Toxalert GVU-NO2 User Manual

TM
DATA
TOXALERT
SHEET
NITROGEN DIOXIDE SENSOR MODEL GVU-NO DIESEL EXHAUST GAS DETECTOR
TYPICAL INSTALLATIONS:
• Parking Garages • Vehicle Maintenance & Storage
• Bus Garages Highway Departments
• Warehouses Public Works
• Car Dealers • Tunnels
GENERAL DESCRIPTION:
The model GVU-NO2 nitrogen dioxide sensor is designed to interface with Toxalert International GVU series control units. The Model GVU-
utilizes an electrochemical sensing element and is designed for
NO
2
ambient monitoring applications. It is intended for use in fixed monitoring installations, and therefore continuous operation. The GVU-NO requires a four-wire connection from a controller that provides a nominal 24VDC power source, common and return signal input. The GVU-NO
has an effective range of 0-10 ppm. The sensor module
2
has indicators for power on, fault status and high NO2.
2
2
The Toxalert Nitrogen Dioxide (NO energy savings. A common producer of NO Diesel exhaust is a know cancer causing agent as reported in the U.S. Department of Health and Human Services’ Current Intelligence bulletin 50 dated August 1988. An electrochemical cell is required to measure such small amounts of NO measuring NO
in increments of 0.1 ppm.
2
) Transmitter combines safety and
2
is diesel engine exhaust.
2
. The device’s sensor is capable of
2
Model GVU-NO
2
FEATURES:
Power on indication
High NO
Fault Indicator
Low voltage class two (2) wiring
Convenient diagnostics
Simple maintenance
Operating range meets OSHA standard
TOXALERT INTERNATIONAL, INC., P.O. BOX 159, MOUND, MINNESOTA 55364 (952) 472-4541 FAX (952) 472-4960
Indication
2
Visit our website at www. toxalert. com
SPECIFICATIONS
Type: Electro-chemical cell diffusion barrier type
•Range: 0 to 10 ppm nitrogen dioxide in air
•Response Time: 30 seconds to 90% indication
•Typical life: Two years in normal service
•Accuracy: +/–5% of full scale
•Resolution: 0.1 ppm
•Operating Temperature: 4º to 122ºF
(–20ºC to 50ºC)
•Relative Humidity: 15 to 90% RH non-condensing
ELECTRICAL DATA:
• Input voltage: 24 VDC (provided from GVU control Unit)
•Wiring: 4 wire non-isolated
UNIT CONSTRUCTION:
•Mounting: Conduit 1/2” and 3/4” NPT or flexible cable
•Housing: Polystyrene, impact-resistant, non flammable, IP66
• Physical: 5.11”x 5.11” x 2.95” (13.0 x 13.0 x 7.5 cm)
•Weight: 14.2 oz.
INSTALLATION INSTRUCTIONS
1. INSTALLATION (For specific
details see sensor manual)
Locate a mounting location away from direct fresh air intakes, and mount vertically on wall or support column approximately 3 to 6 feet above floor. Refer to figures 1 and 2; Table 1 and 2 and installation instruc­tions in GVU series control unit data sheet and install the GVU-NO sensor as follows.
2. MOUNTING SENSOR
Install the module housing onto the end of the supply conduit and bolt into position as required.
3. SENSOR WIRING
WARNING: To prevent fire or shock hazard, turn off power source to control unit before making connections. Comply with all local building codes and ordinances.
2
Figure 1:
TOXALERT INTERNATIONAL, INC., P.O. BOX 159, MOUND, MINNESOTA 55364 (952) 472-4541 FAX (952) 472-4960
Visit our website at www. toxalert. com
INSTALLATION INSTRUCTIONS
NOTE: Refer to Figure 2 and Tables 1 and 2. Use shielded cable to interconnect sensor and control unit if metal conduit is not used, or if conduit also contains AC wiring.
1.) Measure distance between sensing unit and control unit and select proper wire or larger wire from Table 1.
2.) Run wiring between control and sensing unit and into enclosure through access holes. Connect wires from terminal blocks in sensing unit to control unit per Table 2 and GVU series control unit data sheet.
Figure 2:
4. START-UP
Reference Installation Manual
1.) Verify all wiring connections are correct.
2.) Electronics replacement - Carefully fit the electronics over the two posts in the enclosure and
tighten the captive panel screws.
3.) Apply Power
4.) Green power indicator should light
5.) Replace Cover
6.) Allow 1 hour to warm-up
TABLE 1
AW G DO NOT EXCEED
#22 Wire 500 Ft. Sensor to Controller #20 Wire 800 Ft. Sensor to Controller #18 Wire 1300 Ft. Sensor to Controller #16 Wire 2000 Ft. Sensor to Controller
TOXALERT INTERNATIONAL, INC., P.O. BOX 159, MOUND, MINNESOTA 55364 (952) 472-4541 FAX (952) 472-4960
Visit our website at www. toxalert. com
TABLE 2 WIRING CONNECTIONS
GVU-NO
2
CONTROL UNITS
SENSOR GVU-1 GVU-3
J2-1 TB11-24 VDC (+) TB3-H (+24VDC J2-3 TB11-24 VDC (–) TB3-N (–24VDC) J3-1 TB2-1 TB1-A1, B1, C1 J3-3 TB2-7 TB1-A7, B7, C7 ** TB2-5 TB1-A5, B5, C5
** Shield of cable (if used) should be connected at control unit only. Make sure sensor end is taped and isolated from terminals or metal
GVU SERIES PRODUCTS:
CONTROLLERS -
GVU-1 Control unit for use with one sensor GVU-3 Control unit for use with one to three remote sensors GVU-6 Control unit for use with one to six remote sensors GVU-12 Control unit for use with one to twelve remote sensors GVU-18 Control unit for use with one to eighteen remote sensors
REMOTE SENSORS -
GVU-CO Remote carbon monoxide sensor GVU-CO GVU-NO
Remote carbon dioxide sensor
2
Remote nitrogen dioxide sensor
2
GVU-VOC Remote smoke/air quality sensor
GVU-NO2 5/07
TOXALERT INTERNATIONAL, INC., P.O. BOX 159, MOUND, MINNESOTA 55364 (952) 472-4541 FAX (952) 472-4960
Visit our website at www. toxalert. com
Loading...