Tracer TP-9365 User Manual

OPERATOR’S MANUAL
TP-9365
Vacuum/Micron Gauge
Declaration of Conformity
This is to certify that this equipment, designed and supplied by Tracer Products, a division of Spectronics Corporation, 956 Brush Hollow Road, Westbury, New York 11590, USA, meets the essential safety requirements of the European Union and is placed on the market accordingly. It has been constructed in accordance with good engineering practice in safety matters in force in the Community and does not endanger the safety of persons, domestic animals or property when properly installed and maintained and used in applications for which it was made.
Equipment Description PRO-Vac™ Vacuum/Micron Gauge Applicable Directives 73/23/EEC as amended by 93/68/EEC 89/336/EEC as amended by 93/68 EEC Applicable Standards EN 61010-1: 1993 EN 61326: 2000-11, EMC Cl A, Immunity Criteria B CE Implementation Date January, 2002
Any questions relative to this declaration or to the safety of this product should be directed, in writing, to Tracer Products’ Customer Service Department at the address above.
Introduction
The Tracerline® PRO-Vac™ Vacuum/Micron Gauge is a digital gauge designed to accurately measure vacuum levels during evacuation of air conditioning and refrigeration systems from atmosphere down to 1 micron (0.01 mbar, 1 Pa). It uses a proprietary Pirani sensor, the most accurate sensor in its class.
3
Operating Instructions
1. Remove the battery access cover and install the 9-volt battery. An indicator on the display will turn on when the battery needs to be replaced.
2. Connect a dedicated or new charging hose to the PRO-Vac’s tting. a. A previously used hose may contain oil that could affect the
sensor performance.
b. Normal refrigeration hoses do outgas (leak) which may make
it diffi cult to measure below 250 microns. We suggest using a metal braided hose for better accuracy.
c. We recommend using a hose no longer than 3 feet. A longer
hose may make the gauge unable to read lower vacuum levels due to excessive outgassing.
3. Connect the other end of the hose directly to either the high or low side of the system for most accurate readings. For convenience, you can also connect the hose to one of the ports on the vacuum pump itself. To connect the gauge in-line with a manifold set or the vacuum pump, you will need a separate 1/4 inch male by 1/4 inch male by 1/4 inch female T fi tting.
Warning: Pressures greater than 150 psi can damage the sensor. Be sure the system’s refrigerant has been recovered before connecting the PRO-Vac.
4. Turn the PRO-Vac on by pressing the On/Off button. Readings
greater than 1500 will be displayed as 3 digits followed by the
X1000
indicator. For example, a reading of 100,000 is displayed
X1000
as 100
.
5. The PRO-Vac will turn off automatically after 1 hour when
the vacuum reading is above 30,00 microns The last reading before auto shutdown and MEMORY are displayed for 5 seconds when the unit is turned back on. Auto shutdown
4
is disabled when the vacuum level is below 30,000 microns. However, you can turn the PRO-Vac off or on at any pressure.
Vacuum Units Selection
The PRO-Vac can display vacuum in units of microns, mbar, or Pascal. To change units, press and hold the power button for 3 seconds during power-up and the indicator for the active unit ashes. Briefl y press the power button to select the desired units. Press and hold the power button for 1 second to save the setting.
Quick Calibration
The PRO-Vac has a quick calibration feature to allow for equalization to different atmospheric pressures. Press CAL to activate. CAL fl ashes on the display and the reading stabilizes at 760 x 1000. The gauge will maintain this reference point until a new one is set. NOTE: Quick calibration is disabled at vacuum levels below 100,000 microns.
Changing the Filter
The PRO-Vac is equipped with a special fi lter to protect the vacuum sensor from oil and other contaminants. To change the lter, remove the setscrew in the unit’s fi tting. See Figure 1. Use an 11/16” wrench to stabilize the top portion of the fi tting. Then twist off the lower portion of the fi tting using a 1/2” wrench. Use needlenose pliers or a similar item to gently pull out the used lter. Do not attempt to clean or reuse fi lters. Insert a new fi lter with the thicker portion of the O-ring facing away from the gauge’s body. Reattach the refrigerant fl are. Tighten the fi tting with the wrenches and replace the setscrew to ensure vacuum integrity.
5
Figure 1. PRO-Vac Fitting
Remove setscrew and stabilize with 11/16” wrench.
Place 1/2” wrench here and twist off to disassemble fi tting.
Insert new fi lter with a thicker portion of the O-ring facing away from the gauge body, as shown.
Specifi cations
Usage Indoor or outdoor Humidity 95% RH NC max. Battery One 9 volt alkaline Battery life 45 hours Operating temperature 0 °C to 50 °C Pressure range atm. to 1 micron Pollution degree 2 Overvoltage category 2 Altitude 2000 m Weight 7.25 oz Storage temperature -10 °C to +60 °C Accuracy <2000 microns 5%
>2000 microns 10%
Replacement Parts
Replacement parts and accessories for your PRO-Vac are available through the same dealer from whom you bought the instrument.
Replacement, fi lters, package of 5 125920
6
Warranty and Liability
Your PRO-Vac Vacuum/Micron Gauge is of the fi nest design and craftsmanship. As such, Tracer Products warrants that when delivered it will be free from defects in manufacture.
Tracer Products’ obligation under this warranty is limited to repairing or replacing, at the option of Tracer Products, any part(s) of the product which, if properly installed, used and maintained, proves upon factory examination to have been defective in materials or workmanship within one year from the date of delivery.
Tracer Products does not warrant items that deteriorate under normal use, including power cells and sensors. In addition, Tracer Products does not warrant any instrument that has been subjected to misuse, negligence or accident, or has been repaired or altered by anyone other than Tracer Products.
This warranty is in place of all other warranties of quality. There are no other warranties either oral, written, express, implied or statutory. IMPLIED WARRANTIES OF FITNESS FOR PURPOSE AND MERCHANTABILITY ARE EXCLUDED. This warranty and your remedies thereunder are solely as stated in this manual. In no event shall Tracer Products be liable for special, indirect, incidental or consequential damages, nor for any damages arising out of delay in shipment or production.
Return Authorization Procedure
A defective PRO-Vac should be returned to your wholesaler for warranty evaluation. If you have any questions, please contact the Customer Service Department at Tracer Products.
NOTE: Do not return your defective unit directly to the factory without fi rst contacting Tracer Products for a Return Authorization Number.
7
AM08048
074-494-P34
Printed in U.S.A.