TOYODA TOYOPUC CMP-LINK SIO Driver User Manual

TOYODA Machine Works, LTD.
TOYOPUC CMP-LINK SIO Driver
1 System Configuration.......................................................................................................3
2 Selection of External Device ............................................................................................6
3 Example of Communication Setting.................................................................................7
4 Setup Items....................................................................................................................17
6 Supported Device...........................................................................................................43
7 Device Code and Address Code....................................................................................47
8 Error Messages.......................................................... ....................................................50
1
TOYOPUC CMP-LINK SIO Driver
Introduction
This manual describes how to connect the Display and the External Device (target PLC). In this manual, the connection procedure will be described by following the below sections:
System Configuration
1
This section shows the types of External Devices which can be connected and SIO type.
Selection of External Device
2
Select a model (series) of External Device to be connected and connection method.
Example of Communication Settings
3
This section shows setting examples for communicating between the Display and the External Device.
) "1 System Configuration" (page 3)
) "2 Selection of External Device" (page 6)
) "3 Example of Communication Setting" (page
7)
Communication Settings
4
Perform the communication settings between the Display and the External Device. Set communication settings of the Display with GP-Pro EX or in off-line mode.
Cable Diagram
5
This section shows cables and adapters for connecting the Display and the External Device.
Operation
) "4 Setup Items" (page 17)
) "5 Cable Diagram" (page 22)
GP-Pro EX Device/PLC Connection Manual
2
TOYOPUC CMP-LINK SIO Driver

1 System Configuration

The system configuration in the case when the External Device of TOYODA Machine Works, LTD. and the Display are connected is shown.
Series CPU Link I/F
PC2 L2
TOYOPUC-PC2
PC2J THU-2755 (PC/CMP-LINK)
PC3J
TOYOPUC-PC3J
PC3JD PC3JG
*1 When using PC/CMP-LINK (THU-2755) with PC3J command, the link unit in ver. 5.00 or higher is required.
Also, the link unit does not have the settings of PC2J or PC3J selection switch (SW) etc. Error occurs when sending PC3J command to the link unit in less than ver. 5.00.
THU-2652 (computer link module)
Link I/F on the CPU unit (L2 terminal block)
Link I/F on the CPU unit (L1, L2 terminal block)
THU-2755 (PC/CMP-LINK)
Link I/F on the CPU unit (L1 terminal block)
THU-2755 (PC/CMP-LINK)
*1
SIO
Type
RS422 (2wire)
RS422 (2wire)
RS422 (2wire)
RS422 (4wire)
RS422 (2wire)
RS422 (2wire)
RS422 (2wire)
Setting Example Cable Diagram
Setting Example 1 (page 7)
Setting Example 2 (page 9)
Setting Example 3 (page 11)
Setting Example 4 (page 13)
Setting Example 5 (page 15)
Setting Example 3 (page 11)
Setting Example 5 (page 15)
Cable Diagram 1 (page 22)
Cable Diagram 1 (page 22)
Cable Diagram 2 (page 28)
Cable Diagram 3 (page 34)
Cable Diagram 4 (page 38)
Cable Diagram 1 (page 22)
Cable Diagram 1 (page 22)
Connection Configuration
The system configuration in the case when you use the External Device PC2J (n units) of TOYODA Machine Works, LTD. and the GP (1 unit) to realize the 1:n communication with HOST link protocol are connected is shown.
Always set one unit of the Display used in the system.
On the link, you can connect max 16 units of the External Device to one unit of the Display.
GP-Pro EX Device/PLC Connection Manual
3
TOYOPUC CMP-LINK SIO Driver
COM Port of IPC
When connecting IPC with External Device, the COM port which can be used changes with series and SIO type. Please refer to the manual of IPC for details.
Usable port
Series
Usable port
RS-232C RS-422/485(4 wire) RS-422/485(2 wire)
*1
PS-2000B
COM1
COM3 PS-3650A, PS-3651A COM1 PS-3700A (Pentium®4-M)
PS-3710A
COM1
COM3 PS-3711A COM1*1, COM2
, COM2,
*1
, COM4
*1
*1
, COM2*1,
*2
, COM4
--
--
*2
COM3
*2
COM2
*2
COM3
COM2
*2
*2
*1 The RI/5V can be switched. Please switch with the change switch of IPC. *2 It is necessary to set up the SIO type with the Dip switch. Please set up as follows according to SIO
type to be used.
Dip switch setting: RS-232C
Dip switch Setting Description
1 OFF Reserve (always OFF) 2OFF
SIO type: RS-232C
3OFF 4 OFF Output mode of SD (TXD) data: Always output 5 OFF Terminal resistance (220) insertion to SD (TXD): None 6 OFF Terminal resistance (220) insertion to RD (RXD): None 7 OFF Short-circuit of SDA (TXA) and RDA (RXA): Does not Exist 8 OFF Short-circuit of SDB (TXB) and RDB (RXB): Does not Exist 9OFF
10 OFF
GP-Pro EX Device/PLC Connection Manual
RS (RTS) Auto control mode: Disable
4
Dip switch setting: RS-422/485 (4 wire)
Dip switch Setting Description
1 OFF Reserve (always OFF) 2ON 3ON 4 OFF Output mode of SD (TXD) data: Always output 5 OFF Terminal resistance (220) insertion to SD (TXD): None 6 OFF Terminal resistance (220) insertion to RD (RXD): None 7 OFF Short-circuit of SDA (TXA) and RDA (RXA): Does not Exist 8 OFF Short-circuit of SDB (TXB) and RDB (RXB): Does not Exist 9OFF
10 OFF
Dip switch setting: RS-422/485 (2 wire)
Dip switch Setting Description
1 OFF Reserve (always OFF) 2ON 3ON 4 OFF Output mode of SD (TXD) data: Always output 5 OFF Terminal resistance (220) insertion to SD (TXD): None
TOYOPUC CMP-LINK SIO Driver
SIO type: RS-422/485
RS (RTS) Auto control mode: Disable
SIO type: RS-422/485
6 OFF Terminal resistance (220) insertion to RD (RXD): None 7 ON Short-circuit of SDA (TXA) and RDA (RXA): Exist 8 ON Short-circuit of SDB (TXB) and RDB (RXB): Exist 9ON
10 ON
RS (RTS) Auto control mode : Enable
GP-Pro EX Device/PLC Connection Manual
5

2 Selection of External Device

Select the External Device to be connected to the Display.
Setup Items Setup Description
TOYOPUC CMP-LINK SIO Driver
Maker
Driver
Select the maker of the External Device to be connected. Select "TOYODA Machine Works, LTD.".
Select a model (series) of the External Device to be connected and connection method. Select "TOYOPUC CMP-LINK SIO". Check the External Device which can be connected in "TOYOPUC CMP-LINK SIO" in system configuration.
)"1 System Configuration" (page 3)
Check this option when you synchronize the system data area of the Display and th e device (memory) of the External Device. When synchronized, you can use the ladder program of the External Device to switch the display or display the window on the Display.
Cf. GP-Pro EX Reference Manual "Appendix 1.4 LS Area (only for direct
Use System Area
Port Select the Display port to be connected to the External Device.
access method)"
This can be also set with GP-Pro EX or in off-line mode of the Display.
Cf. GP-Pro EX Reference Manual "System Area Setting, 5.14.6 Setting Guide
of [System Setting Window]"
Cf. Maintenance/Troubleshooting "2.14.1 Settings common to all Display
modelsSystem Area Settings"
GP-Pro EX Device/PLC Connection Manual
6
TOYOPUC CMP-LINK SIO Driver

3 Example of Communication Setting

Examples of communication settings of the Display and the External Device, recommended by Pro-face, are shown. When you use the FX Series, use GP-Pro EX and the ladder software to set as below.

3.1 Setting Example 1

Setting of GP-Pro EX
Communication Settings
To display the setting screen, select [Device/PLC Settings] from [System setting window] in workspace.
GP-Pro EX Device/PLC Connection Manual
7
TOYOPUC CMP-LINK SIO Driver
Device Setting
To display the setting screen, click ([Setting]) of External Device you want to set from [Device-Specific Settings] of [Device/PLC Settings]. When you connect multiple External Device, click from [Device-Specific Settings] of [Device/PLC Settings] to add another External Device.
Setting of External Device
Set the computer link module as below. Please refer to the manual of the External Device for more details on settings.
Setup Items Settings
Speed 19200bps Data Bit 8bit Stop Bit 1bit
Parity Bit Even
Card Type CMP link
SET5 Watchdog timer ON
Station No. 0
GP-Pro EX Device/PLC Connection Manual
8
TOYOPUC CMP-LINK SIO Driver

3.2 Setting Example 2

Setting of GP-Pro EX
Communication Settings
To display the setting screen, select [Device/PLC Settings] from [System setting window] in workspace.
Device Setting
To display the setting screen, click ([Setting]) of External Device you want to set from [Device-Specific Settings] of [Device/PLC Settings]. When you connect multiple External Device, click from [Device-Specific Settings] of [Device/PLC Settings] to add another External Device.
GP-Pro EX Device/PLC Connection Manual
9
Setting of External Device
Set the computer link module as below. Please refer to the manual of the External Device for more details on settings.
Setup Items Settings
Speed 19200bps Data Bit 8bit Stop Bit 1bit
Parity Bit Even
TOYOPUC CMP-LINK SIO Driver
Internal Switch
Station No. 1
SW4-1 OFF
SW4-2 ON
GP-Pro EX Device/PLC Connection Manual
10
TOYOPUC CMP-LINK SIO Driver

3.3 Setting Example 3

Setting of GP-Pro EX
Communication Settings
To display the setting screen, select [Device/PLC Settings] from [System setting window] in workspace.
Device Setting
To display the setting screen, click ([Setting]) of External Device you want to set from [Device-Specific Settings] of [Device/PLC Settings]. When you connect multiple External Device, click from [Device-Specific Settings] of [Device/PLC Settings] to add another External Device.
GP-Pro EX Device/PLC Connection Manual
11
Setting of External Device
Set the computer link module as below. Please refer to the manual of the External Device for more details on settings.
Setup Items Settings
Speed 19200bps Data Bit 8bit Stop Bit 1bit
Parity Bit Even
TOYOPUC CMP-LINK SIO Driver
RS422
Connecting Port
STATION No. 0
2wire
GP-Pro EX Device/PLC Connection Manual
12
TOYOPUC CMP-LINK SIO Driver

3.4 Setting Example 4

Setting of GP-Pro EX
Communication Settings
To display the setting screen, select [Device/PLC Settings] from [System setting window] in workspace.
Device Setting
To display the setting screen, click ([Setting]) of External Device you want to set from [Device-Specific Settings] of [Device/PLC Settings]. When you connect multiple External Device, click from [Device-Specific Settings] of [Device/PLC Settings] to add another External Device.
GP-Pro EX Device/PLC Connection Manual
13
Setting of External Device
Set the computer link module as below. Please refer to the manual of the External Device for more details on settings.
Setup Items Settings
Speed 19200bps Data Bit 8bit Stop Bit 1bit
Parity Bit Even
TOYOPUC CMP-LINK SIO Driver
RS422
Connecting Port
STATION No. 0
4wire
GP-Pro EX Device/PLC Connection Manual
14
TOYOPUC CMP-LINK SIO Driver

3.5 Setting Example 5

Setting of GP-Pro EX
Communication Settings
To display the setting screen, select [Device/PLC Settings] from [System setting window] in workspace.
Device Setting
To display the setting screen, click ([Setting]) of External Device you want to set from [Device-Specific Settings] of [Device/PLC Settings]. When you connect multiple External Device, click from [Device-Specific Settings] of [Device/PLC Settings] to add another External Device.
GP-Pro EX Device/PLC Connection Manual
15
Loading...
+ 35 hidden pages