TracoPower TXL 100-24S, TXL 100-15S, TXL 100-0512D, TXL 100-48S, TXL 100-0524D Installation Instructions Manual

...
INSTALLATION INSTRUCTIONS
TXL 100/150 Series Switching Power Supply
TXL 100-3.3S
TXL 100-05S TXL 100-12S TXL 100-15S TXL 100-24S
TXL 100-48S TXL 100-0512D TXL 100-0524D
TXL 100-0521T TXL 100-0522T TXL 100-0533T TXL 100-0534T
TXL 150-12S
TXL 150-24S
TXL 150-48S
AC-Input
Voltage Range
88 – 264VAC
Universal
Input
Output
Power max.
87.5 Watt 3.3V / 25.0A 100 Watt 5.0V / 20.0A 100 Watt 12.0V / 8.5A 100 Watt 15.0V / 6.8A 100 Watt 24.0V / 4.5A 100 Watt 48.0V / 2.1A 100 Watt +5.0V / 12.0A +12.0V / 5.0A 100 Watt +5.0V / 10.0A +24.0V / 3.0A 100 Watt +5.0V / 12.0A +12.0V / 5.0A -5.0V / 1.5A 100 Watt +5.0V / 12.0A +12.0V / 5.0A -12.0V / 1.5A 100 Watt +5.0V / 12.0A +15.0V / 3.0A -15.0V / 1.5A 100 Watt +5.0V / 12.0A +12.0V / 3.0A +24.0V / 2.0A 150 Watt 12.0V / 12.5A 150 Watt 24.0V / 6.3A 150 Watt 48.0V / 3.2A
* DC-Output 1 DC-Output 2 DC-Output 3
Recommended
Circuit breaker
10A
(Characteristic C)
* Output 1 adjustable by potentiometer with a screwdriver. Total output power must not exceed specified max output power.
Input current:
! TXL 100 ! TXL 150
Output Voltage Adjustment range: (Only single output models)
Operating temperature range: Natural Air Convection Cooling
Output Power Derating:
Storage temperature range: Non operating
Connections: T erminal for wiring: Y or Ring shape recommended (max. diameter = 8.0mm)
@ Vin=115VAC @ Vin=230VAC
1.65A typ. 0.95A typ.
2.10A typ. 1.10A typ.
±10% 0°C – +70°C max
32°F – +158°F max above +45°C # 2
above +50°C # 2.5 above 113°F # 2 above 122°F # 2.5%/K (TXL 100-xx Power Supplies)
-10°C – +75°C max
-13°F – +167°F max Screw type terminal COMBICON.
Recommended tightening torqu e 0.5 to 0.7Nm (4.5 t o 6.2l b.in.)
Power Consumption
! TXL 100 ! TXL 150
%
/K (TXL 100-xx Power Supplies)
%
/K (TXL 150-xx Power Supplies)
%
/K (TXL 100-xx Power Supplies)
@ Vin=115VAC @ Vin=230VAC
135 Watt typ. 130 Watt typ. 190 Watt typ. 180 Watt typ.
Case material: Aluminium base and nickel plated steel cover Mounting inserts:
http://www.tracopower.com Rev: 04/02
M3 x P0.5 7 different places; 3 on the side and 4 on the bottom.
Safety Instructions:
! Before installation read these instructions carefully and
completely. This installation instruction cannot account for every possible condition of installation, operation or maintenance. Further information can be obtained from your local distributor’s office or from the product data sheet, which can be downloaded, from the Internet at
www.tracopower.com/products/txl.pdf
! The power supplies are constructed in accordance with the
safety requirements of IEC/EN60950 and UL 1950. They fulfil the requirements for CE-compatibility and carries the CE mark. They are UL and cUL approved.
! Before any installation, maintenance or modification work
ensure that the main switch is switched off and prevented from being switched on again. Non-observance, touching of any live components or improper handling of this power supply can result in death, severe personal injury or substantial property damage. Proper and safe operation is dependent on proper storage, handling, installation and operation.
! Compliance with the relevant national regulations (in the
USA, Europe and other countries) must be ensured. Before operation is started the following conditions must be ensured:
$ Connection to mains supply in compliance wit h national
regulations (VDE0100 and EN50178).
$ By use of stranded wires, all strands must be fastened
in the terminal blocks. (Potential danger of contact with the case)
$ Power supply and mains cables must be sufficiently
fused.
$ The non-fused protective earth connection must be
connected to the FG terminal (Protection class I).
$ All output wires must be rated for the power supply
output current and must be connected with the correct polarity.
$ Sufficient cooling must be ensured.
! Never work on the power supply if power is supplied!
Risk of electric arcs and electrical shock, which can cause death, severe personal injury or substantial property damage.
.
Installation Instructions:
! This power supply is designed for professional indoor
systems. In operation the power supply must not be accessible. It may be installed and put into service by qualified personnel only.
! Do not operate without PE connection! To comply with
EMC and safety standards (CE mark, approvals) the power supply must be operated only if PE terminal is connected to the non-fused earth conductor.
! The correct mounting position for optimal cooling
performance must be observed. Do not cover any ventilation holes. Leave a fee space of minimum 50mm (2in.) above and on the sides of the power supply. Observe power derating. (see our TXL data sheet)
! The internal fuse is not accessible, as it may not be
replaced by the user. If this internal fuse has blown, the power supply has an internal defect and, for safety reasons, must be shipped to the local distributor. In case this internal fuse has to be replaced in the field, replace only with same type and rating of fuse for continued pro­tection against risk of fire.
! Recycling: The unit contains elements that are suitable for
recycling, and components that need special disposal. You are therefore requested to make sure that the power supply will be recycled environment friendly at the end of its service life.
!
Warning:
very substantial amount of energy are present in this power supply during normal operating conditions. Ho wever, these are inaccessible. Improper handling may result in an electric shock or serious burns!
Do not open the power supply until at least 5 minutes after it has been disconnected from the mains on all poles.
$ Only trained personnel may open the power supply. $ Do not introduce any objects into the power supply.
$ Keep away from fire and water
Hazardous voltages and components storing a
The output voltage adjustment potentiometer may only be actuated using an insulated screwdriver.
http://www.tracopower.com Rev: 04/02
Loading...