Trace Engineering PS Series, PS2512, PS2524, PS2212E, PS2524E Owner's Manual

PS Series Inverter/Chargers
AE Configuration - Revision 5 Software
Owner’s Manual
Copyright Trace Engineering Company, Inc. 5916 - 195th Street N. E. Arlington, WA 98223
Telephone: 360/435-8826
Fax: 360/435-2229
www.traceengineering.com
PS Series Inverter/Charger
Part No. 3597
TABLE OF CONTENTS
TABLE OF CONTENTS
IMPORTANT SAFETY INSTRUCTIONS......................................................................................................................................3
GENERAL PRECAUTIONS..........................................................................................................................................................3
SPECIAL NOTICES......................................................................................................................................................................3
PERSONAL PRECAUTIONS........................................................................................................................................................4
INTRODUCTION...............................................................................................................................................................................5
UNIT IDENTIFICATION...................................................................................................................................................................7
MODEL NUMBER.........................................................................................................................................................................8
CERTIFICATION..........................................................................................................................................................................8
CONTROLS, INDICATORS AND COMPONENTS.....................................................................................................................9
ON/OFF POWER SWITCH...........................................................................................................................................................9
INVERTER/CHARGER CIRCUIT BREAKER..............................................................................................................................10
CIRCUIT BREAKERS.................................................................................................................................................................10
‘MAXIMUM AC AMPS IN’ SWITCH ............................................................................................................................................10
LED STATUS INDICATORS.......................................................................................................................................................10
AC SIDE.....................................................................................................................................................................................13
DC SIDE.....................................................................................................................................................................................15
INSTALLATION.............................................................................................................................................................................17
LOCATION.................................................................................................................................................................................17
MOUNTING................................................................................................................................................................................18
VENTILATION............................................................................................................................................................................18
AC WIRING................................................................................................................................................................................18
DC WIRING................................................................................................................................................................................21
QUICK INSTALL.........................................................................................................................................................................26
FUNCTIONAL TEST.....................................................................................................................................................................27
MENU SYSTEM .............................................................................................................................................................................29
OVERVIEW................................................................................................................................................................................29
USER MENU MAP......................................................................................................................................................................30
SETUP MENU MAP....................................................................................................................................................................31
SWRC REMOTE CONTROL......................................................................................................................................................32
USER MENU ..............................................................................................................................................................................35
SETUP MENU............................................................................................................................................................................44
OPERATION...................................................................................................................................................................................55
THEORY OF OPERATION.........................................................................................................................................................55
POWER VS. EFFICIENCY .........................................................................................................................................................56
INVERTER CAPACITY VS TEMPERATURE .............................................................................................................................57
OPERATING MODES .................................................................................................................................................................58
INVERTER MODE......................................................................................................................................................................59
CHARGER MODE ......................................................................................................................................................................62
INVERTER/CHARGER MODE ...................................................................................................................................................68
GENERATOR SUPPORT MODE ...............................................................................................................................................70
AUTOMATIC GENERATOR CONTROL MODE .........................................................................................................................72
UTILITY BACK-UP MODE..........................................................................................................................................................80
UTILITY INTER-ACTIVE MODE.................................................................................................................................................82
ENERGY MANAGEMENT MODES............................................................................................................................................89
USING MULTIPLE INVERTERS .................................................................................................................................................92
TECHNICAL INFORMATION......................................................................................................................................................95
BATTERIES................................................................................................................................................................................95
APPLICATIONS........................................................................................................................................................................108
TROUBLESHOOTING GUIDE..................................................................................................................................................109
INVERTER/CHARGER TERMINOLOGY .................................................................................................................................114
SPECIFICATIONS AND FEATURES ........................................................................................................................................117
DIMENSIONS...........................................................................................................................................................................118
INSTALLATION DIAGRAMS ....................................................................................................................................................120
USER SETTINGS WORKSHEET.............................................................................................................................................122
APPENDIX....................................................................................................................................................................................127
OPTIONS..................................................................................................................................................................................127
OTHER PRODUCTS................................................................................................................................................................129
Copyright Trace Engineering Company, Inc. 5916 - 195th Street N.E. Arlington, WA 98223
Telephone: 360/435-8826
Fax: 360/435-2229
www.traceengineering.com
PS Series Inverter/Charger
Part No. 3597
Page
1
TABLE OF CONTENTS
REFERENCE TABLES & GRAPHS..........................................................................................................................................130
WARRANTY/REPAIR INFORMATION ....................................................................................................................................133
LIMITED WARRANTY..............................................................................................................................................................133
WARRANTY REGISTRATION..................................................................................................................................................133
LIFE SUPPORT POLICY..........................................................................................................................................................133
WARRANTY OR REPAIR SERVICE REQUIRED ....................................................................................................................134
INDEX ............................................................................................................................................................................................135
INDEX OF FIGURES
Figure 1, Identification Label.........................................................................................................................................................7
Figure 2, Certification Label..........................................................................................................................................................8
Figure 3, Inverter Controls and Indicators ....................................................................................................................................9
Figure 4, ‘Maximum AC Amps In’ Switch And LED Status Indicators.........................................................................................10
Figure 5, PS Series AC Side.......................................................................................................................................................13
Figure 6, AC Circuit Board..........................................................................................................................................................13
Figure 7, AC Terminal Block.......................................................................................................................................................14
Figure 8, AC Ground Terminal....................................................................................................................................................14
Figure 9, PS Series DC Side.......................................................................................................................................................15
Figure 10, Airflow Intake Location..............................................................................................................................................18
Figure 11, AC Wire Connections................................................................................................................................................19
Figure 12, Warning Label...........................................................................................................................................................21
Figure 13, Battery to Inverter Cable Connection.........................................................................................................................23
Figure 14, Multiple Point Ground System ...................................................................................................................................25
Figure 15, Single Point Ground System......................................................................................................................................25
Figure 16, SWRC (Remote Control) ...........................................................................................................................................32
Figure 17, Trace PS Series Inverter/Charger Simple Block Diagram..........................................................................................55
Figure 18, Trace PS Series Inverter/Charger Output Waveform.................................................................................................56
Figure 19, Inverter Capacity vs. Temperature............................................................................................................................57
Figure 20, Three-Stage Battery Charging...................................................................................................................................62
Figure 21, BTS (Battery Temperature Sensor)...........................................................................................................................63
Figure 22, Relay RY7 and RY8 Sequence.................................................................................................................................75
Figure 23, Two-Wire Start Wiring Diagram.................................................................................................................................76
Figure 24, Three Wire Start Wiring Diagram (HONDA Type).....................................................................................................77
Figure 25, Three Wire Start Wiring Diagram (ONAN Type)........................................................................................................77
Figure 26, Selling Power from a DC Charging Source; Hypothetical Time of Day Operational History......................................84
Figure 27, Selling Power Stored in the Batteries; Hypothetical Time of Day Operational History...............................................85
Figure 28, Utility Interactive Line-Tie System with Battery Backup (120VAC models)................................................................87
Figure 29, Overvoltage Protection for Battery............................................................................................................................88
Figure 30, Series Configuration: 6-Volt Battery Wiring.............................................................................................................104
Figure 31, Series Configuration: 12-Volt Battery Wiring...........................................................................................................104
Figure 32, Parallel Configuration: 12-Volt Battery Wiring.........................................................................................................105
Figure 33, Series-Parallel Configuration: 6-Volt Battery Wiring................................................................................................106
Figure 34, Series-Parallel Configuration: 12-Volt Battery Wiring..............................................................................................106
Figure 35, AC Waveforms ........................................................................................................................................................115
Figure 36, PS Series Dimensions.............................................................................................................................................118
Figure 37, PS Series Bottom Plate Mounting Dimensions........................................................................................................119
Figure 38, PS Series – Showing Knockout Sizes for AC Wiring...............................................................................................119
Figure 39, PS Series Installation Diagram – Stationary Backup System..................................................................................120
Figure 40, PS Series Installation Schematic.............................................................................................................................121
Figure 41, AWG Wire Size.......................................................................................................................................................131
INDEX OF TABLES
Table 1, Recommended Minimum AC Wire Sizes To Breaker/Fuse Size at 75° C.....................................................................19
Table 2, Minimum Recommended Battery Cable Size Vs. Cable Length...................................................................................21
Table 3, Battery Cable to Maximum Breaker/Fuse Size.............................................................................................................22
Table 4, AC Input Default Settings .............................................................................................................................................64
Table 5, Battery Charger Default Settings..................................................................................................................................65
Table 6, Charging Setpoints for Common Battery Types ...........................................................................................................66
Table 7, Typical Wattage of Common Appliances....................................................................................................................100
Table 8, Battery Charging: Charging Setpoints ........................................................................................................................101
Table 9, Battery State of Charge Voltage Table.......................................................................................................................102
Table 10, Battery Cable Inductance.........................................................................................................................................107
Table 11, Typical Power Consumption of Common Appliances...............................................................................................130
Table 12, AWG to Metric Wire Conversion Chart.....................................................................................................................130
Table 13, Battery Cable to Maximum Breaker/Fuse Size.........................................................................................................131
Table 14, AC Input Default Settings .........................................................................................................................................131
Table 15, Battery Charger Default Settings..............................................................................................................................132
Table 16, Minimum Recommended Battery Cable Size Vs. Cable Length...............................................................................132
Table 17, Recommended Minimum AC Wire Sizes (75° C)......................................................................................................132
Table 18, Safety Ground Wire Size Table................................................................................................................................132
Page
2
Copyright Trace Engineering Company, Inc. 5916 - 195th Street N.E. Arlington, WA 98223
Telephone: 360/435-8826
Fax: 360/435-2229
www.traceengineering.com
PS Series Inverter/Charger
Part No. 3597
IMPORTANT SAFETY INSTRUCTIONS
IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS!
This manual contains important safety and operating instructions as prescribed by UL Standards for the Trace Engineering PS Series Inverter/Chargers for use in residential and commercial applications. This manual specifically covers products with the revision 5.* (* refers to all revisions from 5.0 to 5.9) software.
GENERAL PRECAUTIONS
1. Before using the PS Series Inverter/Charger, read all instructions and cautionary markings on: (a) the inverter/charger; (b) the batteries and; (c) all appropriate sections of this manual.
2. CAUTION - To reduce risk of injury, charge only deep-cycle lead acid, lead antimony, lead calcium, gel cell, absorbed glass mat, or NiCad/NiFe type rechargeable batteries. Other types of batteries may burst, causing personal injury and damage.
3. Do not expose inverter/charger to rain, snow or liquids of any type. The inverter is designed for indoor mounting only. Protect the inverter from splashing if used in vehicle applications.
4. Use of an attachment not recommended or sold by Trace Engineering for the PS Series Inverter/Charger may result in a risk of fire, electric shock, or injury to persons.
5. Do not disassemble the inverter/charger. Take it to a qualified service center when service or repair is required. Incorrect re-assembly may result in a risk of electric shock or fire.
6. To reduce risk of electric shock, disconnect all wiring before attempting any maintenance or cleaning. Turning off the inverter will not reduce this risk. Solar modules produce power when exposed to light. Cover them with opaque material before servicing any connected equipment.
7. WARNING – RISK OF EXPLOSIVE GASSES (a) WORKING IN VICINITY OF A LEAD ACID BATTERY IS DANGEROUS. BATTERIES
GENERATE EXPLOSIVE GASES DURING NORMAL BATTERY OPERATION. FOR THIS REASON, IT IS OF UTMOST IMPORTANCE THAT EACH TIME BEFORE SERVICING EQUIPMENT IN THE VICINITY OF THE BATTERY, YOU READ THIS MANUAL AND FOLLOW THE INSTRUCTIONS EXACTLY.
(b) To reduce risk of battery explosion, follow these instructions and those published by the battery
manufacturer and manufacturer of any equipment you intend to use in the vicinity of the battery. Review cautionary markings on these products and on engine.
SPECIAL NOTICES
1. Tools required to make AC and DC wiring connections: Wire strippers; 1/2" (13MM) open-end or socket wrench; Phillips #2 screwdriver; flat blade 1/4" (6MM) screwdriver.
2. No terminals or lugs are required for hook-up of the AC wiring. AC wiring must be copper wire and rated for 75 °C or higher. The maximum wire size for the AC terminals is #6 AWG (4.11 mm diameter). Battery cables must be rated for 75°C or higher. Crimped and sealed copper ring terminal lugs with a
5/16 hole should be used to connect the battery cables to the DC terminals of the inverter/charger. Soldered cable lugs are also acceptable.
3. Torque all AC wiring connections to 20 inch-pounds. Torque all DC cable connections to 10-15 foot­pounds. Be extra cautious to reduce the risk of dropping a metal tool onto batteries. It could short­circuit the batteries or other electrical parts resulting in sparks that could cause an explosion.
4. This inverter/charger is intended to be used with a battery supply with a nominal voltage that matches the last two digits of the model number, e.g. 12-Volt with a PS2512.
5. For instructions on mounting, see the MOUNTING section on page 18 of this manual.
Copyright Trace Engineering Company, Inc. 5916 - 195th Street N.E. Arlington, WA 98223
Telephone: 360/435-8826
Fax: 360/435-2229
www.traceengineering.com
PS Series Inverter/Charger
Part No. 3597
Page
3
IMPORTANT SAFETY INSTRUCTIONS
6. NOTE: Do not use the keyhole mounting slots for permanent installations. For battery installation and maintenance read the battery manufacturer's installation and maintenance instructions prior to operating.
7. No AC or DC disconnects are provided as an integral part of this inverter. Both AC and DC disconnects must be provided as part of the system installation. Refer to the INSTALLATION section beginning on page 17 for more information.
8. No overcurrent protection for the battery supply is provided as an integral part of this inverter. Overcurrent protection of the battery cables must be provided as part of the system installation. Refer to the INSTALLATION section beginning on page 17 and the DC DISCONNECT AND OVERCURRENT PROTECTION section on page 21 for more information.
9. No over current protection for the AC output wiring is provided as an integral part of this inverter. Overcurrent protection of the AC output wiring must be provided as part of the system installation. Refer to the INSTALLATION section beginning on page 17 and the AC WIRING section on page 18 for more information.
10. The AC output neutral conductor and DC negative conductors are not connected (bonded) to the inverter chassis. Both the input and output conductors are isolated from the enclosure and each other. System grounding, if required by sections 690-40, and 690-42 of the National Electric Code, ANSI/NFPA 70-1996, is the responsibility of the system installer. All installations must comply with local and national electrical codes and standards.
11. GROUNDING INSTRUCTIONS - This inverter/battery charger should be connected to a grounded, permanent wiring system. For most installations, the negative battery conductor should be bonded to the grounding system at one (and only one point) in the system. All installations should comply with national and local codes and ordinances. Refer to the SYSTEM GROUNDING section on page 24 for more information.
PERSONAL PRECAUTIONS
1. Someone should be within range of your voice or close enough to come to your aid when you work near batteries.
2. Have plenty of fresh water and soap nearby in case battery acid contacts skin, clothing, or eyes.
3. Wear complete eye protection and clothing protection. Avoid touching eyes while working near batteries. Wash your hands when done.
4. If battery acid contacts skin or clothing, wash immediately with soap and water. If acid enters eye, immediately flood eye with running cool water for at least 15 minutes and get medical attention immediately.
(a) Baking soda neutralizes lead acid battery electrolyte. (b) Vinegar neutralizes spilled NiCad and NiFe battery electrolyte. (c) Keep a supply on hand in the area of the batteries.
5. NEVER smoke or allow a spark or flame in vicinity of a battery or generator.
6. Be extra cautious to reduce the risk of dropping a metal tool onto batteries. It could short-circuit the batteries or other electrical parts that may result in a spark which could cause an explosion.
7. Remove personal metal items such as rings, bracelets, necklaces, and watches when working with a battery. A battery can produce a short-circuit current high enough to weld a ring or the like to metal, causing severe burns.
8. NEVER charge a frozen battery.
9. If necessary to remove the battery, make sure all accessories are off. Then, remove the grounded terminal from the battery first.
10. If a remote or automatic generator start system is used, disable the automatic starting circuit and/or disconnect the generator from its starting battery while performing maintenance to prevent accidental starting.
Page
4
Copyright Trace Engineering Company, Inc. 5916 - 195th Street N.E. Arlington, WA 98223
Telephone: 360/435-8826
Fax: 360/435-2229
www.traceengineering.com
PS Series Inverter/Charger
Part No. 3597
INTRODUCTION
INTRODUCTION
Congratulations! You are the proud owner of the finest inverter on the market today - and one very complex piece of equipment. The Trace Engineering PS Series Inverter/Charger has many features and capabilities previously either non-existent, or found only in separate products.
With proper installation, the inverter will operate satisfactorily for many applications straight out of the box using the factory default settings. To fully utilize the inverter's generator inter-active, or utility inter-active capabilities, it is necessary to understand the way the inverter operates and then tailor its operation via the SWRC and the user and setup menu systems. This manual will provide the necessary information. However, it is recommended that you consult with your authorized dealer to ensure correct installation and maximum utilization of the numerous features of this product. If you do not understand any aspect of the installation, contact your authorized dealer/installer for assistance.
If you intend to operate the inverter in a utility inter-active mode in which power will be sold to the utility, you must contact the local utility office and get their approval. The utility may require additional information that may not be included in this manual. Please contact your Trace Engineering dealer/installer for assistance.
This manual is specific to models designed for use in Alternative Energy or Back-Up Power systems in permanent structures, such as homes and commercial buildings. As a minimum, you should read the sections of the manual that relate to your type of installation. The MENU SYSTEM section, beginning on page 29, explains how to make changes to the inverter’s user/setup menus. The OPERATION section, beginning on page 55, explains how the inverter works in each of its different modes. Focus on the Operating Modes that relate best to your type of installation and make the appropriate selections and adjustments. Installation diagrams are provided for many of the various applications. This menu system provides control of the inverter, allows features to be enabled, and allows setting of operating parameters.
This is a long manual and much of it is technical. Throughout the manual terms may be used that are unfamiliar, see the INVERTER/CHARGER TERMINOLOGY glossary on page 114 for clarification. If you are an insomniac, properly used, this manual is guaranteed to provide several good nights of sleep.
This manual is specific to REVISION 5* PS AE software . Using the optional SWRC Remote Control, you can verify what revision software your inverter is using by selecting third menu item under the TRACE
ENGINEERING (3) menu heading. Note: * refers to all revisions from 5.0 to 5.9
Before beginning -
Unpack the inverter/charger and verify that you have the correct inverter.
Record your model number and serial number below for future reference
Verify that you have everything listed on the Packaging Checklist sheet included in your box. If any
items are missing, please call Customer Service at (360) 435-8826.
Complete the warranty card and mail it to Trace Engineering within 10 days from the date of purchase Keep your bill of sale as proof of purchase, should any difficulties arise concerning the registration of the warranty card.
Keep the original carton and packing materials It is the best way to keep the inverter safe if it needs to be moved.
Read this manual and enjoy your inverter/charger!
Model Number: _________________________________ Serial Number: __________________________________
Check out our web site at www.traceengineering.com for more information and answers to your FAQ’s
Copyright Trace Engineering Company, Inc. 5916 - 195th Street N.E. Arlington, WA 98223
Telephone: 360/435-8826
Fax: 360/435-2229
www.traceengineering.com
PS Series Inverter/Charger
Part No. 3597
Page
5
INTRODUCTION
Page
6
Copyright Trace Engineering Company, Inc. 5916 - 195th Street N.E. Arlington, WA 98223
Telephone: 360/435-8826
Fax: 360/435-2229
www.traceengineering.com
PS Series Inverter/Charger
Part No. 3597
CONTROLS, INDICATORS AND COMPONENTS
DC Input Voltage
Model Number
DC Charging Amps
Configuration
Product Code
Quarter and Year of
Certification Label
UNIT IDENTIFICATION
This section describes the marking and location of the model and serial number for the PS Series Inverter/Chargers. Use this section to determine the type and model of your inverter/charger. The unit Identification Label on the left side panel of the inverter/charger will show the model number, serial number, DC charging current (maximum and default setting), AC voltage and frequency, configuration, and date of manufacture.
Note: Ensure you have entered your serial number and model number on page 5 for future reference.
Operating Range
Manufacture
and Serial Number
Figure 1, Identification Label
Copyright Trace Engineering Company, Inc. 5916 - 195th Street N.E. Arlington, WA 98223
Telephone: 360/435-8826
Fax: 360/435-2229
www.traceengineering.com
PS Series Inverter/Charger
Part No. 3597
Page
7
CONTROLS, INDICATORS AND COMPONENTS
MODEL NUMBER
The model Number of your inverter determines the different features your unit may have. Consider the following unit with a PS2512 model number:
PS 25 12 *
Model Power Nominal
AC Voltage/Options
DC Voltage
Model: The first letter(s) indicate the model, in this case the PS Series. Power: The first and second positions in the Model Number indicate the continuous AC power output in
hundreds of VA (Volt-Amps). Power levels available start at 1800 up to 2500 Volt-Amps with different DC voltages. In the example above, 25 would stand for a 2500 VA (2.5 kVA) continuous-output inverter.
DC Voltage (Input and Output): The number (12) following the Power rating indicates the nominal battery voltage this inverter/charger requires. The inverter/charger uses this battery voltage to convert to an AC voltage output, and charge the batteries that are connected when powered by the same AC voltage. The number (24) indicates a 24v inverter/charger
AC voltage/Options: The letter(s) following the DC Voltage rating indicate the particular configuration or particular option (s) this inverter/charger is specifically designed to provide. See the SPECIFICATIONS
AND FEATURES section on page 117 for the different voltage and frequency models available. Configuration:
AE: These models are designed for use in Alternative Energy or Back-Up Power systems in permanent structures such as homes and commercial buildings. These units are used where the neutral is required to be “polarized” (or connected) permanently to the safety ground at the AC panel.
MOBILE: These models are designed for use in mobile (RV/Marine) applications. They feature 120 VAC, 60 Hz output and employ automatic ground-to-neutral switching which “polarizes” the inverter’s AC output when operating in Inverter mode and allows the external AC source to “polarize” the neutral when the inverter is in Charge mode.
CERTIFICATION
Figure 2, Certification Label The 120 VAC/60 Hertz models of the PS Series Inverter/Chargers (AE Configured) are Listed to UL
Standard 1741, Power Conditioning Units for use in Residential and Commercial Photovoltaic Power Systems. This label is your guarantee that this inverter/charger has been tested by UL to nationally
recognized Safety Standards and found to be free from reasonably foreseeable risk of fire, electric shock and related hazards. These units are also Listed to CAN/CSA-22.2 No. 107.1-M91, which means these models have been evaluated to Canadian safety requirements, which may be somewhat different from U.S. safety requirements.
This inverter/charger is intended to be installed in a residential or commercial application. This unit should not be installed in an application for which it is not listed (i.e. Land Vehicles or Marine Craft). The inverter may not be damaged; however, it would not comply with safety code requirements and may cause other problems. .
Page
8
Copyright Trace Engineering Company, Inc. 5916 - 195th Street N.E. Arlington, WA 98223
Telephone: 360/435-8826
Fax: 360/435-2229
www.traceengineering.com
PS Series Inverter/Charger
Part No. 3597
CONTROLS, INDICATORS AND COMPONENTS
‘Maximum AC
On/Off Power
AC SIDE
DC SIDE
AC Circuit Board
FRONT SIDE
Inverting/Charger
CONTROLS, INDICATORS AND COMPONENTS
Shown below are the controls and indicators on the PS Series Inverter/Charger. They enable you to control and monitor the operating mode and system status of your inverter/charger. The controls on the PS Series Inverter/Chargers are very straightforward. They feature a momentary On/Off Power switch, an inverting/charger circuit breaker, four LED status indicators, a two-position switch for determining maximum AC input current level and connecting ports for other optional accessories.
The figure below shows the location of the different controls and the Status Indicators .
Branch Circuit
Breakers
(Optional)
AC Circuit Breaker.
Switch
(Inside, under
Access Panel)
Switch and LED
Status Indicators
Figure 3, Inverter Controls and Indicators
ON/OFF POWER SWITCH
Amps In’
SET INVERTER OFF SRCH ON CHG
This switch allows turning the inverter ON and OFF, enabling the SEARCH mode or selecting the charger only mode CHG. The on/off button also resets the inverter in the event it shuts down completely due to a fault condition. The inverter always starts in the OFF position when powered up. Each push changes the mode you are in, continue pressing the ON/OFF power switch until you have your desired selection. Monitor the INVERT (yellow) LED to determine what mode you have selected.
OFF: Disables the inverter. This is the default position of the inverter upon power-up. When the
OFF position is selected, no power will be provided to the AC loads even if an AC source is
available. The red ERROR LED will be on, this indicates that there is no AC available on the output and the INVERT (yellow) LED will be off.
SRCH: Enables the automatic load search mode control system. This system will turn on the
inverter if a large enough load is connected. If not enough AC loads are detected, the INVERT (yellow) LED will blink slowly (one blink/sec). No power will be provided to the AC loads, even if an AC source is available. The sensitivity threshold is defaulted to 48 watts.
SET INVERTER OFF SRCH ON CHG
SET INVERTER OFF SRCH ON CHG
SET INVERTER OFF SRCH ON CHG
ON: Allows the inverter to provide AC voltage to the output and energize the AC loads either from the
battery or from any “synchronized” AC source available on the input. The INVERT (yellow) LED will be on.
CHG: Allows the inverter to operate only as a battery charger. AC power will be available to the AC
loads only if an AC source is available and “synchronized”. This mode is used to prevent discharge of the batteries by the AC loads when a utility outage occurs. The INVERT (yellow) LED will double blink each second (double blink/sec) to indicate that you are in CHG mode. This mode is only available when the SET GRID USAGE menu item is in the FLT mode under the INVERTER SETUP (9) menu heading. When a different mode is selected, this position will be locked out and it will be necessary to use the SET POINTS buttons on the optional SWRC remote to move the cursor. Selecting the CHG mode disables the Automatic Generator Start features.
Copyright Trace Engineering Company, Inc. 5916 - 195th Street N.E. Arlington, WA 98223
Telephone: 360/435-8826
Fax: 360/435-2229
www.traceengineering.com
PS Series Inverter/Charger
Part No. 3597
Page
9
CONTROLS, INDICATORS AND COMPONENTS
‘Maximum AC Amps In’
LED Status Indicators
INVERTER/CHARGER CIRCUIT BREAKER
This circuit breaker protects the unit’s internal wiring while the unit is inverting or charging. It is not used for the pass-through current, which is rated for 50 amps AC. This is not a branch circuit rated breaker, output breakers are required. Press the breaker to reset.
CIRCUIT BREAKERS
An optional, field installable, Breaker Kit can be ordered which will allow direct hook-up up of up to two circuits without the use of a separate sub-panel. The Breaker Kit is available with a single 15 or 20 amp branch circuit rated breaker.
‘MAXIMUM AC AMPS IN’ SWITCH
This switch determines the AC current level at which the inverter begins to back-off the battery charger or operates in parallel to reduce the load on a generator. This prevents the overloading of the AC source and prevents nuisance tripping of the AC source circuit breakers. Typically, this is set to the size of the AC source's (Utility Power or Generator) circuit breaker feeding the inverter or the maximum output amperage ability of the AC source.
The switch can be switched to the AC1 side to limit the input current to 50 Amps or to the AC2 side to limit the input current to 30 amps.
The maximum AC input amp size can be adjusted to different settings in the SET GRID (AC1) AMPS AC and the SET GEN (AC2) AMPS AC menu items using the optional SWRC remote.
switch
Figure 4, ‘Maximum AC Amps In’ Switch And LED Status Indicators
LED STATUS INDICATORS
All PS Series Inverter/Chargers feature four LED status indicators - located on the unit’s front side panel ­that will enable you to monitor the operating mode and system status of your inverter/charger by lighting one or more of the LED’s. The different colored LED’s will light based on the condition or operating mode of the inverter/charger. Refer to the LED colors below to determine you unit’s status.
GREEN = AC IN
ON: An AC source has been applied to the AC input terminals of the inverter. When an AC source is
connected to the input terminals the green LED indicator will come on. After a delay period has passed and once synchronized, the inverter will close an internal relay to connect the AC source to the AC loads and the inverter will begin to charge the battery and the orange LED indicator will turn solid.
Page
Copyright Trace Engineering Company, Inc. 5916 - 195th Street N.E.
10
Arlington, WA 98223
Telephone: 360/435-8826
Fax: 360/435-2229
www.traceengineering.com
PS Series Inverter/Charger
Part No. 3597
CONTROLS, INDICATORS AND COMPONENTS
RED = ERROR
ON: Indicates that there is no AC voltage available on the output. The red error LED is used in conjunction
with the yellow (invert) LED to determine the operating mode of the inverter. If the red LED is on and the yellow (invert) LED is off, then the inverter is in standby (DC power connected but not turned on) and is ready to turn on. With the red LED on and the yellow LED blinking twice a second with a one second pause, then the inverter is in the CHG (charge only) mode and waiting for AC to be connected to the input. If the red LED is on and the yellow (invert) LED is flashing rapidly (4 times/second), this indicates that an error condition exists. Refer to the INVERT (yellow) LED for more information on error causes.
YELLOW = INVERT
OFF – INVERTER/CHARGER IS OFF: The inverter is off and not operational. This is the default position
of the inverter upon power-up. No AC output is available. ON – INVERTER/CHARGER ON: The inverter is operational and AC output is available. Inverter is
providing AC power from the batteries or the input AC source is providing pass-thru power to the output. ONE BLINK/SEC – SEARCH: The yellow LED will blink once each second to indicate the inverter is in
search mode and is looking for an AC load greater than the SEARCH WATTS setting (default = 16 watts). DOUBLE BLINK/SEC – CHARGE ONLY MODE (CHG): The yellow LED will double blink then pause for
a second to indicate that the unit is in Charge Only mode. RAPID BLINK (4/SEC) – ERROR MODE: The yellow LED will blink rapidly to indicate that an operating
error has occurred. This can be caused by over-load or over-current, over-temperature (transformer or heatsink), high or low battery voltage, AC source wired to the output, or an external (stacked) error. When the inverter senses one of these situations, it may protect itself by disconnecting from the loads. There are also advisory and numerous generator-related errors that will not disconnect the AC loads. Refer to each error cause below to help determine your particular error cause.
ERROR CAUSES (AC OUTPUT WILL BE DISCONNECTED):
If an over-current condition exists, the inverter will shutdown and must be reset with the power button. If the error condition is based on over-temperature (transformer or heatsink), or high or low battery voltage the error protection circuitry resets automatically.
Low Battery voltage : Your battery voltage is below the LOW BATTERY CUT OUT (LBCO) VDC setting and the inverter has shut off to prevent over-discharge of the battery. Allow the battery to recharge or connect to an AC source such as a back-up generator. The inverter will reset when the battery exceeds the LBCO setting.
Low inverter voltage : Your inverter/charger monitors the minimum AC voltage level of the AC output. This assures a continuous supply of quality Alternating Current to your electrical loads. The inverter AC output voltage level is determined by the SET INPUT LOWER LIMIT VAC setting. If the AC voltage falls below this setting continuously for 32 seconds the inverter disconnects from the loads and turns on the error LED. The cause for this error could be high battery voltage or an excessively large load.
High Battery voltage : The inverter turns off due to a high battery voltage condition determined by the HBCO (HIGH BATTERY CUT-OUT) setting. This can be caused by the solar array or other charging
source not being regulated. Check the controller for proper operation. Some controllers have a “equalize” setting which over-rides the normal operation, allowing the battery voltage to be unregulated. Return the controller to the “normal” setting and check for proper operation. If you are using NiCad type batteries, you will need to increase the HBCO setting. The inverter will automatically reset once the battery voltage has dropped 1.5 volts below the HBCO setting.
Over-temperature (Transformer or Heatsink) : The transformer or power transistors have exceeded their safe operating temperature and the inverter has turned off. When operating as a battery charger, the inverter will reduce its charging rate to prevent overheating. As an inverter, overheating can be caused by attempting to operate too large of a load for too long, a failure of the inverter cooling fans, or that the air flow into or out of the inverter is being blocked. The inverter will automatically reset once it has cooled. While the inverter has shut down, AC power from any AC source may not continue to pass through the inverter to power AC loads. Any power management provided by the inverter will not be able to occur while the inverter is off.
Copyright Trace Engineering Company, Inc. 5916 - 195th Street N.E. Arlington, WA 98223
Telephone: 360/435-8826
Fax: 360/435-2229
www.traceengineering.com
PS Series Inverter/Charger
Part No. 3597
Page
11
CONTROLS, INDICATORS AND COMPONENTS
Over-current: The load requirement has exceeded the maximum output AC amps. To clear this fault,
disconnect the loads and restart the inverter. To restart the inverter after an overcurrent fault condition, press the On/Off Power Switch only one time. Reconnect the loads one at a time to find the load or combination of loads that caused the problem. If the inverter will not restart with all the AC loads disconnected, remove all AC wiring from the terminal block and try to restart again. If it restarts, the problem is with the wiring. If it does not restart, refer to the other error causes to determine the error.
AC source wired to output: Reports that an AC voltage source was connected directly to the AC output. This can be caused by improper wiring or incorrect installation of the inverter. This condition is much worse than a short circuit and may cause damage to the inverter. Disconnect all wiring from the AC input and output to find the cause. After the cause has been found and corrected, you can restart the inverter by selecting OFF and then ON or SRCH with the On/Off Power Switch
External error (stacked): A problem has occurred with the series interface cable or one of the inverters operated in series. Check the cable for damage and replace it to see if the problem is corrected. Also, check the connecting input and output AC wiring.
ERROR CAUSES (WILL NOT CAUSE AC OUTPUT TO BE DISCONNECTED). Low AC input voltage: Your inverter/charger monitors single cycle voltage problems from the AC
source. The low AC voltage level is determined by the SET INPUT LOWER LIMIT VAC setting. If the AC voltage falls below this setting the INVERT (yellow) LED will flash rapidly and remain on for 3 minutes. This error is an advisory error only and will not drop the AC input.
High AC input voltage: Your inverter/charger monitors single cycle voltage problems from the AC source. The high AC voltage level is determined by the SET INPUT UPPER LIMIT VAC setting. If the AC voltage rises above this setting the INVERT (yellow) LED will flash rapidly and remain on for 3 minutes. This error is an advisory error only and will not drop the AC input.
Generator failed to start: Indicates that the automatic generator start system was not able to successfully start the generator. The system completes five start cycles and requires that the generator operate for a minimum of 5 minutes before the starting attempts counter is cleared. To manually clear this error, press the green GEN MENU button on the SWRC to access the SET GENERATOR menu item, then select OFF and then AUTO or ON.
Generator stopped due to V/F: Indicates that the automatic generator start system was not able to successfully connect to the generator after it was running. If the generator runs for 10 minutes without operating in the AC voltage and frequency tolerance windows, then the automatic start system stops the generator and indicates an error condition. To manually clear this error, press the green GEN MENU button on the SWRC to access the SET GENERATOR menu item, then select OFF and then AUTO or ON.
Gen Max Run Time: An ERROR LED will turn on if the generator run time has exceeded the SET MAXIMUM RUN TIME setting. This setting is intended to indicate excessive generator operation because
the system has not been able to fully charge the battery. Operating heavy loads while charging, an unstable generator or even low electrolyte levels in the battery can cause this. If the default value results in repeated error conditions, then increasing the setting may be necessary for your application. This may occur with systems that have very large batteries that require long charge periods or systems with small generators that have limited battery-charging ability. This ERROR is an advisory indication only and will not stop the generator. You can reset this ERROR LED by selecting OFF and then ON from the SET GENERATOR menu item, accessed by pressing the green GEN MENU button on the SWRC.
Gen speed error: Indicates that the automatic generator start system has detected that the generator frequency is not well adjusted. This error condition will cause the red ERROR LED to illuminate, but will not cause the automatic generator start system to shut down. If the inverter can not synchronize to the generator after a 10-minute period, then the GEN SPEED ERROR condition will be reached.
ORANGE = CHARGE
ON: This orange LED will be lighted when the unit is charging. The inverter is charging at a constant
current, causing battery voltage to rise near the BULK VOLTS DC setting (default = 14.4 VDC). Once at this level, the current will taper off until the battery charger has maintained the batteries near the BULK VOLTS DC setting for the time period of the ABSORPTION TIME setting, at which time it then regulates the charging process at the FLOAT VOLTS DC setting.
Page
12
Copyright Trace Engineering Company, Inc. 5916 - 195th Street N.E. Arlington, WA 98223
Telephone: 360/435-8826
Fax: 360/435-2229
www.traceengineering.com
PS Series Inverter/Charger
Part No. 3597
CONTROLS, INDICATORS AND COMPONENTS
AC Ground
Accessory
AC terminal block
AC circuit board
ACCESS
AC TERMINAL
AC SIDE
knockout
AC knockouts
(located inside)
(located inside)
Terminal
(located inside)
Figure 5, PS Series AC Side
AC CIRCUIT BOARD
By removing the Access Panel, you will be able to gain access to the AC circuit board, which includes the AC terminal block and four RJ11 jacks for connecting specific optional components.
PANEL
Figure 6, AC Circuit Board
RC8AUX GEN BTS
BLOCK
AUX - RJ11 connection jack for the optional plug-in Auxiliary Relay Module. The Auxiliary Relay Module consists of two voltage-controlled relays and is used to simplify installations that have battery voltage related tasks to perform. The relays are single pole double throw, five amp relays. Both the normally closed and normally open contacts are available for each relay. The operation of each relay is individually controlled and adjustable with a SWRC via the user menu. The auxiliary relays on the AUXILIARY RELAY MODULE operate independently of the inverter or charger.
Copyright Trace Engineering Company, Inc. 5916 - 195th Street N.E. Arlington, WA 98223
Telephone: 360/435-8826
Fax: 360/435-2229
www.traceengineering.com
PS Series Inverter/Charger
Part No. 3597
Page
13
CONTROLS, INDICATORS AND COMPONENTS
cover - is used to connect the exposed chassis of the inverter to the
AC grounding system. This terminal accepts wires from #14 AWG to
GEN - RJ11 connection jack for the optional plug-in Generator Relay Module. The Generator Relay Module consists of signal relays and allows connection and automatic control of “two-wire” type generators. The relays are single pole double throw, five amp relays. Both the normally closed and normally open contacts are available for each relay. The operation of each relay is controlled and adjustable with a SWRC via the user menu.
RC8 - RJ11 connection jack for the optional plug-in RC8 remote. Allows remote On/Off control of the inverter at a distance of up to 50 (RC8/50) or 100 (RC8/100) feet away, functionally identical to the On/Off Power Switch on the inverter.
BTS - RJ11 connection jack for the plug-in external Battery Temperature Sensor (BTS). The BTS automatically fine-tunes the charging process of the battery charger in relation to temperature. If the temperature sensor is NOT installed and if the battery is subjected to large temperature variations, a shorter battery life cycle may be expected.
AC TERMINAL BLOCK
AC HOT OUTPUT AC NEUTRAL OUTPUT AC NEUTRAL OUTPUT
AC NEUTRAL INPUT
AC HOT INPUT
Figure 7, AC Terminal Block
A five pole terminal block is provided for hardwiring the inverter’s AC output the AC input connections. It is located on the left-hand side of the inverter, enclosed under the access panel. The terminal block will accept wire up to #6 AWG.
Depending on your unit’s configuration (See the UNIT IDENTIFICATION section on page 7 to determine your unit’s particular configuration) the AC input and output neutrals are configured differently.
This manual is specific to models designed for use in Alternative Energy or Back-Up Power systems in permanent structures, such as homes and commercial buildings. All of the PS Series units marked with the Alternative Energy configuration are designed with the three NEUTRAL terminals being common to each other and can be used in any combination or order. It is often simpler to only connect one AC neutral wire to the inverter and make the other neutral connections at a central point such as at an AC load center, etc. The additional AC NEUTRAL OUTPUT is provided for use when installing the optional Branch Breaker Kit.
AC GROUND TERMINAL
The AC Safety Ground Terminal - assessable through the AC access
#2 AWG.
Figure 8, AC Ground Terminal
Page
Copyright Trace Engineering Company, Inc. 5916 - 195th Street N.E.
14
Arlington, WA 98223
Telephone: 360/435-8826
Fax: 360/435-2229
www.traceengineering.com
PS Series Inverter/Charger
Part No. 3597
DC SIDE
Positive
Negative
DC Ground
Remote Port
CONTROLS, INDICATORS AND COMPONENTS
Battery Cable
Hook-Up
Stacking Port
SWRC or SWCA
Battery Cable
Hook-Up
Connection
Figure 9, PS Series DC Side
STACKING PORT
The stacking port allows two PS Series Inverter/Chargers (AE configuration models only) to be used in the same system. The inverters can be used in a “SERIES” configuration to operate 240 VAC loads and to connect to 120/240 VAC power systems. A series stacking interface cable (SWI) is required to connect the series stacking ports of the inverters. This port is also used to connect two units in a “PARALLEL” configuration. The parallel stacking interface cable (SWI/PAR) allows two inverters to be connected to provide twice the continuous and surge capability at the same AC voltage. See the USING MULTIPLE INVERTERS section on page 92 for more information.
REMOTE PORT
The PS Series can be controlled remotely from the unit by plugging in a SWRC remote control or SWCA communications adapter. See the OPTIONS section starting on page 127 for a complete description of the SWRC and SWCA.
BATTERY POSITIVE & NEGATIVE TERMINALS
These terminals are where you connect your battery cables. WARNING: Ensure your battery/cable polarity is correct, this inverter is not reverse polarity protected. If the positive terminal of the battery
is connected to the negative terminal of the inverter and vice versa, the result will be instantaneous failure of nearly every power transistors. Color-code the cables with colored tape or heat shrink tubing [the standard is red for positive (+) and black for negative (-)] and double-check the polarity with a voltmeter before making the battery connections.
DC EQUIPMENT/CHASSIS GROUND TERMINAL
This connection is used to connect the exposed chassis of the inverter to the DC grounding system. The terminal accepts wires from #14 AWG to #2 AWG.
Copyright Trace Engineering Company, Inc. 5916 - 195th Street N.E. Arlington, WA 98223
Telephone: 360/435-8826
Fax: 360/435-2229
www.traceengineering.com
PS Series Inverter/Charger
Part No. 3597
Page
15
CONTROLS, INDICATORS AND COMPONENTS
Page
16
Copyright Trace Engineering Company, Inc. 5916 - 195th Street N.E. Arlington, WA 98223
Telephone: 360/435-8826
Fax: 360/435-2229
www.traceengineering.com
PS Series Inverter/Charger
Part No. 3597
INSTALLATION
INSTALLATION
This section is very important, since it tells you how to properly install your PS Series Inverter/Charger. It becomes very frustrating when your inverter system does not perform properly, simply because care was not taken during installation. Please read this entire section carefully. You will save time and avoid common mistakes.
This section also describes the requirements and recommendations for installing the PS Series Inverter/Charger. In the U.S., the National Electrical Code (NEC) defines the standards for both the AC and DC wiring in residential and commercial applications. It will list the requirement for wire sizes, overcurrent protection and installation methods and requirements. There are still many other variables not covered by the NEC. Most are determined by the level of automatic operation, the amount of external AC and DC power to be controlled and the loads to be operated.
The NEC standards and regulations are described here in general for your convenience, and are not represented as comprehensive or complete. For comprehensive and complete official standards and regulations, write the addresses listed below:
NFPA - National Fire Protection Association
National Electrical Code Handbook
1 Batterymarch Park, PO Box 9101 Quincy, MA 02269-9101 617-770-3000.
Before beginning the installation of the PS Series Inverter/Charger, read all instructions. Disconnect all sources of AC and DC power to prevent accidental shock. Disable and secure all AC and DC disconnect devices and automatic generator starting devices.
All installations should meet local codes and standards and be performed by qualified personnel such as a licensed electrician. Although the DC electrical system may be “low voltage”, significant
hazards may be present, particularly from short circuits of the battery system. Inverter systems by their nature involve power from multiple sources (inverter, generator, utility, batteries, solar arrays etc.) that add hazards and complexity that can be very challenging.
After you have finished installing your unit, continue with the FUNCTIONAL TEST section on page 27. This functional test should be completed prior to configuring your unit’s Menu System for your specific operation.
LOCATION
Inverters are sophisticated electronic devices and should be treated accordingly. Treat the inverter as you would any fine piece of electronic equipment. When selecting the location to install the inverter, don't think of it in the same terms as the other interfacing equipment, e.g. batteries, diesel generators, motor generators, washing machines etc. This is a highly complex microprocessor controlled device. There are nearly 500,000 silicon junctions in its output devices and integrated circuits. The crystal oscillator runs at 4 megahertz. The drive circuitry timing is accurate to a thousandth of a second. Genetically speaking, it is a cousin to stereo equipment, television sets or computers. The use of conformal-coated circuit boards, plated copper bus bars, powder coated metal components, and stainless steel fasteners improves tolerance to hostile environments. However, in a corrosive or condensing environment (one in which humidity and/or temperature change cause water to form on components) all the ingredients for electrolysis are present ­water, electricity and metals. In a corrosive or condensing environment, the life expectancy of the
inverter is indeterminate and the warranty is voided if corrosion is the cause of failure.
Caution: It is in your best interests to install the inverter in a dry, protected location away from sources of fluctuating or extreme temperatures and moisture. Exposure to saltwater is particularly destructive and potentially hazardous.
Locate the inverter as close to the batteries as possible in order to keep the battery cable length short. However, do not locate the inverter above the batteries or in the same compartment as vented batteries. Batteries generate hydrogen sulfide gas , which is very corrosive to electronic equipment and everything else. They also generate hydrogen and oxygen. If accumulated, an arc caused by the connecting of battery cables or the switching of a relay could ignite this mixture. Mounting the inverter in a ventilated enclosure with sealed batteries is acceptable.
Copyright Trace Engineering Company, Inc. 5916 - 195th Street N.E. Arlington, WA 98223
Telephone: 360/435-8826
Fax: 360/435-2229
www.traceengineering.com
PS Series Inverter/Charger
Part No. 3597
Page
17
INSTALLATION
This inverter can create RFI (Radio Frequency Interference). Keep this in mind when determining the placement of the inverter. You should locate the inverter as far away as possible from any electronic devices that may be susceptible to RFI.
MOUNTING
UL Standard 1741 requires that the inverter be mounted on a vertical surface (on a wall) and that the keyhole slots not be used as the only method of mounting. The purpose of the wall mounting requirement is to orient the inverter so that its bottom cover, which has no holes, will not allow burning material to be ejected in case of an internal fire. Use 1/4” minimum diameter bolts for mounting. The mounting must be capable of supporting twice the weight of the inverter in order to comply with UL 1741.
VENTILATION
Installation of the inverter in a properly ventilated area/enclosure is necessary for efficient operation of the unit. The inverter’s thermal shutdown point will be reached sooner than normal in a poorly ventilated environment and will result in a lower peak power output, reduced surge capability, and potentially shorter inverter life. Note: Do not operate the inverter in a closed-in area or restrict ventilation in any way.
Testing has shown that the volume of the area/enclosure is not as important as the overall ventilation. A minimum airspace clearance of 1-½ inches around the top and 3 inches of clearance at the right side of the inverter will provide adequate ventilation. Because the bottom of the PS Series chassis is not vented, clearance between the enclosure and the bottom of the inverter is not critical. A fresh air intake port should be provided directly to the right side and an exhaust port on the top side will allow cool outside air to flow through the inverter and back out of the enclosure.
AIR FLOW
Figure 10, Airflow Intake Location
AC WIRING
This section describes AC wiring requirements and recommendations; including AC connections; wire sizing; overcurrent devices; GFCI’s; external relays; hookup procedure; and neutral-to-ground switching. Your local electrical code and the National Electrical Code (NEC) define the standards for AC installation wiring, but there are still many installation variables to be considered. Consult the local code and the NEC for the proper wire sizes, connectors and conduit. All installations should meet all local codes and
standards and be performed by qualified personnel such as a licensed electrician. AC WIRE CONNECTIONS IMPORTANT PRECAUTIONS - The AC OUTPUT of the inverter must at no time be connected
directly to utility power or a generator. This condition can be far worse than a short circuit. If the inverter survives this condition, it will shut down until corrections are made.
A five position terminal block is provided to make the AC connections. The terminal block is located on the left-hand side of the inverter, enclosed under an access panel (see page 9 for exact location). The terminal block is used to hardwire all AC connections.
Page
18
Copyright Trace Engineering Company, Inc. 5916 - 195th Street N.E. Arlington, WA 98223
Telephone: 360/435-8826
Fax: 360/435-2229
www.traceengineering.com
PS Series Inverter/Charger
Part No. 3597
INSTALLATION
Before making any AC connections, make sure that the inverter is disconnected from the battery (or battery bank). Feed the wires through conduit fittings located on the left side or left bottom side of the inverter. (Note: Conduit fittings must be purchased separately and are required by code to comply with residential and commercial installations).
The NEC requires that disconnect switches be provided in the AC input and output wiring circuits. AC circuit breakers in an AC load center can be used to meet this requirement. The wiring both in and out of the inverter must also be protected from short circuits and overloads by a fuse or circuit breaker. Consult the NEC or your local code for more information and for other wire sizes. Table 1 on page 19 gives suggestions for wire sizing.
ACCESSORY INPUT
AC GROUND OUT
AC HOT OUT
AC NEUTRAL OUT
AC GROUND IN
AC HOT IN
AC NEUTRAL IN
Figure 11, AC Wire Connections
The three neutral terminals are common to each other and can be used in any combination or order. It is often easier to only connect one AC neutral wire to the inverter and make the other neutral connections at a central point such as in the AC load center, etc. The extra output neutral is used if installing the optional Branch Breaker Kit. Consult your local code for more information and acceptable wire sizes and configurations.
Use Table 1, below, to determine the proper size wire you require for your installation. These recommendations may not meet all local code or the NEC requirements, consult your applicable electrical code for more information regarding acceptable fuse and cable sizes.
Table 1, Recommended Minimum AC Wire Sizes To Breaker/Fuse Size at 75° C
INVERTER MODEL
FULL
PASS-THRU
CAPABILITY
MAXIMUM
FUSE/BREAKER
REQUIRED
CABLE SIZE
REQUIRED
IN CONDUIT
CABLE SIZE
REQUIRED
IN “FREE AIR”*
PS2512/PS2524 50 amps 60 amps # 6 AWG (THHN) # 8 AWG (THHN)
PS2212E/PS2524E 30 amps 30 amps # 10 AWG (THHN) # 12 AWG (THHN)
* The term "free air" is defined by the NEC as cabling that is not enclosed in conduit or a raceway. Cables
enclosed in raceways or conduits have substantially lower continuous current carrying ability due to heating factors.
Copyright Trace Engineering Company, Inc. 5916 - 195th Street N.E. Arlington, WA 98223
Telephone: 360/435-8826
Fax: 360/435-2229
www.traceengineering.com
PS Series Inverter/Charger
Part No. 3597
Page
19
INSTALLATION
AC INSTALLATION GUIDELINES
The following steps are a basic guideline for connection of the AC wiring into and out of the inverter.
1. Disconnect the inverter from the battery bank (if already connected), by either removing the DC side fuse, or opening the DC disconnect. Then remove the AC wiring compartment cover from the front of the inverter by removing the two screws on the cover.
2. If conduit will be utilized (consult code, it may be required in your installation), determine which knockout(s) will be utilized and remove them from the inverter. The knockout sizes are shown in Figure 38, PS Series – Showing Knockout Sizes for AC Wiring on page119. Using appropriate conduit connectors, fasten the conduit to the inverter. Feed all AC wiring through the conduit and into the inverter AC terminal block. Be sure to leave yourself several extra inches of wire to work with. Remember that you need at least two sets of three conductor wiring, one for AC Hot, neutral, and ground into the inverter, and another for AC hot, neutral and ground out of the inverter to the loads. Torque all AC terminals to 10 to 15 inch-pounds .
3. Connect the hot (black) and neutral (white) wires from the AC source to the AC HOT IN and AC NEUTRAL IN terminals in the AC terminal block. The safety ground (green) should be connected to the terminal stud labeled “AC Ground” bolted to the chassis. Repeat the procedure for the AC wiring going to the AC sub-panel which will power the loads, except connect these wires to terminals labeled the AC HOT OUT and AC NEUTRAL OUT.
4. Inspect all wiring for proper installation and then replace and secure the access cover.
IMPORTANT PRECAUTION The AC output of the inverter must at no time be connected directly to utility power or a generator.
This condition can be far worse than a short circuit. If the inverter survives this condition, it will shut down until corrections are made. Connection to a utility or generator must be only done internally by the inverters built-in relays. This allows the inverter to first synchronize to the other AC sources waveform, preventing damage. Connect the utility or generator only to the provided AC HOT IN and AC NEUTRAL IN terminals. When the inverter output is connected directly to an external source, the inverter will shut down and indicate an error. With the SWRC connected, the ERROR CAUSES menu heading will show a YES for the AC SOURCE WIRED TO OUTPUT menu item. Either determine the source of the AC or call a qualified electrician to correct the situation.
EXTERNAL AC TRANSFER RELAYS
It is not acceptable to switch the AC input from one AC source to another while the inverter is connected. While the inverter is connected, switching the AC input from one source to another can result
in a loss of synchronization that can cause a severe overcurrent condition that is far worse than short circuiting the inverter. If a transfer relay is used, it must provide a center “OFF” (“break before make”)
position that causes a loss of input power to the inverter for a period of at least 100 milliseconds.
This will allow the inverter to disconnect from the original AC input and then re-synchronize to the new AC source though the AC input terminal. During the transition period, the inverter will have to operate the load while it re-synchronizes to the new AC source (about a thirty-second period at the minimum). Most transfer relays will switch too fast for the inverter to detect - and will cause the inverter to lose synchronization with the AC source. This is indicated by the inverter shutting down upon transfer and the red ERROR LED indicator turning on.
Manually, hand operated transfer switches may be acceptable since the transfer time can be slow enough for the inverter to detect. The switch must go through a center “OFF” position. They are often used to switch from one generator to another.
120 VAC GROUND FAULT INTERRUPT OUTLETS (GFI’S)
The following 120 VAC GFI's have been tested and found to work satisfactorily with our inverters:
LEVITON 6599 PASS & SEYMOR 1591 4A957 ACE Hardware ACE 33238
Page
20
Copyright Trace Engineering Company, Inc. 5916 - 195th Street N.E. Arlington, WA 98223
Telephone: 360/435-8826
Fax: 360/435-2229
www.traceengineering.com
PS Series Inverter/Charger
Part No. 3597
INSTALLATION
WARNING LABEL
A warning label is provided to inform all personnel that an inverter is installed in your electrical system. This label should be installed at the electrical panel that is being powered by the inverter. Be cautious until the inverter is disconnected from your electrical system.
!
Figure 12, Warning Label
DC WIRING
This section describes DC cabling requirements and recommendations including cable sizing, DC conductor ampacity ratings, overcurrent devices, terminals and lugs, and inverter terminal connections.
WARNING! Battery cables that are very small will melt and burn the first time the inverter is operated at high power levels. The inverter's maximum peak current requirements are high. If battery cables are too small and/or connections are loose, efficiency and maximum output power are degraded. Small cables or loose connections may cause dangerous overheating and a fire.
BATTERY CABLE SIZING
The larger the battery cables the better. Undersized cables result in additional stress on the inverter, lower efficiency, reduced surge power and lower peak output voltage. Don't use cables that are too small and degrade the efficiency that we have worked so hard to achieve and you have paid so much to own.
Also, don’t use cables that are too long - the shorter the better. The lower the DC system voltage, the shorter the cables need to be. If long cables are required, either oversize them substantially, or switch to a higher voltage system, such as 24 vdc or 48 vdc. On 12-vdc system, cables may need to be doubled up (paralleled) to get maximum performance from the inverter.
NOTE: Do not separate the positive and negative cables - taping them together in parallel is best. This reduces the inductance of the wire resulting in a better waveform and reduces the current in the inverter's filter capacitors. Make the battery cables as short as possible.
Although large cables may seem expensive, spending an additional $100 or more to ensure the performance of your inverter is a wise investment. Using cables that are too small is like putting cheap tires on a high performance sports car - the results will be disappointing.
If the system is expected to operate at the inverter’s continuous power level rating for long periods of time (over an hour), larger disconnects and cables may be required. Most systems do not operate at full capacity for periods exceeding an hour and can operate satisfactorily with the following cable and disconnects shown. If your system includes enormous batteries or has a very large DC source able to continuously power the inverter (such as a hydroelectric plant, etc.) then increasing the disconnect and cable sizes may be required to prevent nuisance tripping of a breaker or blowing of fuses.
The following table gives recommended minimum cable sizes for various cable lengths and inverter voltages. These recommendations may not meet all local or NEC code requirements. Use only copper cables.
Table 2, Minimum Recommended Battery Cable Size Vs. Cable Length
INVERTER MODEL
PS2512 267 amps #4/0 AWG / 67.4 mm2#4/0 AWG / 107 mm2Not Recommended
PS2524/PS2524E 134 amps #2/0 AWG / 67.4 mm2#2/0 AWG / 67.4 mm2#4/0 AWG / 107 mm
PS2212E 235 amps #2/0 AWG / 67.4 mm2#4/0 AWG / 107 mm2#4/0 AWG / 107 mm
Copyright Trace Engineering Company, Inc. 5916 - 195th Street N.E. Arlington, WA 98223
TYPICAL DC
AMPS
1 TO 3 FEET
ONE WAY
Telephone: 360/435-8826
Fax: 360/435-2229
www.traceengineering.com
3 TO 5 FT
ONE WAY
5 TO 10 FT
ONE WAY
PS Series Inverter/Charger
Part No. 3597
Page
2
2
21
INSTALLATION
DC DISCONNECT AND OVERCURRENT PROTECTION
For safety and to comply with regulations, battery over-current protection is required. Fuses and disconnects must be sized to protect the wiring in the system. The fuse or disconnect is required to open before the wire reaches its maximum current carrying capability.
For residential and commercial electrical systems, the National Electrical Code requires both overcurrent protection and a disconnect switch. These installation parts are not supplied as part of the inverter. However, Trace Engineering offers a DC rated, UL listed, circuit breaker disconnect specifically designed for use with Trace inverters for applications requiring NEC compliance. Two amperage ratings are available - a DC250 (250 amps) and a DC175 (175 amps). These disconnects are available in a single or double pole configuration to handle either one or two inverters. The DC disconnect enclosure will accommodate up to four smaller breakers for use as DC load disconnects, PV array disconnects, etc. and the top is designed to allow direct connection of up to two Trace Engineering charge controllers. The Trace DC disconnect is not designed to accept doubled (paralleled) cables which may be required for long cable runs. Also, the plastic red and black covers on the end of the inverter are not designed to accommodate dual cables. If dual cables are used, the optional conduit box (PSCB)) should be used.
When sizing the DC disconnect, the expected continuous load on the inverter is used to determine the DC current involved. You must account for the efficiency loss through the inverter, which increases the DC current draw. Divide the maximum continuous current draw by the lowest efficiency to determine the DC current, a 25% safety margin should be included to comply with the code requirements. When a breaker has been selected as the overcurrent device, tighter sizing may be acceptable since the breaker is more easily reset when compared to a high current, bolt-in type fuse.
Some installations may not require conduit or a means of disconnection, although overcurrent protection (fuse) is still required. Trace Engineering offers a fuseblock (TFB) that provides the code required inverter overcurrent protection for these applications.
TFB’s include a fast acting, current limiting class-T fuse to protect your battery, inverter and high amperage cables from damage by short circuits and overloads. This fuse provides extremely fast protection when a short circuit occurs. When properly selected, it also has a time delay that allows the inverter to surge to full power without blowing the fuse. A slide off cover prevents accidental contact with the fuse’s live terminals. For maximum protection, install the fuseblock within 18 inches (45 cm) of the battery. The fuses are available in 110, 200, 300, and 400 amp sizes.
Use Table 3 below, to determine the proper size disconnect (breaker) or fuse for the battery cables you are using. These recommendations may not meet all local code or the NEC requirements, consult your applicable electrical code for more information regarding acceptable fuse and cable sizes.
Table 3, Battery Cable to Maximum Breaker/Fuse Size
CABLE SIZE
REQUIRED
RATING IN
CONDUIT
MAXIMUM
BREAKER SIZE
RATING IN
“FREE AIR”
MAXIMUM
FUSE SIZE
00 AWG 175 amps 175 amps 265 amps 300 amps*
0000 AWG 250 amps 250 amps** 360 amps 400 amps*
* The NEC allows rounding up to the next standard fuse size from the cable rating, i.e. 150-amp cable size rounds up to a standard 175-amp size. The term "free air" is defined by the NEC as cabling that is not enclosed in conduit or a raceway. Cables enclosed in raceways or conduits have substantially lower continuous current carrying ability due to heating factors.
** Nuisance tripping is possible if operated at 2.5 kVA continuously with a 250-amp breaker
Contact your Trace dealer to order the inverter disconnects/fuses or see the OTHER PRODUCTS section on page 129 for more information.
Page
22
Copyright Trace Engineering Company, Inc. 5916 - 195th Street N.E. Arlington, WA 98223
Telephone: 360/435-8826
Fax: 360/435-2229
www.traceengineering.com
PS Series Inverter/Charger
Part No. 3597
INSTALLATION
BATTERY CABLE CONNECTIONS
Cables must have crimped (or preferably, soldered and crimped) copper compression lugs unless aluminum mechanical lugs are used. Soldered connections alone are not acceptable. We suggest using high quality, UL-listed Trace Engineering battery cables. These cables are available in a specific assortment of sizes from 1-½ to 10 feet, and in 2/0 or 4/0 AWG. They are color-coded and have pressure crimped, sealed ring terminals. Contact your Trace Engineering dealer to order. Figure 13, illustrates the proper method to connect the battery cables to the PS Series Inverter/Charger.
Do not place anything between
battery cable lug and terminal surface. Assemble exactly as
shown.
2/0 Copper Compression Lug 2/0 Aluminum Mechanical Lug
Figure 13, Battery to Inverter Cable Connection
INSTALLATION GUIDELINES - BATTERY CABLES Warning! This inverter is not reverse polarity protected. If the positive terminal of the battery is
connected to the negative terminal of the inverter and vice versa, the result will be instantaneous failure of nearly every power transistor. This type of damage is obvious and requires an extensive rebuilding of the inverter at your own cost. It is not covered by the warranty.
Ensure that the inverter is off before connecting or disconnecting the battery cables and that all AC power is disconnected from the inverter’s inputs.
Determine the correct size battery cable to use for your installation from Table 2, Minimum Recommended Battery Cable Size Vs. Cable Length on page 21 and the proper size disconnect/fuse
from Table 3, Battery Cable to Maximum Breaker/Fuse on page 22. Color-code the cables with colored tape or heat shrink tubing [the standard colors are red for positive (+) and black for negative (-)]. Always double-check the polarity with a voltmeter before making the battery connections
Install the over-current device (fuse or circuit breaker) between the inverter and battery - as close as possible to the battery - in the ungrounded conductor [typically the positive (red) cable]. Connect a cable from the battery negative terminal to the negative (black) terminal on the inverter.
Observe Battery Polarity! Place the battery cable ring terminals over the stud and directly against the inverter’s battery terminals. Red is positive (+), Black is negative (-). Use a 1/2-inch wrench or socket to tighten the 5/16 SAE nut to 10-15 foot/pounds. Do not place anything between the cable ring terminal and
the flat metal part of the terminal or overheating of the terminal may occur. DO NOT APPLY ANY TYPE OF ANTI-OXIDANT PASTE until after the battery cable wiring is tightened to 10–15 foot-pounds!
Note: Connecting the battery cables to the inverter battery terminals may cause a brief spark or arc -
usually accompanied by a "snapping" sound. This is normal - don't let it scare you. It is simply the internal capacitors of the inverter being charged.
Copyright Trace Engineering Company, Inc. 5916 - 195th Street N.E. Arlington, WA 98223
Telephone: 360/435-8826
Fax: 360/435-2229
www.traceengineering.com
PS Series Inverter/Charger
Part No. 3597
Page
23
INSTALLATION
SYSTEM GROUNDING
Even system designers and electricians often misunderstand system grounding. The subject is more easily discussed if it is divided into three separate subjects. The grounding requirements vary by country and application. Consult local codes and the NEC for specific requirements. Refer to Table 18, Safety Ground Wire Size Table on page 132 for safety ground wire sizes.
EQUIPMENT OR CHASSIS GROUNDS
This is the simplest part of grounding. The idea is to connect the metallic chassis of the various enclosures together to have them at the same voltage potential, which reduces the possibility for electric shock. It also provides a path for fault currents to flow through to blow fuses or trip circuit breakers. The size of the connecting conductors should be coordinated with the size of the overcurrent devices involved. Under some circumstances, the conduit and enclosures themselves will provide the current paths.
GROUNDING ELECTRODES/GROUND RODS
The purpose of the grounding electrode (often called a ground rod) is to “bleed” off any electrical charge that may accumulate in the electrical system and to provide a path for “induced electromagnetic energy” or lightning to be dissipated. The size for the conductor to the grounding electrode or grounding system is usually based on the size of the largest conductor in the system. Most systems use a 5/8” (16 mm) copper plated rod 6 feet (2 meters) long driven into the earth as grounding electrode. It is also common to use copper wire placed in the concrete foundation of the building as a grounding system. Either method may be acceptable, but the local code will prevail. Connection to the ground electrode should be done with special clamps located above ground where they can be periodically inspected.
It is often desirable to use multiple ground rods in larger system. The most common example is providing a direct path from the solar array to earth near the location of the solar array. Most electrical codes want to see the multiple ground rods connected by a separate wire with its own set of clamps. If this is done, it is a good idea to make the connection with a bare wire located outside of the conduit (if used) in a trench, the run of buried wire may be a better grounding electrode than the ground rods!
Well casings and water pipes can also be used as grounding electrodes. Under no circumstance should a gas pipe or line be used. Consult local codes and the NEC for more information.
BONDING THE GROUNDING SYSTEM
This is the most confusing part of grounding. The idea is to connect one of the current carrying conductors (usually the AC neutral and DC negative) to the grounding system. This connection is why we call one of the wires “neutral” in the North American type electrical systems. You can touch this wire and the grounding system and not be shocked. When the other ungrounded conductor (the hot or positive) touches the grounding system, current will flow through it to the point of connection to the grounded conductor and back to the source. This will cause the overcurrent protection to stop the flow of current, protecting the system. This point of connection between the grounding system (ground rod, vehicle frame, boat hull, etc.), the current carrying grounded conductor (AC neutral and DC negative), and the equipment grounding conductor (green ground wire, equipment ground) is often called a “bond”. It is usually located in the overcurrent protection device enclosure. Although it can be done at the inverter, codes do not generally allow it since the inverter is considered a “serviceable” item that may be removed from the system. In residential systems, it is located at the service entrance panel, after the power has gone through the kilowatt-hour meter of the utility. In mobile applications (RV and marine), this “bond” is provided by the different AC sources on board.
Bonding must be done at only one point in an electrical system. Our systems inherently have two separate electric systems - a DC system and an AC system. This means that two bonding points will occur in all inverter applications. The bonding point will also be connected to the equipment (chassis) grounding conductors. It is common to have two separate conductors connect the ground electrode and the two bonding points. Each conductor should use a separate clamp.
In some countries, the neutral is not bonded to the grounding system. This means you may not know when a fault has occurred since the overcurrent device will not trip unless a “double” fault occurs. In some marine electrical codes, this type of system is also used.
Page
24
Copyright Trace Engineering Company, Inc. 5916 - 195th Street N.E. Arlington, WA 98223
Telephone: 360/435-8826
Fax: 360/435-2229
www.traceengineering.com
PS Series Inverter/Charger
Part No. 3597
INSTALLATION
Generator
Ground
Zero Voltage Difference
across Component Grounds
BATTERY
Inverter
Ground
Battery
Ground
Voltage
Difference
Voltage
Difference
BATTERY
Generator
Inverter
Battery
GROUNDING VS. LIGHTNING
This information is intended to provide basic grounding techniques that will help prevent inverter damage due to lightning. It is not intended to be a complete course on grounding or a guarantee against protection during a lightning strike situation. The NEC is the ultimate authority as to legitimate grounding techniques for your electrical system.
If an electrical system has components grounded at different points in the earth, large voltage differences will exist between these points during a lightning strike (Figure 14, Multiple Point Ground System). If this voltage appears between the AC and DC side of the inverter, it will fail. All Trace inverters are designed to withstand a minimum of 1750 volts between AC and ground, and 500 volts between DC and ground.
ONE GROUND FOR ALL EQUIPMENT
The first step in inverter protection is to make sure that all equipment in the system is physically grounded at the same location. This assures that there is no voltage potential between grounds in the system (Figure 15, Single Point Ground System). No voltage means no current flow through the system. Practically speaking, this would mean connecting the generator and battery grounds together, as well as the case or “safety” grounds in the system, and then attaching all to the same earth grounding rod (See the NEC for specific information on grounding requirements, and hardware).
In severe conditions, the generator frame should physically be isolated from the earth by a wood frame or some other insulating means. This assures that the single point ground system is maintained.
KEEP EQUIPMENT CLOSE TOGETHER
All equipment involved in a system should physically be located as close as possible to one another. This reduces the potential that is developed between the ground site and the individual components of the system during a lightning strike. This single point grounding greatly reduces the potential for lightning damage to electrical equipment.
If you are unable to achieve single-point grounding due to large distances between equipment or other variables, other means of lightning protection must be considered. Consult a reputable lightning protection company.
Equipment all grounded at
same point. No voltage
across system, and no
current flow through
equipment and wiring.
GENERATOR INVERTER
BANK
Lightning
Strike
GENERATOR INVERTER
Ground
Equipment acts as a
conductor due to
voltage between the
grounds. Bad!
Ground
Ground
Lightning
Strike
BANK
Figure 14, Multiple Point Ground System Figure 15, Single Point Ground System
Copyright Trace Engineering Company, Inc. 5916 - 195th Street N.E. Arlington, WA 98223
Telephone: 360/435-8826
Fax: 360/435-2229
www.traceengineering.com
PS Series Inverter/Charger
Part No. 3597
Page
25
INSTALLATION
QUICK INSTALL
This section is provided for installers, licensed electrical contractors, and knowledgeable laymen as a quick reminder on the essential steps to quickly install the Trace PS Series Inverter/Charger. If you haven’t had experience with the PS Series Inverters/Charger, you are urged to read the entire
INSTALLATION section before installing the inverter/charger.
MOUNTING
Mount the unit securely in a clean, dry, properly ventilated enclosure. Do not mount the unit in the same enclosure as vented or maintenance-free type vented batteries. Bolt the unit securely. Allow adequate clearance to allow access to the indicators or controls.
DC CABLING
1. Connect a cable from the positive terminal of the battery (or battery bank) to the battery positive (red) terminal of the inverter. See Table 16 in the Appendix to determine the proper size cable and length of run needed to use with your inverter model and for your specific application. The National Electric Code (NEC) requires the use of a DC fuse or disconnects with this cable. See Table 13 in the Appendix to determine the correct size fuse or breaker to use.
2. Connect an appropriate sized cable from the battery’s negative terminal to the negative (black) terminal on the inverter. Torque all terminals to 10-15 foot-pounds. A 'snap' caused by charging the internal capacitors may occur. This is normal.
3. Connect a cable from the DC Ground terminal on the inverter to the system ground.
AC IN CABLING
See Table 17, Recommended Minimum AC Wire Sizes (75° C in the Appendix to determine the appropriate AC wire size.
1. Remove the knockout from the inverter chassis and install a strain relief or conduit in which to route the AC cabling in and out.
2. Connect the black wire from the hot side of the AC power to the terminal labeled AC HOT IN on the inverter.
3. Connect the white wire from the neutral side of the AC power source to the terminal labeled AC NEUTRAL IN on the inverter.
4. Connect the green wire from the ground of the AC power source to the AC Ground Terminal of the inverter/charger.
AC OUT CABLING
1. Connect the black wire between the terminal marked AC HOT OUT to the hot bus of your AC load center or AC sub-panel.
2. Connect the white wire from the terminal marked AC NEUTRAL OUT to the neutral bus of your AC load center or sub-panel.
3. Connect the AC Ground Terminal of the inverter to the safety ground bus of the AC load center or sub-panel.
WRAP UP
1. Secure all wiring with wire ties or other non-conductive fasteners to prevent chafing or damage. Use strain reliefs, grommets, or conduit to prevent damage to the wiring where it passes through any apertures. Tighten all connections to the correct torque (AC Connections at 20 inch-pounds; DC Connections at 10-15 foot-pounds).
2. Make a final check of all wiring, then reconnect to the AC power source.
Turn the inverter ON and check inverter operation (See the FUNCTIONAL TEST section on page 27).
Page
26
Copyright Trace Engineering Company, Inc. 5916 - 195th Street N.E. Arlington, WA 98223
Telephone: 360/435-8826
Fax: 360/435-2229
www.traceengineering.com
PS Series Inverter/Charger
Part No. 3597
FUNCTIONAL TEST
FUNCTIONAL TEST
Once the AC and DC wiring have been installed and connected, take a moment to go back over all connections and make sure they are secure and have been installed properly. Ensure that there is no AC or DC power provided to the inverter/charger and that all AC loads are disconnected from the output of the inverter.
The below steps will complete a functional test of the inverter. If any area fails, figure out why before proceeding. The TROUBLESHOOTING GUIDE section, starting on page 109, will hopefully help solve problems you may encounter.
1. After ensuring the correct polarity, apply battery (DC) power to the inverter by turning on the battery bank DC disconnect or connecting the proper fuse inline to the battery to complete the battery circuit. The inverter will power up and the ERROR (red) LED will be on (indicates no AC output), but the inverter will remain in the OFF mode. The ERROR (red) LED should be the only LED on at this time – if not, troubleshoot before continuing.
2. Press the ON/OFF switch twice (SEARCH then ON) to turn the inverter on. Monitor your INVERTING (yellow) LED to ensure what mode you are in :
OFF – The Inverter/Charger is off. This is the default position of the inverter upon power-up. No
inverter or pass-thru power will be applied to the AC loads
ONE BLINK/SEC – The Inverter/Charger is in Search mode and is looking for an AC load greater than
the SEARCH WATTS setting ( default = 16 watts).
DOUBLE BLINK/SEC - The Inverter/Charger is in the Charge Only mode. The inverter will operate
only as a charger (MAXIMUM AC AMPS IN switch must be in the AC1 position to use the Charge Only mode).
RAPID BLINK (4/sec) - Indicates that an operating error has occurred. The inverter is protected from
conditions caused by over-load, over-current, over-temperature (transformer or heatsink), high-battery, low-battery, low AC dropout or an external (stacked) error. If the inverter senses one of these situations, it will protect itself by disconnecting from the AC loads. This error condition also occurs from numerous generator-related errors, but will not disconnect the AC loads. Refer to the TROUBLESHOOTING GUIDE starting on page 109 to help determine your particular error cause.
ON – Indicates the Inverter/Charger is on. The inverter will produce a low audible “buzz” is able to
provide power to the AC loads.
If the inverter does not produce a low audible “buzz” or come on, check all connections. Check the inverter’s DC voltage on the positive (+) and negative (–) terminals. If the DC voltage is low, the battery bank needs to be charged externally. Charge the battery bank and restart the functional test.
3. With the inverter ON, check the AC voltage on the AC output terminal of the inverter and ensure you get the correct AC voltage for your particular unit. After confirming the correct AC voltage, connect your AC output breaker and place a load on the inverter (plug in a light or other load to an outlet the inverter is powering), and make sure it works.
4. Check your battery charger. To charge your batteries, provide AC power - by plugging in a power cord or turning on the AC input breaker - to the AC HOT IN and NEUTRAL IN terminals on the inverter. The AC IN (Green) LED should come on, indicating that AC power is getting to the inverter. After a minimum 20 seconds delay, the CHARGE (Orange) LED on the inverter should be on, indicating the charger is working properly. If you have an SWRC, it should indicate which charge stage (bulk or float) the inverter is currently in. Any AC loads powered by the inverter should also work at this point since the AC input power (Utility or Generator) is passed through the inverter to power the loads.
5. Disconnect AC power. Take away the AC input power by turning the AC power breaker off or unplugging the AC power cord. The inverter should transfer to inverter mode immediately. The INVERT (Yellow) LED should come on to indicate this. The inverter will begin to produce an audible “buzz” as it takes power from the batteries and uses it to power the loads. The loads should continue to operate uninterrupted.
6. This completes the functional test, if all areas pass, the inverter is ready for use. If any of the inverter’s internal setpoints are to be adjusted, consult the MENU SYSTEM section starting on page 29.
Copyright Trace Engineering Company, Inc. 5916 - 195th Street N.E. Arlington, WA 98223
Telephone: 360/435-8826
Fax: 360/435-2229
www.traceengineering.com
PS Series Inverter/Charger
Part No. 3597
Page
27
FUNCTIONAL TEST
Page
28
Copyright Trace Engineering Company, Inc. 5916 - 195th Street N.E. Arlington, WA 98223
Telephone: 360/435-8826
Fax: 360/435-2229
www.traceengineering.com
PS Series Inverter/Charger
Part No. 3597
Loading...
+ 114 hidden pages