycle time.
RT-PRC005-EN
Low Voltage Connections
The wiring of the low voltage connections
to the unit and the zone sensors is as
simple as 1-1, 2-2, and 3-3. This simplified
system makes it easy for the installer to
wire
Single-Side Service
Single-side service is standard on all
Precedent units.
5
Features and
Benefits
Micro Controls
Several years ago, Trane was the first to
introduce microprocessor controls into
the Light Commercial Market. That
design, along with immeasurable
experience, has provided the technology
for Trane’s second-generation ReliaTel™
microprocessor controls.
ReliaTel™ Micro:
• Provides unit control for heating,
cooling, and ventilating by utilizing input
from sensors that measure outdoor
and indoor temperature.
• Improves quality and reliability through
the use of time-tested microprocessor
controls and logic.
• Prevents the unit from short cycling,
considerably improving compressor
life.
• Ensures that the compressor will run for
a specific amount of time, which allows
oil to return for better lubrication,
enhancing the reliability of the
compressor.
• Reduces the number of components
required to operate the unit, thereby
reducing possibilities for component
failure.
• Eliminates the need for field-installed
components with its built-in anti-shortcycle timer, time delay relay and
minimum ‘’on’’ time controls. These
controls are factory tested to assure
proper operation.
• Requires no special tools to run the
Precedent unit through its paces during
testing. Simply place a jumper between
Test 1 and Test 2 terminals on the Low
Voltage Terminal Board and the unit will
walk through its operational steps. The
unit automatically returns control to the
zone sensor after stepping through the
test mode a single time, even if the
jumper is left on the unit.
• As long as the unit has power and the
LED is lit, the Micro is operational. The
light indicates that the Micro is
functioning properly.
• Features expanded diagnostic
capabilities when used with Trane’s
Integrated Comfort
• As an energy benefit, softens electrical
‘’spikes’’ by staging on fans,
compressors and heaters.
• The Intelligent Fallback or Adaptive
Control is a benefit to the building
occupant. If a component goes astray,
the unit will continue to operate at
predetermined temperature set points.
• Intelligent Anticipation is a standard
feature of the Micro. Functioning
constantly, the Micro and zone sensors
work together in harmony, to provide
tight comfort control.
Electromechanical Controls
TM
Systems.
• For the simpler job that does not
require a building automation system,
or expanded diagnostics capabilities,
Precedent offers electromechnical
controls. This 24-volt control includes
the control transformer, contactor
pressure lugs for power wiring.
6RT-PRC005-EN
Features and
Benefits
Factory-installed Options
Dehumidification (Hot Gas Reheat)
Option
This option allows for increased outdoor
air ventilation. It reduces humidity levels
while increasing comfort level in the air
space. Cooling can operate without a
demand for dehumidification. The hot gas
reheat coil is designed to deliver
maximum reheat temperatures and
pivot to allow for easy access cleaning.
Hinged Access Doors
These doors permit easy access to the
filter, fan/heat, and compressor/control
sections. They reduce the potential roof
damage from screws or sharp access
door corners.
Economizer
Equipped with either dry bulb, reference
or comparative enthalpy sensing, this
feature provides free cooling as the
outdoor temperature and/or humidity
decreases. Economizers, correctly
installed, offer a valuable energy savings.
Factory-installed economizers save time
and ensure proper installation.
Through the Base Electrical Utility
Access
Factory provided through the base
openings simplify wiring and piping.
Because these utility openings frequently
minimize the number of roof
penetrations, the integrity of roofing
materials is enhanced.
Phase Monitor
Phase monitor shall provide 100%
protection for motors and compressors
against problems caused by phase loss,
phase imbalance, and phase reversal.
Phase monitor is equipped with an LED
that provides an ON or FAULT indicator.
Clogged Filter/Fan Fail Switches
These sensors allow a zone sensor
service light or Integrated Comfort
System to indicate a dirty filter or a fan
that’s not working. The field installation
charges for these valuable feedback
devices often eliminate them from
consideration. Factory installation can
make such features a good investment.
Unit Mounted Disconnect or Circuit
Breaker
Codes require a method of assured unit
shutdown for servicing. Field-installed
disconnects sometimes interfere with
service access. Factory installation of unit
disconnects reduces costs, assures
proper mounting and provides the
opportunity to upgrade to unit circuit
breaker protection.
Trane Communication Interface
Available factory or field-installed. This
module when applied with ReliaTel™
easily interfaces with Trane’s Integrated
Comfort
TM
System.
Unit Disconnect
Convenience Outlet
RT-PRC005-EN
7
Features and
Benefits
Quality and Reliability Testing
• All Precedent™ designs were
rigorously rain tested at the factory to
ensure water integrity.
• Actual shipping tests were performed
to determine packaging requirements.
Units were test shipped around the
country to determine the best
packaging.
• Factory shake and drop tests were
used as part of the package design
process to help assure that the unit
arrives at the job site in top condition.
• Rigging tests include lifting a unit into
the air and letting it drop one foot,
assuring that the lifting lugs and rails
hold up under stress.
VariTrac
™
• We perform a 100% coil leak test at the
factory. The evaporator and condenser
coils are leak tested at 200 psig and
pressure tested to 450 psig.
• All parts are inspected at the point of
final assembly. Sub-standard parts are
identified and rejected immediately.
• Every unit receives a 100% unit run test
before leaving the production line to
make sure it lives up to rigorous Trane
requirements.
We test designs at our factory not on our
customers!
Va riTra c
When Trane’s changeover VAV System
for light commercial applications is
coupled with Precedent, it provides the
latest in technological advances for
comfort management systems and can
allow thermostat control in every zone
served by VariTrac.
8RT-PRC005-EN
Features and
Benefits
The following options round-out the
complete line of Precedent™ options:
— 0 - 50% Manual or Motorized
Outside Air
— Hail Protection Quality Coil Guards
— Electric Heaters
— Supply and/or Return Smoke
Detectors
— High Pressure Cutout
(standard on 3-phase models with
scroll compressors and all standard
efficiency 3-ton models)
— Thermal Expansion Valve for a wider
range of applications
— Discharge Air Sensor
— Wide array of Zone Sensors and
Thermostats
— Factory built Roof Curb
— Power Exhaust
— LonTalk Communications Interface
One of Our Finest Assets:
Trane Sales Representatives are a
Support group that can assist you with:
— Product
— Application
— Service
— Training
— Special Applications
— Specifications
— Computer Programs and much more
Precedent has the features and benefits
that make it first class in the light
commercial rooftop market. Designed
with input from field contractors and
engineers, its airflow performance is
outstanding.
Precedent…The same Trane
quality…with added flexibility.
RT-PRC005-EN
9
Application
Considerations
Application of this product should be
within the cataloged airflow and cooling
considerations.
Low Ambient Cooling
The Precedent™ line features, with
ReliaTel™ microprocessor controls, low
ambient cooling down to 0F. With
electromechanical controls, Precedent
features low ambient cooling to 40F.
Contact your local Trane Representative
for more assistance with low ambient
cooling applications.
Barometric Relief
This product line offers an optional
barometric relief damper. for use in
conjunction with economizer option. This
accessory consists of gravity dampers
which open with increased pressure. As
the building air pressure increases, the
pressure in the unit return air section
also increases, opening the dampers and
relieving the conditioned space.
NOTE: THE EFFECTIVENESS OF
BAROMETRIC RELIEF DAMPER DURING
ECONOMIZING OPERATION IS SYSTEM
RELATED.
PRESSURE DROP OF THE RETURN AIR
SYSTEM SHOULD BE CONSIDERED TO
CONTROL BUILDING PRESSURIZATION.
Condensate Trap
The evaporator is a draw-thru
configuration. A trap must be field
provided prior to start-up on the cooling
cycle.
Clearance Requirements
The recommended clearances identified
with unit dimensions should be
maintained to assure adequate service
maximum capacity and peak operating
efficiency. Actual clearances which
appear inadequate should be reviewed
with the local Trane sales personnel.
Unit Pitch
These units have reversible sloped
condensate drain pans. Units must be
installed level, any unit slope must be
toward the side of unit where condensate
drain is connected.
10RT-PRC005-EN
Selection
Procedures
Cooling Capacity
Step 1
Calculate the building’s total and sensible
cooling loads at design conditions. Use
the Trane calculation methods or any
other standard accepted method.
As a starting point, a rough determination
must be made of the size of the unit. The
final selection will be made after
examining the performance at the given
conditions. Divide the total cooling load by
nominal BTUH per ton (12 MBh per ton);
then round up to the nearest unit size.
59 MBh / 12 MBh = approx. 5 tons
Step 3
Table PD-15 shows that a THC060A4 has
a gross cooling capacity of 62.4 MBh and
48.4 MBh sensible capacity at 2000 cfm
and 95 DB outdoor ambient with 80 DB,
67 WB air entering the evaporator.
To Find Capacity at Intermediate
Conditions Not in the Table
When the design conditions are between
two numbers that are in the capacity
table, interpolation is required to
approximate the capacity. Note:
Extrapolation outside of the table
conditions is not recommended.
Step 4
In order to select the correct unit which
meets the building’s requirements, the
fan motor heat must be deducted from
the gross cooling capacity. The amount of
heat that the fan motor generates is
dependent on the effort by the motor cfm and static pressure. To determine the
total unit static pressure:
External Static (duct system)
0.36 wg
Standard Filter 1 in.0.15 wg
from Table PD-73
Economizer0.18 wg
(100% Outside Air)from Table
PD-73
Electric Heater Size 6 kW0.056 wg
from Table PD-73
(reference “Heating Capacity” section on
this page for determination of heater
size)
Total Static Pressure0.75 wg
Note: The Evaporator Fan Performance
Table PD-50 has deducted the pressure
drop for a 1 in. filter already in the unit
(see note below Table PD-24). Therefore,
the actual total static pressure is 0.75 -
0.15 (from Table PD - 73) = 0.60 wg.
With 2000 cfm and 0.60 wg.
Table PD-50 shows .90 bhp for this unit.
Note below the table gives a formula to
calculate Fan Motor Heat,
2.829 x bhp + .4024 = MBH.
2.829 x .83 + .4024 = 2.75 MBH.
Now subtract the fan motor heat from
the gross cooling capacity of the unit:
Net Total Cooling Capacity
= 62.4 MBH - 2.95 = 59.45 MBH.
If the performance will not meet the
required load of the building’s total or
sensible cooling load, try a selection at
the next higher size unit.
Heating Capacity
Step 1
Calculate the building heating load using
the Trane calculation form or other
standard accepted method.
Step 2
Size the system heating capacity to
match the calculated building heating
load. The following are building heating
requirements:
A
Total heating load of 15 MBH
B
2000 cfm
C
460 volt/3 phase Power Supply
The electric heat accessory capacities
are listed in Table PD-74 From the table,
a 6 kW heater will deliver 20.48 MBH at
480 volts. In order to determine capacity
at 460 volts, the heater voltage
correction factor from Table PD-75 must
be used. Therefore, 20.48 MBH x .9118
(voltage correction factor) = 18.80 MBH.
Air Delivery Selection
External static pressure drop through
the air distribution system has been
calculated to be 0.60 inches of water.
Enter Table PD-50 for a THC060A4 at
2000 cfm and 0.60 static pressure. The
standard direct drive motor will give the
desired airflow at a rated bhp of 0.90
and 998 rpm.
RT-PRC005-EN
11
Selection
Procedure
Dehumidification Selection
Typical 10 ton THC120A
2000 cfm Total Supply airflow
800 cfm Outside Air (40%)
1200 cfm Return Air
0.41” External Static Pressure
OA Conditions
Part load day and raining
68°F db
67°F wb
RA’ conditions
75°F db
63°F wb
Step 1: Determine the mixed/
entering air condition (MA’)
MA’ = (% outside air*outside air dry-bulb
temperature) + (% return air*return air
dry-bulb temperature)
MA’ = (0.40*68°F) + (0.60*75°F)
MA’ = 72.20°F db
Note: Repeat for wet-bulb
temperature (wb).
Plot on psychrometric chart.
MA’
72.2°F db
65°F wb
Step 2: Determine leaving
unit
temperature
Leaving Unit Temperature = SA’
Utilize the TOPSS™ program to
determine the leaving unit temperature.
45°F db
44°F wb
43°F dp
Step 3: Determine reheat
temperature rise
Go to PD-78 for reheat temperature rise:
26.7°F db
68°F DB,
OA
67°F WB
75°F DB,
RA'
52% RH
MA' 72.2°F DB
SA'
SA
Chart C-1
65°F WB
47°F DB
73°F DB
SA'
SA'
REHEAT
OAOAOA
MA'
MA'
SA
SA
Note: Reheat temperature rise is based
on supply airflow and leaving evaporator
coil temperature.
Step 4: Determine leaving unit
temperature
Reheat temperature (obtained in step 3)
+ SA’
26.7°F db + 47°F = 73.7°F db
SA=73.7°F
Consider Chart C-1. If the space relative
humidity is equal to or above the space
relative humidity setpoint, the
Dehumidification Option will:
RA'
RA'
Step 5: Determine static pressure
drop add for reheat
Table PD-73 shows a static pressure drop
of 0.09” wc 0.41”+ 0.09” = 0.5” wc
Table PD-65 indicates that a standard
motor and field installed low static drive
kit is needed for this airflow and static
pressure range.
• Energize compressor or both
compressors (2 stage compressor units).
• Hot gas reheat valve is energized and
hot gas is diverted to the reheat coil.
• Dehumidification/reheat is terminated
when space humidity is reduced to 5%
below relative humidity setpoint.
At MA’, air enters the RTU. The RTU filters,
cools, and dehumidifies the air as it
moves through the evaporator coil. Air
leaves the evaporator coil saturated at
the preset dew point condition (SA’) and
is reheated by the hot gas reheat coil to
deliver 73.7°F (SA) supply air to the
space.
036 =3 Ton
048 =4 Ton
060 =5 Ton
072 =6 Ton
090 =7½ Ton, Single Compressor
092 =7½ Ton, Dual Compressor
102 =8½ Ton
120 =10 Ton
DIGIT 7 - Major Design Sequence
A = First
DIGIT 8 - Unit Voltage
1 = 208-230/60/1
3 = 208-230/60/3
4 = 460/60/3
W = 575/60/3
K = 380/60/3
DIGIT 9 - Unit Controls
E = Electromechanical
R = ReliaTel™Microprocessor
DIGIT 10 - Heating Capacity
0 = No Electric Heat
A = 5 kW (1 phase)
B = 6 kW (3 phase)
C = 9 kW (3 phase)
D = 10 kW (1 phase)
E = 12 kW (3 phase)
F = 14 kW (1 phase)
G = 18 kW (1 and 3 phase)
J = 23 kW (3 phase)
K = 27 kW (3 phase)
N = 36 kW (3 phase)
P = 54 kW (3 phase)
DIGIT 11 - Minor Design Sequence
A = First Sequence
Example:
Model number TSC036A3RBA**C000A10001A1 describes a unit with the following characteristics: DX Cooling, 3 ton nominal cooling capacity, 208-230/60/3 power supply, ReliaTel™ controls, 6 kW
electric heater model. 0-100% dry bulb economizer without barometric relief, standard direct drive motor, standard access panels/filters, standard condenser coil with no coil protection, through the
base electric, non-fused disconnect, no convenience outlet or communications interface, standard refrigeration coil, high pressure control, return air smoke detector, and clogged filter switch.
DIGITS 12, 13 - Service Sequence
** = Factory Assigned
DIGIT 14 - Fresh Air Selection
0 = No Fresh Air
A = Manual Outside Air Damper 0-50%
B = Motorized Outside Air Damper 0-50%
C = Economizer, Dry Bulb 0-100%
without Barometric Relief
D = Economizer, Dry Bulb 0-100%
with Barometric Relief
E = Economizer, Reference Enthalpy
0-100% without Barometric Relief
F = Economizer, Reference Enthalpy
0-100% with Barometric Relief
G = Economizer, Comparative Enthalpy
0-100% without Barometric Relief
H = Economizer, Comparative Enthalpy
0-100% with Barometric Relief
DIGIT 15 - Supply Fan/Drive Type/Motor
0 = Standard Drive
1 = Oversized Motor
2 = Optional Belt Drive Motor
DIGIT 16 - Hinged Service Access/Filters
0 = Standard Panels/Standard Filters
A = Hinged Access Panels/Standard Filters
B = Standard Panels/2” Pleated Filters
C = Hinged Access Panels/2” Pleated
Filters
DIGIT 17 - Condenser Coil Protection
0 = Standard Coil
1 = Standard Coil with Hail Guard
2 = Epoxy Coated Condenser Coil
3 = Epoxy Coated Condenser Coil with
Hail Guard
DIGIT 18 - Through the Base Provisions
0 = No Through the Base Provisions
A = Through the Base Electric
0 = Standard Refrigeration System
A = Thermal Expansion Valve (TXV)
B = Dehumidification (Hot Gas Reheat
Coil)
DIGIT 23 - Refrigeration Controls
0 = No Refrigeration Control
1 = High Pressure Control
2 = Frostat
3 = Crankcase Heater
4 = High Pressure Control and Frostat
5 = High Pressure Control and Crankcase
Heater
6 = Frostat and Crankcase Heater
7 = High Pressure Control, Frostat and
Crankcase Heater
DIGIT 24 - Smoke Detector
0 = No Smoke Detector
A = Return Air Smoke Detector
B = Supply Air Smoke Detector
C = Supply and Return Air Smoke
Detectors
DIGIT 25 - Monitoring Controls
0 = No Monitoring Control
1 = Clogged Filter Switch
2 = Fan Failure Switch
3 = Discharge Air Sensing Tube
4 = Clogged Filter Switch and Fan Fail
Switch
5 = Clogged Filter Switch and Discharge
Air Sensing Tube
6 = Fan Fail Switch and Discharge Air
Sensing Tube
7 = Clogged Filter and Fan Fail Switches
and Discharge Air Sensing Tube
8 = Novar Return Air Sensor
RT-PRC005-EN
13
General
(3 - 5 Ton)
Data
Standard Efficiency
Table GD - 1 — General Data
3 Ton Convertible Units4 Ton Convertible Units5 Ton Convertible Units
SEER
Nominal CFM / ARI Rated CFM1,200/1,2001,600/1,6001,600/1,6002,000/2,0002,000/2,0002,000/2,000
ARI Net Cooling Capacity36,00048,00047,00060,00060,00060,000
System Power (kW)3.79
Direct Drive Indoor Fan — TypeFC CentrifugalFC CentrifugalFC CentrifugalFC CentrifugalFC CentrifugalFC Centrifugal
No. Used 111111
Diameter x Width (in.)10 x 1011 x 1111 x 1111 x 1111 x 1112x11/–
Drive Type/No. SpeedsDirect/2Direct/2Direct/2Direct/2Direct/2Direct/2
No. Motors111111
Motor HP (Standard/Oversized).33/.50.60/.80.60/.80.90/1.00.90/1.0 01.0/–
Motor RPM (Low/High Speed)950/1060930/1000930/1000985/110 0985/1100935/1100
Oversized Motor RPM
(Low/High Speed)110 0/11451000/11001000/110 01080/11351080/1135—
Motor Frame Size
(Standard/Oversized)48/4848/4848/4848/4848/4848/—
Belt Drive Indoor Fan — TypeFC Centrifugal—FC Centrifugal—FC Centrifugal—
No. Used1—1—1—
Diameter x Width (in.)11 x 11—11 x 11—11 x 11—
Drive Type/No. SpeedsBelt/Variable Speed
No. Motors1—1—1—
Motor HP1.00—1.0 0—1.00—
Motor RPM1750—1750—1750—
Motor Frame Size56—56—56—
Filters — Type Furnished
(No.) Size Recommended (in.)(2) 20 x 25 x 1(2) 20 x 25 x 1(2) 20 x 25 x 1(2) 20 x 25 x 1(2) 20 x 25 x 1(2) 20 x 25 x 1
Refrigerant Charge (Lbs of R-22)
NOTES:
1. Cooling Performance is rated at 95 F ambient, 80 F entering dry bulb, 67 F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is net and includes
the effect of fan motor heat. Units are suitable for operation to ±20% of nominal cfm. Certified in accordance with the Unitary Air-Conditioner Equipment certification program, which is
based on ARI Standard 210/240 except AK (380V/60 Hz).
2. SEER is rated at ARI conditions and in accordance with DOE test procedures.
3. Outdoor Sound Rating shown is tested in accordance with ARI Standard 270. For more information refer to Table PD-72.
4. Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.
5. TSC036A1 SEER is 10.5.
6. Belt Drive Motor is not available for TSC036A1.
7. Optional 2” Pleated Filters also available.
8. TSC036A1 System Power (kW) is 3.91.
1
TSC036A1, A3, A4, AWTSC048A1TSC048A3, A4, AWTSC060A1TSC060A3, A4, AW TSC060AK
Nominal CFM / ARI Rated CFM2,400/2,1003,000/2,6253,000/2,6253,400/3,0004,000/3,200
ARI Net Cooling Capacity69,00090,00087,000100,000
Integrated Part Load Value (IPLV)
System Power (kW)6.78.748.459.71
Belt Drive Indoor Fan — TypeFC CentrifugalFC CentrifugalFC CentrifugalFC CentrifugalFC Centrifugal
No. Used11111
Diameter x Width (in.)12 x 1212 x 1212 x 1215 x 1515 x 15
Drive Type/No. SpeedsBelt/Variable SpeedBelt/Variable Speed Belt/Variable SpeedBelt/Variable Speed Belt/Variable Speed
No. Motors11111
Motor HP (Standard/Oversized)1.00/2.00
Motor RPM (Standard/Oversized)17501750175017501750/3450
Motor Frame Size5656565656
Filters — Type Furnished
10
(No.) Size Recommended (in.)(4) 16 x 25 x 2(4) 16 x 25 x 2(4) 16 x 25 x 2(4) 20 x 25 x 2(4) 20 x 25 x 2
Refrigerant Charge (Lbs of R-22)
NOTES:
1. Cooling Performance is rated at 95 F ambient, 80 F entering dry bulb, 67 F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is net and includes
the effect of fan motor heat. Units are suitable for operation to ±20% of nominal cfm. Certified in accordance with the Unitary Air-Conditioner Equipment certification program, which is
based on ARI Standard 210/240 except AK (380V/60 Hz).
2. SEER is rated at ARI conditions and in accordance with DOE test procedures.
3. Integrated Part Load Value is rated in accordance with ARI Standard 210/240 or 360. Units are rated at 80°F ambient, 80°F entering dry bulb, and 67°F entering wet bulb ar ARI rated cfm.
4. Outdoor Sound Rating shown is tested in accordance with ARI Standard 270. For more information refer to Table PD-72.
5. Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.
6. EER shown is for downflow airflow. EER for horizontal airflow is 10.3.
7. ARI Net Cooling Capacity shown is for downflow airflow. Cooling Capacity for Horizontal airflow TSC102A is 99,000; TSC120A is 112,000.
8. Integrated Part Load Value (IPLV) shown is for downflow airflow. IPLV for Horizontal airflow TSC092A is 10.8, TSC102A is 11.5; TSC120A is 11.0.
9. System Power (kW) shown is for downflow airflow. System Power (kW) forHorizontal airflow TSC102A is 9.61; for TSC120A is 10.87.
10. Optional 2” Pleated Filters also available.
11. Outdoor motor is 0.75 hp for AK (380V/60 Hz units).
12. Standard indoor motor is 2.00 hp for AK (380V/60 Hz) units.
TSC072A3, A4, AW, AKTSC090A3,A4,AW, AKTSC092A3, A4, AWTSC102A3, A4, AW, AK TSC120A3, A4, AW, AK
10.310.310.310.310.4
3——
4
8890878686
11
12
1/0.70
2.00/3.002.00/3.002.00/3.003.00/5.00
8
11. 1
11
1/0.701/0.751/0.75
11. 9
7
8
9
ThrowawayThrowawayThrowawayThrowawayThrowaway
5
7.111.56.2 Circuit 17.9 Circuit 17.2 Circuit 1
3.4 Circuit 24.0 Circuit 2 5.3 Circuit 2
114,000
11. 5
10.96
6
7
8
9
RT-PRC005-EN
15
General
(3 - 5 Ton)
Data
High Efficiency
Table GD - 3 — General Data
3 To n4 To n 5 Ton
Convertible UnitsConvertible UnitsConvertible Units
Cooling Performance
Gross Cooling Capacity38,00049,80062,10062,400
/ EER
SEER
Nominal CFM / ARI Rated CFM1,200/1,2001,600/1,6002,000/2,0002,000/2,000
1
2
ARI Net Cooling Capacity36,60047,50059,00059,500
System Power (kW)3.334.485.735.56
Direct Drive Indoor Fan — TypeFC CentrifugalFC CentrifugalFC CentrifugalFC Centrifugal
No. Used1111
Diameter x Width (in.)10 x 1011 x 1111 x 1111 x 11
Drive Type/No. SpeedsDirect/2Direct/2Direct/2Direct/2
No. Motors1111
Motor HP (Standard/Oversized).33/.50.60/.80.90/1.00.90/1.00
Standard Motor RPM (Low/High Speed)950/1060930/1000985/1100985/1100
Oversized Motor RPM (Low/High Speed)1100/114510 00/11001080/11351080/1135
Motor Frame Size (Standard/Oversized)48/4848/4848/4848/48
Belt Drive Indoor Fan — TypeFC CentrifugalFC Centrifugal—FC Centrifugal
No. Used11—1
Diameter x Width (in.)11 x 1111 x 11—11 x 11
Drive Type/No. SpeedsBelt/Variable Speed
No. Motors11—1
Motor HP1.001.00—1.00
Standard Motor RPM17501750—1750
Motor Frame Size5656—56
Filters — Type Furnished
7
(No.) Size Recommended (in.)(2) 20 x 25 x 1(2) 20 x 25 x 1(2) 20 x 30 x 1(2) 20 x 30 x 1
Optional Hot Gas Reheat Coil - TypeLancedLanced—Lanced
Tube Size (in.) OD0.3750.375—0.375
Face Area (sq. ft)2.222.22—2.22
Rows/FPI1/161/16—2/16
Refrigerant Charge (Lbs of R-22)
4
Standard5.3
Optional Hot Gas Reheat Coil5.38.5—10.7
NOTES:
1. Cooling Performance is rated at 95 F ambient, 80 F entering dry bulb, 67 F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is net and includes
the effect of fan motor heat. Units are suitable for operation to ±20% of nominal cfm. Units are certified in accordance with the Unitary Air-Conditioner Equipment certification program,
which is based on ARI Standard 210/240.
2. EER and SEER are rated at ARI conditions and in accordance with DOE test procedures.
3. Outdoor Sound Rating shown is tested in accordance with ARI Standard 270. For more information refer to Table PD-72.
4. Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.
5. Refrigerant Charge shown is for 3 phase. 1 phase Refrigerant Charge is 8.1.
6. Belt Drive Motor is not available for THC036A1, THC048A1.
7. Optional 2” Pleated Filters also available.
8. Refrigerant Charge shown is for 3 phase. 1 phase Refrigerant Charge is 4.5.
9. TXV is supplied from the factory as standard with the Dehumidification (Hot Gas Reheat) option.
10. With Dehumidification (Hot Gas Reheat) option: Direct/2.
11. 2" pleated filters is a factory installed option. 2" pleated filters is standard with the Dehumidification (Hot Gas Reheat) option.
Convertible UnitsConvertible UnitsConvertible UnitsConvertible Units
Cooling Performance
Gross Cooling Capacity73,00094,000103,000117,000
2
EER
1
Nominal CFM / ARI Rated CFM2,400/2,1003,000/2,6253,400/3,0004,000/3,200
ARI Net Cooling Capacity70,00090,000
Integrated Part Load Value (IPLV)
System Power (kW)6.09
Belt Drive Indoor Fan — TypeFC CentrifugalFC CentrifugalFC CentrifugalFC Centrifugal
No. Used1111
Diameter x Width (in.)12 x 1215 x 1515 x 1515 x 15
Drive Type/No. SpeedsBelt/Variable Speed Belt/Variable SpeedBelt/Variable Speed Belt/Variable Speed
No. Motors1111
Motor HP (Standard/Oversized)1.00/2.002.00/3.002.00/3.003.00/5.00
Motor RPM (Standard/Oversized)1750175017501750/3450
Motor Frame Size56565656
Filters — Type Furnished
9
(No.) Size Recommended (in.)(4) 16 x 25 x 2(4) 20 x 25 x 2(4) 20 x 25 x 2(4) 20 x 25 x 2
Optional Hot Gas Reheat Coil — Type—LancedLancedLanced
Tube Size (in.) OD—0.3750.3750.375
Face Area (sq. ft.)—5.195.195.19
Rows/FPI—2/162/162/16
Refrigerant Charge (Lbs of R-22)
NOTES:
1. Cooling Performance is rated at 95 F ambient, 80 F entering dry bulb, 67 F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is net and includes
the effect of fan motor heat. Units are suitable for operation to ±20% of nominal cfm. Certified in accordance with the Unitary Air-Conditioner Equipment certification program, which is
based on ARI Standard 210/240.
2. SEER is rated at ARI conditions and in accordance with DOE test procedures.
3. Integrated Part Load Value is rated in accordance with ARI Standard 210/240 or 360. Units are rated at 80°F ambient, 80°F entering dry bulb, and 67°F entering wet bulb ar ARI rated cfm.
4. Outdoor Sound Rating shown is tested in accordance with ARI Standard 270. For more information refer to Table PD-72.
5. Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.
6. EER shown is for downflow airflow. EER for horizontal airflow: THC072A - 11.3, THC092A and THC102A - 11.3, THC120A - 10.7.
7. System Power (kW) shown is for downflow airflow. System Power (kW) for horizontal airflow: THC072A - 6.2, THC092A - 7.88, THC102A - 8.58, THC120A - 10.09.
8. Integrated Part Load Value (IPLV) shown is for downflow airflow. IPLV for horizontal airflow: THC092A - 11.5, THC102A - 11.6, THC120A - 11.5.
9. Optional 2” Pleated Filters also available.
10. Net Cooling Capacity shown is for downflow airflow. Net Cooling for horizontal airflow: THC092A - 89,000, THC102A - 97,000, THC120A - 108,000.
5
THC072A3, A4, AWTHC092A3, A4, AWTHC102A3, A4. AWTHC120A3, A4, AW
6
11. 5
3—
7
11. 5
11. 9
7.83
6
10
8
7
11. 5
98,000
12.1
8.52
6
10
8
7
89918988
ThrowawayThrowawayThrowawayThrowaway
10.76.4 Circuit 17.4 Circuit 111.0 Circuit 1
6.2 Circuit 27.1 Circuit 27.3 Circuit 2
11. 2
109,000
12.0
9.73
6
10
8
7
RT-PRC005-EN
17
Performance
(3, 4 Ton)
Data
Standard Efficiency
Table PD-1 — Gross Cooling Capacities (MBH) 3 Ton Single/Three Phase TSC036A1, A3, A4, AW
Table PD-24— Direct Drive Evaporator Fan Performance 3, 4 and 5 Ton TSC036A, TSC048A, TSC060A
TonsModel No. CFMESPBHPESPBHPESPBHPESPBHP
3TSC036A 12000.660.400.340.300.840.450.740.41
4TSC048A 16000.660.550.510.491.000.750.740.64
5TSC060A
3TSC036A 12000.710.400.390.300.890.450.790.41
4TSC048A 16000.710.550.560.491.050.750.790.64
5TSC060A
Fan motor heat (MBH) = 3.72 x Fan Bhp + .24.
Trane’s factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and
continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance
tripping or premature motor failure. Our product’s warranty will not be affected.
NOTES:
1. Data includes pressure drop due to wet coil and filters.
2. 5 ton oversized motor performance is with 12 x 11 FC blower wheel.
3. YSC060AK uses a 1.0 hp direct drive motor and 12x11 FC centrifugal blower wheel. Refer to oversized motor column for the standard motor
For Standard Evaporator Fan Speed (RPM), reference Table PD-68.
NOTES:
Data includes pressure drop due to standard filters and wet coils.
No accessories or options are included in pressure drop data.
Refer to Table PD-73 to determine additional static pressure drop due to other options/accessories
Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
1. Field Supplied Fan Sheave AK69 required. Field Supplied Belt may be necessary.
2. Field Supplied Fan Sheave AK41 required. Field Supplied Belt may be necessary.
.10.20.30.40.50.60.70.80.901.00
1-HP Standard Motor
& Field Supplied
Low Static Drive (1)1-HP Standard Motor & Drive
External Static Pressure (Inches of Water)
Trane’s factory supplied motors, in commercial equipment, are
definite purpose motors, specifically designed and tested to
operate reliably and continuously at all cataloged conditions.
Using the full horsepower range of our fan motors as shown in
our tabular data will not result in nuisance tripping or
premature motor failure. Our product’s warranty will not be
affected.
For Standard Evaporator Fan Speed (RPM), reference Table PD-68.
NOTES:
Data includes pressure drop due to standard filters and wet coils
No accessories or options are included in pressure drop data.
Refer to Table PD-73 to determine additional static pressure drop due to other options/accessories.
Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
1. Field Supplied Fan Sheave AK69 required. Field Supplied Belt may be necessary.
2. Field Supplied Fan Sheave AK41 required. Field Supplied Belt may be necessary.
Trane’s factory supplied motors, in commercial equipment, are
definite purpose motors, specifically designed and tested to operate
reliably and continuously at all cataloged conditions. Using the full
horsepower range of our fan motors as shown in our tabular data
will not result in nuisance tripping or premature motor failure. Our
product’s warranty will not be affected.
For Standard Evaporator Fan Speed (RPM), reference Table PD-68.
NOTES:
Data includes pressure drop due to standard filters and wet coils.
No accessories or options are included in pressure drop data.
Refer to Table PD-73 to determine additional static pressure drop due to other options/accessories
Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
1. Field Supplied Fan Sheave AK61 required. Field Supplied Belt may be necessary.
.10.20.30.40.50.60.70.80.901.00
1-HP Standard Motor & Field Supplied 1-HP Standard Motor & Drive
Low Static Drive (1)
External Static Pressure (Inches of Water)
Trane’s factory supplied motors, in commercial equipment, are
definite purpose motors, specifically designed and tested to operate
reliably and continuously at all cataloged conditions. Using the full
horsepower range of our fan motors as shown in our tabular data
will not result in nuisance tripping or premature motor failure. Our
product’s warranty will not be affected.
For Standard Evaporator Fan Speed (RPM), reference Table PD-68.
NOTES:
Data includes pressure drop due to standard filters and wet coils
No accessories or options are included in pressure drop data.
Refer to Table PD-73 to determine additional static pressure drop due to other options/accessories.
Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
1. Field Supplied Fan Sheave AK61 required. Field Supplied Belt may be necessary.
2. Field Supplied Fan Sheave AK41 required. Field Supplied Belt may be necessary.
Trane’s factory supplied motors, in commercial equipment, are
definite purpose motors, specifically designed and tested to operate
reliably and continuously at all cataloged conditions. Using the full
horsepower range of our fan motors as shown in our tabular data
will not result in nuisance tripping or premature motor failure. Our
product’s warranty will not be affected.
.10.20.30.40.50.60.70.80.901.00
1-HP Standard Motor & Field Supplied1-HP Standard Motor & Drive
For Standard Evaporator Fan Speed (RPM), reference Table PD-68.
NOTES:
Data includes pressure drop due to standard filters and wet coils.
No accessories or options are included in pressure drop data.
Refer to Table PD-73 to determine additional static pressure drop due to other options/accessories
Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
1. Field Supplied Fan Sheave AK56 required. Field Supplied Belt may be necessary.
.10.20.30.40.50.60.70.80.901.00
1-HP Standard Motor & Field Supplied 1-HP Standard Motor & Drive
Low Static Drive (1)
External Static Pressure (Inches of Water)
Trane’s factory supplied motors, in commercial equipment, are
definite purpose motors, specifically designed and tested to operate
reliably and continuously at all cataloged conditions. Using the full
horsepower range of our fan motors as shown in our tabular data
will not result in nuisance tripping or premature motor failure. Our
product’s warranty will not be affected.
For Standard Evaporator Fan Speed (RPM), reference Table PD-68.
NOTES:
Data includes pressure drop due to standard filters and wet coils
No accessories or options are included in pressure drop data.
Refer to Table PD-73 to determine additional static pressure drop due to other options/accessories.
Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
1. Field Supplied Fan Sheave AK56 required. Field Supplied Belt may be necessary.
.10.20.30.40.50.60.70.80.901.00
External Static Pressure (Inches of Water)
Trane’s factory supplied motors, in commercial equipment, are
definite purpose motors, specifically designed and tested to operate
reliably and continuously at all cataloged conditions. Using the full
horsepower range of our fan motors as shown in our tabular data
will not result in nuisance tripping or premature motor failure. Our
product’s warranty will not be affected.
For Standard Evaporator Fan Speed (RPM), reference Table PD-68.
NOTES:
Data includes pressure drop due to standard filters and wet coils.
No accessories or options are included in pressure drop data.
Refer to Table PD-73 to determine additional static pressure drop due to other options/accessories.
1-HP Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024. 2-HP Fan Motor Heat (MBH) = 3.000 x Fan BHP+.5000
1. Field Supplied Fan Sheave AK84 and Belt AX34 required.
.10.20.30.40.50.60.70.80.901.00
External Static Pressure (Inches of Water)
Trane’s factory supplied motors, in commercial equipment, are
definite purpose motors, specifically designed and tested to operate
reliably and continuously at all cataloged conditions. Using the full
horsepower range of our fan motors as shown in our tabular data
will not result in nuisance tripping or premature motor failure. Our
product’s warranty will not be affected.
For Standard Evaporator Fan Speed (RPM), reference Table PD-68.
NOTES:
Data includes pressure drop due to standard filters and wet coils
No accessories or options are included in pressure drop data.
Refer to Table PD-73 to determine additional static pressure drop
due to other options accessories.
1-HP Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
2-HP Fan Motor Heat (MBH) = 3.000 x Fan BHP+.5000
1. Field Supplied Fan Sheave AK84 and Belt AX34 required.
.10.20.30.40.50.60.70.80.901.00
1-HP Standard Motor
& Field Supplied
Low Static Drive (1)
External Static Pressure (Inches of Water)
1-HP Standard Motor & Drive
Trane’s factory supplied motors, in commercial equipment, are
definite purpose motors, specifically designed and tested to operate
reliably and continuously at all cataloged conditions. Using the full
horsepower range of our fan motors as shown in our tabular data
will not result in nuisance tripping or premature motor failure. Our
product’s warranty will not be affected.
For Standard Evaporator Fan Speed (RPM), reference Table PD-68.
NOTES:
Data includes pressure drop due to standard filters and wet coils.
No accessories or options are included in pressure drop data.
Refer to Table PD-73 to determine additional static pressure drop due to other options/accessories
2-HP Fan Motor Heat (MBH) = 3.000 x Fan BHP+.5000
.10.20.30.40.50.60.70.80.901.00
2-HP Standard Motor & Field Supplied Low Static Drive (1) 2-HP Standard Motor & Drive
External Static Pressure (Inches of Water)
Trane’s factory supplied motors, in commercial equipment, are
definite purpose motors, specifically designed and tested to operate
reliably and continuously at all cataloged conditions. Using the full
horsepower range of our fan motors as shown in our tabular data
will not result in nuisance tripping or premature motor failure. Our
product’s warranty will not be affected.
For Standard Evaporator Fan Speed (RPM), reference Table PD-68.
NOTES:
Data includes pressure drop due to standard filters and wet coils.
No accessories or options are included in pressure drop data.
Refer to Table PD-73 to determine additional static pressure drop due to other options/accessories
2-HP Fan Motor Heat (MBH) = 3.000 x Fan BHP+.5000
.10.20.30.40.50.60.70.80.901.00
2-HP Standard Motor & Field Supplied Low Static Drive (1) 2-HP Standard Motor & Drive
External Static Pressure (Inches of Water)
Trane’s factory supplied motors, in commercial equipment, are definite purpose
motors, specifically designed and tested to operate reliably and continuously at
all cataloged conditions. Using the full horsepower range
of our fan motors as shown in our tabular data will not result in nuisance
tripping or premature motor failure. Our product’s warranty will not be
affected.
For Standard Evaporator Fan Speed (RPM), reference Table PD-68.
NOTES:
Data includes pressure drop due to standard filters and wet coils.
No accessories or options are included in pressure drop data.
Refer to Table PD-73 to determine additional static pressure drop due to other options/accessories.
2-HP Fan Motor Heat (MBH) = 2.000 x Fan BHP+.5000.
3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.4750.
1. Field Supplied Motor Sheave 1VL40L x 7/8 and Fan Sheave AK71 required.
.10.20.30.40.50.60.70.80.901.00
2-HP Standard Motor & Field Supplied Low Static Drive (1) 2-HP Standard Motor & Drive
External Static Pressure (Inches of Water)
Trane’s factory supplied motors, in commercial equipment, are
definite purpose motors, specifically designed and tested to operate
reliably and continuously at all cataloged conditions. Using the full
horsepower range of our fan motors as shown in our tabular data
will not result in nuisance tripping or premature motor failure. Our
product’s warranty will not be affected.
For Standard Evaporator Fan Speed (RPM), reference Table PD-68.
NOTES:
Data includes pressure drop due to standard filters and wet coils.
No accessories or options are included in pressure drop data.
Refer to Table PD-73 to determine additional static pressure drop due to other options/accessories.
2-HP Fan Motor Heat (MBH) = 2.000 x Fan BHP+.5000.
3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.4750.
1. Field Supplied Motor Sheave 1VL40L x 7/8 and Fan Sheave AK71 required.
.10.20.30.40.50.60.70.80.901.00
2-HP Standard Motor & Field
Supplied Low Static Drive (1)
External Static Pressure (Inches of Water)
2-HP Standard Motor & Drive
3-HP Oversized Motor
2-HP Standard Motor & High Static
Trane’s factory supplied motors, in commercial equipment, are
definite purpose motors, specifically designed and tested to operate
reliably and continuously at all cataloged conditions. Using the full
horsepower range of our fan motors as shown in our tabular data
will not result in nuisance tripping or premature motor failure. Our
product’s warranty will not be affected.
For Standard Evaporator Fan Speed (RPM), reference Table PD-68.
NOTES:
Data includes pressure drop due to stnadard filters and wet coils.
No accessories or options are included in pressure drop data.
Refer to Table PD-73 to determine additional static pressure drop due to other options/accessories
2-HP Fan Motor Heat (MBH) = 2.000 x Fan BHP+.5000.
3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.4750.
1. Field Supplied Fan Sheave AK79 and Belt AX38 required.
.10.20.30.40.50.60.70.80.901.00
2-HP Standard Motor & Field Supplied 2-HP Standard Motor
External Static Pressure (Inches of Water)
Low Static Drive (1) & Drive
Trane’s factory supplied motors, in commercial equipment, are
definite purpose motors, specifically designed and tested to operate
reliably and continuously at all cataloged conditions. Using the full
horsepower range of our fan motors as shown in our tabular data
will not result in nuisance tripping or premature motor failure. Our
product’s warranty will not be affected.
For Standard Evaporator Fan Speed (RPM), reference Table PD-68.
NOTES:
Data includes pressure drop due to standard filters and wet coils.
No accessories or options are included in pressure drop data.
Refer to Table PD-73 to determine additional static pressure drop due to other options/accessories
2-HP Fan Motor Heat (MBH) = 2.000 x Fan BHP+.5000.
3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.4750.
1. Field Supplied Fan Sheave AK79 and Belt AX38 required.
.10.20.30.40.50.60.70.80.901.00
2-HP Standard Motor & Field Supplied2-HP Standard Motor & Drive
External Static Pressure (Inches of Water)
Low Static Drive (1)
3-HP Oversized Motor & Drive
Trane’s factory supplied motors, in commercial equipment, are
definite purpose motors, specifically designed and tested to operate
reliably and continuously at all cataloged conditions. Using the full
horsepower range of our fan motors as shown in our tabular data
will not result in nuisance tripping or premature motor failure. Our
product’s warranty will not be affected.
For Standard Evaporator Fan Speed (RPM), reference Table PD-68.
NOTES:
Data includes pressure drop due to standard filters and wet coils.
No accessories or options are included in pressure drop data.
Refer to Table PD-73 to determine additional static pressure drop due to other options/accessories
3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.475. 5-HP Fan Motor Heat (MBH) = 2.950 x Fan BHP+.470.
1. Field Supplied Motor Sheave 1VM50 x 7/8”, Fan Sheave AK89 and Belt AX40 required.
.10.20.30.40.50.60.70.80.901.00
3-HP Standard Motor & Field Supplied
Low Static Drive (1)
External Static Pressure (Inches of Water)
3-HP Standard Motor & Drive
Trane’s factory supplied motors, in commercial equipment, are
definite purpose motors, specifically designed and tested to operate
reliably and continuously at all cataloged conditions. Using the full
horsepower range of our fan motors as shown in our tabular data
will not result in nuisance tripping or premature motor failure. Our
product’s warranty will not be affected.
For Standard Evaporator Fan Speed (RPM), reference Table PD-68.
NOTES:
Data includes pressure drop due to standard filters and wet coils.
No accessories or options are included in pressure drop data.
Refer to Table PD-73 to determine additional static pressure drop due to other options/accessories
3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.475. 5-HP Fan Motor Heat (MBH) = 2.950 x Fan BHP+.470.
1. Field Supplied Motor Sheave 1VM50 x 7/8”, Fan Sheave AK89 and Belt AX40 required.
.10.20.30.40.50.60.70.80.901.00
3-HP Standard Motor & Field Supplied
Low Static Drive (1)
3-HP Standard Motor & Drive
External Static Pressure (Inches of Water)
Trane’s factory supplied motors, in commercial equipment, are
definite purpose motors, specifically designed and tested to operate
reliably and continuously at all cataloged conditions. Using the full
horsepower range of our fan motors as shown in our tabular data
will not result in nuisance tripping or premature motor failure. Our
product’s warranty will not be affected.
Table PD-41— Direct Drive Evaporator Fan Performance — 3, 4, and 5 Ton — THC036A, THC048A, THC060A
External Static Pressure (Inches of Water) & Motor Power (Bhp)
UnitHigh SpeedLow SpeedHigh SpeedLow Speed
Tons Model No.CFMESPBHPESPBHPESPBHPESPBHP
3THC036A12000.550.400.290.300.740.440.650.41
Horizontal12600.510.410.190.300.700.450.610.42
4THC048A16000.600.550.440.490.940.750.680.64
Horizontal16800.510.560.320.490.890.780.590.66
5THC060A20000.740.900.450.661.031.050.810.95
Horizontal21000.640.930.300.660.941.100.680.96
3THC036A12000.600.400.340.300.790.440.700.41
Downflow12600.560.410.240.300.750.450.660.42
4THC048A16000.650.550.490.490.990.750.730.64
Downflow16800.560.560.370.490.940.780.640.66
5THC060A20000.790.900.500.661.081.050.860.95
Downflow21000.690.930.350.660.991.100.730.96
Fan motor heat (MBH) = 3.72 x Fan Bhp + .24.
Trane’s factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate
reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will
not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.
NOTE:
1. Data includes pressure drop due to wet coil and filters.
2. 5 ton oversized motor performance is with 12 x 11 FC blower wheel.
For Standard Evaporator Fan Speed (RPM), reference Table PD-68.
NOTES:
Data includes pressure drop due to standard filters and wet coils.
No accessories or options are included in pressure drop data.
Refer to Table PD-73 to determine additional static pressure drop due to other options/accessories
Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
1. Field Supplied Fan Sheave AK69 required. Field Supplied Belt may be necessary.
2. Field Supplied Fan Sheave AK41 required. Field Supplied Belt may be necessary.
.10.20.30.40.50.60.70.80.901.00
1-HP Standard Motor
& Field Supplied
Low Static Drive (1)1-HP Standard Motor & Drive
External Static Pressure (Inches of Water)
Trane’s factory supplied motors, in commercial equipment, are
definite purpose motors, specifically designed and tested to
operate reliably and continuously at all cataloged conditions.
Using the full horsepower range of our fan motors as shown in
our tabular data will not result in nuisance tripping or
premature motor failure. Our product’s warranty will not be
affected.
***MINIMUM AIR VOLUME REQUIRED FOR USE WITH OPTIONAL ELECTRIC HEAT IS 960 CFM.
NOTES:
Data includes pressure drop due to standard filters and wet coils.
Data does not include pressure drop due to reheat coil.
1 HP Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
1. BAYLSDR006A Required.
2. BAYLSDR006A Required.
.10.20.30.40.50.60.70.80.901.00
1-HP Standard Motor
& Low Static Drive
Accessory Kit (1)
External Static Pressure (Inches of Water)
1-HP Standard Motor & Low Static
Drive Accessory Kit (2)
1-HP Standard Motor & Drive
Trane’s factory supplied motors, in commercial equipment, are
definite purpose motors, specifically designed and tested to operate
reliably and continuously at all cataloged conditions. Using the full
horsepower range of our fan motors as shown in our tabular data
will not result in nuisance tripping or premature motor failure. Our
product’s warranty will not be affected.
For Standard Evaporator Fan Speed (RPM), reference Table PD-68.
NOTES:
Data includes pressure drop due to standard filters and wet coils.
No accessories or options are included in pressure drop data.
Refer to Table PD-73 to determine additional static pressure drop due to other options/accessories
Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
1. Field Supplied Fan Sheave AK69 required. Field Supplied Belt may be necessary.
2. Field Supplied Fan Sheave AK41 required. Field Supplied Belt may be necessary.
Trane’s factory supplied motors, in commercial equipment, are
definite purpose motors, specifically designed and tested to
operate reliably and continuously at all cataloged conditions.
Using the full horsepower range of our fan motors as shown in
our tabular data will not result in nuisance tripping or
premature motor failure. Our product’s warranty will not be
affected.
***MINIMUM AIR VOLUME REQUIRED FOR USE WITH OPTIONAL ELECTRIC HEAT IS 960 CFM.
NOTES:
Data includes pressure drop due to standard filters and wet coils.
Data does not include pressure drop due to reheat coil.
1 HP Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
1. BAYLSDR006A Required.
2. BAYLSDR006A Required.
.10.20.30.40.50.60.70.80.901.00
1-HP Standard Motor & Low
Static Drive Accessory Kit (1)
1-HP Standard Motor & Low
Static Drive Accessory Kit (2)
External Static Pressure (Inches of Water)
1-HP Standard Motor & Drive
Trane’s factory supplied motors, in commercial equipment, are
definite purpose motors, specifically designed and tested to
operate reliably and continuously at all cataloged conditions.
Using the full horsepower range of our fan motors as shown in
our tabular data will not result in nuisance tripping or
premature motor failure. Our product’s warranty will not be
affected.
For Standard Evaporator Fan Speed (RPM), reference Table PD-68.
NOTES:
Data includes pressure drop due to standard filters and wet coils.
No accessories or options are included in pressure drop data.
Refer to Table PD-73 to determine additional static pressure drop due to other options/accessories
Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
1. Field Supplied Fan Sheave AK61 required. Field Supplied Belt may be necessary.
.10.20.30.40.50.60.70.80.901.00
1-HP Standard Motor & Field Supplied 1-HP Standard Motor & Drive
Low Static Drive (1)
External Static Pressure (Inches of Water)
Trane’s factory supplied motors, in commercial equipment, are
definite purpose motors, specifically designed and tested to operate
reliably and continuously at all cataloged conditions. Using the full
horsepower range of our fan motors as shown in our tabular data
will not result in nuisance tripping or premature motor failure. Our
product’s warranty will not be affected.
***MINIMUM AIR VOLUME REQUIRED FOR USE WITH OPTIONAL ELECTRIC HEAT IS 1280 CFM.
NOTES:
Data includes pressure drop due to standard filters and wet coils.
Data does not include pressure drop due to reheat coil.
1 HP Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
1. BAYLSDR007A Required.
2. BAYLSDR007A Required.
.10.20.30.40.50.60.70.80.901.00
1-HP Standard Motor &
Low Static Drive
Accessory Kit (1)
External Static Pressure (Inches of Water)
1-HP Standard Motor & Low Static Drive Accessory Kit (2)
Trane’s factory supplied motors, in commercial equipment, are
definite purpose motors, specifically designed and tested to operate
reliably and continuously at all cataloged conditions. Using the full
horsepower range of our fan motors as shown in our tabular data
will not result in nuisance tripping or premature motor failure. Our
product’s warranty will not be affected.
For Standard Evaporator Fan Speed (RPM), reference Table PD-68.
NOTES:
Data includes pressure drop due to standard filters and wet coils.
No accessories or options are included in pressure drop data.
Refer to Table PD-73 to determine additional static pressure drop due to other options/accessories
Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
1. Field Supplied Fan Sheave AK61 required. Field Supplied Belt may be necessary.
2. Field Supplied Fan Sheave AK41 required. Field Supplied Belt may be necessary.
Trane’s factory supplied motors, in commercial equipment, are
definite purpose motors, specifically designed and tested to operate
reliably and continuously at all cataloged conditions. Using the full
horsepower range of our fan motors as shown in our tabular data
will not result in nuisance tripping or premature motor failure. Our
product’s warranty will not be affected.
***MINIMUM AIR VOLUME REQUIRED FOR USE WITH OPTIONAL ELECTRIC HEAT IS 1280 CFM.
NOTES:
Data includes pressure drop due to standard filters and wet coils.
Data does not include pressure drop due to reheat coil.
1 HP Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
1. BAYLSDR007A Required.
2. BAYLSDR007A Required.
.10.20.30.40.50.60.70.80.901.00
1-HP Standard Motor & Low
Static Drive Accessory Kit (1)
1-HP Standard Motor & Low Static Drive Accessory Kit (2)
External Static Pressure (Inches of Water)
1-HP Standard Motor & Drive
Trane’s factory supplied motors, in commercial equipment, are
definite purpose motors, specifically designed and tested to operate
reliably and continuously at all cataloged conditions. Using the full
horsepower range of our fan motors as shown in our tabular data
will not result in nuisance tripping or premature motor failure. Our
product’s warranty will not be affected.
For Standard Evaporator Fan Speed (RPM), reference Table PD-68.
NOTES:
Data includes pressure drop due to standard filters and wet coils.
No accessories or options are included in pressure drop data.
Refer to Table PD-73 to determine additional static pressure drop due to other options/accessories
Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
1. Field Supplied Fan Sheave AK56 required. Field Supplied Belt may be necessary.
.10.20.30.40.50.60.70.80.901.00
1-HP Standard Motor & Field Supplied 1-HP Standard Motor & Drive
Low Static Drive (1)
External Static Pressure (Inches of Water)
Trane’s factory supplied motors, in commercial equipment, are
definite purpose motors, specifically designed and tested to operate
reliably and continuously at all cataloged conditions. Using the full
horsepower range of our fan motors as shown in our tabular data
will not result in nuisance tripping or premature motor failure. Our
product’s warranty will not be affected.
***MINIMUM AIR VOLUME REQUIRED FOR USE WITH OPTIONAL ELECTRIC HEAT IS 1600 CFM.
NOTES:
Data includes pressure drop due to standard filters and wet coils.
Data does not include pressure drop due to reheat coil.
1 HP Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
1. BAYLSDR008A Required.
2. BAYLSDR008A Required.
.10.20.30.40.50.60.70.80.901.00
1-HP Standard Motor & Low
Static Drive Accessory Kit (1)
External Static Pressure (Inches of Water)
1-HP Standard Motor & Low
Static Drive Accessory Kit (2)
1-HP Standard
Motor & Drive
Trane’s factory supplied motors, in commercial equipment, are
definite purpose motors, specifically designed and tested to operate
reliably and continuously at all cataloged conditions. Using the full
horsepower range of our fan motors as shown in our tabular data will
not result in nuisance tripping or premature motor failure. Our
product’s warranty will not be affected.
For Standard Evaporator Fan Speed (RPM), reference Table PD-68.
NOTES:
Data includes pressure drop due to standard filters and wet coils.
No accessories or options are included in pressure drop data.
Refer to Table PD-73 to determine additional static pressure drop due to other options/accessories
Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
1. Field Supplied Fan Sheave AK56 required. Field Supplied Belt may be necessary.
.10.20.30.40.50.60.70.80.901.00
External Static Pressure (Inches of Water)
Trane’s factory supplied motors, in commercial equipment, are
definite purpose motors, specifically designed and tested to
operate reliably and continuously at all cataloged conditions.
Using the full horsepower range of our fan motors as shown in
our tabular data will not result in nuisance tripping or
premature motor failure. Our product’s warranty will not be
affected.
***MINIMUM AIR VOLUME REQUIRED FOR USE WITH OPTIONAL ELECTRIC HEAT IS 1600 CFM.
NOTES:
Data includes pressure drop due to standard filters and wet coils.
Data does not include pressure drop due to reheat coil.
1 HP Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
1. BAYLSDR008A Required.
2. BAYLSDR008A Required.
.10.20.30.40.50.60.70.80.901.00
1-HP Standard Motor & Low
Static Drive Accessory Kit (1)
External Static Pressure (Inches of Water)
1-HP Standard Motor & Low
Static Drive Accessory Kit (2)
1-HP Standard Motor & Drive
Trane’s factory supplied motors, in commercial equipment, are
definite purpose motors, specifically designed and tested to
operate reliably and continuously at all cataloged conditions.
Using the full horsepower range of our fan motors as shown in
our tabular data will not result in nuisance tripping or
premature motor failure. Our product’s warranty will not be
affected.
For Standard Evaporator Fan Speed (RPM), reference Table PD-68.
NOTES:
Data includes pressure drop due to standard filters and wet coils.
No accessories or options are included in pressure drop data.
Refer to Table PD-73 to determine additional static pressure drop due to other options/accessories
1-HP Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024. 2-HP Fan Motor Heat (MBH) = 3.000 x Fan BHP+.5000
1. Field Supplied Fan Sheave AK84 and Belt AX34 required.
.10.20.30.40.50.60.70.80.901.00
1-HP Standard Motor & Field Supplied1-HP Standard Motor & Drive
Low Static Drive (1)
External Static Pressure (Inches of Water)
Trane’s factory supplied motors, in commercial equipment, are
definite purpose motors, specifically designed and tested to operate
reliably and continuously at all cataloged conditions. Using the full
horsepower range of our fan motors as shown in our tabular data
will not result in nuisance tripping or premature motor failure. Our
product’s warranty will not be affected.
For Standard Evaporator Fan Speed (RPM), reference Table PD-68.
NOTES:
Data includes pressure drop due to standard filters and wet coils.
No accessories or options are included in pressure drop data.
Refer to Table PD-73 to determine additional static pressure drop due
to other options/accessories.
1-HP Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
2-HP Fan Motor Heat (MBH) = 3.000 x Fan BHP+.5000
1. Field Supplied Fan Sheave AK84 and Belt AX34 required.
2. Field Supplied Fan Sheave AK54 and Belt AX30.
.10.20.30.40.50.60.70.80.901.00
1-HP Standard Motor & Field Supplied1-HP Standard Motor & Drive
Low Static Drive (1)
External Static Pressure (Inches of Water)
Trane’s factory supplied motors, in commercial equipment,
are definite purpose motors, specifically designed and tested
to operate reliably and continuously at all cataloged
conditions. Using the full horsepower range of our fan
motors as shown in our tabular data will not result in
nuisance tripping or premature motor failure. Our product’s
warranty will not be affected.
2-HP Oversized
Motor & Drive
1-HP Standard Motor & High Static
Drive Kit (or 2-HP Oversized Motor)
For Standard Evaporator Fan Speed (RPM), reference Table PD-68.
NOTES:NOTES:
NOTES:
NOTES:NOTES:
Data includes pressure drop due to standard filters and wet coils.
No accessories or options are included in pressure drop data.
Refer to Table PD-73 to determine additional static pressure drop due to other options/accessories
2-HP Fan Motor Heat (MBH) = 2.000 x Fan BHP+.5000.
3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.4750
1. Field Supplied Fan Sheave AK79 and Belt AX38 required.
.10.20.30.40.50.60.70.80.901.00
External Static Pressure (Inches of Water)
2-HP Standard Motor & Drive
Trane’s factory supplied motors, in commercial equipment, are
definite purpose motors, specifically designed and tested to operate
reliably and continuously at all cataloged conditions. Using the full
horsepower range of our fan motors as shown in our tabular data will
not result in nuisance tripping or premature motor failure. Our
product’s warranty will not be affected.
***MINIMUM AIR VOLUME REQUIRED FOR USE WITH OPTIONAL ELECTRIC HEAT IS 2400 CFM.
NOTES:
Data includes pressure drop due to standard filters and wet coils.
Data does not include pressure drop due to reheat coil.
1 HP Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
1. BAYLSDR009A Required.
2. BAYLSDR009A Required.
.10.20.30.40.50.60.70.80.901.00
2-HP Standard Motor & Low Static Drive
Accessory Kit (1)
External Static Pressure (Inches of Water)
Trane’s factory supplied motors, in commercial equipment, are
definite purpose motors, specifically designed and tested to operate
reliably and continuously at all cataloged conditions. Using the full
horsepower range of our fan motors as shown in our tabular data
will not result in nuisance tripping or premature motor failure. Our
product’s warranty will not be affected.
For Standard Evaporator Fan Speed (RPM), reference Table PD-68.
NOTES:NOTES:
NOTES:
NOTES:NOTES:
Data includes pressure drop due to standard filters and wet coils.
No accessories or options are included in pressure drop data.
Refer to Table PD-73 to determine additional static pressure drop due to other options/accessories
2-HP Fan Motor Heat (MBH) = 2.000 x Fan BHP+.5000.
3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.4750
1. Field Supplied Fan Sheave AK79 and Belt AX38 required..
.10.20.30.40.50.60.70.80.901.00
2-HP Standard Motor & Field Supplied
Low Static Drive (1)
External Static Pressure (Inches of Water)
2-HP Standard Motor & Drive
Trane’s factory supplied motors, in commercial equipment, are definite purpose
motors, specifically designed and tested to operate reliably and continuously at
all cataloged conditions. Using the full horsepower range of our fan motors as
shown in our tabular data will not result in nuisance tripping or premature motor
failure. Our product’s warranty will not be affected.
***MINIMUM AIR VOLUME REQUIRED FOR USE WITH OPTIONAL ELECTRIC HEAT IS 2400 CFM.
NOTES:
Data includes pressure drop due to standard filters and wet coils.
Data does not include pressure drop due to reheat coil.
1 HP Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
1. BAYLSDR009A Required.
2. BAYLSDR009A Required.
.10.20.30.40.50.60.70.80.901.00
2-HP Standard Motor & Low
Static Drive Accessory Kit (1)
Trane’s factory supplied motors, in commercial equipment, are
definite purpose motors, specifically designed and tested to operate
reliably and continuously at all cataloged conditions. Using the full
horsepower range of our fan motors as shown in our tabular data
will not result in nuisance tripping or premature motor failure. Our
product’s warranty will not be affected.
External Static Pressure (Inches of Water)
2-HP Standard Motor & Low Static Drive Accessory Kit (2)
For Standard Evaporator Fan Speed (RPM), reference Table PD-68.
NOTES:
Data includes pressure drop due to standard filters and wet coils.
No accessories or options are included in pressure drop data.
Refer to Table PD-73 to determine additional static pressure drop due to other options/accessories
2-HP Fan Motor Heat (MBH) = 2.000 x Fan BHP+.5000.
3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.4750
1. Field Supplied Fan Sheave AK79 and Belt AX38 required.
.10.20.30.40.50.60.70.80.901.00
2-HP Standard Motor & Field Supplied
External Static Pressure (Inches of Water)
Low Static Drive (1)
2-HP Standard Motor & Drive
Trane’s factory supplied motors, in commercial equipment, are definite purpose
motors, specifically designed and tested to operate reliably and continuously at
all cataloged conditions. Using the full horsepower range of our fan motors as
shown in our tabular data will not result in nuisance tripping or premature
motor failure. Our product’s warranty will not be affected.
***MINIMUM AIR VOLUME REQUIRED FOR USE WITH OPTIONAL ELECTRIC HEAT IS 2720 CFM.
NOTES:
Data includes pressure drop due to standard filters and wet coils.
Data does not include pressure drop due to reheat coil.
1 HP Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
1. BAYLSDR009A Required.
2. BAYLSDR009A Required.
.10.20.30.40.50.60.70.80.901.00
2-HP Standard Motor & Low Static Drive
Accessory Kit (1)
External Static Pressure (Inches of Water)
Trane’s factory supplied motors, in commercial
equipment, are definite purpose motors,
specifically designed and tested to operate reliably
and continuously at all cataloged conditions. Using
the full horsepower range of our fan motors as
shown in our tabular data will not result in nuisance
tripping or premature motor failure. Our product’s
warranty will not be affected.
For Standard Evaporator Fan Speed (RPM), reference Table PD-68.
NOTES:
Data includes pressure drop due to standard filters and wet coils.
No accessories or options are included in pressure drop data.
Refer to Table PD-73 to determine additional static pressure drop due to other options/accessories
2-HP Fan Motor Heat (MBH) = 2.000 x Fan BHP+.5000.
3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.4750
1. Field Supplied Fan Sheave AK79 and Belt AX38 required.
.10.20.30.40.50.60.70.80.901.00
2-HP Standard Motor & Field Supplied
2-HP Standard Motor & Drive3-HP Oversized Motor & Drive
Low Static Drive (1)
External Static Pressure (Inches of Water)
Trane’s factory supplied motors, in commercial equipment, are definite purpose
motors, specifically designed and tested to operate reliably and continuously at
all cataloged conditions. Using the full horsepower range of our fan motors as
shown in our tabular data will not result in nuisance tripping or premature
motor failure. Our product’s warranty will not be affected.
***MINIMUM AIR VOLUME REQUIRED FOR USE WITH OPTIONAL ELECTRIC HEAT IS 2720 CFM.
NOTES:
Data includes pressure drop due to standard filters and wet coils.
Data does not include pressure drop due to reheat coil.
1 HP Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
1. BAYLSDR009A Required.
2. BAYLSDR009A Required.
.10.20.30.40.50.60.70.80.901.00
2-HP Standard Motor & Field Supplied
Low Static Drive Accessory Kit (1)
External Static Pressure (Inches of Water)
2-HP Standard Motor & Field Supplied
Low Static Drive Accessory Kit (1)
2-HP Oversize Motor & Drive
Trane’s factory supplied motors, in commercial equipment, are
definite purpose motors, specifically designed and tested to operate
reliably and continuously at all cataloged conditions. Using the full
horsepower range of our fan motors as shown in our tabular data
will not result in nuisance tripping or premature motor failure. Our
product’s warranty will not be affected.
3-HP Standard Motor & Field Supplied Low Static Drive (1)
3200————————7341.037701.178041.318391.458711.60901 1.74
3600————7141.027491.147821.278151.418471.578791.73909 1.899392.04
4000——7341.167681.308031.448341.588631.728941.879232.04952 2.21979 2.39
44007641.367951.498251.638571.798881.959162.109432.259702.41997 2.591024 2.78
48008281.748571.888842.029132.189422.369702.539962.7010212.861045 3.031070 3.22
For Standard Evaporator Fan Speed (RPM), reference Table PD-68.
NOTES:
Data includes pressure drop due to standard filters and wet coils.
No accessories or options are included in pressure drop data.
Refer to Table PD-73 to determine additional static pressure drop due to other options/accessories
3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.475.
5-HP Fan Motor Heat (MBH) = 2.950 x Fan BHP+.470.
1. Field Supplied Motor Sheave 1VM50 x 7/8 inch, Fan Sheave AK89, and Belt AX40 required.
.10.20.30.40.50.60.70.80.901.00
External Static Pressure (Inches of Water)
3-HP Standard Motor & Drive
Trane’s factory supplied motors, in commercial equipment, are
definite purpose motors, specifically designed and tested to operate
reliably and continuously at all cataloged conditions. Using the full
horsepower range of our fan motors as shown in our tabular data
will not result in nuisance tripping or premature motor failure. Our
product’s warranty will not be affected.
***MINIMUM AIR VOLUME REQUIRED FOR USE WITH OPTIONAL ELECTRIC HEAT IS 3200 CFM.
NOTES:
Data includes pressure drop due to standard filters and wet coils.
Data does not include pressure drop due to reheat coil.
3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.475.
1. BAYLSDR010A Required.
2. BAYLSDR010A Required.
.10.20.30.40.50.60.70.80.901.00
External Static Pressure (Inches of Water)
3-HP Standard Motor & Low
Static Drive Accessory Kit (1)
3-HP Standard Motor & Low
Static Drive Accessory Kit (2)
Trane’s factory supplied motors, in commercial equipment,
are definite purpose motors, specifically designed and tested
to operate reliably and continuously at all cataloged
conditions. Using the full horsepower range of our fan motors
as shown in our tabular data will not result in nuisance
tripping or premature motor failure. Our product’s warranty
will not be affected.
For Standard Evaporator Fan Speed (RPM), reference Table PD-68.
NOTES:
Data includes pressure drop due to standard filters and wet coils.
No accessories or options are included in pressure drop data.
Refer to Table PD-73 to determine additional static pressure drop due to other options/accessories
3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.475.
5-HP Fan Motor Heat (MBH) = 2.950 x Fan BHP+.470.
1. Field Supplied Motor Sheave 1VM50 x 7/8 inch, Fan Sheave AK89, and Belt AX40 required
.10.20.30.40.50.60.70.80.901.00
External Static Pressure (Inches of Water)
3-HP Standard Motor & Drive
5-HP Oversized Motor & Drive
Trane’s factory supplied motors, in commercial equipment, are
definite purpose motors, specifically designed and tested to operate
reliably and continuously at all cataloged conditions. Using the full
horsepower range of our fan motors as shown in our tabular data
will not result in nuisance tripping or premature motor failure. Our
product’s warranty will not be affected.
***MINIMUM AIR VOLUME REQUIRED FOR USE WITH OPTIONAL ELECTRIC HEAT IS 3200 CFM.
NOTES:
Data includes pressure drop due to standard filters and wet coils.
Data does not include pressure drop due to reheat coil.
3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.475.
1. BAYLSDR010A Required.
2. BAYLSDR010A Required.
.10.20.30.40.50.60.70.80.901.00
3-HP Standard Motor & Low
Static Drive Accessory Kit (1)
External Static Pressure (Inches of Water)
3-HP Standard Motor & Low
Static Drive Accessory Kit (2)
Trane’s factory supplied motors, in commercial equipment, are definite
purpose motors, specifically designed and tested to operate reliably and
continuously at all cataloged conditions. Using the full horsepower
range of our fan motors as shown in our tabular data will not result in
nuisance tripping or premature motor failure. Our product’s warranty
will not be affected.
For minimum design airflow, see airflow performance table for each unit.
To calculate temp rise at different air flow, use the following formula: Temp. rise across Electric Heater =
NOTE:
1. Minimum allowable aiflow with a 17.4 or 17.6 KW heater is 1440 cfm.
Single PhaseThree PhaseSingle PhaseThree PhaseSingle PhaseThree Phase
1
kW x 3414
1.08 x CFM
2000 CFM
Table PD-77 — 6-10 Tons Air Temperature Rise Across Electric Heaters (Degrees F)
For minimum design airflow, see airflow performance table for each unit.
To calculate temp rise at different air flow, use the following formula: Temp. rise across Electric Heater =
NOTE:
1. Minimum allowable aiflow with a 17.4 or 17.6 KW heater is 1440 cfm.
T#C090A3, A4, AW
kW x 3414
1.08 x CFM
1
4000 CFM
57RT-PRC005-EN
Performance
Data
Table PD-78— Hot Gas Reheat Temperature Rise
TonsSCFM35404550556065
396017.617.317.016.616.215.815.5
TonsSCFM35404550556065
4144017.917.717.417.116.916.516.2
TonsSCFM35404550556065
5160020.320.119.919.719.519.319.0
TonsSCFM35404550556065
7½240016.717.318.018.719.320.120.9
TonsSCFM35404550556065
8½272016.617.418.218.919.720.321.0
TonsSCFM35404550556065
10320018.719.520.321.222.022.723.4
NOTES:
1. Temperature rise does not account for indoor fan heat.
2. 70 deg OD Ambient Temperature.
3. For units with the Dehumidification (Hot Gas Reheat) option.
Zone Sensors are the building
occupant’s comfort control devices for
Precedent™ units with the Micro control:
Manual Changeover — Heat, Cool or Off
System Switch. Fan Auto or Off Switch.
One temperature
setpoint lever.
Manual/Automatic Changeover —
Auto, Heat, Cool or Off System Switch.
Fan Auto or Off Switch. Two temperature
setpoint levers.
Optional Status
Indication LED
lights, System On,
Heat, Cool, or
Service.
Remote Sensor — Sensor(s) available
for all zone sensors to provide remote
sensing capabilities.
Integrated ComfortTM System —
Sensor(s) available with optional
temperature adjustment and override
buttons to provide
central control
through a Trane
Integrated
Comfort
Dual Thermistor Remote Zone Sensor
This sensor will allow the customer to
reduce the total number of remote
sensors to obtain space temperature
averaging. This sensor should be utilized
with ReliaTel controls.
Digital Display Zone Sensor
The Digital LCD (Liquid Crystal Display)
zone sensor has the look and functionality
of standard zone
sensors. This sensor
includes a digital
display of set point
adjustment and
space temperature
in F (Fahrenheit) or C
(Celsius). Includes
FAN and SYSTEM
buttons (supports
the service functions
of the standard
sensor). E-squared
memory stores last
programmed set points. Requires 24 VAC
(Volts AC). This sensor should be utilized
with ReliaTel™ controls.
TM
system.
Programmable Night Setback — Auto
or manual changeover with seven-day
programming. Keyboard selection of
Heat, Cool, Fan, Auto, or On. All
programmable sensors have System On,
Heat, Cool, Service LED/indicators as
standard. Night Setback Sensors have
one (1) Occupied, one (1) Un-occupied,
and two (2) Override programs per day.
Humidity Sensor — Field installed,
wall-mounted or duct-mounted humidity
sensor is used to control activation of the
hot gas reheat
dehumidification
option. The
humidity sensor
can be set for
humidity levels
between 40% and
60% relative
humidity by
adjusting the
ReliaTel Options
Module.
CO
Sensing — The CO2 sensor shall
2
have the ability to to monitor space
occupancy levels within the building by
measuring the parts per million of CO
(Carbon Dioxide) in the air. As the CO
levels increase,
the outside air
damper
modulates to
meet the CO
space ventilation
requirements.
The CO
accessory shall
be available as
field installed.
2
2
2
2
59RT-PRC005-EN
Zone
Controls
Electromechanically Controlled
Units
Conventional Thermostats are the
building occupant’s comfort control
devices for electromechanically
controlled units.
Manual Changeover — One Heat, One
Cool Thermostat.
Heat, Cool or Off
System Switch.
Fan Auto or On
Switch. Set Point
Dial. Adjustable
Heat Anticipator.
Automatic
Changeover — One Heat, Two Cool
Thermostat. Off, Auto System Switch.
Auto/On Fan Switch.
80
70
90
60
TM
60
90
70
80
HEAT
50 60 70 80
FAN
50 60 70 80
AUTO ON
50 60 70 80
OFF AUTO
COOL
TM
Programmable Electronic Night Setback
Thermostat — Heating setback and
cooling setup with 7-day, 5-1-1
programming
capability.
Available in two
heating/cooling or
one heating/
cooling versions
with automatic
changeover.
For specific wiring information, see the installation instructions.
All wiring except power wires is low voltage.
All customer supplied wiring to be copper and must conform to applicable electrical codes (such as NEC or CEC) and local electrical codes. Wiring shown dotted is to be
furnished and installed by the customer.
Table W-2 — Factory-installed Options Net Weights (Lbs)
Accessory3-5 Tons6-10 Tons
Economizer2636
Barometric Relief710
Powered Exhaust—80
Motorized Outside Air Damper2030
Manual Outside Air Damper1626
Roof Curb70115
Oversized Motor58
Belt Drive Motor31—
Smoke Detector, Return77
Smoke Detector, Supply55
Coil Guards1220
Hinged Doors1012
Powered Convenience Outlet3838
Through the Base Electrical813
Electric Heaters1530
Unit Mounted Circuit Breaker55
Unit Mounted Disconnect55
Novar Control88
Dehumidification (Hot Gas Reheat) Coil1525
NOTES:
1.Weights for options not listed are < 5 lbs.
2.Net weight should be added to unit weight when ordering factory-installed
accessories.
Net Weight
1,2
84RT-PRC005-EN
Mechanical
Specifications
General
The units shall be convertible airflow.
The operating range shall be between
115°F and 0°F in cooling as standard
from the factory for units with
microprocessor controls. Operating
range for units with electromechanical
controls shall be between 115°F and
40°F. Cooling performance shall be
rated in accordance with ARI testing
procedures. All units shall be factory
assembled, internally wired, fully
charged with R-22, and 100 percent run
tested to check cooling operation, fan
and blower rotation, and control
sequence before leaving the factory.
Wiring internal to the unit shall be
colored and numbered for simplified
identification. Units shall be UL listed
and labeled, classified in accordance to
UL 1995/CAN/CSA No. 236-M90 for
Central Cooling Air Conditioners.
Canadian units shall be CSA Certified.
Casing
Unit casing shall be constructed of zinc
coated, heavy gauge, galvanized steel.
Exterior surfaces shall be cleaned,
phosphatized, and finished with a
weather-resistant baked enamel finish.
Unit’s surface shall be tested 1000
hours in a salt spray test in compliance
with ASTM B117. Cabinet construction
shall allow for all maintenance on one
side of the unit. Service panels shall
have lifting handles and be removed
and reinstalled by removing only a
single fastener while providing a water
and air tight seal. All exposed vertical
panels and top covers in the indoor air
section shall be insulated with a
cleanable foil-faced, fire-retardent
permanent, odorless glass fiber
material. The base of the unit shall be
insulated with 1/2 inch, 1 pound density
foil-faced, closed-cell material. All
insulation edges shall be either
captured or sealed.The unit’s base pan
shall have no penetrations within the
perimeter of the curb other than the
raised 1
return openings to provide an added
water integrity precaution, if the
condensate drain backs up. The base of
the unit shall have provisions for forklift
and crane lifting, with forklift
capabilities on three sides of the unit.
1
/8 inch high downflow supply/
Unit Top
The top cover shall be one piece
construction or where seams exist, it
shall be double-hemmed and gasketsealed. The ribbed top adds extra
strength and prevents water from
pooling on unit top.
Filters
One inch, throwaway filters shall be
standard on all 3-5 ton units. The filter
rack can be converted to two inch
capability. Two inch filters shall be factory
supplied on all 6-10 ton units. Optional 2inch pleated filters shall be available.
Compressors
All 3 ton standard units shall have directdrive, hermetic, reciprocating type
compressors. The reciprocating type
compressors have a centrifugal oil pump
providing positive lubrication to moving
parts. Motor shall be suction gas-cooled
and shall have a voltage utilization range
of plus or minus 10 percent of unit
nameplate voltage. Crankcase heater,
internal temperature, and currentsensitive motor overloads shall be
included for maximum protection.
Compressors shall have internal spring
isolation and sound muffling to minimize
vibration transmission and noise. Low
pressure switches shall be standard.
3 ton high efficiency and 4-10 ton
standard and high efficiency units shall
have direct-drive, hermetic, scroll type
compressors with centrifugal type oil
pumps. Motor shall be suction gascooled and shall have a voltage
utilization range of plus or minus 10
percent of unit nameplate voltage.
Internal overloads shall be provided with
the scroll compressors. Crankcase
heaters shall be included on 7½ ton
standard efficiency units.
Refrigerant Circuits
Each refrigerant circuit offers a choice of
independent fixed orifice expansion
devices or thermal expansion valve.
Service pressure ports, and refrigerant
line filter driers are factory-installed as
standard. An area shall be provided for
replacement suction line driers.
Evaporator and Condenser Coils
Internally finned, 5/16” copper tubes
mechanically bonded to a configured
aluminum plate fin shall be standard.
Coils shall be leak tested at the factory to
ensure the pressure integrity. The
evaporator coil and condenser coil shall
be leak tested to 200 psig and pressure
tested to 450 psig. The condenser coil
shall have a patent pending 1 + 1 + 1
hybrid coil designed with slight gaps for
ease of cleaning. A removeable,
reversible, double-sloped condensate
drain pan with provision for through the
base condensate drain is standard.
Outdoor Fans
The outdoor fan shall be direct-drive,
statically and dynamically balanced,
draw-through in the vertical discharge
position. The fan motor shall be
permanently lubricated and shall have
built-in thermal overload protection.
Indoor Fan
All 3-5 ton 3-phase units offer a choice of
direct-drive, FC, centrifugal fans or belt
driven, FC centrifugal fans with
adjustable motor sheaves. 3-5 ton direct
drive oversized motors shall be available
for high static operations. All 6-10 ton
units shall have belt drive motors with
an adjustable idler-arm assembly for
quick-adjustment to fan belts and motor
sheaves. All motors shall be thermally
protected. All indoor fan motors meet
the U.S. Energy Policy Act of 1992
(EPACT).
85RT-PRC005-EN
Mechanical
Specifications
Controls
Unit shall be completely factory-wired
with necessary controls and contactor
pressure lugs or terminal block for power
wiring. Unit shall provide an external
location for mounting a fused disconnect
device.
A choice of microprocessor or
electromechanical controls shall be
available.
Microprocessor controls provide for all 24
volt control functions. The resident control
algorithms shall make all heating, cooling,
and/or ventilating decisions in response
to electronic signals from sensors
measuring indoor and outdoor
temperatures. The control algorithm
maintains accurate temperature control,
minimizes drift from set point, and
provides better building comfort. A
centralized Microprocessor shall provide
anti-short cycle timing and time delay
between compressors to provide a
higher level of machine protection.
24-volt electromechanical control circuit
shall include control transformer and
contactor pressure lugs for power wiring.
Units shall have single point power entry
as standard.
Accessories/Options
Electric Heaters
Factory or field-installed electric heat
modules shall be available for installation
within basic unit. Electric heater elements
shall be constructed of heavy-duty nickel
chromium elements internally delta
connected for 240 volt, wye connected
for 480 and 600 volt. Staging shall be
achieved through the unitary control
processor (UCP). Each heater package
shall have automatically reset high limit
control operating through heating
element contactors. All heaters shall be
individually fused from the factory, where
required, and shall meet all NEC and CEC
requirements when properly installed.
Power assemblies shall provide singlepoint connection. Electric heat modules
shall be UL listed or CSA certified.
Roof Curb
The roof curb shall be designed to mate
with the unit’s downflow supply and
return and provide support and a water
tight installation when installed properly.
The roof curb design shall allow fieldfabricated rectangular supply/return
ductwork to be connected directly to the
curb. Curb design shall comply with
NRCA requirements. Curb shall be
shipped knocked down for field assembly
and shall include wood nailer strips.
Economizer
This accessory shall be either field or
factory-installed and shall be available
with or without barometric relief. The
assembly includes fully modulating 0-100
percent motor and dampers, minimum
position setting, preset linkage, wiring
harness with plug, spring return actuator
and fixed dry bulb control. The barometric
relief shall provide a pressure operated
damper that shall be gravity closing and
shall prohibit entrance of outside air
during the equipment “off” cycle.
Optional solid state or differential
enthalpy control shall be available for
either factory or field installation. The
factory-installed economizer arrives in
the shipping position and shall be moved
to the operating position by the installing
contractor.
Powered Exhaust
The field installed powered exhaust,
available for 6-10 ton units, shall provide
exhaust of return air, when using an
economizer, to maintain better bulding
pressurization.
Remote Potentiometer
The minimum position setting of the
economizer shall be adjusted with this
accessory.
Manual Outside Air Damper
Factory or field-installed rain hood and
screen shall provide up to 50 percent
outside air.
Motorized Outside Air Dampers
Factory or field-installed manually set
outdoor air dampers shall provide up to
50 percent outside air. Once set, outdoor
air dampers shall open to set position
when indoor fan starts. The damper shall
close to the full closed position when
indoor fan shuts down.
86RT-PRC005-EN
Mechanical
Specifications
Discharge Air Sensing
This factory or field-installed option
provides true discharge air sensing in
heating models. This sensor is a status
indicator readable through Tracer™ or
Tracker™. This option is available for
microprocessor controlled units.
Oversized Motors
Factory or field-installed direct drive
oversized motors shall be available for
high static applications.
Through the Base Electrical Access
An electrical service entrance shall be
factory provided allowing electrical
access for both control and main power
connections inside the curb and through
the base of the unit. Option will allow for
field installation of liquid-tight conduit and
an external field-installed disconnect
switch.
Through the Base Electrical with
Disconnect Switch
Factory-installed 3-pole, molded case,
disconnect switch with provisions for
through the base electrical connections
are available. The disconnect switch will
be installed in the unit in a water tight
enclosure with access through a swinging
door. Factory wiring will be provided from
the switch to the unit high voltage
terminal block. The switch will be UL/CSA
agency recognized. Note: The disconnect
switch will be sized per NEC and UL
guidelines but will not be used in place of
unit overcurrent protection.
Through the Base Electrical with Circuit
Breaker
This option is a factory-installed, thermal
magnetic, molded case, HACR Circuit
Breaker with provisions for through the
base electrical connections. The circuit
breaker will be installed in a water tight
enclosure in the unit with access through
a swinging door. Factory wiring will be
provided from the switch to the unit high
voltage terminal block. The circuit breaker
will provide overcurrent protection, be
sized per NEC and UL guidelines, and be
agency recognized by UL/CSA.
Powered or Unpowered Convenience
Outlet
This factory-installed option is a GFCI,
120v/15amp, 2 plug, convenience outlet,
either powered or unpowered. When the
convenience outlet is powered, a service
receptacle disconnect will be available.
The convenience outlet is powered from
the line side of the disconnect or circuit
breaker, and therefore will not be affected
by the position of the disconnect or circuit
breaker. This option can only be ordered
when the Through the Base Electrical with
either the Disconnect Switch or Circuit
Breaker option is ordered.
Phase Monitor
Phase monitor shall provide 100%
protection for motors and compressors
against problems caused by phase loss,
phase imbalance, and phase reversal.
Phase monitor is equipped with an LED
that provides an ON or FAULT indicator.
Clogged Filter/Fan Failure Switch
A dedicated differential pressure switch is
available, factory-installed, to achieve
active fan failure indication and/or
clogged filter indication. These indications
will be registered with either a zone
sensor with status indication lights or an
Integrated Comfort™ System. This option
is available for microprocessor controlled
units.
Reference or Comparative Enthalpy
Factory-installed Reference or
Comparative Enthalpy option shall be
available when a factory-installed
Economizer is ordered. This option is
available for microprocessor controlled
units.
High Pressure Cutout
This factory-installed option is offered for
units that do not have High Pressure
cutout as standard. All 3-phase units with
scroll compressors include High Pressure
Cutout as standard.
Hinged Access Doors
Sheet metal hinges are available factoryinstalled on the Filter/Evaporator, Supply
Fan/Heat, and the Compressor/Control
Access Doors.
87RT-PRC005-EN
Mechanical
Specifications
Supply and/or Return Air Smoke
Detector
With this option factory-installed, if smoke
is detected, all unit operation will be shut
down. Reset will be manual at the unit.
Return Air Smoke Detectors require
minimum allowable airflow when used
with certain models. See the Installation,
Operation, and Maintenance (IOM)
manual for the models affected and the
minimum allowable airflow required. This
option is available for microprocessor
controlled units.
Black Epoxy Coated Condenser Coil
The coil provides corrosion protection to
condenser coils for seacoast application.
The protection is a factory-applied
thermoset vinyl coating, bonded to
normal aluminum fin stock. The uniform
thickness of the bonded vinyl layer
exhibits excellent corrosion protection in
salt spray tests performed in accordance
with ASTM B117.
Dehumidification Option
The dehumidification (hot gas reheat)
option shall be a factory-installed option
that provides increased dehumidification.
The option shall consist of a hot-gas
reheat coil located on the leaving air side
of the evaporator coil prepiped and
circuited.
The option shall be equipped with
crankcase heater(s), low pressure
switch(es), Frostat™, and a thermostatic
expansion valve(s) (TXV) as standard.
Control Options
Trane Communication Interface
This factory or field-installed option shall
be provided to interface microprocessor
controlled units with the Trane Integrated
Comfort
LonTalk® Communication Interface
This factory or field-installed option shall
be provided to allow the unit to
communicate as a Tracer™LCI-R device
or directly with generic LonTalk Network
Building Automation System Controls.
TM
systems.
Zone Sensor
This field-installed control shall be
provided to interface with the Micro
equipped units and shall be available in
either manual, automatic programmable
with night setback, with system
malfunction lights, or remote sensor
options.
Thermostat
Two stage heating and cooling operation
or one stage heating and cooling shall be
available, for field installation, in either
manual or automatic changeover.
Automatic programmable electronic with
night set back shall also be available.
Differential Pressure Switches
These factory or field-installed sensors
allow individual fan failure and dirty filter
indication for microprocessor controlled
units. The fan failure switch will disable all
unit functions and “flash” the Service
LED on the zone sensor. The dirty filter
switch will light the Service LED on the
zone sensor and will allow continued unit
operation.
Enthalpy Control
Replaces the dry bulb control with a wet
bulb changeover controller which has a
fully adjustable set point. Enthalpy control
offers a higher level of comfort control,
along with energy savings potential, than
the standard dry bulb control. This is due
to the additional wet bulb sensing
capability. This option shall be available
for microprocessor controlled units. It can
be field-installed, or factory-installed with
the factory-installed economizer.
Differential Enthalpy
Replaces the standard dry bulb control
with two enthalpy sensors that compare
total heat content of the indoor air and
outdoor air to determine the most
efficient air source. This control option
offers the highest level of comfort control,
plus energy efficiency, available. This
option shall be available for
microprocessor controlled units. It can be
field-installed, or factory-installed with the
factory-installed economizer.
88RT-PRC005-EN
Mechanical
Specifications
Low Ambient Cooling
All microprocessor units shall have
cooling capabilities down to 0°F as
standard. Electromechanical models
have cooling capabilites to 40°F as built,
or to 0°F by adding the optional low
ambient (frostat) control.
Thermal Expansion Valve
All units shall have a short orifice
refrigerate control metering device. For
more exact refrigerant flow, when using
unit in low airflow applications, a Thermal
Expansion Valve option shall be available.
Novar Unit Controls
Optional Novar rooftop unit controls shall
be factory installed and tested. The
Novar electronic thermostat module will
interface to the unit microprocesser and
will control the unit to the desired stage of
cooling or heating.
Novar Return Air Sensor
This option, when used in conjunction
with Novar Controls, will contain a factory
provided and wired zone temperature
sensor located in the return air stream.
CO
Sensing
2
The CO2 sensor shall have the ability to
monitor space occupancy levels within
the building by measuring the parts per
million of CO
As the CO
damper modulates to meet the CO
space ventilation requirements. The CO
accessory shall be available as field
installed.
Ventilation Override Accessory
With the Ventilation Override Accessory
installed, the unit can be set to transition
up to 3 different pre-programmed
sequences for Smoke Purge,
Pressurization, and Exhaust. The
transition occurs when a binary input on
the RTOM is closed (shorted). This would
typically be a hard wired relay output
from a smoke detector or fire control
panel. The ventilation override accessory
shall be available as field installed.
(Carbon Dioxide) in the air.
2
levels increase, the outside air
2
2
2
Digital Display Zone Sensor
The Digital LCD (Liquid Crystal Display)
zone sensor has the look and functionality
of standard zone sensors. This sensor
includes a digital display of set point
adjustment and space temperature in F
(Fahrenheit) or C (Celsius). Includes FAN
and SYSTEM buttons (supports the
service functions of the standard sensor).
E-squared memory stores last
programmed set points. Requires 24 VAC
(Volts AC). This sensor should be utilized
with ReliaTel™ controls.
Dual Thermistor Remote Zone Sensor
This sensor will allow the customer to
reduce the total number of remote
sensors to obtain space temperature
averaging. This sensor should be utilized
with ReliaTel controls.
Humidity Sensor
Field installed, wall-mounted humidity
sensor is used to control activation of the
hot gas reheat dehumidification option.
The humidity sensor can be set for
humidity levels between 40% and 60%
relative humidity by adjusting the ReliaTel
Options Module.
Humidity Sensor
Field installed, duct-mounted humidity
sensor is used to control activation of the
hot gas reheat dehumidification option.
The humidity sensor can be set for
humidity levels between 40% and 60%
relative humidity by adjusting the ReliaTel
Options Module.
89RT-PRC005-EN
90RT-PRC005-EN
91RT-PRC005-EN
*High Efficiency Units only
Trane
A business of American Standard Companies
www.trane.com
For more information contact your local dealer
(distributor), local district office, or e-mail us at
comfort@trane.com
Literature Order Number
File Number
Supersedes
Stocking Location
RT-PRC005-EN
PL-UN-RT-TSC/THC 3-10 TONS-PRC005-EN-2-04
PL-UN-RT-TSC/THC 3-10 TONS-PRC005-EN-12-03
06-03 Webb/Mason 2-04 Electronic Only
Trane has a policy of continuous product and product data improvement and reserves the right to change design
and specifications without notice.