Toyotomi CCT70A-M, CCT140A-M Service Manual

Service Manual
MODEL:
CCT70A-M CCT140A-M
Four-way Cassette Type
Four-way Cassette Type
1. Features ......................................................................................................
2. Dimensions .................................................................................................
3. Service Space .............................................................................................
4. Wiring Diagrams .........................................................................................
5. Air Velocity and Temperature Distributions(Reference Data) ..................
6. Electric Characteristics ..............................................................................
7. Sound Levels ..............................................................................................
8. Accessories ................................................................................................
9. The Specification of Power ........................................................................
10. Field Wiring ...............................................................................................
Features
Four-way Cassette Type
1. Features
1.1 New panel (60k standard)
Ø New panel with 360° airflow supply Ø Air intake grille lift function for supper thin cassette, convenient for maintenance.
1.2 3D screw fan technology
Ø 3D screw indoor fan technology reduces the air resistance, increases the air volume and improves the
heat exchange efficiency. Operate quietly.
1.3 Air passage function
Ø Reserves the space for air outlet from the side of indoor unit; Its availed to connect air duct from side to
nearby small rooms. For duct connecting
Features
Four-way Cassette Type
1.4 Drainage pump
Ø Build-in water pump which pumping head is 750mm upmost. Its convenient to install drainage piping
under most space condition.
1.5 LED display
Ø Digital LED interface, makes the unit more elegant. Ø Normally display the setting temperature Ø LED can display the Error Code to make the malfunction checking easier.
Dimensions
Four-way Cassette Type
2. Dimensions
CCT70A-M
4-install hanger
Gas side
Liquid side
E-parts box
Pump inspect hole
Drain hole
CCT140A-M
4-install hanger
Gas side
Liquid side
E-parts box
Pump inspect hole
Drain hole
Service Space
Four-way Cassette Type
3. Service Space
The indoor unit should be installed in a location that meets the following requirements:
There is enough room for installation and maintenance.
The ceiling is horizontal, and its structure can endure the weight of the indoor unit.
The outlet and the inlet are not impeded, and the influence of external air is the least.
The air flow can reach throughout the room.
The connecting pipe and drainpipe could be extracted out easily.
There is no direct radiation from heaters.
Wiring Diagrams
Four-way Cassette Type
Wiring Diagrams
CCT70A-M
Wiring Diagrams
Four-way Cassette Type
CCT140A-M
Air Velocity and Temperature Distributions(Reference Data)
Four-way Cassette Type
5. Air Velocity and Temperature Distributions(Reference Data)
Airflow velocity
Temperature
Electric Characteristics
Four-way Cassette Type
6. Electric Characteristics
Model
Indoor Units Power Supply
Hz
Voltage Min. Max. MFA
CCT70A-M 50 220-240V 198V 254V 25
CCT140A-M 50 380-415V 342V 418V 15
Remark:
MFA: Max. Fuse Amps. (A)
7. Sound Levels
1.0m
FOUR-WAY CASSETTE TYPE
Microphone
Model
Noise level dB(A)
H M L
CCT70A-M 42 40 39
CCT140A-M 44 42 41
Accessories
Four-way Cassette Type
8. Accessories
Installation Fittings
Name Shape Quantity
1. Expansible hook
4
2. Installation hook
4
3. Installation paper board
1
4. Bolt M5
4
Tubing & Fittings
5. Connecting pipe group 1
6. Binding tape
6
7.Soundproof/insulation sheath
2
Drainpipe Fittings
8. Out-let pipe sheath
1
9. Out-let pipe clasp
1
10. Tightening band
20
11. Drain joint
1
12. Seal ring
1
Protect Pipe Fittings
13. Wall conduit
1
14. Wall conduit cover
1
Remote controller & Its Frame
15. Remote controller
1
16. Frame
1
17. Mounting screw(ST2.9×10-C-H)
2
18. Alkaline dry batteries (AM4)
2
Others
19. Owner's manual
1
20. Installation manual
1
The Specification of Power
Four-way Cassette Type
9. The Specification of Power
Cooling & heating
Type 24000 Btu/h
48000
Btu/h
Power
Phase 1-phase 3-phase Frequency and Voltage
220-240V, 50Hz 380-415V, 50Hz
Circuit Breaker/ Fuse (A) 40/25 25/15 Indoor Unit Power Wiring (mm2) 3×2.5 5×2.5
Indoor/Outdoor Connecting Wiring (mm2)
Ground Wiring 4.0 2.5 Outdoor Unit Power Wiring
3×2.5 5×2.5
Strong Electric Signal
3×1.5 3×1.0
Weak Electric Signal
2-core shield
wire 2×0.75
Field Wiring
Four-way Cassette Type
10. Field Wiring
Wiring chart
MCC-24HRN1
Field Wiring
Four-way Cassette Type
CCT140A-M
Outdoor Units
Outdoor Units
Part 3
Outdoor Units
1. Dimensions .................................................................................................
2. Service Space .............................................................................................
3. Piping Diagrams .........................................................................................
4. Wiring Diagrams .........................................................................................
5. Electric Characteristics ..............................................................................
6. Operation Limits .........................................................................................
7. Sound Levels ..............................................................................................
Loading...
+ 35 hidden pages