S7-200 S7-300 (provides baudrates up to 12M (when the PLC is able to support this) S7-400 (provides
baudrates up to 12M) FM-devices Sinamix (Step7-direct-driver up V1.20 or PLCVCom up V2.71)
MicroMaster and other electrical drives and inverter-feds (Step7-direct-driver up V1.20 or PLCVCom up
V2.71) Sinumerik (only PLC-side) SEW-EURODRIVE power inverter and at last routing of S7-PLCs
3 Connecting options
S7-USB directly connected to the PC.
S7-USB is connected to the PC via a USB hub.
S7-USB Connection options with control terminal
4 Installation
4.1 Hardware
The S7/MPI-USB is plugged directly into the PLC. Via the USB cable of the module can be connected to the
PLC as follows:
Normal installation (for programming)
The MPI cable will be connected to the S7 PLC via the 9 pin connector (short side of the cable). The USB
connector on the long side of the cable will be connected with the computer.
S7/MPI-USB as HMI (Human Machine Interface) – adapter
The HMI – function provides the possibility to connect a operator panel (which has instead of a MPI
interface a USB device and understands the HMI protocol) with a S7 PLC (300/400). Connect the cable
between the terminal and the PLC. The HMI – protocol must be part of the operator panel.
There must be a serial communication with the operator panel if this op is new/used at the first time.
Therefore connect your operator panel with the serial COM interface of your computer. After the
communication has been running successfully the panel is ready to be connected to the PLC.
4.2 Software
To communicate with the PLC, please install following products for MPI-USB, S7-USB, MPI-II[only USB], MPILAN and S7-LAN:
ProductDriver
TIA-Portal
Simatic-Manager TIC ⇒ “TIC ETH/USB” for MPI, PPI or PROFIBUS
Starter-Software TIC ⇒ “TIC ETH/USB” for MPI or PROFIBUS
MicroWinTIC ⇒ “TIC ETH/USB” for PPI and S7-22x-PLC
MicroWinPLCVCom for S7-21x-PLC (no MultiMaster-protocol)
PG-2000PLCVCom or for S7-LAN/MPI-LAN direct in interface-settings
S7 for Windows TIC ⇒ “TIC ETH/USB” for MPI or PROFIBUS over PD/PC-interface
S7 for Windows PLCVCom
To communicate with the PLC, please install following products for MPI/PPI and MPI-II[only serial]:
TIC ⇒ “TIC ETH/USB” for MPI, PPI or PROFIBUS
configuration of driver with control-panel ⇒ setting PD/PC-interface
ProductDriver
TIA-Portalno support because Siemens has taken out the serial support in the driver “PC-Adapter”
Simatic-Manager included driver “PC-Adapter” for MPI and PROFIBUS
Starter-Software included driver “PC-Adapter” for MPI and PROFIBUS
MicroWinincluded driver “PC/PPI-cable”
PG-2000Standard-function, configuration in the interface-settings
S7 for Windows Standard-function, configuration in the interface-settings
4.3 USB-driver-installation for 32-bit-systems
The S7-Interface S7-USB, MPI-USB or MPI-II-Cabel over USB as well as the devices of TeleService-family will
be connected to USB 1.1-compatible port of the PC.
This opens the Hardware-Installation-Wizard:
We don´t need a connection to Windows update.
Select now “Install from a list or specific location”:
Upon a successful installation the “PI_Usb.Sys driver” will be displayed without any warnings in the device
manager:
Will this entry in the device manager shown with a “yellow exclamation mark”, then please install the
driver again or look in the driver properties about the reason.
If the driver has to be updated, please use the function “Update …” in the driver properties:
If the driver has to be deleted, please use the function “Uninstall” in the driver properties:
If you install older versions of PLCVCom, Step7-direct-driver or S7IFC, the actual usb-driver will be possible
overwritten by previous versions because it was included until 01/11/2012 in their install-shields!
4.4 USB-driver-installation for Win7 64-bit
The S7-Interface S7-USB, MPI-USB or MPI-II-Cabel over USB as well as the devices of TeleService-family will
be connected to USB 1.1-compatible port of the PC.
After the first plug of the device Win7 displays the message „Installing device driver software“ and after
some time „Device driver software was not installed“. This messages could be closed.
Please start the windows device manager in the control panel.
Please select “Browse my computer for driver software” and define as source the folder “..\USB-Treiberx64”. Either in the folder where the downloaded drivers were extracted or the directory on the product CD:
After pressing “Next” the message appears of windows UAC
If the driver has to be deleted, please use the function “Uninstall” and set the check-box in “Delete the
driver software for this device”:
If you install older versions of PLCVCom, Step7-direct-driver or S7IFC, the actual usb-driver will be possible
overwritten by previous versions because it was included until 01/11/2012 in their install-shields!
Green LED OFFPower OFF (S7-USB is not supplied with voltage)
Green LED is blinking BUS Communication
Green LED is onPower ON (S7-USB is supplied with voltage)
Yellow LED is OFFno error in the communication
1x Module does not come into bus
2x Participants provided with the same MPI address
Yellow LED is blinking
3x Wrong MPI baud rate is used
4x Detected parity error on the bus
5x Buffer overflow condition in module
6 Implementing
Connect your module as described in the chapter “ Hardware installation ” to the PLC and to the
programming device or to your computer.
If you want to respond to a PLC via the module you have to comply the requirements as described in the
chapter “system requirements” . In addition,please make sure that the module is properly connected
6.1 Using the PLC-VCOM
(The PLC-VCOM is only needed if your module is not connected via the 9 pin COM port to the computer. For
products with USB, Ethernet connection, etc., the PLC-VCOM is required)
1. Start the PLC - VCOM application (If it has not already started yet).
2. Click in the main window of the PLC-VCOM, in the status area “configure”. The configuration wizard will
start.
3. It lists all the found modules / cables and the additional information’s such as IP address and MAC
address of the module.
4. Choose the desired MPI cable and click „OK“ to go on.
5. If the connection is established the chosen cable is shown in the section state and on the left side you
can see the status connected.
6. It also displays, the PLC-VCOM the IP address for the module and the IP address of the computer which
is connected to the module.
If you have any problems with the use of PLC-VCOM software, go to the chapter PLC – VCOM and look there
for operating instructions.
6.2 Programming software to use with direct
access
After you have adjusted and connected the PLC-VCOM or the programming adapter to the COM-port on
your computer, you will be able to connect with your programming software
to the PLC and work with it.
How you have to adjust your programming software is described in the following points:
6.2.1 PG2000 für S7 (V5.10)
1. Start the PG 2000 software by using the desktop link or by using the application entry in the start menu.
2. Choose from “View” ⇒ “S7-300/400” In the menu “Options“ click “Interfaces“..
3. A dialog appears, in which you are able to set the “AG-Interface” (COM-port) in the section “Interfaces”.
4. Configure the baud rate in the section “Bus access“ to “19,2k“. Below change the value for PC - MPI to
“187,5kBaud“.
5. Save your configuration by pressing “OK“.
6. Now the software is ready to establish a connection to the PLC Click the symbol “Open“ and afterwards
press “PLC”. Alternative you can click:
„File“ ⇒ „Open“ ⇒ „PLC“
3. A Dialog with a list box named “Interface Parameter Assignment Used:” appears. This box should offer
some “PC - Adapter” entries If this is the case, please continue with the step MPI settings or Profibus
settings. If you can't find these entries go ahead with step PC-Adapter orTCP/IP installation.
6.2.2.1 PC-Adapter(Auto, MPI, PROFIBUS)
4. Click on „Choose“ to add these entries to the PG/PC interface configuration
\
5. In this dialog you can deinstall every installed construction set Furthermore you can add various
modules (see “Selection”) Choose „PC - Adapter“ from the „Selection“ box on the left side and click on
„Install“.
6. The chosen construction set will be installed and a question appears which asks you to use the “MPI“
access for the PLC used. Click “Yes“ if you want to use the „MPI“communication type. Otherwise click
“No“(e.g. if you want to use the “PROFIBUS“ communication type).
6.2.2.2 TCP/IP RFC1006 Communication
7. Press “Select” to add the RFC1006 required elements to the PG / PC - interface configuration.
8. In the dialog “Select”, choose“ TCP / IP” and click on “Install”.
9. After successful installation, click “Close”.
10. Back to the “Set PG/PC interface“ dialog you will now find the desired entries called “PC Adapter(Auto)“ (not supported), “PC - Adapter(MPI)“ and “PC - Adapter(PROFIBUS)“. Now you are able to
configure the bus. If you want to use the “MPI“communication type go ahead with step MPI setting . The
settings for “PROFIBUS” is explained in Profibus setting .
Configure the interface as described in Set PD/PC-Interface.
S7-USB user manual23 / 852019/10/05 05:07
To use one of the other options please go ahead and read in the manual of WinCC software.
5. Please wait until the project is created. The project content will be shown in the left part of the main
window.
1. Click in the drop - down menu “target system” on “Display Accessible Nodes”.
2. If you can see the list with possible Bus-devices, a communication over the cable has taken place.
“Direct” connected devices will be shown, also the conditions if it is an “active” or “passive” assembly.
3. In this window you can edit each assembly with his blocks.
6. For a proper working communication with the PLC there must be defined how the software has to
Configure the interface as described in Set PD/PC-Interface.
communicate with the PLC Therefore you have to right-click on “Tag Management” it opens the context
1. Start WinCC by using the desktop link or the program entry in the start menu.
menu. Choose “New Driver Connection … “.
2. Choose „New” in the menu „File” or click on the white („letter”) symbol to start a new project.
7. In the „Add new driver“ dialog select the driver which fits to your PLC For a S7 PLC choose „SIMATIC S7
Protocol Suite.chn“. If you want to use an other PLC please inform yourself first, which driver fits with your
PLC.
It is very important that the selected driver fits with the PLC otherwise the connection cannot be
3. The next dialog offers you several project types “Single-User Project”, “Multi-User Project” and “Client
established..
Project”. The next steps are the describing for the “Single- User Project”.
8. You should see now in the Explorer under the branch “Tag Management” the branch “SIMATIC S7
PROTOCOL SUITE”. Expand the branch and many protocols for various compounds will appear. The General
way of proceeding a new connection is to: Right-click on the desired connection (MPI - > Picture: “MPI“,
TCP/IP - > Picture: “TCP/IP“). A context menu opens. Click on „New Driver Connection…”. This manual
describes the connection configurations for MPI and TCP/IP
MPI
4. “OK” leads you to a new dialog. Type in the “Project Name” and the “Subfolder” of the project path. The
chosen configuration is confirmed with “Create”.
9. Now you are able to type in the name of the connection. With a click on “Configuration“ a new dialog
will appear. Now you are able to set the properties of the connection. Set up the station address of the PLC
(in this example “2“). Confirm with “OK” until you are back to the main window. Read further
”Communication and fault diagnosis “ .
10. A dialog appears where you can configure the connection parameters. Set up the IP - Address of the
module and configure the rack number as well as the slot number. Confirm this configuration by clicking
“OK”. Example configuration:
IP - address 192.168.1.55
Rack - Number: 0
Slot - Nr.: 2
11. With a right-click on the new connection you can start the properties dialog. In this dialog please click
on properties.
12. In this “Channel unit properties” you are able to see all “available connections”. Choose the latest
created connection and click again on „Properties”. Now you can see all the variables which has been
created for this connection. In fact this connection is a new connection so there should not be any variable
in the list. To add a new variable click on „New”.
13. Now you are able to set up the name of the variable and different more properties. In our example, we
assign the following values: Name: „S7LAN_MW0“
Data type : „unsigned 16 - Bit value“
Length: „2“
Address: „MW0“
Format adaptation: „WordToUnsignedWord“ Click on „Choose” beside the Address to define the address
from the variable.
Example configuration: The data area from the variable is set to „Mark“ and the address is set to „Word”.
The edit box „MW“ is set to „0”.
14. Confirm all open dialogs with „OK“ until you reach the main window.
15. The connection needs to know which network interface card it should be used to send data via the
S7-USB user manual26 / 852019/10/05 05:07
Loading...
+ 59 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.