TOYODenki VF66 EIP66-Z Operating Manual

TOYO INTELLIGENT INVERTER
EIP66-Z Operating Manual

Preface

Thank you very much for choosing our inverter optional board.
This manual describes handling of the optional board EIP66-Z designed for VF66 inverter. Please read this manual
thoroughly to use EIP66-Z properly.
This manual describes the terminal block functions of EIP66-Z board, wiring, switch settings and VF66 inverter
settings. For the EtherNet/IP communication functions, refer to "EIP66-Z Communication Protocol Manual."
To use various functions according to intended use as well as the inverter functions, read the operating
instructions of VF66 inverter main unit or dedicated manual thoroughly before use.

Be Sure To Read This Before Use

Safety Notice

To use the EIP66-Z correctly, be sure to completely read this manual and all other attached documents before installation, operation, maintenance, and inspection. You need to have a good knowledge of equipment, safety information, and all notices before using the EIP66-Z. Read also the operating instructions of VF66 inverter main unit and other related manuals thoroughly before use for safe operations.
In this manual, safety notices are ranked as "Danger," "Warning," and "Caution."
WARNING
When improper use may cause a dangerous situation, and death or serious injury may result.
CAUTION
When improper use may cause a dangerous situation, medium-level or minor injury may result, and only physical damage may result. However, it can cause serious results depending on the situation. Cautions described in this manual are all important. Be sure to observe them.
CAUTION [Installation]
Do not use the product if it is found damaged or deformed in unpacking. It may cause failure/malfunction. Do not put a flammable material near the product. It may catch fire. Do not give a shock to the product by dropping or toppling it. It may cause failure/damage to the product. Do not install an optional board with damage or missing part to perform operations. It may cause injury.
WARNING [Wiring]
Check that the input power is turned off before wiring. Otherwise, electric shock/fire may result.
After turning off the power, wait at least ten minutes before opening the inverter front cover.
Be sure to connect a ground wire.
Otherwise, electric shock/fire may result.
Let an electrical engineering technician do the wiring work.
Otherwise, electric shock/fire may result.
Be sure to install the main unit before wiring.
Otherwise, electric shock/fire may result.
CAUTION [Wiring]
Be sure to attach and lock the communication cable and connector. Otherwise, failure/malfunction may result.
WARNING [Operation]
Be sure to attach the inverter front cover before turning on the input power.
Do not remove the cover while the inverter is energized. Ignoring this may cause electric shock.
Do not operate the switches with wet hands.
Ignoring this may cause electric shock.
While the inverter is energized, do not touch the inverter terminals even when the inverter is stopped.
Ignoring this may cause electric shock.
Resetting an alarm with the operation signal input causes a sudden restart.
Perform resetting after making sure that the operation signal is off. Otherwise, you may be injured.
The inverter operation setting is available from low to high speed. Check the allowable range of motor
or machine carefully before starting operation.
Otherwise, injury/failure/damage may result.
CAUTION [Operation]
Do not touch the inverter radiation fin or discharge resistor because it can be very hot. Ignoring this may cause burn injury.
WARNING [Maintenance/inspection and part replacement]
Be sure to turn off the power before performing inspection. Otherwise, electric shock/injury/fire may result. Only the specified person must perform maintenance/inspection and part replacement. Use an insulated tool for maintenance/inspection. Otherwise, electric shock/injury may result.
CAUTION [Others]
Never modify the product.
Otherwise, electric shock/injury may result.
CAUTION [General cautions]
Some figures in this manual are shown with the cover or safety shield removed for the purpose of detailed
descriptions. However, for actual operations, be sure to attach the specified cover or safety shield and follow
the instructions in this manual.
Note that these safety precautions and specifications described in each manual are subject to change without
notice.

Contents

Be Sure To Read This Before Use .................................................................................................................................... 4
Safety Notice............................................................................................................................................................... 4
CHAPTER 1 Function Overview ............................................................................................................................................ 7
CHAPTER 2 Basic Specifications ...................................................................................................................................... 8
2. 1 Multifunction Input Terminal Specifications .......................................................................................... 8
2. 2 Analog Input/Output Terminal Specifications .......................................................................................... 9
2. 3 PG Input/Output Terminal Specifications .................................................................................................. 9
2. 4 EtherNet/IP Communication Function Connector/Terminal Specifications ........................................ 10
2. 5 EtherNet/IP Communication Specifications .............................................................................................. 10
2. 6 Others ................................................................................................................................................................ 11
CHAPTER 3 Board Description .......................................................................................................................................... 12
3. 1 Part Names ......................................................................................................................................................... 12
3. 2 EIP66-Z Switches ............................................................................................................................................. 13
3. 3 How to Mount ..................................................................................................................................................... 14
3. 4 LED ...................................................................................................................................................................... 16
CHAPTER 4 Multifunction Input ...................................................................................................................................... 18
4. 1 Multifunction Input ....................................................................................................................................... 18
CHAPTER 5 Analog Input/Output Function .................................................................................................................... 21
5. 1 Analog Input (2) ............................................................................................................................................. 21
5. 2 Analog Input (2) Gain/Offset Adjustment ................................................................................................ 22
5. 3 How to Use Analog Input (2)........................................................................................................................ 24
5. 4 Analog Output (2) ........................................................................................................................................... 27
5. 5 Analog Output (2) Gain/Offset Adjustment .............................................................................................. 28
CHAPTER 6 PG Input/Output Function ............................................................................................................................ 31
6. 1 PG Input Signal ............................................................................................................................................... 31
6. 2 PG Output Signal ............................................................................................................................................. 33
CHAPTER 7 EtherNet/IP Communication Function ......................................................................................................... 34
7. 1 EtherNet/IP Connection ................................................................................................................................. 34
7. 2 EtherNet/IP Communication Function Setting .......................................................................................... 35

CHAPTER 1 Function Overview

EIP66-Z is attached to the connector of the board (VFC66-Z) inside the VF66 inverter to use. EIP66-Z is equipped
with the EtherNet/IP adapter function (slave station), analog input/output function, multifunction input and
PG input/output function.
EtherNet/IP is a public network standard, and the specification and protocol are made public by ODVA (Open
DeviceNet Vendor Association, Inc.) to provide mutual compatibility between the devices of the same type by
multiple vendors.
The EIP66-Z EtherNet/IP communication function allows users to input a command related to operation, speed, torque, etc. to the VF66 inverter or monitor the situations including the inverter operation/protection status, current and voltage. In addition, reading/rewriting of inverter settings and reading of traceback data, protection history and monitoring data are available. For the EtherNet/IP communication functions, refer to "EIP66-Z Communication Protocol Manual." This function can also be used as an input/output signal of the internal PLC function of the VF66 inverter. For the internal PLC function, refer to the VF66 PC Tool manual.
CAUTION [Safety precautions]
Read this manual thoroughly before use for proper handling.
Our inverter is not designed/manufactured for the devices or systems used in a life-threatening
situation.
Do not use this inverter for special use, such as riding mobile object, medical care, aerospace,
nuclear power control, submarine repeater/system, etc.
This inverter is manufactured under stringent quality control; however, install safety equipment
to avoid a serious accident for the important facility which may put human lives in danger by failure
of the inverter
or the facility to which a serious loss is caused by failure of the inverter.
Contact us to use this product for the load other than three-phase AC motors.
Electrical work is required for this inverter. Let an electrical engineering technician do the work.

CHAPTER 2 Basic Specifications

2. 1 Multifunction Input Terminal Specifications

Multifunction input
EIP66-Z terminal block TB1
Terminal name
Usage
Description
PS (2 terminals)
Multifunction input
+12 V power supply terminal
Outputs a direct voltage of +12 V.
G (2 terminals)
GND terminal
Do not connect G terminal to the ground terminal. Do not bring PS and G terminals into contact or connect them.
MI6
Multifunction input terminal (6)
(Maximum input voltage 24 VDC/maximum input current 3 mA) The same operation as VF66 inverter console is enabled by inputting a signal to the multifunction input terminal. [Under the default condition, the followings are set by the VF66 inverter setting parameter: Area c.]
Preset speed selection 1 is set for the multifunction input terminal (6). Preset speed selection 2 is set for the multifunction input terminal (7). Preset speed selection 3 is set for the multifunction input terminal (8). Acceleration or deceleration time selection 1 is set for the multifunction
input terminal (9).
* For more information about multifunction input terminals, refer to the operating instructions of VF66 inverter main unit.
MI7
Multifunction input terminal (7)
MI8
Multifunction input terminal (8)
MI9
Multifunction input terminal (9)
Multifunction input source/sink mode setting jumper connector
EIP66-Z jumper connector
Connector
symbol
Usage
Description
CN-SO
Source mode
Change the connection of jumper socket to jumper connector to switch between the source and sink modes. Be sure to turn off the inverter power before changing the connection of jumper socket. [The source mode is selected in the default condition.]
For the source mode, install a switch, etc. between the multifunction input terminals (6) to (9) and PS terminal to turn ON/OFF. For the sink mode, install a switch, etc. between the multifunction input terminals (6) to (9) and G terminal
to turn ON/OFF.
For more information, refer to CHAPTER 4.
CN-SI
Sink mode

2. 2 Analog Input/Output Terminal Specifications

Analog input/output function
EIP66-Z terminal block TB1
Terminal name
Usage
Description
AIN2
Analog input/output
Analog input (2) terminal
For the analog input (2) terminal, the input range can be selected from 0 to ±10 V, 0 to 10 V, and 4 to 20 mA by switching of SW1 and changing of VF66 inverter setting parameter. (For switching of the input range, refer to CHAPTER 5.)
・ The input impedance at analog voltage input is 150 kΩ. ・ The input resistance at analog current input is 250 Ω.
[The 0 to 10 V input is selected in the default condition.] * For more information about the analog input (2) terminal, refer to the operating instructions of VF66 inverter main unit.
AOT2
Analog output (2) terminal
For the analog output (2) terminal, the output range can be selected
from 0 to 10 V and 0 to ±10 V (maximum current: 1 mA) by changing of
VF66 inverter setting parameter.
[The setting is made so that the inverter output current becomes 5 V/inverter rated current in the default condition.]
* For more information about the analog output (2) terminal, refer to the operating instructions of VF66 inverter main unit.
G2
GND terminal
Do not connect G2 terminal to the ground terminal.

2. 3 PG Input/Output Terminal Specifications

PG input/output function
EIP66-Z terminal block TB2
Terminal name
Usage
Description
+12
+12 V power supply terminal
Outputs a direct voltage of +12 V.
G (3 terminals)
GND terminal
Do not connect G terminal to the ground terminal.
A
PG input terminal
Inputs A, B, U/Z, V or W signal of 12 V power supply PG (complementary output).
B
U/Z V W
PGOUT
PG output terminal
Outputs a waveform of frequency divided A signal of PG.
10

2. 4 EtherNet/IP Communication Function Connector/Terminal Specifications

Communication function connector specifications (RJ-45 8 poles)
EIP66-Z connector CN3/4
Pin No.
Usage
Description
1
TX+
Transmission signal line (+)
2
TX-
Transmission signal line (-)
3
RX+
Reception signal line (+)
4
-
Unused
5 - 6
RX-
Reception signal line (-)
7
-
Unused
8
-
Communication function terminal specifications
EIP66-Z terminal block TB3
Terminal
name
Usage
Description
FG
Safety ground terminal
FG terminal (M4) for CN3/CN4

2. 5 EtherNet/IP Communication Specifications

EtherNet/IP communication specifications
Ethernet
Compliance standard
IEEE802.3i (10BASE-T)/IEEE802.3u (100BASE-TX)
Transmission speed
10/100 Mbps (automatic switching)
Communication mode
Full-duplex/half-duplex (automatic switching)
Connection type
Star/daisy chain connection
Interface
RJ-45 connector
Transmission distance (between nodes or node and hub)
Within 100 m (depends on the specification of used cable)
Connected cable
Shielded twisted pair cable (STP): Category 5 or higher Straight, cross (automatic switching)
EtherNet/IP
IP address setting
Set by the setting parameter of VF66 inverter main unit.
Communication function
Cyclic communication (Implicit message) Message communication (Explicit message)
Vendor ID
178
Product Code
13
Device Type
AC Drive Profile
Product Name
EIP66 Series
ACD function (Address Conflict Detection)
Supported Conformance test
EtherNet/IP CT-11
EDS file
EIP66 Series 1_0.eds
11

2. 6 Others

Other standard specifications conform to the VF66 inverter. For more information, refer to the operating instructions of VF66 inverter main unit.
WARNING [Wiring]
Check that the input power is turned off before wiring.
Otherwise, electric shock/fire may result.
Be sure to turn off the inverter power before changing the connection of jumper socket.
Otherwise, electric shock/injury/failure/malfunction may result.
CAUTION [Wiring]
Never connect the G and G2 terminals to a ground. Ignoring this may cause failure/damage. Do not bring the PS and G terminals into contact or connect them.
Ignoring this may cause failure/damage.
12

CHAPTER 3 Board Description

3. 1 Part Names

PS PS MI8 G AIN2 AOT2
MI6 MI7 MI9 G G2
CN-SI CN-SO
EIP66-Z
TB1
TB2
SW1
SW3
SW2
CN1 CN2
+12
A
B
G
G
U/Z
V
W
G
PG
OUT
CN5
CN3
Port0
CN4 Port1
LINK0 LINK1
TxRx0 TxRx1
LED1 LED2
LED5 LED6
MS NS
LED4
LED3
LED7
LED8
LED9
LED10 RDY LED11 RUN
CN7
JP3 JP4
TB3 FG
⑨ ⑩
⑪ ⑫
Figure 3. 1 EIP66-Z board
VFC66-Z connector (CN1, CN2) PG frequency division output switch (SW2) PG signal ON/OFF switch (SW3) External extension option (for future extension) connector (CN5) Analog input/output, multifunction input (TB1) Analog input signal characteristics changeover switch (SW1) Jumper connector for switching multifunction input signal characteristics (CN-SI, CN-SO) PG input/output terminal block (TB2) EtherNet/IP module status (MS) LED (LED5 green/red) EtherNet/IP network status (NS) LED (LED6 green/red) EtherNet/IP link (LINK) LED (LED3, LED4 green) EtherNet/IP transmission and reception (TxRx) LED (LED1, LED2 yellow) EtherNet/IP communication RJ-45 connector (CN3, CN4) Status LED (LED7, LED8, LED9) Maintenance connector, jumper connector, LED (CN7, JP3, JP4, LED10, LED11) FG terminal block (TB3)
For the connector connected to (4), use a Molex housing: 5051-12 and gold-plated terminal: 2759G or 2759PBG. For the connection and use of CN5, refer to the operating instructions of IOEXT66-Z.