Trane 100, XV 90, 80, 120R9V User Manual

Upflow/Horizontal Two-stage Condensing Gas-Fired Furnace
XV 90
TUY060,080,100,120R9V Variable Speed Blower Variable Speed Inducer
PUB. NO. 22-1682-05-0802 (EN)
General Features
NATURAL GAS MODELS
Central heating furnace designs are certified by the International Approval Services (IAS) for both natural and L.P. gas. Limit setting and rating data were established and approved under standard rating conditions using American National Standards Institute standards.
SAFE OPERATION
The Integrated System Control has solid state devices, which continuously monitor for presence of flame, when the system is in the heating mode of operation. Dual solenoid combination gas valve and regulator provide extra safety.
QUICK HEATING
Durable, cycle tested, heavy gauge
aluminized steel heat exchanger
quickly transfers heat to provide warm conditioned air to the structure. Low energy power vent blower, to increase efficiency and provide a positive discharge of gas fumes to the outside.
BURNERS
Multi-port In-shot burners will give years of quiet and efficient service. All models can be converted to L.P. gas without changing burners.
INTEGRATED SYSTEM CONTROL
Exclusively designed operational program provides total control of furnace limit sensors, blowers, gas valve, flame control and includes self diagnostics for ease of service. Also contains connection points for E.A.C./humidifier.
CONDENSATE DRAIN
Built-in trap which can drain from either side when the furnace is installed upflow.
AIR DELIVERY
The variable speed, direct drive blower motor, has sufficient airflow for most heating and cooling requirements, will switch from heating to cooling speeds on demand from room thermostat. The blower door safety switch will prevent or terminate furnace operation when the blower door is removed.
SECONDARY HEAT EXCHANGER
The XV 90 has a special type 29-4C™ stainless steel secondary heat exchanger to reclaim heat from flue gases which would normally be lost outside.
STYLING Heavy gauge steel and “wrap-around” cabinet construction is used in the
cabinet with baked-on enamel finish for strength and beauty. The heat exchanger section of the cabinet is completely lined with foil faced fiberglass insulation. This results in quiet and efficient operation due to the excellent acoustical and insulating qualities of fiberglass. Built-in bottom pan and alternate bottom, left or right side return air connection in vertical position.
FEATURES AND GENERAL OPERATION
The XV 90 High Efficiency Gas Furnaces employ a Hot Surface Ignition system, which eliminates the waste of a constant burning pilot. The integrated system control lights the main burners upon a demand for heat from the room thermostat. Complete front service access.
a. Low energy power venter. b. Vent proving differential switch.
© 2002 American Standard Inc. All Rights Reserved
2 Pub. No. 22-1682-05-0802 (EN)
Contents
Feature Summary
Features and Benefits
Standard Equipment Optional Equipment
General Data
TUY060R9V3V TUY080R9V3V TUY100R9V4V TUY120R9V5V
Performance Data
Electrical Data
Field Wiring
Dimensions
2
4
6
7
11
12
15
3Pub. No. 22-1682-05-0802 (EN)
Features and Benefits
XV 90 STANDARD EQUIPMENT
• Variable speed indoor blower
• Silicon Nitride Igniter with adaptive
heat up
• Variable speed induced draft blower
• Direct/Non-Direct vent option
• Fused 24 volt control circuit
• Manual reset burner safety switches
• Power supply 115/1/60
• Convertible to horizontal on left side
• 2-stage gas valve
• PVC venting-1 or 2 pipe option
• Accessory hook-up capability
• Integrated solid state control with
self-diagnostics
• Attractive color accents
• Heavy gauge aluminized steel heat
exchanger
• Multi-port In-shot burners
• HInged blower door
• Perfect fit door latches
• Insulated blower door
• Gasketed blower door
• Internal filter rack
• Standard filter sizes
• Two tone color
• Complete front service access
• Left/right gas connection
• Adjustable fan off times
• Cleanable high velocity filters
• Optional L.P conversion kit
• Selectable cooling fan off delay
eliminates need for BAY24X045
time delay kit
Lifetime limited primary heat
exchanger or secondary heat
exchanger warranty to original
owner (Residential use)
• 5 Year limited parts warranty
4 Pub. No. 22-1682-05-0802 (EN)
Features and Benefits
OPTIONAL EQUIPMENT
Thermostat, Mechanical 2-Stage Heating/1-Stage Cooling .......................................................................................... TAYSTAT241 [ ]
Thermostat, Heating/Cooling Single Stage (Mounts Horizontally) .................................................................................... AY28X092 [ ]
Thermostat, Heating/Cooling Single Stage (Mounts Vertically) .................................................................................... BAYSTAT305 [ ]
Thermostat, Electronic Programmable 2-Stage Heating/2-Stage Cooling .................................................................. TAYSTAT302C [ ]
Thermostat, Electronic Programmable 1-Stage Heating/1-Stage Cooling .................................................................. TAYSTAT300C [ ]
Propane Conversion Kit ......................................................................................................................................... BAYLPKT210A [ ]
Electronic Air Filter, “Perfect Fit” Super Efficiency (14-1/2" Wide Gas Furnace) ......................................................... TFE145A9FR0 [ ]
Electronic Air Filter, “Perfect Fit” Super Efficiency (17-1/2" Wide Gas Furnace) ......................................................... TFE175A9FR0 [ ]
Electronic Air Filter, “Perfect Fit” Super Efficiency (21" Wide Gas Furnace) ............................................................... TFE210A9FR0 [ ]
Electronic Air Filter, “Perfect Fit” Super Efficiency (24-1/2" Wide Gas Furnace) ......................................................... TFE245A9FR0 [ ]
Electronic Air Filter, “Perfect Fit” High Efficiency (14-1/2" Wide Gas Furnace) .......................................................... TFM145A9FR0 [ ]
Electronic Air Filter, “Perfect Fit” High Efficiency (17-1/2" Wide Gas Furnace) .......................................................... TFM175A9FR0 [ ]
Electronic Air Filter, “Perfect Fit” High Efficiency (21" Wide Gas Furnace) ................................................................ TFM210A9FR0 [ ]
Electronic Air Filter, “Perfect Fit” High Efficiency (24-1/2" Wide Gas Furnace) .......................................................... TFM245A9FR0 [ ]
Electronic Air Filter, “Perfect Fit” Standard Efficiency (14-1/2" Wide Gas Furnace) ..................................................... TFP145A9FR0 [ ]
Electronic Air Filter, “Perfect Fit” Standard Efficiency (17-1/2" Wide Gas Furnace) ..................................................... TFP175A9FR0 [ ]
Electronic Air Filter, “Perfect Fit” Standard Efficiency (21" Wide Gas Furnace) .......................................................... TFP210A9FR0 [ ]
Electronic Air Filter, “Perfect Fit” Standard Efficiency (24-1/2" Wide Gas Furnace) ..................................................... TFP245A9FR0 [ ]
Coil Enclosure (14-1/2" Wide Cabinets) .................................................................................................................. BAYCLE1400C [ ]
Coil Enclosure (17-1/2" Wide Cabinets) .................................................................................................................. BAYCLE1700C [ ]
Coil Enclosure (21" Wide Cabinets) ........................................................................................................................ BAYCLE2100C [ ]
Coil Enclosure (24-1/2" Wide Cabinets) .................................................................................................................. BAYCLE2400C [ ]
Side Filter Rack ........................................................................................................................................................ BAYFLTR200 [ ]
Filter Kit/Horizontal Conversion TUY060, 080-R ......................................................................................................... BAYFLTR203 [ ]
Filter Kit/Horizontal Conversion TUY100-R ................................................................................................................ BAYFLTR204 [ ]
Filter Kit/Horizontal Conversion TUY120-R ................................................................................................................ BAYFLTR205 [ ]
Filter Accessory Kit Upflow 14.5" Furnaces ............................................................................................................... BAYFLTR317 [ ]
Filter Accessory Kit Upflow 21" Furnaces .................................................................................................................. BAYFLTR321 [ ]
Filter Accessory Kit Upflow 24.5" Furnaces ............................................................................................................... BAYFLTR324 [ ]
High Altitude Switch TUY060R .............................................................................................................................. BAYHALT2451 []
High Altitude Switch TUY080, 100R ...................................................................................................................... BAYHALT2461 []
High Altitude Switch TUY120R .............................................................................................................................. BAYHALT2471 []
Concentric Vent Kit ............................................................................................................................................... BAYVENT100A [ ]
Sidewall Vent Termination Kit ................................................................................................................................. BAYVENT200B [ ]
Manufactured/Mobile Home Kit ............................................................................................................................. BAYMFGH100A [ ]
1 Optional kit allows 200 ft. max. vent length from 5,000-12,000 feet above sea level. See installer's guide.
5Pub. No. 22-1682-05-0802 (EN)
General Data
TUY-R9V PRODUCT SPECIFICATIONS1
MODEL
RATINGS
2
1st Stage Input BTUH
1st Stage Capacity BTUH (ICS)
2nd Stage Input BTUH
2nd Stage Capacity BTUH (ICS) AFUE (ICS) Temp. Rise (Min.-Max.) °F.
BLOWER DRIVE
Dia.-Width (In.) No. Used Speeds (No.) CFM vs. in. w.g. Motor HP R.P.M. Volts/Ph/Hz
COMBUSTION FAN - TYPE
Drive - No. Speeds Motor HP - RPM Volts/Ph/Hz FL Amps
FILTER — Furnished?
Type Recommended Filter (No.-Size-Thk.)
VENT — Size (In.)
HEAT EXCHANGER
Type -Fired
-Unfired
Gauge (Fired)
ORIFICES — Main
Nat. Gas. Qty. — Drill Size L.P. Gas Qty. — Drill Size
GAS VALVE
DIRECT IGNITION DEVICE
Type
BURNERS — Type
Number
POWER CONN. — V/Ph/Hz
Ampacity (In Amps) Max. Overcurrent Protection (Amps)
PIPE CONN. SIZE (IN.)
DUCT CONN.
DIMENSIONS
Crated (In.) Uncrated
WEIGHT
Shipping (Lbs.)/Net (Lbs.)
1 Central Furnace heating designs are certified by AGA and CSA. 2 For U.S. applications, above input ratings (BTUH) are up to 2,000 feet, derate 4% per 1,000 feet for elevations above 2,000 feet above sea level. For Canadian applicaitons, above
input ratings (BTUH) are up to 4,500 feet, derate 4% per 1,000 feet for elevations above 4,500 feet above sea level.
3 Based on U.S. government standard tests. 4 The above wiring specifications are in accordance with National Electrical Code; however, installations must comply with local codes.
3
3
4
TUY060R9V3V
39000 37000 60000 56000
93.0
35 - 65
DIRECT
10 x 8
1
VARIABLE
SEE FAN PERF. TABLE
1/2
VARIABLE
115/1/60
CENTRIFUGAL
DIRECT - VARIABLE
1/15 - 5000
115/1/60
1.1
YES
HIGH VELOCITY
1 X 17 X 25 X 1
2 ROUND
ALUMINIZED STEEL TYPE 1
20
3 - 45 3 - 56
REDUNDANT - TWO STAGE
HOT SURFACE IGNITER
IN-SHOT
3
115/1/60
8.4 15
0.50
SEE OUTLINE DRAWING
H X W X D
41-3/4 X 19-1/2 X 30-1/2
SEE OUTLINE DRAWING
158/146
TUY080R9V3V
52000 49000 80000 73000
92.5
35 - 65
DIRECT
10 x 8
1
VARIABLE
SEE FAN PERF. TABLE
1/2
VARIABLE
115/1/60
CENTRIFUGAL
DIRECT - VARIABLE
1/15 - 5000
115/1/60
1.1
YES
HIGH VELOCITY
1 X 17 X 25 X 1
2 ROUND
ALUMINIZED STEEL TYPE 1
20
4 - 45 4 - 56
REDUNDANT - TWO STAGE
HOT SURFACE IGNITER
IN-SHOT
4
115/1/60
8.4 15
0.50
SEE OUTLINE DRAWING
H X W X D
41-3/4 X 19-1/2 X 30-1/2
SEE OUTLINE DRAWING
158/148
TUY100R9V4V
65000 62000
100000
93000
93.0
35 - 65
DIRECT
10 x 10
1
VARIABLE
SEE FAN PERF. TABLE
1
VARIABLE
115/1/60
CENTRIFUGAL
DIRECT - VARIABLE
1/15 - 5000
115/1/60
1.1
YES
HIGH VELOCITY
1 - 20 X 25 X 1
3 ROUND
ALUMINIZED STEEL TYPE 1
20
5 - 45 5 - 56
REDUNDANT - TWO STAGE
HOT SURFACE IGNITER
IN-SHOT
5
115/1/60
11.4 15
0.50
SEE OUTLINE DRAWING
H X W X D
41-3/4 X 23 X 30-1/2
SEE OUTLINE DRAWING
171/160
TUY120R9V5V
78000
74000 120000 112000
92.5
40 - 70
DIRECT
10 x 10
1
VARIABLE
SEE FAN PERF. TABLE
1
VARIABLE
115/1/60
CENTRIFUGAL
DIRECT - VARIABLE
1/25 - 5000
115/1/60
1.1
YES
HIGH VELOCITY
1 - 24 X 25 X 1
3 ROUND
ALUMINIZED STEEL TYPE 1
20
6 - 45 6 - 56
REDUNDANT - TWO STAGE
HOT SURFACE IGNITER
IN-SHOT
6
115/1/60
11.4 15
0.50
SEE OUTLINE DRAWING
H X W X D
41-3/4 X 26-1/2 X 30-1/2
SEE OUTLINE DRAWING
205/193
6 Pub. No. 22-1682-05-0802 (EN)
Performance Data
*UY060R9V3V FURNACE COOLING AIRFLOW (CFM) AND POWER (WATTS) VS. EXTERNAL STATIC PRESSURE WITH FILTER
OUTDOOR
UNIT SIZE
(TONS)
1.5
2.0
2.5
3
NOTES: * First letter may be "A" or "T"
1. At continuous fan setting: Heating or Cooling airflows are approximately 50% of selected cooling value.
2. LOW airflow (350 cfm/ton) is COMFORT & HUMID CLIMATE setting; NORMAL airflow (400 cfm/ton) is typical setting; HIGH airflow (450 cfm/ton) is DRY CLIMATE setting.
AIRFLOW
SETTING
LOW
(350 CFM/TON)
NORMAL
(400 CFM/TON)
HIGH
(450 CFM/TON)
LOW
(350 CFM/TON)
NORMAL
(400 CFM/TON)
HIGH
(450 CFM/TON)
LOW
(350 CFM/TON)
NORMAL
(400 CFM/TON)
HIGH
(450 CFM/TON)
LOW
(350 CFM/TON)
NORMAL
(400 CFM/TON)
HIGH
(450 CFM/TON)
DIP SWITCH SETTING EXTERNAL STATIC PRESSURE
SW 1 SW 2 SW 3 SW 4 0.1 0.3 0.5 0.7 0.9
ON ON OFF ON
ON ON OFF OFF
ON ON ON OFF
OFF ON OFF ON
OFF ON OFF OFF
OFF ON ON OFF
ON OFF OFF ON
ON OFF OFF OFF
ON OFF ON OFF
OFF OFF OFF ON
OFF OFF OFF OFF
OFF OFF ON OFF
CFM
WATTS
CFM
WATTS
CFM
WATTS
CFM
WATTS
CFM
WATTS
CFM
WATTS
CFM
WATTS
CFM
WATTS
CFM
WATTS
CFM
WATTS
CFM
WATTS
CFM
WATTS
5756557590575
64070640
110
70085700
125
700
700
100
130
800
800
115
155
900
900
140
195
875
875
130
175
235
195
275
360
180
1000
235
1125
295
1050
260
1200
330
1325
425
1000
1125
1050
1200
1325
125
640 140
700 160
700 170
800 200
900 240
875 230
1000
285
1125
345
1050
305
1200
385
1300
460
550 155
630 175
700 200
700 210
800 250
900 290
875 270
1000
335
1100
370
1050
350
1100
385
1175
425
-
-
-
-
-
-
-
900 310
925 318
920 315
940 330
1000
365
*UY060R9V3V FURNACE HEATING AIRFLOW (CFM) AND POWER (WATTS) VS. EXTERNAL STATIC PRESSURE WITH FILTER
AIRFLOW
SETTING
LOW ON ON
HEATING
1ST
STAGE
HEATING
2ND
STAGE
NOTES: * First letter may be "A" or "T" ** Factory setting
MEDIUM LOW OFF ON
NORMAL ** ON OFF
HIGH OFF OFF
LOW ON ON
MEDIUM LOW OFF ON
NORMAL ** ON OFF
HIGH OFF OFF
1st Stage Capacity = 2nd Stage Capacity =
DIP SWITCH SETTING EXTERNAL STATIC PRESSURE
SW 7 SW 8 0.1 0.3 0.5 0.7 0.9
CFM
TEMP. RISE
WATTS
CFM
TEMP. RISE
WATTS
CFM
TEMP. RISE
WATTS
CFM
TEMP. RISE
WATTS
CFM
TEMP. RISE
WATTS
CFM
TEMP. RISE
WATTS
CFM
TEMP. RISE
WATTS
CFM
TEMP. RISE
WATTS
600
57 85
700
49 90
775
44
105
870
39
135
860
61
140
1000
53
190
1125
47
250
1250
42
340
600
57
110
700
49
130
775
44
155
870
39
185
920
57
200
1000
53
255
1125
47
315
1250
42
405
37,000 56,000
600
57
155
700
49
175
775
44
195
870
39
235
920
57
245
1000
53
305
1125
47
370
1250
42
445
600
57
190
700
49
210
775
44
240
870
39
290
920
57
300
1000
53
340
1025
51
355
1100
48
390
7Pub. No. 22-1682-05-0802 (EN)
-
-
-
-
670
79
245
700
75
255
775
68
285
1000
53
355
Performance Data
TUY080R9V3V FURNACE COOLING AIRFLOW (CFM) AND POWER (WATTS) VS. EXTERNAL STATIC PRESSURE WITH FILTER
OUTDOOR
UNIT SIZE
(TONS)
2.0
2.5
3.0
3.5
NOTES: Continuous Fan is with Thermostat Fan Switch on and Dip Switches 5 and 6 in the "ON" position.
1. At continuous fan setting: Heating or Cooling airflows are approximately 50% of selected cooling value.
2. LOW airflow (350 cf m/ton) is COMFORT & HUMID CLIMATE setting; NORMAL airflow (400 cfm/ton) is typical setting; HIGH airflow (450 cfm/ton) is DRY CLIMATE setting.
AIRFLOW SETTING
(See Notes)
LOW
(350 CFM/TON)
NORMAL
(400 CFM/TON)
HIGH
(450 CFM/TON)
LOW
(350 CFM/TON)
NORMAL
(400 CFM/TON)
HIGH
(450 CFM/TON)
LOW
(350 CFM/TON)
NORMAL
(400 CFM/TON)
HIGH
(450 CFM/TON)
LOW
(350 CFM/TON)
NORMAL
(400 CFM/TON)
HIGH
(450 CFM/TON)
DIP SWITCH SETTING EXTERNAL STATIC PRESSURE
SW 1 SW 2 SW 3 SW 4 0.1 0.3 0.5 0.7 0.9
ON ON OFF ON
ON ON OFF OFF
ON ON ON OFF
OFF ON OFF ON
OFF ON OFF OFF
OFF ON ON OFF
ON OFF OFF ON
ON OFF OFF OFF
ON OFF ON OFF
OFF OFF OFF ON
OFF OFF OFF OFF
OFF OFF ON OFF
CFM
WATTS
CFM
WATTS
CFM
WATTS
CFM
WATTS
CFM
WATTS
CFM
WATTS
CFM
WATTS
CFM
WATTS
CFM
WATTS
CFM
WATTS
CFM
WATTS
CFM
WATTS
75084750
840 109
940 136
850 113
960 150
1080
1020
1170
1290
1170
1360
1360
195
175
240
310
250
365
355
1110
1020
1180
1320
1190
1390
1390
122
840
146
940
177
850
150
990 200
255
225
300
410
315
445
450
1000
1120
1040
1200
1350
1210
1400
1400
750 154
840
181
940 215
870 200
230
315
280
365
470
370
500
520
720 185
840 226
940 274
890 250
1020
305
1120
365
1050
330
1200
415
1340
520
1210
435
1360
535
1350
535
710 221
820 264
940 318
890 295
1010
350
1080
390
1050
375
1130
420
1150
440
1100
405
1210
475
1180
460
TUY080R9V3V FURNACE HEATING AIRFLOW (CFM) AND POWER (WATTS) VS. EXTERNAL STATIC PRESSURE WITH FILTER
HEATING
1ST
STAGE
HEATING
2ND
STAGE
NOTES: ** Factory setting
AIRFLOW
SETTING
LOW ON ON
MEDIUM LOW OFF ON
NORMAL ** ON OFF
HIGH OFF OFF
LOW ON ON
MEDIUM LOW OFF ON
NORMAL ** ON OFF
HIGH OFF OFF
DIP SWITCH SETTING EXTERNAL STATIC PRESSURE
SW 7 SW 8 0.1 0.3 0.5 0.7 0.9
CFM
TEMP. RISE
WATTS
CFM
TEMP. RISE
WATTS
CFM
TEMP. RISE
WATTS
CFM
TEMP. RISE
WATTS
CFM
TEMP. RISE
WATTS
CFM
TEMP. RISE
WATTS
CFM
TEMP. RISE
WATTS
CFM
TEMP. RISE
WATTS
1st Stage Capacity = 2nd Stage Capacity =
800
56
105 860
52
115
960
46
150
1080
41
195
1100
62
205
1210
57
265
1360
50
365
1360
50
355
800
56
140 880
51
165
990
45
200
1110
40
255
1100
62
260
1240
55
340
1390
49
445
1390
49
450
49,000 73,000
800
56
180 890
50
215
1000
44
230
1120
40
315
1120
61
320
1260
54
410
1400
49
500
1400
49
520
8 Pub. No. 22-1682-05-0802 (EN)
800
56
220 920
48
265
1020
44
310
1120
40
365
1120
61
370
1260
54
470
1360
50
535
1350
51
535
800
56
265 910
49
320
1010
44
350
1080
41
390
1090
63
400
1130
61
430
1210
57
475
1180
58
465
Performance Data
TUY100R9V4V FURNACE COOLING AIRFLOW (CFM) AND POWER (WATTS) VS. EXTERNAL STATIC PRESSURE WITH FILTER
OUTDOOR
UNIT SIZE
(TONS)
3.0
3.5
4.0
NOTES: Continuous Fan is with Thermostat Fan Switch on and Dip Switches 5 and 6 in the "ON" position.
1. At continuous fan setting: Heating or Cooling airflows are approximately 50% of selected cooling value.
2. LOW airflow (350 cf m/ton) is COMFORT & HUMID CLIMATE setting; NORMAL airflow (400 cfm/ton) is typical setting; HIGH airflow (450 cfm/ton) is DRY CLIMATE setting.
AIRFLOW
SETTING
(See Notes)
LOW
(350 CFM/TON)
NORMAL
(400 CFM/TON)
HIGH
(450 CFM/TON)
LOW
(350 CFM/TON)
NORMAL
(400 CFM/TON)
HIGH
(450 CFM/TON)
LOW
(350 CFM/TON)
NORMAL
(400 CFM/TON)
HIGH
(450 CFM/TON)
DIP SWITCH SETTING EXTERNAL STATIC PRESSURE
SW 1 SW 2 SW 3 SW 4 0.1 0.3 0.5 0.7 0.9
ON ON OFF ON
ON ON OFF OFF
ON ON ON OFF
OFF ON OFF ON
OFF ON OFF OFF
OFF ON ON OFF
ON OFF OFF ON
ON OFF OFF OFF
ON OFF ON OFF
CFM
WATTS
CFM
WATTS
CFM
WATTS
CFM
WATTS
CFM
WATTS
CFM
WATTS
CFM
WATTS
CFM
WATTS
CFM
WATTS
1040
165
1210
235
1340
390
1200
225
1390
335
1590
490
1370
325
1640
515
1840
700
1040
220
1210
285
1370
390
1220
280
1430
425
1590
575
1420
415
1640
585
1840
780
1040
1230
1400
1230
1430
1590
1430
1640
1770
270
360
465
365
495
625
490
655
795
1030
320
1230
415
1390
525
1250
425
1430
560
1580
685
1340
550
1590
680
1630
725
1030
375
1230
475
1370
580
1230
485
1400
590
1420
615
1410
595
1420
615
1470
655
TUY100R9V4V FURNACE HEATING AIRFLOW (CFM) AND POWER (WATTS) VS. EXTERNAL STATIC PRESSURE WITH FILTER
HEATING
1ST
STAGE
HEATING
2ND
STAGE
NOTES: ** Factory setting
AIRFLOW
SETTING
LOW ON ON
MEDIUM LOW OFF ON
NORMAL ** ON OFF
HIGH OFF OFF
LOW ON ON
MEDIUM LOW OFF ON
NORMAL ** ON OFF
HIGH OFF OFF
DIP SWITCH SETTING EXTERNAL STATIC PRESSURE
SW 7 SW 8 0.1 0.3 0.5 0.7 0.9
CFM
TEMP. RISE
WATTS
CFM
TEMP. RISE
WATTS
CFM
TEMP. RISE
WATTS
CFM
TEMP. RISE
WATTS
CFM
TEMP. RISE
WATTS
CFM
TEMP. RISE
WATTS
CFM
TEMP. RISE
WATTS
CFM
TEMP. RISE
WATTS
1st Stage Capacity = 2nd Stage Capacity =
920
60
130
1020
54
165
1160
48
220
1350
41
320
1290
67
275
1410
61
3561 1640
53
530
1970
44
855
920
60
180
1020
54
220
1160
48
260
1380
40
400
1290
67
355
1460
59
455
1640
53
590
1920
45
895
62,000 93,000
920
60
220
1020
54
260
1160
48
325
1400
40
470
1330
65
430
1460
59
520
1640
53
660
1780
48
820
920
60
280
1010
55
310
1160
48
390
1400
40
540
1340
64
490
1460
59
590
1600
54
695
1660
52
760
920
60
320
1000
56
365
1150
48
430
1390
40
585
1320
65
545
1370
63
590
1410
61
620
1520
57
695
9Pub. No. 22-1682-05-0802 (EN)
Performance Data
TUY120R9V5V FURNACE COOLING AIRFLOW (CFM) AND POWER (WATTS) VS. EXTERNAL STATIC PRESSURE WITH FILTER
OUTDOOR
UNIT SIZE
(TONS)
3.5
4.0
5
NOTES: Continuous Fan is with Thermostat Fan Switch on and Dip Switches 5 and 6 in the "ON" position.
1. At continuous fan setting: Heating or Cooling airflows are approximately 50% of selected cooling value.
2. LOW airflow (350 cf m/ton) is COMFORT & HUMID CLIMATE setting; NORMAL airflow (400 cfm/ton) is typical setting; HIGH airflow (450 cfm/ton) is DRY CLIMATE setting.
AIRFLOW SETTING
(See Notes)
LOW
(350 CFM/TON)
NORMAL
(400 CFM/TON)
HIGH
(450 CFM/TON)
LOW
(350 CFM/TON)
NORMAL
(400 CFM/TON)
HIGH
(450 CFM/TON)
LOW
(350 CFM/TON)
NORMAL
(400 CFM/TON)
HIGH
(450 CFM/TON)
DIP SWITCH SETTING EXTERNAL STATIC PRESSURE
SW 1 SW 2 SW 3 SW 4 0.1 0.3 0.5 0.7 0.9
OFF ON OFF ON
OFF ON OFF OFF
OFF ON ON OFF
ON OFF OFF ON
ON OFF OFF OFF
ON OFF ON OFF
OFF OFF OFF ON
OFF OFF OFF OFF
OFF OFF ON OFF
CFM
WATTS
CFM
WATTS
CFM
WATTS
CFM
WATTS
CFM
WATTS
CFM
WATTS
CFM
WATTS
CFM
WATTS
CFM
WATTS
1210
220
1400
305
1590
425
1390
305
1620
420
1840
600
1800
570
2050
845
2160
995
1210
270
1440
390
1600
520
1400
375
1650
530
1830
690
1780
630
2010
875
2040
935
1220
1450
1610
1430
1670
1820
1780
1860
1920
325
465
600
445
595
765
705
805
875
1230
400
1450
510
1600
645
1440
515
1640
660
1670
700
1700
695
1710
735
1780
805
1230
445
1410
560
1380
575
1420
565
1480
600
1490
620
1530
615
1530
655
1620
730
TUY120R9V5V FURNACE HEATING AIRFLOW (CFM) AND POWER (WATTS) VS. EXTERNAL STATIC PRESSURE WITH FILTER
HEATING
1ST
STAGE
HEATING
2ND
STAGE
NOTES: ** Factory setting
AIRFLOW
SETTING
LOW ON ON
MEDIUM LOW OFF ON
NORMAL ** ON OFF
HIGH OFF OFF
LOW ON ON
MEDIUM LOW OFF ON
NORMAL ** ON OFF
HIGH OFF OFF
DIP SWITCH SETTING EXTERNAL STATIC PRESSURE
SW 7 SW 8 0.1 0.3 0.5 0.7 0.9
CFM
TEMP. RISE
WATTS
CFM
TEMP. RISE
WATTS
CFM
TEMP. RISE
WATTS
CFM
TEMP. RISE
WATTS
CFM
TEMP. RISE
WATTS
CFM
TEMP. RISE
WATTS
CFM
TEMP. RISE
WATTS
CFM
TEMP. RISE
WATTS
1st Stage Capacity = 2nd Stage Capacity =
1090
62
165
1210
56
220
1340
50
295
1430
47
390
1660
63
485
1870
56
675
2060
51
880
2200
48
1030
1120
60
225
1200
56
280
1360
50
350
1570
43
490
1690
62
590
1870
56
745
1990
53
890
2090
50
965
74,000 112,000
1080
1200
1370
1580
1680
1810
1850
1940
63
270
56
330
49
425
43
565
62
640
58
770
57
810
54
895
1070
63
310
1180
57
395
1380
49
495
1570
43
625
1640
64
675
1680
62
715
1710
61
750
1790
58
830
1010
67
380
1160
58
455
1330
51
535
1390
49
565
1460
72
600
1490
70
625
1530
68
665
1640
64
750
10 Pub. No. 22-1682-05-0802 (EN)
Electrical Data
SCHEMATIC DIAGRAMS FOR GAS FURNACES
LEGEND
TUY060,080,100,120R9V-V
From Dwg. 21D341111 P03
11Pub. No. 22-1682-05-0802 (EN)
TO 115 V 1 PH., 60 HZ., POWER SUPPLY PER LOCAL CODES
HUM SEE NOTE 5
EAC SEE NOTE 5
Field Wiring
FIELD WIRING DIAGRAM FOR SINGLE STAGE HEATING
TO 115 V 1 PH., 60 HZ., POWER SUPPLY PER LOCAL CODES
HUM SEE NOTE 5
EAC SEE NOTE 5
From Dwg. 21B341127 Rev. 0
FIELD WIRING DIAGRAM FOR 2 STAGE HEATING THERMOSTAT
From Dwg. 21B341126 Rev. 0
12 Pub. No. 22-1682-05-0802 (EN)
Field Wiring
FIELD WIRING DIAGRAM FOR SINGLE STAGE HEATING/COOLING
(OUTDOOR SECTION WITHOUT TRANSFORMER)
From Dwg. 21B341125 Rev. 1
FIELD WIRING DIAGRAM FOR 2 STAGE HEATING SINGLE STAGE COOLING
(OUTDOOR SECTION WITHOUT TRANSFORMER)
From Dwg. 21B341124 Rev. 1
13Pub. No. 22-1682-05-0802 (EN)
TO 115 V 1 PH., 60 HZ., POWER SUPPLY PER LOCAL CODES
HUM SEE NOTE 5
EAC SEE NOTE 5
Field Wiring
FIELD WIRING DIAGRAM FOR 2 STAGE HEATING TWO STAGE COOLING
(OUTDOOR SECTION WITHOUT TRANSFORMER)
From Dwg. 21B341128 Rev. 0
14 Pub. No. 22-1682-05-0802 (EN)
Dimensions
(ALL DIMENSIONS ARE IN INCHES)
TUY-R9V-V OUTLINE DRAWING
15Pub. No. 22-1682-05-0802 (EN)
Trane
A business of American Standard Companies www.trane.com
File No. PL-UN-FURN-TDD-D-1 3/98 P. I .