Trane 060E, 36, 48 User Manual 2

Split System Heat Pump Product Data
XL16i
4TWX6024, 036, 048 & 060E
2, 3, 4 & 5 Tons
PUB. NO. 22-1754-17
• CLIMATUFF™ 2-stage scroll
compressor
• Efficiency up to 18.0 SEER and
9.0 HSPF
•All Aluminum SPINE FIN™ coil
WEATHERGUARD™ II top shields
unit
DURATUFF™ weather proof and
rust proof base
COMFORT ”R”™ mode approved
for better comfort indoors
QUICK-SESS™ cabinet,
service access and refrigerant connections with full coil protection
WEATHERGUARD™ fasteners
•Glossy corrosion resistant finish
tarpaulin gray cabinet with anthracite gray top
•Internal compressor high/low
pressure & temperature protection
•Liquid line filter/drier
•Low sound with advanced variable
speed fan motor
•Service valve cover
•R-410A refrigerant
•From 70 to 100% capacity
modulation
•100% run test in the factory
•Low ambient cooling to 55° as
shipped
Extended warranties available
© 2011 Trane 2 22-1754-17
Contents
Features and Benefits 2
General Data 4
Product Specifications 4 A-weighted Sound Power Level [dB(A)] 4 Accessory Description and Usage 5 AHRI Standard Capacity Rating Conditions 5
Model Nomenclature 6
Electrical Data 7
Dimensions 10
Mechanical Specifications 11
22-1754-17 3
General Data
Product Specifications
Model No. 1 4TWX6024E1 4TWX6036E1 4TWX6048E1 4TWX6060E1
Electrical Data V/Ph/Hz 2 230/1/60 230/1/60 230/1/60 230/1/60 Min Cir Ampacity 14 22 28 39 Max Fuse Size (Amps) 20 35 45 60
Compressor CLIMATUFF® - SCROLL CLIMATUFF® - SCROLL CLIMATUFF® - SCROLL CLIMATUFF® - SCROLL RL AMPS - LR AMPS 10.3 - 52 16.7 - 82 21.2 - 104 28.8 - 152.9 Outdoor Fan FL Amps 0.74 0.74 1.00 2.80 Fan HP 1/8 1/8 1/5 1/3 Fan Dia (inches) 27.6 27.6 27.6 27.6
Coil Spine Fin™ Spine Fin™ Spine Fin™ Spine Fin™ Refrigerant R-410A 10/3-LB/OZ 10/8-LB/OZ 12/9-LB/OZ 13/3-LB/OZ Line Size - (in.) O.D. Gas 3 5/8 3/4 7/8 1-1/8 Line Size - (in.) O.D. Liquid 3 3/8 3/8 3/8 3/8
Dimensions H x W x D (Crated) 53.4 x 35.1 x 38.7 57.4 x 35.1 x 38.7 57.4 x 35.1 x 38.7 57.4 x 35.1 x 38.7 Weight - Shipping 305 307 360 361 Weight - Net 257 257 310 311
Start Components YES NO NO NO Sound Enclosure NO NO NO NO Compressor Sump Heat YES YES YES YES
Optional Accessories: 4
Rubber Isolator Kit BAYISLT101 BAYISLT101 BAYISLT101 BAYISLT101 Snow Leg - Base & Cap 4" High BAYLEGS002 BAYLEGS002 BAYLEGS002 BAYLEGS002 Snow Leg - 4" Extension BAYLEGS003 BAYLEGS003 BAYLEGS003 BAYLEGS003 Hard Start Kit Scroll BAYKSKT260 BAYKSKT260 BAYKSKT260 Extreme Condition Mounting Kit BAYECMT004 BAYECMT004 BAYECMT004 BAYECMT004 Vertical Discharge Air Kit Base 4 BAYVDTA003 BAYVDTA004 BAYVDTA004 BAYVDTA004
Auto Charge Solenoid Kit BAYCAKT001 BAYCAKT001 BAYCAKT001 BAYCAKT001
Refrigerant Lineset 5 TAYREFLN9* TAYREFLN7* TAYREFLN3* TAYREFLN4*
1 Certified in accordance with the Air-Source Unitary Heat Pump Equipment certification program which is based on AHRI Standard 210/240. 2 Calculated in accordance with N.E.C. Only use HACR circuit breakers or fuses. 3 Standard line lengths - 60'. Standard lift - 25' Suction and Liquid line.
For Greater lengths and lifts refer to refrigerant piping software Pub# 32-3312-0†. (†denotes latest revision)
4 For accessory description and usage, see page 5. 5 * = 15, 20, 25, 30, 40 and 50 foot lineset available.
A-weighted Sound Power Level [dB(A)]
MODEL
4TWX6024E 72 40.4 50.8 53.7 59.9 62.2 57.9 56.1 48.4
4TWX6036E 72 39.3 49.6 55.7 60.5 62.9 57.7 54.7 47.3
4TWX6048E 72 42 57.3 56.6 64 63.3 57.2 53.5 46.2
4TWX6060E 74 31.9 58.9 57.1 64.8 66.4 59.8 55.9 51.2
Note: Rated in accordance with AHRI Standard 270-2008.
4 22-1754-17
SOUND POWER
LEVEL [dB(A)]
A-WEIGHTED FULL OCTAVE SOUND POWER LEVEL dB - [dB(A)]
63 125 250 500 1000 2000 4000 8000
General Data
Accessory Description and Usage
Rubber Isolators — 5 rubber donuts to isolate condens-
ing unit from mounting frame or pad. Use on any application where sound transmission needs to be minimized.
Extreme Conditions Mounting Kit — Bracket kits to secure­ly mount condensing unit to a frame or pad without removing any panels. Use in areas with high winds, or on commercial rooftops, etc.
Low Ambient Cooling — For low ambient cooling below 55° see Application Guide APP-APG013-EN.
AHRI Standard Capacity Rating Conditions
AHRI STANDARD 210/240 RATING CONDITIONS
(A) Cooling 80°F DB, 67°F WB air entering indoor coil,
95°F DB air entering outdoor coil.
(B) High Temperature Heating 47°F DB, 43°F WB air entering
outdoor coil, 70°F DB air entering indoor coil.
(C) Low Temperature Heating 17°F DB, 15°F WB air entering
outdoor coil, 70°F DB air entering indoor coil.
(D) Rated indoor airflow for heating is the same as for cooling.
AHRI STANDARD 270 RATING CONDITIONS — (Noise rating numbers are determined with the unit in cooling opera­tion.) Standard Noise Rating number is at 95°F outdoor air.
22-1754-17 5
Model
Refrigerant Type
4 = R-410A
TRANE
Product Type
W = Split Heat Pump T = Split Cooling
Product Family
Z = Leadership – Two Stage X = Leadership R = Replacement/Retail M or B = Basic A = Light Commercial
Family SEER
3 = 13 6 = 16 0 = 20 4 = 14 8 = 18 5 = 15 9 = 19
Split System Connections 1-6 Tons
0 = Brazed
Nominal Capacity in 000s of BTUs
Major Design Modifications
Power Supply
1 = 200-230/1/60 or 208-230/1/60 3 = 200-230/3/60 4 = 460/3/60
Secondary Function
Minor Design Modifications
Outdoor Units
4TWX6036E1000AA
Refrigerant Type
4 = R-410A
Application
TE = Fully Convertible TG = Semi Convertible TF = Front Return
Product Family
E = Leadership – Variable Speed P = Leadership C = Replacement/Retail B = Basic
Flow Control
0 = No Flow Control 3 = Nonbleed TXV
Feature Identifier
0 = Standard Unit F = Air-Tite™
Nominal Capacity in 1000’s (BTUH)
Major Design Change
Power Supply
1 = Single Phase
Electrical Connection
0 = Pig Tails B = Circuit Breaker D = Pull Disconnect
Future Option – Factory Installed Heater Nominal KW Value
Minor Design Modifications
Unit Parts Identifier
NOTE: There will be a phase-in of new model numbers for new air handlers over next 2 years.
Air Handlers – Residential
4TEE3F36A1 AA000
Gas Furnaces
TU D2B080AC AAV32
Coils –
Nomenclature
6 22-1754-17
4TXCB001 C C3 H CAA
Residential
Refrigerant Type
4 - R410A
Product Family
T-Premium (Heat Pump or Convertible Coil)
Coil Design
X - Direct Expansion Evaporator Coil
Product Family
C - Cased A Coil A - Uncased A Coil F - Cased Horizontal Flat Coil
Coil Width (Cased/Uncased)
A - 14.5" / 13.3" B - 17.5" / 16.3" C - 21.0" / 19.8" D - 24.5" / 23.3" H - 10.5"
Refrigerant Line Coupling
0 - Brazed
Model Number Distinguisher
Major Design Change
Efficiency
C - Standard S - Hi Efficiency (Derived from 10 SEER products)
Refrigerant Control
3 - TXV - Non-Bleed
Coil Circuitry
H - Heat Pump
Airflow Configuration
A - Upflow Only U - Upflow / Downflow H - Horizontal Only C - Convertible - Upflow, Downflow, Left or Right Airflow
Minor Design Change
Unit Parts Identifier
Electrical Data
Schematic Diagrams
(SEE LEGEND)
4TWX6024
22-1754-17 7
Printed from D156993P02
Electrical Data
Schematic Diagrams
(SEE LEGEND)
4TWX6036E
Printed from D156631P06 Rev 00
8 22-1754-17
Electrical Data
Schematic Diagrams
(SEE LEGEND)
4TWX6048E
125
22-1754-17 9
Printed from D156977
GR/YL
ACR -A/C REC TIFIER
R
DF C
RD
K1
BLBLOR
BL
YL/BK
OR
TO POWE R SUPPL Y PE RUNIT NAMEPL A TE AND L OC AL C ODES
SUM P H T R
BK BK
BR/RD
MS-1
LED
GR
OOBBR
OR
SC
OR
RD
K3
K1
YY X2Y0
OR
YL/BK
HPCO
Y L
MS
B
YLRD
BL
RD
E E V C
R Y2 Y1
O
YL/RD
YL/RD
WH
S
H W
BL
YL
Y2C
BL
BL
K2
T1 T2
ACR
S
NOT E4&5
ODT-B
ODT-A
Electrical Data
Schematic Diagrams
(SEE LEGEND)
4TWX6060E
PR/WH
CS
RD
BR
125
OR
CR
YL
Y L
CSR-1
OR
CSR
RD
BK
BK
VARIABLESPEED
Y lo
Y
3
Y 2C
1
YL/RD
Y2
BK
W3
X 2
W2
W1
BK
B
R
TOP OWER SUP PLY
PERLOCAL CODE S
Y L
BK
OR
COM PR ESSOR
SOLENOID
YL
YL
OPTIONAL
OPTIONAL
BL YL
LP CO
BL
T EMP
E E V
START KITBAY KSKT263
O
Y 1
TDR
D R
/
L
31
Y
YL
REMOTE
BK
BK
BK
BK
BL
RD
P-T RD
TDL
BK/B L
SC R
CBS
ODS
AI R HAND LER
HEAT
CON TR OLS
B
K
/
B
L
IOL
CP R
BR/RD
YL/BR
1 6
PR/WH
TYPICAL HEAT/C OOL
THERMOSTAT
J
G
T
F
B
TNS 24V
R
O
CBS-COIL BOTTOMSENSOR
CF -FANCAPACI TOR
CN -WIRE C ONNE CT OR
CPR-COMPRESSOR
CR -RUN CAPACITOR
CS-STARTINGCAPACITOR
CSR -CAPACIT OR SW IT CHINGRELAY
DFC-DEFROSTCONTROL
EEV-ELECT RONIC EXPVALVE
EEVC -ELECTRONICEXP VALVECONTROL
F -INDOORFANRE LAY
BK/BL
MS-2
L Y
/ R G
BL
BK/BL
O
Y 1
Y 2
W2
W1
G
B
R
HPCO-HIGHPRE SSURECUTOUTSWITCH
IOL -INTERNAL OV E RLOAD PRO TE CTO R
LPCO -LOW PRESSURE CUTOUT SWITC H
MS -COMPR ESSOR MOT OR C ONT AC TOR
ODA - OUTD OOR ANTIC IPATOR
OFT-OUTDOORFAN THERMOSTAT
ODS-OU
TDOOR TEMPERATURESENSOR
ODT -OUTDOORTHERM OSTAT
P-TRD-PRESSURE T RANSDUCER
SC -SWITCHOVERVALVESOL ENOID
SM -SYSTE M O N-OFF SWI TCH
TDL -DISCHARGE LINE T HERMOSTA T
TDR-TIMEDE LAYRELAY(5SECDELAYON)
TNS-TRANSFORME R
TEMP -SENSOR ,TEMPERATURE
Y2C-HIGH C APA CIT YCONTROLRELAY
BK
V ARIA BLE
GR
SPEED
BL
OD FA N
BR
MOTOR
WH
Y L
WAR NING
inju
AG E !
ryordeath.
HAZARD OUSVOLT
DISC ONNECT ALL ELECTRICALPOWER INCLUDINGREMOTEDISCONN ECTS BEFORE SERV ICING .
Fai lureto disconnect power beforeservicing cancausesevere personal
CAUTION
USE C OPPER CONDUCTORSONLY!
UNIT TERMI NALS A RE NOTDESIGNED TO AC CEPT OTHER TY PES OF C ONDU CTORS.
Failure to do so may causedamage to the equipment.
NOTES:
1. B ESURE POWE R SUPPL Y AGR E ES
WITH EQUIPMENTNAM
2. P OWER WI RING ANDGROUNDING OF EQUIPMEN TMUSTCOMPLYWITH LOC AL CODES.
3.LOW VOLTAGE W IRING T O BE NO.18 AWGMINIMUM COND UCTOR.
4. OD T-BMUSTBE SET LOWERTHAN ODT-A
5. IF ODT-BISNOT USED,CONNECT AJUM PER W
IRE FROMW3 TOW2. I FODT -A ISNOT U SED,
CONNECT AJUMPERWIR E FROM W2 TO W 1.
6. I FELECTRIC HEATER DOESNOT HAVE A3RD CONTAC TOR (C H).CONNECT AJUMPERWIREFROM W3 TO W2.IF E L ECTR IC HEATER DOESNOTHAVE A2NDCONTAC TOR(BH). CONNECT AJUM PERWIRE FROM W2 TOW1.
7. X2 MU ST BE CONNECTE DTO VARIABL E SPE ED AIR HANDL E R T ER M INAL W3 ASSHOWN, F ORPROPE INDOOR AIRFL OWDURI NGTHE DEFROSTCYCLE
8. BE SU RE T H E JU MPE RBETWEEN RAND BK IS CUTORREMOVE
9. WITH OANDY/Y2ENERGIZED, INDOOR FANISAT80% A IR F LOW.
10.WITHO,Y/Y2AND BK ENERGIZED, INDOOR FANISAT 100%AIRFLOW .
FORCANADIANINSTALLATIONS
POUR INST ALLATIONSCANADIENNES
CAUTION: NOTSUITABLEFOR USEON
SYST EMSEXCEEDING150V-T O-GROUND
ATTENTION:NE CONVIENT PASAUX
INSTALLATIONSDEPL USDE150VA
LATER RE
EPLATE.
D.
Printed from D156631P08
10 22-1754-17
Dimensions
4TWX6 Outline Drawing
Note: All dimensions are in MM (Inches).
MODELS BASE A B C D E F G H J K
4TWX6024E 4 1267 (49-7/8) 946 (37-1/4) 870 (34-1/4) 5/8 3/8 152 (6) 98 (3-7/8) 219 (8-5/8) 86 (3-3/8) 730 (28-3/4)
4TWX6036E 4 1369 (53-7/8) 946 (37-1/4) 870 (34-1/4) 3/4 3/8 152 (6) 98 (3-7/8) 219 (8-5/8) 86 (3-3/8) 730 (28-3/4)
4TWX6048E 4 1369 (53-7/8) 946 (37-1/4) 870 (34-1/4) 7/8 3/8 152 (6) 98 (3-7/8) 219 (8-5/8) 86 (3-3/8) 730 (28-3/4)
4TWX6060E 4 1369 (53-7/8) 946 (37-1/4) 870 (34-1/4) 1-1/8 3/8 152 (6) 98 (3-7/8) 219 (8-5/8) 86 (3-3/8) 730 (28-3/4)
From Dwg. D152635 Rev. 16
22-1754-17 11
Mechanical Specifications
General
The 4TWX6 is fully charged from the factory for matched indoor section and up to 15 feet of piping. This unit is designed to operate at outdoor ambient temperatures as high as 115°F. Cooling capacities are matched with a wide se­lection of air handlers and furnace coils that are AHRI certified. The unit shall be certified to UL 1995. Exterior is designed for outdoor application.
Casing
Unit casing is constructed of heavy gauge, G60 galvanized steel and painted with a weather-resistant powder paint on all louvers and panels. Cor­rosion and weatherproof CMBP-G30 DuraTuff™ base.
Refrigerant Controls
Refrigeration system controls include condenser fan, compressor contactor and high pressure switch. High and low pressure controls are inherent to the compressor. A factory installed liquid line drier is standard.
Compressor
The Climatuff® 2-stage compressor features internal over temperature and pressure protection and hermetic motor. Other features include: roto lock suction and discharge refrigerant connections, centrifugal oil pump and modular plugs for electrical connections.
Condenser Coil
The outdoor coil provides low airflow resistance and efficient heat transfer. The coil is protected on all four sides by louvered panels.
Low Ambient Cooling
As manufactured, this unit has a cool­ing capability to 55°F. For low ambient cooling below 55° see Application Guide APP-APG013-EN.
Trane www.trane.com
Trane has a policy of continuous product and product data improvement and it reserves the right to change
design and specifications without notice.
08/11
Loading...