Tranberg TEF 1058 User Manual

THERMOSTAT
PIPE & WALL MOUNTED
ZONE 1, ZONE 2 & SAFE AREA
USER MANUAL
Subject to change without prior notice TUM5134 REV. G 06.09.2017
IMPORTANT
Read this instruction carefully before installing the product
R. Stahl Tranberg AS
E info@stahl-tranberg.com | stahl-tranberg.com
Main office: Strandsvingen 6 | N-4032 Stavanger | Norway | T +47 51 57 89 00 | F +47 51 57 89 50 Office Oslo: Luhrtoppen 2 | N-1470 Lørenskog | Norway | T +47 24 08 44 10
HEATING CABLE
TEF 1058 IECEx HEAT TRACING THERMOSTAT BOX USER MANUAL
INTRODUCTION
Thank you for purchasing this product! For installation, maintenance and assurance of a long life of this product, please follow this manual.
CONTENT IN BOX
The product is fully assembled, and ready for installation.
SAFETY PRECAUTIONS
Only qualified personel are allowed to perform installation and maintenance taskes to this equipment.
The junction box is equipped for termination of heat tracing and is ready for installation when leaving the production facilities of Tranberg AS. Changes made to the product which do not confirm to the approvals of this equipment, is a safety violation. The manufacturer is under no circumstances responsible for personal injuries, death or any other damage caused by such activities. Any damage done to the equipment during transportation is not the responsibility of Tranberg AS. If the content is not complete, file a claim to the producer immediately.
glands and blinds may be ised. Gland has to be chosen according to cable diameter used.
Strap the transition unit to pipe with pipestraps.
Assembly the flaxible conduit according to the spesial
gland. see fig. 2
Assembly of pipe mounted type fig. 02
Mount thermostat junction box either standing or
hanging to pipe by pipestraps.
Remove dust protection or stopping plugs and install
gland to be used. Drain is to be mounted at the lowest point. For holes not in use, these must be inserted with stopping plugs. Only certified cable glands and blinds may be used. Gland has to be chosen according to cable diameter used.
Temperature sensor
The sensor should be strapped in good thermal contact with the pipe or equipment. In addition to general mechan­ical protection, the sensor should be protected so that the thermal insulation cannot be tapped between the sensor and the heated surface. The sensor is normally fixed to pipe or object by use of aluminium tape. Other methods could be thermowells suitable for the application.
MAINTENANCE/REPAIR/MODIFICATION
Maintenance according to national regulations and
company practice.
Before opening the junction box make sure that the
power is disconnected.
Servicing the junction box is done be checking the in-
tactness of the junction box, gasket and glands. If nec­essary lubricate the lid bolt threads with grease type Renolit Unitemp 2 from Fuchs.
If repair or overhaul is necessary this may only be done with Tranberg spare parts.
Modification of the JB or change of design are not permit­ted, exept for installing additional glands and terminals ac­cording to the approval of the JB.
APPROVAL
Presafe 14ATEX4124 IECEx PRE 14.0001
INSTALLATION INSTRUCTIONS
Note!
The widened area of the capillary tube, shall be clamped by the cable gland sealing ring. The sealing ring is not dimensioned for the Ø1,5mm capillary tube.
Termination
In order to maintain the mode of protection, the conductors will have to be connected with special care. The isolation must reach up to the terminals and the conductor must not be damaged. Termination of heat cables must be according to cable specification given by supplier of these. Tighten all terminals, also those vacant. Reinstall lid and tight bolts firmly with suitable tool by hand force. Over tightening may impair the protection category.
Connection:
L-N: Power cable / Input 2-N: Heating cable / output N/C contact 4-N: Output N/O contact
ϑ>
1
4
2
Assembly of wall mounted type fig. 01
Mount the thermostat junction box by at least 2 pcs. M6
bolts placed diagonally on a wall or proper supported rack.
Remove dust protection or stopping plugs and install
gland to be used. For holes not in use these must be inserted with stopping plugs. Only certified cable
LPE N 4
2
POWER IN
100A107492
TEF 1058 IECEx HEAT TRACING THERMOSTAT BOX USER MANUAL
Fig. 01
Glastape
Transition unit
Swivel with grommet and washer
Flexible conduit
Pipestrap
Pipe
Sensor
Sensor entry
Cable gland with swivel, grommet and washer for sensor
Enclosure
Tag support Tag plate
000A109545
Fig. 02
Drainplug to be mounted at the lowest point
Insulation
Pipe
Transition unit
Sensor
Detail of flexible conduit
Fig. 03
Glastape
Pipestrap
Detail of sensor entry
Sensor entry
000A109545
Enclosure
Tag support
Tag plate
TEF 1058 IECEx HEAT TRACING THERMOSTAT BOX USER MANUAL
TECHNICAL DATA
Housing: Acid proof stainless steel
Nominal voltage: 230 VAC
Main switching capacity: 16 (2.5)A PF=1(0.6) (N/C contact)
6.3 (2.5)A PF=1(0.6) (N/O contact)
IP-grade: IP66/67 (IP67 without drain plug)
TAMB: -50°C to +50°C (Silicone)
-20°C to +40°C (EPDM)
Max. cable diam: 6mm²
Ex marking: Ex d e IIC Gb
Ex eb IIC Ex e mb IIC Gb
T6/T5/T4
R. Stahl Tranberg AS
E info@stahl-tranberg.com | stahl-tranberg.com
Main office: Strandsvingen 6 | N-4032 Stavanger | Norway | T +47 51 57 89 00 | F +47 51 57 89 50 Office Oslo: Luhrtoppen 2 | N-1470 Lørenskog | Norway | T +47 24 08 44 10