![](/html/7b/7b1e/7b1ec3ef5aea25f7b596f00ad5fb141dfd7e57a67434e5b6b230f5cdc1524ca7/bg1.png)
TOXALERT
™
COMBUSTIBLE GAS MODULE MODEL TOX-COMB/ANA
APPLICATIONS
–
Battery Charging
− Office Buildings, UPS Rooms
− Warehouses – Electric Forklift Charging
− Golf Courses – Electric Golf Cart Charging
Compressed Natural Gas (CNG) – Vehicle Storage
Boiler Room – Natural Gas Leaks
Military & Commercial Airport Hangers – Jet Fuels
Laboratories – Natural Gas
Gasoline Storage
Waste Water Treatment Plants
Gas & Oil Operations
Underground Utility Vaults/Huts
TOX-COMB/ANA
Chemical/Petrochemical Plants
PRODUCT DESCRIPTION:
The Model Tox-Comb/ANA Combustible Transmitter/Sensor Module is designed to interface with Toxalert
Models Tox-4ANA and ToxControl controllers. It can also interface with PLC/DDC building automation
systems using standard 4-20mA loop controllers.
The Model Tox-Comb/ANA is highly reliable and very cost effective for the detection of common combustible
gas hazard applications. The module requires a three wire connection to controller which provides the nominal
24VDC power and the module sources a 4-20mA current in proportion to the combustible gas concentration.
The Model Tox-Comb/ANA can be used either indoors or outdoors. The flame arrester utilizes a patented
coating which makes it water repellent. Also, splash guard and duct mounting accessories are available.
FEATURES:
Catalytically aided platinum bead sensor.
0-100% LEL range.
Poison resistant sensor standard.
Water repellent patented sensor coating.
Linear 4-20mA output.
% LEL readout provided during calibration –
using any volt meter.
Indoor or outdoor use.
Explosion proof construction (Class 1, Div. 1,
Groups B, C, D).
TOXALERT INT’L, INC., P.O. BOX 159, MOUND, MINNESOTA 55364 952/472-4541 FAX 952/472-4960
www.toxalert.com
![](/html/7b/7b1e/7b1ec3ef5aea25f7b596f00ad5fb141dfd7e57a67434e5b6b230f5cdc1524ca7/bg2.png)
MODEL TOX-COMB/ANA
SPECIFICATIONS:
SENSOR CALIBRATION
Type: Catalytically aided platinum bead Adjustments: Zero, span
Range: 0 – 100 LEL Test Points: Current, voltage, output
Response: 90% in 45 seconds
Typical Life: Three years in normal service ENVIRONMENTAL (TEMPERATURE)
Zero Drift: Less than 5% per year Operating: -40° to 185° F (-40° to 85° C)
Humidity: 0- 99% RH, non condensing
ELECTRICAL DATA CONSTRUCTION
Wiring: 3 wire non-insolated Electrical Class: Class 1, Div., Groups B, C & D
Input Voltage: 11 – 30 VDC Mounting: Conduit or flexible cable
Input Current: 200 mA at 24 VDC Physical: 7.25” x 3.5” x 3.5”
Input Power: 2.3 W (18.4 cm x 8.9 cm x 8.9 cm)
Output: 4 to 20mA signal Weight: 1.5 pounds (0.68 kg)
Loop Resistance: 800 Ohms Housing: Cast Aluminum
Partial List of Available Combustible Gases
Acetic Acid
Acetone
Acetylene
Butane
Iso-Butane
Butene-1
iso-Butyle Alcohol
ios-Butyl Benzene
Dimethylpentane
Ethane
Splash Guard
•
Calibration adaptors •Remote sensor option
•Splash guards •Duct mount kit
•Calibration kits •Remote horns & strobes
Ethyl Acetate
Ethyl Alcohol
Ethylene
Diethyl Ether
Dimethyl Ether
Heptane
Hexane
Hydrogen
Methane
Methyl Acetate
Available Accessories
Methyl Alcohol
Methylethyl Ketone
Natural Gas
Octane
Pentane
Propane
Propyl Alcohol
Toluene
Xylene
JP-4 (Jet Fuel)
Strobe Light
ToxComb/ANA Revised 11/12 2 of 2
Calibration Adaptor
CalKit
TOXALERT INT’L, INC., P.O. BOX 159, MOUND, MINNESOTA 55364 952/472-4541 FAX 952/472-4960
www.toxalert.com