![](/html/3c/3ca8/3ca8e3e06010caa7373642e7f813d0f586d48665caf7c2a52389bd048b8ed88a/bg1.png)
INSTALLATION
CP & RCP Series
INSTRUCTIONS
Radiant Ceiling Panel Heaters
GENERAL INFORMATION:
Wiring: Check voltage on nameplate of heater to make sure it conforms with supply voltage. 277 volt heaters
operated at 240 volt and 240 volt heaters operated at 208 volts will give a capacity of 75% rated wattage.
All wiring must conform to the N.E.C./C.E.C. and existing local code requirements.
Location: Heaters are intended for ceiling mount only. If the situation requires, heating panels may be installed
directly adjacent to walls and to other heating panels.
WARNING: Adhere to all applicable building codes and regulations when installing or using ceiling
heaters. Failure to do so could cause improper activation of re suppression systems leading to property
damage or bodily injury.
AVERTISSEMENT: respecter tous les codes et réglementations applicables lors de l’installation ou de
l’utilisation de radiateurs de plafond. L’omission de le faire pourrait entraîner une mauvaise activation
des systèmes de suppression des incendies entraînant des dommages matériels ou corporels.
Controls: Heaters may be controlled by a wall mounted line voltage or pilot duty thermostat, timer or other
suitable device. (Controls are not supplied with heaters).
Insulation: Insulation is built into the ceiling heaters above the heating element surface to reduce heat loss
through the ceiling and deect the heat downward into the heated space. Additional insulation placed in the
ceiling is highly recommended to further reduce the upward passage of heat.
Handling Panels are factory supplied in a white egg shell textured nish to match surrounding ceiling areas as
closely as possible. Since this nish is more difcult to clean than a high gloss type, it is suggested that the
installer wear clean gloves to prevent unnecessary soiling.
CLEANING/MAINTENANCE
Cleaning should be done with a vacuum cleaner and soft brush attachment. Gently go over the face of the panel
and remove any dust or lint. There is no other maintenance required for the heater.
1 of 7REV 11/15/18 ECO 1-7483 FORM: 9688
![](/html/3c/3ca8/3ca8e3e06010caa7373642e7f813d0f586d48665caf7c2a52389bd048b8ed88a/bg2.png)
Model
No.
CP805 23 3/4 (603MM) 47 3/4 (1213MM) 1 24 X 48 (610MM X 1219MM) 500 208
CP125 23 3/4 (603MM) 47 3/4 (1213MM) 1 24 X 48 (610MM X 1219MM) 500 120/240
CP705 23 3/4 (603MM) 47 3/4 (1213MM) 1 24 X 48 (610MM X 1219MM) 500 277
CP807 23 3/4 (603MM) 47 3/4 (1213MM) 1 24 X 48 (610MM X 1219MM) 750 208
CP127 23 3/4 (603MM) 47 3/4 (1213MM) 1 24 X 48 (610MM X 1219MM) 750 120/240
CP707 23 3/4 (603MM) 47 3/4 (1213MM) 1 24 X 48 (610MM X 1219MM) 750 277
CP802 23 3/4 (603MM) 23 3/4 (603MM) 1 24 X 24 (610MM X 610MM) 250 208
CP122 23 3/4 (603MM) 23 3/4 (603MM) 1 24 X 24 (610MM X 610MM) 250 120/240
CP702 23 3/4 (603MM) 23 3/4 (603MM) 1 24 X 24 (610MM X 610MM) 250 277
CP803 23 3/4 (603MM) 23 3/4 (603MM) 1 24 X 24 (610MM X 610MM) 375 208
CP123 23 3/4 (603MM) 23 3/4 (603MM) 1 24 X 24 (610MM X 610MM) 375 120/240
CP703 23 3/4 (603MM) 23 3/4 (603MM) 1 24 X 24 (610MM X 610MM) 375 277
A B C
Panel Size
T-Bar Spacing Watts Volts
B
A
RADIANT
PANEL
C= PANEL DEPTH = 1"
B
RECESSED HEATING
PANEL WITH INVERTED
"T" STYLE FRAME
FRAME FOR RECESSED
HEATING PANEL
A
REV 11/15/18 ECO 1-7483 FORM: 9688 2 of 7
![](/html/3c/3ca8/3ca8e3e06010caa7373642e7f813d0f586d48665caf7c2a52389bd048b8ed88a/bg3.png)
Model
No.
RCP805 21 3/4 (552MM) 47 3/4 (1213MM) 1 22 1/2 (571MM) 48 12 (1232MM) 500 208
RCP125 21 3/4 (552MM) 47 3/4 (1213MM) 1 22 1/2 (571MM) 48 12 (1232MM) 500 120/240
RCP705 21 3/4 (552MM) 47 3/4 (1213MM) 1 22 1/2 (571MM) 48 12 (1232MM) 500 277
RCP807 21 3/4 (552MM) 47 3/4 (1213MM) 1 22 1/2 (571MM) 48 12 (1232MM) 750 208
RCP127 21 3/4 (552MM) 47 3/4 (1213MM) 1 22 1/2 (571MM) 48 12 (1232MM) 750 120/240
RCP707 21 3/4 (552MM) 47 3/4 (1213MM) 1 22 1/2 (571MM) 48 12 (1232MM) 750 277
RCP802 21 3/4 (552MM) 21 3/4 (552MM) 1 22 1/2 (571MM) 22 1/2 (571MM) 250 208
RCP122 21 3/4 (552MM) 21 3/4 (552MM) 1 22 1/2 (571MM) 22 1/2 (571MM) 250 120/240
RCP702 21 3/4 (552MM) 21 3/4 (552MM) 1 22 1/2 (571MM) 22 1/2 (571MM) 250 277
RCP803 21 3/4 (552MM) 21 3/4 (552MM) 1 22 1/2 (571MM) 22 1/2 (571MM) 375 208
RCP123 21 3/4 (552MM) 21 3/4 (552MM) 1 22 1/2 (571MM) 22 1/2 (571MM) 375 120/240
RCP703 21 3/4 (552MM) 21 3/4 (522MM) 1 22 1/2 (571MM) 22 1/2 (571MM) 375 277
A B C D E
Panel Size FRAME OUT SIZE
Watts Volts
B
A
RADIANT
PANEL
C= PANEL DEPTH = 1"
B
RECESSED HEATING
PANEL WITH INVERTED
"T" STYLE FRAME
FRAME FOR RECESSED
HEATING PANEL
A
3 of 7REV 11/15/18 ECO 1-7483 FORM: 9688