For the latest prices, please check AutomationDirect.com.
FC Series Signal Conditioners
FC-33
DC Selectable Signal Conditioner with
FC-11
4-20 mA Isolated Signal Conditioner
3-way isolation
Field configurable input and output ranges of 0-5V, 0-10 V,
0-20 mA and 4-20 mA with 1500 VDC isolation between
input and output, and 1500 VDC isolation from 24 volt power
and input/output. LED indicates normal operation and is used
in conjunction with the calibration pushbutton for the internal
calibration process.
• 3-way 1500 V isolation
• Push button calibration
FC-T1
Thermocouple/mV Isolated Signal
Conditioner
Field configurable input for type J, K, E, T, R, S, B, N and C
thermocouples or ±156.25 mV inputs with 1500 VDC isolation
between input and the 4-20 mA output. Cold junction compensation and burnout detection. Alarm/run LED.
• 1500 V isolation
• Cold junction compensation (CJC)
• Internal diagnostics (burnout detection or calibration errors)
Loop powered 4-20 mA input/output signal with 1500 VDC
isolation between input and output.
• 1500 V isolation • Loop powered
FC-R1
RTD Input Signal Conditioner
Loop powered, non-isolated, 3-wire unit converts an RTD input
to a linear 4-20 mA signal. User selectable CU10, PT100 or
PT1000 input.
FC-P3
Potentiometer Input, Analog Output
Signal Conditioner
Field configurable input and output, input ranges of 3-wire
potentiometer 0 to 100 ohms through 0 to 100 kilohms, and
output ranges of 0-5V, 0-10 V, 0-20 mA or 4-20 mA. Field
calibrated to 10% of potentiometer full range.
FC-B34
FC-35B
Unipolar Voltage or Current to Bipolar
Voltage Signal Conditioner
Field configurable input and output, unipolar input ranges of
0-5V, 0-10 V, 0-20 mA or 4-20 mA, and bipolar output ranges of
±100 mV, ±50 mV, ±5V, ±10V, ±15V. Field calibrated with
offset and span adjustments.
Field configurable input and output, bipolar input ranges of
±100 mV, ±50 mV, ±5V, ±10V, ±15V, and unipolar output
ranges of 0-5V, 0-10 V, 0-20 mA or 4-20 mA. Field calibrated
Bipolar Voltage to Unipolar Voltage or
Current Signal Conditioner
with offset and span adjustments.
FC-3RLY2
Analog Input, 2-Relay, Limit Alarm
Field configurable analog to relay limit alarm powered by 24VAC/
VDC and Input signal ranges of 0-15V, 0-30V or 0-20mA. Trip/
Release Point programmed via DIP switches. LED’s indicate
operating status.
FC-ISO-D
Encoder Signal Conditioner and Optical
Isolator - Differential Line Driver Output
Ideal for use with single-ended (open collector, NPN, pull-up,
push-pull, totem pole) or differential line driver encoders. Three
complementary inputs (A, B, Z, A-not, B-not, Z-not) are rated
for 4.5-7.5 and 12-26 VDC and frequency response up to
1 MHz.
Optical isolation separates the input signals from three differential
line driver outputs (A, B, Z, A-not, B-not, Z-not) rated for 5VDC.
tPSC-1
Signal Conditioners
FC-3RLY4
Analog Input, 4-Relay, Limit Alarm
Field configurable analog to relay limit alarm powered by 24VAC/
VDC and Input signal ranges of 0-15V, 0-30V or 0-20mA. Trip/
Release Point programmed via DIP switches. LED’s indicate
operating status.
FC-ISO-C
Encoder Signal Conditioner and Optical
Isolator - Open Collector Output
Ideal for use with single-ended (open collector, NPN, pull-up,
push-pull, totem pole) or differential line driver encoders. Three
complementary inputs (A, B, Z, A-not, B-not, Z-not) are rated
for 4.5-7.5 and 12-26 VDC and frequency response up to
1 MHz.
Optical isolation separates the input signals from three
complementary open collector outputs (A, B, Z, A-not, B-not,
Z-not) rated for 5-36 VDC that can be used in single-ended
configurations.
1-800-633-0405
For the latest prices, please check AutomationDirect.com.
FC-33 DC Selectable Signal Conditioner
$130.00
UL file E200031
Overview
The FC-33 is a DIN-rail or side-mount, selectable input/output
signal conditioner with 1500 VDC isolation between input and
output, and 1500 VDC isolation between 24-volt power and input/
output. The field configurable input/output types allow a wide
ranging capability for 0-5V, 0-10V, 0-20 mA and 4-20 mA signals.
The FC-33 has built-in self-calibration, but also has OFFSET (zero)
and SPAN (full scale) adjustments of the output signal. The OFFSET
has an adjustment range of 0 to 25% of full scale input and the
SPAN has an adjustment of 80% to 102%.
Level LED: The LED is a powerful tool when setting up the signal
conditioner. During normal operation the LED will blink at a proportional rate to the selected input signal level. When performing field
calibration the LED is used for indication of the internal calibration
process.
CAL-Pushbutton: This pushbutton, along with various switch
settings, allows you to calibrate the OFFSET and/or SPAN for your
application or to restore factory default calibration.
Specifications
Input Ranges
Input Impedance
Output Ranges
Load Impedance
Maximum Load / Current
Sample Duration Time
Filter Characteristic
Linearity Error
Stability
Accuracy vs. Temperature
Input Power
Recommended Fuse
Isolation
Maximum Inaccuracy of
Output
Output Current
Approx. Field Cal. Range
Operating Temperature
Storage Temperature
Relative Humidity
Vibration
Shock
Noise Immunity
0-5 V, 0-10 V, 0-20 mA, 4-20 mA
250 q, ±0.1% current input
200 Kq / 400 Kh Voltage input
0-5 V, 0-10 V, 0-20 mA, 4-20 mA
2 Kq minimum, voltage output
0 q minimum, current output
550 q @ 24 VDC (sink/source)
10 mS
-3 dB @ 3 Hz, -6 dB/octave
0.05% FSO maximum
0.05% FSO maximum
0.005%/ °C, (50ppm/°C)
24 VDC, ±10% @ 50 mA
0.032 mA, Series 217, current inputs
1500 VDC input - output*
1500 VDC power - input*
1500 VDC power - output*
*applied for 1 second
0.05% @ 25°C, FSO maximum
0.25% @ 0-60°C, FSO maximum
21 mA maximum (for mA output)
0 - 25%
(0 - 1.5 V / 5 V mode)
80% - 102%
(4 - 5.1 V / 5 V mode)
0-60°C (32 to 140°F)
-20 to 70°C (-4 to 158°F)
5 to 90% (non-condensing)
ML STD 810C 514.2
ML STD 810C 516.2
NEMA ICS3-304
Application
The FC-33, field configurable isolated input/output signal
conditioner, is useful in eliminating ground loops and interfacing sensors to PLC analog input modules. The FC-33 has
3-way isolation; this feature solves many types of configuration problems. For example, the signal conditioner can be
configured for a sinking input and a sourcing output. It also
allows signal translation from current input to voltage output
or voltage input to current output.
This feature would be useful in a system design with a limited
type and number of channels – for example: eight channels of
0-10 VDC, seven of which are used, and one 4-20 mA input
transmitter.
tPSC-2
Signal Conditioners
1-800-633-0405
For the latest prices, please check AutomationDirect.com.
FC-11 4-20mA Isolated Signal Conditioner
$97.00
Specifications
UL file E200031
Overview
The FC-11 is a DIN-rail or side-mount, 4-20 mA Input/Output
loop powered signal conditioner with 1500 VDC isolation
between input and output.
The FC-11 has a user-selectable factory calibration. The output
can also be calibrated with OFFSET (zero) and SPAN (full scale)
adjustments. The OFFSET has an adjustment range of 0 to 25%
of full scale input and the SPAN has an adjustment of 80% to
102%.
Application
The FC-11 isolated input/output signal conditioner is useful in
eliminating ground loops and sinking/sourcing issues when interfacing to PLC analog input modules. The FC-11 design feature
solves many types of configuration problems. For example, the
signal conditioner can solve the problem of connecting a sinking
input transmitter to a sinking analog input module.
Input Ranges
Extended Input range
Input Burden Voltage
1
2
Maximum Input Current
Output Burden Voltage
3
Output Range
Extended Output Range
1
Maximum Load Impedance
Maximum Output Current
Sample Duration Time
Linearity Error
Max Inaccuracy of Output
Filter Characteristics
Stability
Accuracy vs. Temperature
Isolation
Operating Temperature
Storage Temperature
Relative Humidity
Vibration
Shock
Noise Immunity
NOTES:
1. When adjusting SPAN and OFFSET potentiometer
2. Voltage required to power internal circuitry
3. Formula, [(output load) x 20 mA] + 8.5 V,.i.e.: 13.5 VDC @ 250 q
4. Internal analog converter resolution is 12-bit
4-20 ma
3.5 mA to 20.6 mA, ± 1%
6.8 VDC
34 mA @ 9.7 VDC
8.5 VDC minimum
4-20 mA
3.5 mA to 20.6 mA, ± 1%
650 q @ 24 VDC, 1000 q 29 VDC
23 mA @ 29 VDC
18 mS maximum
0.1% FSO maximum
0.05% @ 25°C, FSO maximum,
0.3% @ 0-60°C, FSO maximum
-3 dB @ 200 Hz, -6 dB / octave
0.1% FSO maximum
± 0.0065% / °C (65ppm / °C)
1500 VDC Input - Output
0 to 60°C (32 to 140°F)
-20 to 70°C (-4 to 158°F)
5 to 90% (non-condensing)
ML STD 810C 514.2
ML STD 810C 516.2
NEMA ICS3-304