Toxalert GVU-2R User Manual

TM
DATA
TOXALERT
SHEET
CARBON MONOXIDE SENSOR MODEL GVU-CO
TYPICAL INSTALLATIONS:
• Parking Garages • Vehicle Maintenance & Storage Apartments Highway Departments Condominiums Utilities Ofce Buildings Public Works
• Bus Garages • Police Stations
• Fire Stations • Post Ofces
• Warehouses • Ice Arenas
GENERAL DESCRIPTION:
The GVU-CO carbon monoxide sensor is designed to interface with Toxalert Internationals GVU series control. (It is not a stand alone sensor). The sensor is microprocessor based and is temperature and humidity compensated for stability. It has a range from 0 to 250 ppm. The transducer utilizes a tin-oxide sensing element that is cleaned and sampled by the microprocessor. The GVU-CO indicates its status with a two color LED (light emitting diode). When the LED is flashing green, operation is normal and not in alarm. When the LED is flashing red, the unit is in alarm (high CO). A continuous red or green indicates sensor failure and an extinguished LED indicates power failure.
GVU-CO
FEATURES:
• Microprocessor based • Humidity & Temperature compensated
• Power On Indication • Sensor Failure Indicator
• High CO Indication • Operating range meets OSHA Std. 1910-1000
• Completely solid state for long life • Locking Enclosure
• Low voltage class two (2) wiring
TOXALERT INTERNATIONAL, INC., P.O. BOX 159, MOUND, MINNESOTA 55364 (952) 472-4541 FAX (952) 472-4960
Visit our website at www. toxalert. com
SPECIFICATIONS:
• Input Power: 12 VDC; 360 mA
(provided from control unit).
Sensor Output: 0 to 5 VDC (non linear); on at a nominal 4 VDC and off at 0 VDC.
• Environmental: Operating- Temperature: -4˚ F to 122˚ F (-20˚ C to 50˚ C) Optional: -20˚ F to 122˚ F (-28˚ C to 50˚ C) Relative Humidity: 0 to 95% non condensing.
• Enclosure:
Nema 1 standard (others available) Dimensions: 7 1/4” H x 7 3/4” W x 2 1/2” D
(184.15 x 196.85 x 63.5 mm)
INSTALLATION INSTRUCTIONS:
• Electrical Connections: At marked screw terminal strip.
Response Time: 30 seconds full scale.
Storage­ Temperature: -20˚ F to 158˚ F (-28˚ C to 70˚ C) Relative Humidity: 0 to 95% non condensing.
Keylocking Finish: Tan Enamel Weight: 3 lbs. (1.3 kg)
TOXALERT INTERNATIONAL, INC., P.O. BOX 159, MOUND, MINNESOTA 55364 (952) 472-4541 FAX (952) 472-4960
Visit our website at www. toxalert. com
NOTE: Refer to Figure 2 and Tables 1 and 2. Use shielded cable to interconnect sensor and control unit if metal conduit is not used, or if conduit also contains AC wiring.
1.) Measure distance between sensing unit and control unit and select proper wire or larger wire from Table 1.
2.) Run wiring between control and sensing unit and into enclosure through access holes. Connect wires from terminal blocks in sensing unit to control unit per Table 2 and GVU series control unit data sheet.
TABLE 1 AWG DO NOT EXCEED
#22 Wire 500 Ft. Sensor to Controller #20 Wire 800 Ft. Sensor to Controller #18 Wire 1300 Ft. Sensor to Controller #16 Wire 2000 Ft. Sensor to Controller
3.) Verify all wiring connections and turn power on to sensor.
3. BURN -IN:
Burn-in period allows sensor to stabilize before proceeding with alarm setting procedure.
1.) Verify sensor has power, sensor LED should
be flashing green or red.
2.) Allow systems to burn-in for a minimum of 72 hours with power turned on to sensor.
3.) When 72 hours have elapsed, proceed with system checkout according to GVU series control unit data sheet.
Sensor is factory calibrated to 50 ppm CO and requires no field calibration for installation.
If the GVU-CO indicator LED is not flashing, this indicates sensor failure, please contact your local representative or TOXALERT International.
TABLE 2 WIRING CONNECTIONS
GVU-CO CONTROL UNITS SENSOR GVU-1 GVU-3
1 TB2-7 TB1-A7,B7,C7
2* TB2-6 TB1-A6,B6,C6 4 TB2-1 TB1-A1,B1,C1 5 TB2-4 TB1-A4,B4,C4 ** TB2-5 TB1-A5,B5,C5
* Optional-power to sensor indication. ** Shield of cable (if used) should be connected at control unit only. Make sure sensor end is taped and isolated from terminals or metal.
GVU SERIES PRODUCTS:
CONTROLLERS
GVU-1 Control unit for use with one sensor
GVU-3 Control unit for use with one to three remote sensors GVU-6 Control unit for use with one to six remote sensors GVU-12 Control unit for use with one to twelve remote sensors
GVU-18 Control unit for use with one to eighteen remote sensors
REMOTE SENSORS –
GVU-CO Remote carbon monoxide sensor GVU–NO GVU-CO2 Remote CO sensor GVU–VOC Remote smoke/air quality sensor
GVU-CO revised 4/14
TOXALERT INTERNATIONAL, INC., P.O. BOX 159, MOUND, MINNESOTA 55364 (952) 472-4541 FAX (952) 472-4960
Visit our website at www. toxalert. com