Datasheet TBL Datasheet (TRACOPOWER)

Features
UL 1310 UL 508
CB
Scheme
IEC/EN 60950-1
Low profile case, module height only 55mm
Fits into flat control panels used in
building automation
Safety class ll product
UL508 listed
5 power ranges from 15 to 150 W
Universal input range 85 to 264 VAC
Operating temperature range:
–25 °C to +70 °C max.
Adjustable Output Voltage
Short circuit and overload protection
Industrial Power Supplies
TBL Series, 15 to 150 Watt
DC–OK indicator
Easy snap-on mounting on DIN-rail
3 year product warranty
The TBL series is a new range of small DIN-rail mount power supplies which have been designed particularly with building- and factory automation applications in mind. The ultra-compact low profile cases fit in the standardized wall mounted con­trol panels used in the building automation industry. The power supplies can be operated at full load across an ambient temperature range of –25°C to +60°C with­out need of additional cooling. Universal input voltage range and full compliance with all important safety and EMC standards qualifies the TBL series power sup­plies for worldwide markets. For commercial and residential applications requesting safety class ll the product is approved to UL 1310.
Models
Order Code Output Power
(max.)
TBL 015-105 12 W 5.0 VDC 2.4 A TBL 015-112 12 VDC 1.25 A TBL 015-124 TBL 030-112 12 VDC 2.5 A TBL 030-124 TBL 060-112 12 VDC 4.5 A TBL 060-124 TBL 090-112 12 VDC 6.0 A TBL 090-124 TBL 150-124 150 W 24 VDC 6.25 A
15 W
30 W
60 W
90 W
Output Voltage*
(nom.)
24 VDC 0.63 A
24 VDC 1.25 A
24 VDC 2.5 A
24 VDC 3.75 A
* adjustable
Output Current
(max.)
http://www.tracopower.com Page 1 of 3
Industrial Power Supplies
TBL Series 15 to 150 Watt
Input Specifications
Input voltage – nominal 100 – 240 VAC – AC range 85 – 264 VAC (output power derating 5 %/V for opertion below 90 VAC)
Input frequency 47 – 63 Hz Harmonic limits EN 61000-3-2, Class A Efficiency at 230 VAC (typ.) – TBL 015-105 model: 73 %
– TBL 015 / 030 models: 81 % – TBL 150 model: 87 % other models: 85 %
Output Specifications
Output voltage adjustable range 5 VDC model: 5.0 – 5.2 VDC 12 VDC models: 12 – 16 VDC 24 VDC models: 24 – 28 VDC
Output regulation 1 % Ripple and noise (20MHz bandwidth) < 100 mV pk-pk Electronic short circuit protection current limitation at 100 – 150 % typ.
(automatic recovery) Hold-up time 115 VAC 230 VAC
min. 10 ms min. 20 ms
General Specifications
Temperature ranges – Operating – 25 °C to +70 °C max. Power derating 2.5 %/K above 60 °C Humidity (non condensing) 5 – 95 % rel. H Temperature coefficient 0.02 %/K Safety standards UL 508, UL 1310, class II
IEC/EN 60950-1, UL 60950-1, EN 50178, EN 60204, EN 61558-2-8 CSA C22.2 No. 60950-1 2003
Safety approvals – CB report IEC/EN 60950 -1 report in process – UL approval UL 508 listed, www.ul.com -> certifications UL 1310, www.ul.com -> certifications
File no. to be adviced
CSA certification UL 60950-1, CSA 60950-1-03
report in process
– GS certification EN 60950-1, EN 60204, EN 61558-2-8 report in process
Electromagnetic compatibility (EMC), emissions EN 61000-6-3 – Conducted RI suppression on input EN 55022 class B – Radiated RI suppression EN 55022 class B
Electromagnetic compatibility (EMC), immunity EN 61000-6-2 – Electrostatic discharge (ESD) EN 61000-4-2 4 kV / 8 kV – Radiated RF field immunity EN 61000-4-3 3 V/m – Electrical fast transient / burst immunity EN 61000-4-4 1 kV / 0.5 kV – Surge immunity line – ground EN 61000-4-5 2 kV – Surge immunity line – line EN 61000-4-5 1 kV – Surge immunity output EN 61000-4-5 0.5 kV – Immunity to conducted RF disturbances EN 61000-4-6 3 V – Mains voltage dips and interruptions EN 61000-4-11 30 % /10 mS, 60 % /100 mS
http://www.tracopower.com Page 2 of 3
J
enatschstrasse 1 · CH-8002 Zurich · Switzerland
Tel. +41 43 311 45 11 · Fax +41 43 311 45 45 · info@traco.ch · www.tracopower.com
Industrial Power Supplies
Vadj
59.5 (2.34)
37.1 (1.46)
21.1 (0.83)
69.5 (2.74)
45.0 (1.77)
89.5 (3.52)
54.5 (2.15) W
TBL Series 15 to 150 Watt
General Specifications
Safety class degree of protection class II Case protection IP 20 (IEC 60529)
Environment – Vibration acc. IEC 60068-2-6; 3 axis, sine sweep, 10 – 55 Hz, 0.075 mm – Shock acc. IEC 60068-2-27 3 axis, 15 g half sine, 11 ms
Enclosure material plastic FR2010-110C (UL 94V-0 rated) Mounting DIN-rails as per EN 50022-35x15/7.5
(snap-on with self-locking spring)
Connection screw terminals with combi-type screw heads for wire size 0.5 – 1.5 mm²
Installation instructions www.tracopower.com/products/tbl_inst.pdf
Case Dimensions
AC Input DC Output DC Output
Model Width (W) Weigth* TBL 015 TBL 030 TBL 060 TBL 090 TBL 150
26.3 (1.04) 100 (3.53)
52.5 (2.07) 160 (5.64)
70.0 (2.76 230 (8.11)
105.0 (4.13) 340 (12.0) 175 (6.89) tba
Dimensions in [mm], () = Inch Tolerances: ±0.5 mm (±0.02)
Wiring
Description Wire size
all models: L, N only (2 pin terminal) AWG 26 – 16 / 1.5 mm² max.
15 – 30 W models: single terminal AWG 26 – 14 / 1.5 mm² max.
60 – 150 W models: double terminal AWG 26 – 14 / 1.5 mm² max.
Specifications can be changed any time without notice.