OCTOBER 2002 MAXI-T MANUAL
SYSTEM OPERATING PROCEDURES
INITIAL START-UP OF UPS UNIT
• Turn the INVERTER KEY SWITCH to the off position.
• For 3 - 5kVA units
• Place the ROTARY BYPASS switch into the TEST position.
• For 8 - 20kVA units
• Close the BYPASS ISOLATOR (SW2).
• Open the OUTPUT ISOLATOR (SW1).
• Close the AC input circuit breaker (CB1).
• The LCD will activate.
• After a period of approximately 30 seconds the analogue values and status alarms will be
displayed.
• The unit will synchronise to input reserve source.
• Depress ALARM CANCEL button to silence alarm.
• Turn the INVERTER KEY SWITCH to the “ON” position.
• The unit will start up when synchronised to mains (reserve source).
• The UPS output voltage will ramp up to 230VAC.
• Ensure that *NO ACTIVE ALARMS* is displayed in the alarm status block and that the
battery voltage is greater than 360VDC (432VDC is the charging value).
• Measure the DC differential voltage across F1 and close this fuse if the voltage is less
than 30VDC.
• Repeat for F2 and F3.
• Turn the INVERTER KEY SWITCH to the “OFF” position and confirm LOAD ON BYPASS
is displayed on the LCD DISPLAY.
• For 3 - 5kVA units
• Place the ROTARY BYPASS switch into the NORMAL position.
• For 8 - 20kVA units
• Close the OUTPUT ISOLATOR (SW1).
• Open the BYPASS ISOLATOR (SW2).
• Turn the INVERTER KEY SWITCH to the “ON” position (CW) and depress ALARM
CANCEL button to silence alarm.
• Confirm *NO ACTIVE ALARMS* is displayed on the LCD DISPLAY within 60 sec.
• The unit is operating normally.