SALTBURN / DALBY SMOKE CONTROL ISSUE 2 06/07/2015
UNPACK THE STOVE
Carefully cut the straps and lift the box up over the top of the stove. Remove the packing
from round the outside of the stove, leaving the plastic cover on if building work is still
in progress. It is important to protect the paint finish from any damage, water, dust
or fire cement. Using a 17mm spanner, remove the two bolts attaching the stove to the
pallet and then replace the bolts into the stove legs, these are used as levelling bolts if
required.
Open the stove door and remove the packaging from inside the stove, there is some above
the baffle and the heavy one inside the stove contains the spigot for the flue outlet.
Remove the bag inside the ashpan, this contains the operating tool, instructions, and a pair
of stove gloves
CLEARANCES
It is recommended that the appliance is sited next to and on a non-combustible surface. A
minimum clearance of 150mm at the sides 300mm above and 50mm from the back of the
stove body will allow air circulation and not impede the performance of the stove.
If it is necessary to site the stove near a combustible surface a minimum of 500 mm at the
back and 650 mm at the sides must be maintained. It is recommended that this appliance is
installed on a solid, level, non-combustible hearth conforming to current Building
Regulations. This appliance has been tested for hearth temperatures and the maximum
temperature was 59 degrees C so is also suitable for a 12mm hearth.
INSTALLATION
A minimum flue draught of 24 Pa is required for nominal heat output. As referred to in
document J of the Building regulations, no purpose provided ventilation is normally
required for the Saltburn / Dalby Smoke Control stove. The appliance must be installed on
a floor with an adequate load-bearing capacity. If an existing construction doesn’t meet
the prerequisite, suitable measures (e.g. load distributing plate) shall be taken to achieve it.
It is important that any inlet grilles are so positioned that they are not liable to blockage.
It is essential that the stove has adequate air supply for combustion and ventilation.
Apertures provided for this purpose shall not be restricted.
Please note where the external air kit is fitted an air vent is still required in the same
room as the stove depending on air tightness of the room, please refer to Building
Regulations Part J
Fit the collar on the top of the stove. A flat-bladed screw driver and 8mm spanner will be
required.
The Saltburn / Dalby Smoke Control requires a Class 1 chimney of it’s own, a shared
chimney will not be suitable. The chimney must be sound, free from leaks and swept