Toxalert GVU-18 User Manual

TM
DATA
TOXALERT
SHEET
CO / CO2 / NO2 / OR VOC MONITOR MODEL GVU-6 VEHICLE EXHAUST GAS DETECTOR MODEL GVU-12
MODEL GVU-18
TYPICAL INSTALLATIONS:
Parking Garages • Vehicle Maintenance & Storage Apartments Highway Departments Condominiums Utilities Office Buildings Public Works
Bus Garages Police Stations
Fire Stations Post Offices
Warehouses Ice Arenas
Car Dealers Tunnels
Welding Shops
GENERAL DESCRIPTION:
The GVU-6,12 and 18 ventilation control systems combine toxic gas-based and time-based fan control modes in all solid-state, low maintenance, cost effective product.
The GVU-6 series controller can monitor up to six (6) GVU-CO sensors; six (6) GVU-CO or any combination of these. The GVU-6 Controller consists of the power supply , solid state clocks, time delays, fan control, terminal strips, and power on indicator.
The GVU-12 series controller can monitor up to twelve (12) GVU-CO sensors; twelve (12) GVU-CO twelve (12) GVU-VOC sensors; or any combination of these. The GVU-12 Controller consists of the power supply, solid state clocks, time delays, fan control, terminal strips, and power on indicator.
The GVU-18 series controller can monitor up to eighteen (18) GVU-CO sensors; eighteen (18) GVU-CO eighteen (18) GVU-VOC sensors; or any combination of these. The GVU­18 Controller consists of the power supply, solid state clocks, time delays, fan control, terminal strips, and power on indicator.
The GVU-CO sensor is microprocessor based and is temperature and humidity compensated for stability. The GVU-CO sensor range is 0 to 250 ppm. The transducer utilizes a tinoxide sensing element that is cleaned and sampled by the microprocessor. The GVU-CO indicates its status via a two color LED (light emitting diode). When the LED is flashing green, operation is normal and not in alarm. When the LED is flashing red, the unit is in alarm (high CO); a continuous red or green indicates sensor failure; and LED extinguished indicates power failure.
sensors, six (6) GVU-NO2 sensors, six (6) GVU-VOC sensors;
2
sensors, twelve (12) GVU-NO2 sensors,
2
sensors, eighteen (18) GVU-NO2 sensors,
2
Model GVU-6
See separate specification data sheet for information regarding GVU-CO nitrogen dioxide sensor and GVU-VOC smoke/air quality sensor. See last page for ordering information.
TOXALERT INTERNATIONAL, INC., P.O. BOX 159, MOUND, MINNESOTA 55364 (952) 472-4541 FAX (952) 472-4960
Visit our website at www. toxalert. com
carbon dioxide sensors, GVU-NO
2
2
FEATURES
• Fully electronic for long life
• User adjustable alarm setting
• Minimum fan run time
• User adjustable 2nd stage activation
• Trouble Free Operation
• Visual indication of high gas concentration
• Operating range meets OSHA std. 1910.1000
VENTILATION CONTROL
Should a high gas concentration occur (above user-adjustable alarm level), an alarm signal from any sensor unit starts a 30 second delay. Should the concentration persist through the delay period, the “alarm” clock is activated. The “on” time of this clock, is user-adjustable in discrete settings from 5 to 55 minutes. Upon activation of the “alarm” clock, the “fan-on” relay energizes and remains energized until the “alarm” clock” times out. Should the high concentration still be above the alarm level, the “fan-on” relay will remain ON and the “alarm” relay will energize. This condition is maintained until the high concentration drops.
OPTIONS:
• Audible alarm w/push button audio silence • Sensor status indicators per sensor
• Fan on indicator • Second zone of fan control
• Fan override switch • 7-day time clock
SPECIFICATIONS
Input Power: 120VAC, 60Hz, 1 A (fused) Relay Contacts: 24 VAC, 2A resistive, 1.5 inductive Minimum Fan On Time: Adjustable in 5 minute Finish: Control Unit: Gray enamel intervals Enclosure: Nema 1 standard, others available Dimensions:
GVU-6 20”H x 12”W x 6” D
(508 mm x 305 mm x 152.4 mm)
GVU-12 20”H x 20”W x 6” D
(508 mm x 508 mm x 152.4 mm)
GVU-18 20”H x 24”W x 6” D
(508 mm x 609 mm x 152.4 mm)
GVU SERIES PRODUCTS:
CONTROLLERS –
GVU-1 Control unit for use with one sensor GVU-3 Control unit for use with one to three remote sensors GVU-6 Control unit for use with one to six remote sensors GVU-12 Control unit for use with one to twelve remote sensors GVU-18 Control unit for use with one to eighteen remote sensors
REMOTE SENSORS –
GVU-CO Remote carbon monoxide sensor GVU-NO GVU-CO
Remote carbon dioxide sensor GVU-VOC Remote smoke/air quality sensor
2
ANNUAL CALIBRATION CHECK IS RECOMMENDED
Remote nitrogen dioxide sensor
2
MODEL GVU-6, 12, 18 1/06
TOXALERT INTERNATIONAL, INC., P.O. BOX 159, MOUND, MINNESOTA 55364 (952) 472-4541 FAX (952) 472-4960