The model GVU-VOC diesel smoke full spectrum sensor is designed
to interface with Toxalert International’s GVU series control units.
The GVU-VOC is a microprocessor-based air quality sensor utilizing
metal-oxide semi conductor technology. This is a full spectrum sensor
sensitive to a wide variety of air pollutants such as smoke,
hydrocarbons, gasoline fumes, acetone, toluene, etc. (see Table 3).
The GVU-VOC indicates its status with indicators for auto-power
on and processor normal, ok, low, mid or high for level of
contaminant detected.
BACKGROUND:
The diesel engine exhausts a great percentage of smoke (soot) as
well as, many hydrocarbons (e.g., ethylene, formaldehyde, methane,
benzene, and polynuclear aromatic hydrocarbons) and toxic gases
(e.g., nitric oxide, nitrogen dioxide and oxides of sulfur). The smoke
is particularly evident at the beginning of a work shift, when all
the buses or tracks are started in a maintenance/storage facility.
Even though, the exhaust smoke is not classified as a toxic, it is considered a carcinogen (reference:
carcinogenic effects of exposure to diesel exhaust - NIOSH Publication No. 88-116). Therefore many facility
owners are monitoring the smoke/hydrocarbons (VOC) as well as, the toxic oxides of nitrogen.
For best operation, locate a mounting location away from
direct fresh air intakes, doors and supply diffusers and
mount vertically on wall or support column approximately 5
to 6 feet above floor. An alternate location is in the ceiling
space of facilities with top discharge diesel vehicles. Refer to
figures 1 and 2; Table 1 and 2 and installation instructions in
GVU series control unit data sheet and install the GVUVOC sensor as follows.
2. COVER REMOVAL
Screw set-screw in bottom of cover in (clockwise) and
remove cover.
3. MOUNTING
The sensor has mounting provisions to install directly on a
standard electrical box.
4. SENSOR WIRING
WARNING: To prevent fire or shock hazard, turn
off power source to control unit before making
connections. Comply with all local building codes and
ordinances.
NOTE: Refer to Figure 2 and Tables 1 and 2. Use shield
cable to interconnect sensor and control unit if metal conduit is not used, or if conduit also contains AC wiring.
1.)Measure distance between sensing unit
and control unit and select proper wire or larger wire
from Table 1.
2.)Run wiring between control and sensing
unit and into enclosure through access
holes. Connect wires from terminal
blocks in sensing unit to control unit per
Table 2 and GVU series control unit
data sheet.
5. START-UP
TABLE 1
AW GDO NOT EXCEED
#22 Wire500 Ft. Sensor to Controller
#20 Wire800 Ft. Sensor to Controller
#18 Wire1300 Ft. Sensor to Controller
#16 Wire2000 Ft. Sensor to Controller
1.)Verify all wiring connections are correct
and are tight.
2.)Apply power and note the status LEDs.
Initially the LEDs will flash in sequence
(OK, LOW, MID, HIGH and AUTO)
to indicate a successful start-up. The
device will then enter a three minute
warm-up cycle and this is indicated by a
TABLE 2WIRING CONNECTIONS
GVU-VOCCONTROL UNITS
SENSORGVU-1GVU-3
flashing AUTO LED and lit OK LED.
This mode will continue for three minutes
until the sensor has reached operating
** Shield of cable (if used) should be connected at control unit only.
Make sure sensor end is taped and isolated from terminals or metal.
temperature.
3.)After the initial warm-up period, the device will enter normal operation. This will be indicated by
the AUTO LED being lit and also one pollution level LED being lit (OK, LOW, MID or HIGH).
Note that the sensor is calibrated at manufacture to be suitable for use in average room conditions. The
sensor filter will accumulate dust over a period of inactive time and the sensor must be allowed to burnin before proper operation. This time will vary depending on the storage time, but the unit will be suitable for pre-commissioning after about 30 minutes.
4.)Replace cover.
TABLE 3
PARTIAL LIST OF CONTAMINATES DETECTED BY TOXALERT INTERNATIONAL GVUVOC SENSOR.
CHEMICALCOMMON SOURCE
EthyleneDiesel exhaust
Benzene, Toluene, XyleneDiesel exhaust, solvents and motor fuels
MethaneDiesel exhaust, decomposition and sysnthesis
FormaldehydeDiesel exhaust, disinfectants and preservatives
Methyl Ethyl KetoneSolvents and cleaning products
AcetoneSolvents and organic synthesis
Ethyl AlcoholSolvents and liquor fermentation
HydrogenUsed in synthetics
Hydrogen SulfideWater and putrefying matter
Methyl AlcoholSolvents, antifreeze and synthetics
Methyl ChlorideSolvents, paints and refrigerants
Vinyl ChlorideTextiles and polymers
TrichloroethyleneSolvents and cleaning agents
PropaneFuels and chemical synthesis
Carbon MonoxideCombustion of carbon
Freon-22Refrigerants and aerosols
AmmoniaSolvents and refrigerants
GVU SERIES PRODUCTS:
CONTROLLERS -
GVU-1Control unit for use with one sensor
GVU-3Control unit for use with one to three remote sensors