Toxalert TOX-O2-4 User Manual

TM
DATA
TOXALERT
SHEET
OXYGEN SENSOR MODEL TOX-O2
FEATURES
• 10 year sensing element life • Power indicator
• Low voltage circuits • Sensor failure indicator
• Linear 4 to 20 mA output • Loop current indicator
• Explosion Proof Housing • Interfaces directly to DDC systems
• Meets ASHRAE Std. 15-1994 • Relay output indicators
• Two Form C relay outputs
The Models TOX-O2 oxygen sensors are an electrochemical cell with extremely long sensor element life. The sensor element is the self-powered, diffusion limited, metal-air battery type. The rate at which atmosphere gases can get to the electrode through a diffusion barrier is dependent on the concentration of gases (O in the atmosphere. A voltage is generated that is proportional to the rate of consumption of oxygen in the sensor cell.
in this case)
2
Most electrochemical sensors use a very thin plastic membrane and have a short life. The TOXALERT oxygen sensor uses a heavy membrane which allows gas to diffuse into the sensor making it extremely robust and stable, plus it gives the element exception­ally long life expectancy, but still responds quickly to oxygen con­tent changes.
The model TOX-O tor oxygen levels and to close “warning” contacts, when oxygen levels drop to 19.5%, for the operation of ventilation equipment. A second set of “alarm” contacts are provided to operate alarm(s) and /or signal building management systems (BMS), when oxygen levels drop to 18.5%. The warning and alarm setpoints are field adjustable.
The model TOX-O a linear 4 to 20 mA output signal. This signal may be interfaced directly to a TOXALERT control unit or any other standard BMS controller and provide actual percent oxygen concen­tration for control and/or display.
TOXALERT INTERNATIONAL, INC., P.O. BOX 159, MOUND, MINNESOTA 55364 (952) 472-4541 FAX (952) 472-4960
/4 oxygen sensor/controller is designed to moni-
2
TOX-O2/1
/1 oxygen sensor/transmitter is designed to monitor oxygen levels and has
2
Visit our website at www. toxalert. com
GUIDE SPECIFICATIONS
MODEL TOX-O
/1 ANALOG SENSOR:
2
Provide an oxygen sensor(s) with a range of 0 to 25% and a linear 4 to 20 mA output signal over its range. The sensors output shall be designed to work into a minimum of a 500 OHM load. The sensor shall be housed in an industrial style explosion proof housing. The sensing element shall be electro chemical diffusion barrier type and be designed for ten (10) year element life. Electro chemical cells with a three year or less expected life are not acceptable. The sensor shall be 24 vdc powered and its 4 to 20 mA output shall be directly proportional to the percent of oxygen being detected. If the sensor should fail, it shall drive its output signal to zero indicating zero percent oxygen and an alarm condition.
The oxygen sensor shall have the following diagnostic light emitting diodes (LED’s):
1) Power
2) Sensor failure
3) LOOP UP (LED varies in intensity indicating 4 to 20 mA loop current to controller).
Sensor shall have volt meter terminals on face of sensor to indicate percent oxygen being detected.
MODEL TOX-O
/4 RELAY SENSOR:
2
Provide an oxygen sensor(s) with a range of 0 to 25%, have a 4 to 20 mA output signal and two adjustable output relays over its range. The sensor shall be housed in an industrial style explosion proof housing. The sensing element shall be electro chemical diffusion barrier type and be de­signed for ten (10) year element life. Electro chemical cells with a three year or less expected life are not acceptable. The sensor shall be 24 vdc powered. If the sensor should fail, it shall drive its output signal to zero indicating zero percent oxygen and energizing both output relays.
The oxygen sensor shall have the following diagnostic light emitting diodes (LED’s):
1) Warning relay energized
2) Alarm relay energized
3) Power
4) Sensor failure
The warning relay and alarm relay shall be Form C contacts and the relay setpoints shall be field adjustable without calibration gas. Relay contacts shall be rated for 1 amp at 24 vdc.
Sensor shall have volt meter terminals on face of sensor to indicate percent oxygen being detected.