Town & Country Fireplaces Installation And Operating Instructions Manual
Specifications and Main Features
Frequently Asked Questions
User Manual
INSTALLER: Leave this manual with the appliance.
CONSUMER: Retain this manual for future reference.
WARNING: If the information in these
instructions is not followed exactly, a re or
explosion may result causing property damage,
personal injury or death.
FOR YOUR SAFETY
Installation and service must be performed
by a qualied installer, service agency or the
gas supplier.
WHAT TO DO IF YOU SMELL GAS
• Donottrytolightanyappliance.
• Donottouchanyelectricalswitch.
•Donotuseanyphoneinyourbuilding.
• Immediatelycallyourgassupplierfrom
a neighbour’s phone. Follow the gas
supplier’s instructions.
• Ifyoucannotreachyourgassuppliercall
the re department.
Do not store or use gasoline or other ammable
vapors and liquids in the vicinity of this or any
other appliance.
SERIAL #
TCWS38
INSTALLATION
AND OPERATING
INSTRUCTIONS
This appliance may be installed in an aftermarket
permanently located, manufactured home (USA only)
or mobile home, where not prohibited by local codes.
This appliance is only for use with the type of gas
indicated on the rating plate. This appliance is
not convertible for use with other gases, unless a
certied kit is used.
This appliance is suitable for installation in a
bedroom or bed sitting room.
011214-48 TCWS38_D 5056.42523D
MODEL
TCWS38
SERIES D
MODULAR DIRECT VENT
FIREPLACE
FOR YOUR SAFETY - Do not install or operate your Town & Country replace without rst
reading and understanding this manual. Any installation or operational deviation from the following instructions voids the Town & Country Fireplaces
This appliance and its individual shut off valve must be disconnected from gas supply piping
system during any pressure testing of that system at test pressures in excess of 1/2 psig
(3.5 kPa).
This appliance must be isolated from the gas supply piping system by closing its individual
manual shut off valve during any pressure testing of the gas supply piping system at test
pressures equal to or less than 1/2 psig (3.5 kPa).
Note: When lit for the rst time, the appliance will emit a slight odour for a couple of hours.
This is due to the curing of paints, sealants and lubricants used in the manufacturing process.
This condition is temporary. Open doors and windows to ventilate area. Smoke and fumes
caused by the curing process may cause discomfort to some individuals.
Do not use the replace if any part has been under water. Immediately call a qualied service
technician to inspect the replace and to replace any part of the control system and any gas
control which has been under water.
TM
Warranty and may prove hazardous.
Safety
We recommend that our gas hearth
products be installed and serviced
by professionals who are certied
in the United States by the National
Fireplace Institute
Specialists
®
(NFI) as NFI Gas
Due to high temperatures, this gas appliance should be located out of traffic and away from
furniture and draperies.
Children and adults should be alerted to the hazards of high surface temperatures and
should stay away to avoid burns or clothing ignition.
Young children should be carefully supervised when they are in the same room as the
appliance. Toddlers, young children and others may be susceptible to accidental contact
burns. A physical barrier is recommended if there are at risk individuals in the house. To
restrict access to the replace or stove, install an adjustable safety gate to keep toddlers,
young children and other at risk individuals out of the room and away from hot surfaces.
Clothing or other ammable material should not be placed on or near the appliance.
Any grill, panel or door removed for servicing the unit must be replaced prior to operating.
Failure to do so may create a hazardous condition.
Installation and repair should be done by a qualied service person. The appliance should
be inspected before use and at least annually by a professional service person. More
frequent cleaning may be required due to excessive lint from carpeting, bedding material,
etc.. It is imperative that control compartments, burners and circulating air passageways
of the appliance be kept clean.
It is our policy that no responsibility is assumed by the Company or by any of its employees
or representatives for any damages caused by an inoperable, inadequate, or unsafe
condition which is the result, either directly or indirectly, of any improper operation or
installation procedures.
This appliance must not be connected to a chimney ue serving a separate solid fuel
burning appliance.
TCWS38_D 011214-48
3
Important Note for the Commonwealth of Massachusetts:
From Massachusetts Rules and Regulations 248 CMR 5.08:
(a) For all side wall horizontally vented gas fuelled equipment installed in every dwelling, building or structure used in whole or in part for residential
purposes, including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is less than seven (7) feet above
nished grade in the area of the venting, including but not limited to decks and porches, the following requirements shall be satised.
1. INSTALLATION OF CARBON MONOXIDE DETECTORS. At the time of installation of the side wall horizontal vented gas fuelled equipment, the
installing plumber or gas tter shall observe that a hard wired carbon monoxide detector with an alarm and battery back-up is installed on the oor level
where the gas equipment is to be installed, in addition, the installing plumber or gas tter shall observe that a battery operated or hard-wired carbon mon-
oxide detector with an alarm is installed on each additional level of the dwelling, building or structure served by the side wall horizontal vented gas fuelled
equipment. It shall be the responsibility of the property owner to secure the services of qualied licensed professionals for the installation of hard-wired
carbon monoxide detectors.
a. In the event that the side wall horizontally vented gas fuelled equipment is installed in a crawl space or an attic, the hard-wired carbon monoxide
detector with alarm and battery back-up may be installed on the next adjacent oor level.
b. In the event that the requirements of this subdivision cannot be met at the time of completion of installation, the owner shall have a period of thirty
(30) days to comply with the above requirements; provided, however, that during said thirty (30) day period, a battery operated carbon monoxide detector
with an alarm shall be installed.
2. APPROVED CARBON MONOXIDE DETECTORS. Each carbon monoxide detector as required in accordance with the above provisions shall
comply with NFPA 720 and be ANSI/UL 2034 listed as IAS certied.
3. SIGNAGE. A metal or plastic identication plate shall be permanently mounted to the exterior of the building at a minimum height of eight (8) feet
above grade directly in line with the exhaust vent terminal for the horizontally vented gas fuelled heating appliance or equipment. The sign shall read, in
print size no less than one-half (1/2) inch in size, “GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS”.
4. INSPECTION. The state or local gas inspector of the side wall horizontally vented gas fuelled equipment shall not approve the installation unless,
upon inspection, the inspector observes carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR 5.089(2)(a) 1
through 4.
(b) EXEMPTIONS. The following equipment is exempt from 248 CMR 5.089(2)(a) 1 through 4.
1. The equipment listed in Chapter 10 entitled “Equipment Not Required To Be Vented” in the most current edition of NFPA 54 as adopted by the
Board; and
2. Product Approved side wall horizontal vented gas fuelled equipment installed in a room or structure separate from the dwelling, building or structure
used in whole or in part for residential purposes.
(c) MANUFACTURER REQUIREMENTS – GAS EQUIPMENT VENTING SYSTEM PROVIDED. When the manufacturer of Product Approved side wall
horizontally vented gas equipment provides a venting system design or venting system components with the equipment, the instructions provided by the
manufacturer for installation of the equipment and the venting system shall include:
1. Detailed instructions for the installation of the venting system design or the venting system components; and
2. A complete parts list for the venting system design or venting system.
(d) MANUFACTURER REQUIREMENTS – GAS EQUIPMENT VENTING SYSTEM NOT PROVIDED. When the manufacturer of a Product Approved
side wall horizontally vented gas fuelled equipment does not provide the parts for venting the fuel gases, but identies “special venting systems”, the
following requirements shall be satised by the manufacturer.
1. The referenced “special venting system” instructions shall be included with the appliance or equipment installation instructions; and
2. The “special venting systems” shall be Product Approved by the Board, and the instructions for that system shall include a parts list and detailed
installation instructions.
(e)) A copy of all installation instructions for all Product Approved side wall horizontally vented gas fuelled equipment, all venting instructions, all parts
lists for venting instructions, and/or all venting design instructions shall remain with the appliance or equipment at the completion of the installation.
TCWS38_D 011214-48
4
C
Fireplace Dimensions
Fig. #1
57 15/16"
48 7/16"
5 15/16"
7 5/8"
23 7/16"
40 7/16"
45 1/16"
22 1/8"
Minimum Clearances to Combustible Material
Fig. #2
COMBUSTIBLE FRAMING AND
FINISH WALL ABOVE STANDOFFS
MAY USE COMBUSTIBLE
FACING MATERIAL IN THIS AREA
NON-COMBUSTIBLE
FINISH MATERIAL
SEE FIG #11 & 12
A
B
STEEL FRAMING
STA N DOFFS
D
E
F
C
NON-COMBUSTIBLE ZONE.
DO NOT INSTALL ANY COMBUSTIBLE MATERIAL, ELECTRICAL WIRING OR GAS PLUMBING IN
THIS AREA.
22 1/8"
29 3/4"
25 7/16"
MANTEL CLEARANCE
CHART
* MANTEL CLEARANCE
A 9”
B 6”
C 3”
Fig. #3
CEILING
TOP OF LINTEL BAR
FIREPLACE FRONT
24"
*
21 5/8"
OMBUSTIBLE FLOOR
**
ADJACENT WALL
OR MANTEL SUPPORT
4“
6”
UNIT MAY BE RECESSED UP TO 6” WITH
NONCOMBUSTIBLE MASONRY TYPE MATERIAL
** MANTEL DEPTH
D 12”
E 6 3/4”
F 1 1/2”
Minimum Clearances:
Side standoffs .......................................................0 in. (0 mm)
Back standoffs ...................................................... 0 in. (0 mm)
Top standoffs ........................................................0 in. (0 mm)
Bottom of appliance ..............................................0 in. (0 mm)
Adjacent side wall .................................................4 in. (102 mm)
Ceiling to appliance ............................................ 24 in. (610 mm)
*Mantel to appliance .................. ..........See Figure #2
Mantel support ......................................................4 in. (102 mm)
Vent pipe including Elbows ............................1 3/4" in. (45 mm)
TCWS38_D 011214-48
5
Fig. #4
Installation Requirements
The Town & Country Fireplace installation and venting must conform to the current
CAN/CGA-B149 installation code (in Canada) or the current National Fuel Gas Code,
ANSI Z223.1 (in the USA), and approved per local codes. Only qualied (licensed or
trained) personnel should install this product.
In the state of Massachusetts, only a licensed Plumber and Gas Fitter may install
this product.
SAFETY
BARRIER
SCREEN
Fig. #5
Fig. #6
Manufactured (Mobile) Home
In some jurisdictions, the Town & Country Fireplace may be installed in Manufactured Homes
after the "rst sale". Consult local codes for approval. The replace must be fastened
in place.
Install in accordance with the current standard Mobile Homes, CAN/CSA Z240 MH (in
CANADA), and the Manufacturer's Home Construction and Safety Standard, Title 24
CFR, Part 3280 or the current Standard for Fire Safety Criteria for Manufactured Home
Installations, Sites and Communities ANSI/NFPA 501A (in the USA).
Window Frame Removal
Warning: Turn off the replace, and allow ample time for the unit to cool before
proceeding.
Caution: The ceramic glass is very fragile, and should be handled with care.
The window frame is held in place by two spring-loaded latches that are operated by a
one-piece latch handle.
1. Remove safety barrier screen (Fig #4) by prying the top portion of the screen toward
you, then lift the screen from its tabs (inset) located at the base of the window frame.
2. Remove the TC Finishing Touch Trim Kit from the window frame. (If installed)
LATCH HANDLE
Fig. #7
3. Using a screwdriver (Fig #5) or other similar object, push against the notch in the
top of the latch and grab the bottom of the latch handle as it protrudes (Fig #6). Lift
handle until latch hook disengages. Repeat for other side while holding glass so it
does not tip out.
4. Tilt the top of the window frame out to clear the top edge of the unit. Grasp the sides
of the frame and lift up and out to disengage from its bottom track.
5. Place the window frame in a safe place to avoid damage.
6. Re-assemble in reverse order. Latch handle should snap into place and be ush with
window frame when engaged correctly.
7. Reinstall Trim Kit if required.
8. Reinstall safety barrier screen.
TIP:
To ensure glass is properly latched, grasp the top left and right
sides of the glass frame, under moderate pressure it should pull
forward and return to original position evenly on both sides.
TCWS38_D 011214-48
6
Standoffs
Fig. #8
TOP STANDOFFS
Locating The Fireplace
The standoffs are shipped loose
inside the replace and must be
installed on the top and the side of
the replace as shown in Fig. #8.
Do this once the replace is on
site and in position.
HANDLE
CONTROL
BOX
In planning the installation for the replace, it is necessary to determine where the unit is to
be installed, location of vent system and where gas supply piping may be plumbed. Various
installations are possible, such as, into an existing wall, a corner, a built-in wall or a wall
projection (Fig. #9). Due to high temperatures, do not locate this replace in areas of high
traffic or near furniture or draperies.
The minimum clearances from the replace to combustible surfaces must be adhered
to and are shown in Fig. #2 and Fig. #3.
Fig. #9
EXAMPLES OF COMMON LOCATIONS
SEE FIG #13 FOR DIMENSIONS
TCWS38_D 011214-48
7
Framing and Finishing
Note: The replace should be in place
and venting installed before framing in
or building an enclosure around the unit.
The Town & Country replace must be framed
in as described below or totally enclosed
with non-combustible material, such as
facing brick.
Determine the total thickness of facing
material to be used. A thickness of 3/4” will
allow the nishing surface to be ush with
the front of the unit. If preferred, additional
masonry type non-combustible material can
be installed above and to the sides up to 6
inches proud of the appliance.
The nishing material must not interfere
with glass frame access or movement.
A Steel Stud Framing Kit is supplied with the
replace and must be used unless the
replace is totally enclosed with
non-combustible material. Assemble the
framing kit as per the instructions on pages 10
& 11 of this manual. Attach the steel frame to
the replace once the replace is in its nal
position. Secure the steel frame to the framing
brackets on each side of the unit. Ensure that
the studs are set back far enough to allow for
thickness of nishing surface.
The sides, back and top of the replace can
be framed in up to the steel studs and the
replace standoffs using conventional
lumber. Consult local building codes for
specic requirements.
Due to high temperatures, non-combustible
backer board, such as cement board or its
equivalent, must be used to sheet in the front
of the replace, extending 12” above and 5
9/16”to the side of the framing edge bars.
(Fig #11) Standard sheet rock (dry wall) may
be used beyond this.
If the backer board is not to be nished with
other non-combustible material such as tiles, it
is recommended that top sections of the board
be a single sheet of calcium silicate board
or its equivalent. Taped and mudded joints
may crack due to the elevated temperatures.
Chase Insulation: When installing this
replace against a non-insulated exterior wall
or chase, it is recommended that the outer
walls be insulated to same degree as other
exterior walls. Do not place replace directly
against the insulation. Cover the insulation
and plastic vapour barrier with a solid surface,
such as dry wall (sheet rock). Consult local
codes. Do not insulate or use plastic vapour
barrier within the framing kit.
CAUTION: SEE FIGURE #11a BEFORE
PROCEEDING.
NOTE:
The chase must be properly
sealed at the ceiling level or
between oors in a multilevel
installation.
Fig. #10
NON-COMBUSTIBLE ZONE. DO NOT INSTALL
ANY COMBUSTIBLE MATERIAL, ELECTRICAL
WIRING, INSULATION, PLASTIC VAPOR
BARRIER OR GAS PLUMBING WITHIN THE
STEEL STUD FRAMING
61 5/8”
STEEL STUD FRAMING KIT DIMENSIONS
(Supplied with replace)
ALL OTHER FRAMING CAN
BE DONE WITH
CONVENTIONAL LUMBER
IT IS HIGHLY RECOMMENDED THAT
A FULL HEADER BE INSTALLED
ABOVE THE FRAMING KIT
45 1/8”
TCWS38_D 011214-48
8
Fig. #11
NON-COMBUSTIBLE BOARD DETAIL
NON-COMBUSTIBLE
BOARD IN THESE
AREAS
Fig. #11a
IF FINISHING THE WALL ABOVE THE UNIT
WITH PAINT, THE FRAMING KIT SHIPPED
WITH THE UNIT SHOULD BE DISCARDED.
USE FULL SHEETS OF CALCIUM
SILICATE BOARD OR EQUIVALENT
AND FULL LENGTH METAL STUDS TO
FINISH AND FRAME AROUND THE UNIT.
CALCIUM SILICATE BOARD IS A HIGH GRADE
MATERIAL WITH CEMENT, QUARTZ AND
NATURAL MINERALS AS THE MAIN RAW
MATERIALS. (NOTE: CALCIUM SILICATE IS
1/2” THICK)
NON-COMBUSTIBLE
MATERIAL MUST EXTEND
11 7/8" ABOVE AND 10 1/8"
TO THE SIDES OF THE
FRAMING EDGES.
Fig. #12
NON-COMBUSTIBLE RECESSED
INSTALLATION DETAIL
NON-COMBUSTIBLE
BOARD
STEEL STUDS
NON-COMBUSTIBLE
MASONRY TYPE MATERIAL
CAUTION: CALCIUM SILICATE BOARD CAN
BE DAMAGED IF DROPPED OR STRUCK.
HANDLE WITH CARE. INSPECT BOARD
PRIOR TO INSTALLATION AND DO NOT USE
IF CRACKED.
NOTE: IT IS RECOMMENDED TO PRE-DRILL
MOUNTING HOLES IN THE BOARD PRIOR
TO SECURING TO THE FRAMING. THIS WILL
PREVENT THE BOARD FROM CRACKING.
NON-COMBUSTIBLE
BOARD
4 1/2”
Fig. #13
61 5/8"
11 3/4"
FRAMING
LINTEL
RANGE
23 11/16"
to
25 7/16"
RANGE
1/32" - 3 1/8"
TCWS38_D 011214-48
RANGE
25 5/16"
to
26 3/4"
37 3/4"
72"
1/2"
72"
26 11/16"
61 5/8"
101 13/16"
45 1/8"
61 5/8"
9
Fig. #14
Steel Stud Framing Kit
FRONT VIEW
4
BEND OUT FRAMING
TABS TO FRONT
(Fig #16)
TCWS.38FRKIT
6
2
3
6
2
3
5
8
7
8
4
ItemDescriptionQty.
1SCREW, WAFER #8 x 1/2
(Not shown)
2STUD, SIDES 45” L2
3STUD, OUTER SIDES 45” L2
4STUD, UPPER/LOWER
61 1/2” L
Each Kit Contains:
Pkg
40
2
ItemDescriptionQty.
5INNER CROSS BRACE
39 3/4” L
6STUD, CENTER 23 1/4” L2
7LOWER CROSS BRACE
39 3/4” L
8FRAMING PLATE4
10
1
1
TCWS38_D 011214-48
NOTE: Sheet metal parts have sharp edges, use
caution whe handling.
Frame Assembly
1. On a at surface, place 1 upper/lower stud (#4)
horizontally. This will become the
top-most horizontal stud. Stand all pieces up on
their narrow ends throughout assembly.
2. Place 2 center studs (#6) perpendicular to, and
below the above upper/lower stud. Using the
screw holes on the upper/lower stud as a guide,
place each center stud aprox 8” on either side of
the upper/lower stud center point so that they are
in-line with the screw holes.
3. Use wafer screws (1) to join the upper/lower stud
(4) and the center studs (6) together.
4. Position Inner Cross Brace (5) horizontally along
the bottom ends of the 2 center studs (6) and fasten with wafer screws to the center-most 2 positions along the cross brace.
6. Position the Lower Cross Brace (7) between the
two side studs and about 6” from the lower ends
of the side studs. Attach each end of the lower
cross brace to the side studs with wafer screws.
7. Attach the remaining upper/lower stud (4) at the
bottom of, and perpendicular to the side studs.
8. Place and attach the two Outer Side studs (3) tab side out - at each end of both the top upper/
lower stud and bottom upper/lower stud and attach with wafer screws.
9. Once the top side of the frame is complete, turn
it over so that the wafer screws can be used to
fasten the other side of the frame.
5. Position Side Studs (2) at each end of the assembled frame so that the side studs are perpendicular to the upper/lower stud and inner cross brace.
Use wafer screws to fasten the side studs to the
assembled frame.
Fig. #15
at side
of frame
side of frame with
screw holes
NOTE: After frame is assembled, make
sure to have the side of the frame
without the screw holes facing toward
the inside of the room.
TCWS38_D 011214-48
11
2. Attach the Assembled Frame to the Unit
4. Install Non-Combustible Board
Fig. #16
• Attach the framing kit to the unit.
(Fig. #16).
3. Secure to Existing Framing
• Bend out the tabs 90 degrees before
inserting the unit into its framed housing
(Fig. #17).
• Secure the frame assembly to the wood
frame through the tabs.
NON COMBUSTIBLE
BOARD
• Use drywall screws, #8, to install the
non-combustible board(Fig. #18).
Fig. #18
Fig. #17
This replace may be recessed up to a
maximum depth of 6”, this recess must
be constructed from non combustible
material. The space between the
outside lintels and the rebox must be
completely free of any debris and the
window with trim tted must be able
to move freely. No building material
is permitted to protrude past the lintel
bars attached to the replace under
ANY circumstance.
NON-COMBUSTIBLE
FINISH MATERIAL
Adjustable Lintel
Fig. #19
Non combustible building
material may not extend
past this point
Area inside Lintel must
remain free of obstructions
TCWS38_D 011214-48
12
Lintel Adjustment
1. The adjustable lintel assembly has
two orientations for desired nishing. A
anged edge and a hemmed edge. (Fig
#19) The lintel comes factory installed
with the ange edge out. If the desired
edge is different from the factory setting,
use the following steps to change the
Lintel edge.
2 Remove saftey barrier screen (Fig.#20).
3. Remove the window trim (Fig.#20).
4. Loosen the securing bolts in the upper
and lower corners on each side of the
lintel and remove the lintel. Rotate the
assembly to have the desired edge away
from the replace(Fig .#21).
5. The lintel assembly can then be adjusted
to align ush with your facing material by
sliding in or out approximately 1”.
Fig. #20
SAFETY BARRIER
SCREEN
Fig. #21
WINDOW TRIM
FLANGED
EDGE
3/8 SECURING BOLT
HEMMED
EDGE
6. Tighten the securing bolts. (Fig.#21).
7. Re-attach the window trim.
8. Reinstall safety screen.
Hearth Extension
* Caution:
A minimum 2” thick non-combustible hearth
extension extending 18” in front of this
replace must be tted if a combustible
sub oor extends in front of the replace.
To ensure that the hearth does not interfere
with the window frame the replace must be
raised to ensure that the hearth extension
is no more than 1” above the bottom of the
replace.
The fireplace can be raised using
combustible or non-combustible materials
ensuring that it is fully supported along the
full width and depth of the replace.
Fig. #22
HEARTH EXTENSION
WINDOW FRAME
*
(See
Caution)
WINDOW TRACK
SUB-FLOOR
TCWS38_D 011214-48
13
Electrical
The gas control system is located on the right hand side of the rebox behind an access
panel and the decorative rebox panel (if installed). The replace is operated via a wall
control and a hand held remote control unit.
Note: Installation must be performed by a qulaied
installer, service agency or gas supplier.
The wall control is connected to the replace by a 40 ft. communication cable supplied
with the replace.
Installation
FIREBOX ACCESS PANEL
Fig. #23
1. Place the replace in the desired location.
2. Remove the window from the replace.
3. Remove access panel from right hand side of the rebox (Fig #23).
4. Connect 110 V. AC electrical supply to the wires installed inside the junction box
(Fig #24). The replace is rated at 110 volts, 60Hz, 0.25A. The optional power vent kit
is rated at 115 volts, 60Hz, 1.8A.
The electrical wires can be accessed from both inside and outside the junction box by
removing one of the two small access panels (Figs #24 & 25).
5. Attach the wall switch to the framing in the desired
location (Figs #26 & 27) (40 ft is supplied with replace).
6. Route the wall switch control cable (supplied) as required to
the wall switch (Fig #27).
VACUUM
SWITCH
7. Attach one end of the wall switch control cable to the wall
control. (Fig #27), and the other end to the interface board
(Fig #25).
Fig. #25
8. Insert the 4 supplied “AA” batteries into the battery pack of the
wall switch. (Fig #28).
9. If not already installed, install the burner using the instructions
supplied with the burner kit.
10. Turn on the gas supply and check that all connections are tight
and leak free.
INSIDE ACCESS
PANEL
11. Turn on gas and electrical supplies.
12. Move the center button on the wall control (Fig #26) to the “ON”
position. The igniter will start to spark. After a short delay, the
pilot will light followed by the main burner.
Fig. #24
OUTER ACCESS PANEL
TRANSFORMER
JUNCTION BOX
REGULATOR
BOARD
POWER
VENT
SWITCH
JUNCTION BOX
GAS CONNECTOR
14
WALL SWITCH
CONNECTOR
MODULE
INTERFACE BOARD
TCWS38_D 011214-48
Wall Switch and Remote Control
Fig. #26
Linking the remote control unit to the
wall switch.
1. Begin by moving the selector toggle
on the wall switch to the “REMOTE”
position.
Fig. #27
TO FIREPLACE
2. Insert a straightened paper clip into
the “PROGRAM” slot on the wall
switch.
3. Press the internal “PROGRAM” button
once and wait until you hear 3 beeps
from the wall switch.
Fig. #28
4. Press the ON/OFF button of the
remote unit. Once the wall unit beeps
3 times, the remote is programmed.
5. The toggle on the wall switch must be
kept in the “REMOTE” position in order
to use the remote control unit.
Selecting Natural Vent and Power Vent Modes
The NV / PV (Natural Vent / Power Vent) switch (Fig #29) on the interface board
(Fig #25) is set according to which type of evacuating vent system is present. If
the replace is vented without the assistance of a power vent, the switch should
be set to “NV”. If using a power vent, “PV” should be selected. Follow the
instructions provided with the power vent kit for proper installation.
TCWS38_D 011214-48
Fig. #29
15
Loading...
+ 33 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.