TRACOPOWER TEP 150WI Technical data

DC/DC Converters
TEP 150WI Series, 150 Watt
Features
Shielded metal case with screw terminals
Compact dimensions: 98 x 52 x 34 mm
Ultra-wide 4:1 input voltage range
Very high efficiency up to 87%
Constant current output characteristic for
battery load applications
Operating temp. range –40°C to +75°C
Reverse input protection
I/O isolation 2250 VDC (basic insulation)
Easy chassis and wall mounting
3-year product warranty
pending
The TEP-150WI Series is a family of high power density dc-dc converter modules with ultra-wide 4:1 input voltage range which come in an ultra-compact metal case with screw terminal connection. Suitable for a wide range of applications, the TEP-150WI series was particularly designed with industrial applications in mind. The modules have flanges for easy chassis or wall mounting. A very high efficien­cy allows an operating temperature up to +50°C with natural convection cooling. Further features include adjustable output voltage with constant current characteris­tic for battery charger applications.
Models
Order code* Input voltage Output voltage Output current max. Efficiency typ.
TEP 150-2412WI TEP 150-2413WI TEP 150-2415WI TEP 150-2416WI TEP 150-2418WI TEP 150-4812WI TEP 150-4813WI TEP 150-4815WI TEP 150-4816WI TEP 150-4818WI
* – add suffix –N for negative remote control, see page 3 -> Remote On/Off
http://www.tracopower.com
9 – 36 VDC
(24 VDC nominal) 24 VDC 6.3 A 86 %
18 – 75 VDC
(48 VDC nominal) 24 VDC 6.3 A 87 %
12 VDC 12.5 A 85 % 15 VDC 10 A 85 %
28 VDC 5.4 A 86 % 48 VDC 3.2 A 86 % 12 VDC 12.5 A 86 % 15 VDC 10 A 86 %
28 VDC 5.4 A 87 % 48 VDC 3.2 A 87 %
Page 1 of 4
DC/DC Converters
TEP 150WI Series 150 Watt
Input Specifications
Input current at no load 24 Vin, 12 – 15 VDC models: 80 mA typ. 24 Vin, 24 – 48 VDC models: 95 mA typ. 48 Vin, 12 – 15 VDC models: 60 mA typ. 48 Vin, 24 – 48 VDC models: 75 mA typ.
Input current at full load 24 Vin models: 7.7 A typ. 48 Vin models: 3.8 A typ.
Start-up voltage / under voltage shut down 24 Vin models: 8.8 VDC / 8.2 VDC typ. 48 Vin models: 17.6 VDC / 16.5 VDC typ
Surge voltage (100 msec. max.) 24 Vin models: 50 V 48 Vin models: 100 V
Conducted noise (input) EN 55022 level A, FCC part 15, level A without external components
ESD (electrostatic discharge) EN 61000-4-2, air ±8 kV, contact ± 6 kV, perf. criteria A
Radiated immunity EN 61000-4-3, 10 V/m, perf. criteria A Fast transient / Surge EN 61000-4-4, ± 2 kV, perf. criteria A
EN 61000-4-5, ± 1 kV perf. criteria A With external input capacitor e.g. Nippon
chemi-con KY 200 µF, 100 V, ESR 48 mOhm or with chassis mount option –CFM
Conducted immunity EN 61000-4-3, 10 Vrms, perf. criteria A Reverse voltage protection parallel diode Recommended input fuse (slow blow) 24 Vin models: 15 A
48 Vin models: 10 A
Output Specifications
Voltage set accuracy ±1% Output voltage adjustment +20% by external resistor see application note:
www.tracopower.com/products/tep150wi-application.pdf
Regulation – Input variation Vin min. to Vin max. 0.2 % max. – Load variation 0 – 100 % 0.4 % max.
Temperature coefficient ±0.02 %/K Minimum load not required Ripple and noise (20 MHz Bandwidth) 5 VDC models: 75 mVpk-pk max.
12 & 15 VDC models: 100 mVpk-pk max. 24 & 28 VDC models: 200 mVpk-pk max. 48 VDC models: 300 mVpk-pk max.
Start up time (nominal Vin and constant resistive load) 25 ms typ. (at power On or remote On) Transient response (25 % load step change) 200 µs typ. Output current limitation constant current at 105 -120 % of Iout max. Over voltage protection at 125 -140 % of Vout nom. Short circuit protection indefinite, automatic recovery Capacitive load 12 VDC models: 40‘000 µF max.
15 VDC models: 26‘000 µF max. 24 VDC models: 10‘000 µF max. 28 VDC models: 7‘600 µF max. 48 VDC models: 2‘600 µF max.
All specifications valid at nominal input voltage, full load and +25°C after warm-up time unless otherwise stated.