TOTALINE P707, P707-SHR1504, P707-SHR2004 Installation And Operation Instructions Manual

INSTALLATION
P707 AND OPERATION INSTRUCTIONS
Part Numbers P707-SHR1504 and 2004
SAFETY CONSIDERATIONS......................1
GENERAL ........................................1
INSTALLATION ................................ 2-10
Step 1 — Unit Location...........................2
Step 2 — Unit Mounting .......................... 2
Step 3 — Install Drain Line ....................... 3
Step 4 — Locate and Install Weather Hoods......3
Step 5 — Install Ducting To Weather Hood
Location ....................................... 3
Step 6 — Install Indoor Ductwork System ........4
• SUPPLY AIR DUCTING
• EXHAUST AIR DUCTING
• INSTALL DUCTING
• INSTALLATION EXAMPLES
Step 7 — Airflow Balancing ......................6
• AIRFLOW STATION METHOD
• PITOT TUBE BALANCING PROCEDURE
• BALANCING DAMPER ADJUSTMENT
Step 8 — Install Accessories ..................... 9
Step 9 — Electrical Connection to Furnace
(Air Systems Directly Connected to Furnace) .. 9
OPERATION...................................10,11
Winter ...........................................10
Spring...........................................10
Summer......................................... 10
Fall ..............................................10
Modes of Operation ............................. 10
• CONTINUOUS/VENTILATION MODE
• INTERMITTENT/STANDBY MODE
• DEFROST (FAN SHUTDOWN)
MAINTENANCE .................................11
Motor ........................................... 11
Chassis .........................................11
Condensation Panel............................. 11
Drain and Drain Line ............................ 11
Outside Hoods ..................................11
Filters ........................................... 11
Heat Recovery Core ............................. 11
TROUBLESHOOTING............................12
Heat Recovery
Ventilator
Before installation, always check to be sure main power to systems are OFF. Electrical shock can cause personal injury or death.
GENERAL
The P707-SHR1504 and P707-SHR2004 Heat Recovery Ventilators (HRV) are used to exchange indoor stale air with outside fresh air. The HRV unit is equipped with a special ener­gy recovery core which transfers sensible heat with the fresh incoming air. The cross-flow design core allows entering and leaving airstreams to transfer heat energy without mixing.
The HRV is available in 2 sizes with airflow ranges of 150 cfm (SHR1504), and 200 cfm (SHR2004). The design of this unit is horizontal. Special attention should be given to duct application, balancing the HRV, and locating unit for easy access and routine maintenance. See Table 1 and Fig. 1 for performance data.
AIRFLOW (L/S)
SHR 2004
SHR 1504
120 160
AIRFLOW (CFM)
200 240
300
250
200
150
100
50
0
1.2
0.8
0.6
0.4
0.2
STATIC PRESSURE (IN. WG)
190 38 57 76 94 114
1
0
40080
Fig. 1 — Fan Performance
STATIC PRESSURE (PA)
SAFETY CONSIDERATIONS
Installing, starting up, and servicing ventilation equipment can be hazardous due to system pressures, electrical compo­nents and equipment location (roofs, elevated structures, etc.). Only trained, qualified installers and service mechanics should install, start up, and service this equipment.
When working on the equipment, observe precautions in the literature and on tags, stickers, and labels attached to the equipment. Follow all safety codes.
Manufacturer reserves the right to
discontinue, or change at any time,
specifications or designs without notice
and without incurring obligations.
Table 1 — Performance Data
UNIT
SHR 1504 72% 69% SHR 2004 71% 76%
REPLACEMENT CO MPON EN TS DIVI SIO N LITERATURE NUMBER P7 07- 5SI © CARRIER CORPORATION 2004 4-04 REPLACES: New PRINTED IN U.S.A. CATALOG NUMBER 570-332
APPARENT SENSIBLE
EFFECTIVENESS
AT 32 F (0° C)
APPARENT SENSIBLE
EFFECTIVENESS
AT –13 F (–24 C)
INSTALLATION
Step 1 — Unit Location —
The HRV must be located in a heated space where it can be conveniently serviced. Typically the HRV is located in the mechanical room or an area close to the outside wall where the weather hoods will be mounted. If a basement area is not convenient or does not exist, a utility or laundry room may be used. See Fig. 2 for dimensions.
Attic installations are not normally recommended due to the complexity of work to install, freezing conditions in the attic, and the difficulty of access for service and cleaning.
Connecting appliances to the HRV is not recommended (such as a clothes dryer, range top, stovetop fan, or central vacuum system). These appliances may cause lint, dust or grease to collect in the HRV, damaging the unit.
NOTE: Connecting any of these type of appliances to the HRV will invalidate the warranty.
Locate the unit close to the outside wall on which the supply and exhaust hoods will be mounted. There should be a nearby power supply of 120 volts, 60 Hz available.
There should be access to a water drain for condensate removal of the unit during defrost.
The unit should be located in a heated area (attic installation is not recommended). The location should also minimize any noise level that would be created by the unit in the living area.
Make sure there is adequate access for future maintenance.
Step 2 — Unit Mounting — The unit is typically hung
from the ceiling for mounting. See Fig. 2 for unit dimensions. Perform the following to mount the HRV:
1. Place fastening hooks on the strapping board or the floor joists. See Fig. 3.
3
2. Attach a hanging chain (provided) to each no. 10 bolts (provided) on the top 4 corners of the unit and tighten. See Fig. 4.
3. Hang the unit by slipping a link onto the hanging hooks, making sure the unit is level. Unit condensate will not drain properly unless unit is level. See Fig. 5.
/4-in.
Fig. 3 — Install Fastening Hooks
Fig. 4 — Install Hanging Chain
Fig. 5 — Unit Mounting
OUTDOOR
(FRESH AIR)
EXHAUST
(TO OUTSIDE)
INTAKE
AIR
A
UNITABCD E
SHR 1504
SHR 2004
1
/4″ (56 mm) 231/2″ (596 mm) 25/8″ (67 mm) 173/8″ (441 mm) 161/8″ (413 mm)
2
1
/4″ (56 mm) 277/8″ (707 mm) 25/8″ (67 mm) 173/8″ (441 mm) 201/2″ (520 mm)
2
EXHAUST AIR FROM
FRESH AIR
BCD
INSIDE
TO INSIDE
E
6"
Fig. 2 — Unit Dimensions
2
Step 3 — Install Drain Line — Through normal op-
eration and during defrost mode, the HRV may produce some condensation. This water should be directed to flow into a nearby drain, or be removed by a condensate pump. The HRV and all condensate lines must be installed in a space where the temperature is maintained above the freezing point. A P-trap should be made in the drain line. This will prevent odors from being drawn back up into the unit.
To install the drain line, install the drain nipple provided.
See Fig. 6.
Install the drain hose onto the drain nipple. Loop the hose to create a P-trap as shown in Fig. 7. Run the hose to a nearby drain.
Step 4 — Locate and Install Weather Hoods —
The intake weather hood should be located upstream and at least 4 to 6 ft away from the exhaust weather hood. The intake weather hood should be at least 6 ft away from dryer vents and furnace exhaust (on medium or high efficiency furnaces) and a minimum of at least 6 ft from driveways, oil fill pipes, gas meters, or garbage containers.
Locate the hoods at least 18 in. above the ground, or above the depth of expected snow accumulation. The hoods should be at least 3 ft from the corner of the building. Do not locate in a garage, attic or crawl space.
A well designed and installed ducting system will allow the HRV to operate at its maximum efficiency. Always keep duct runs as short and straight as possible.
To install the intake and exhaust weather hoods, perform the following:
1. Using the collar of the outside hood, outline the intake and exhaust holes to be cut. The hole should be slightly larger than the collar to allow for the thickness of the insulated flexible duct. See Fig. 8.
2. Cut a holes using the outline from Step 1. See Fig. 8. When cutting or drilling holes, be careful not to dam­age electrical wiring or other hidden objects in wall.
3. Pull the insulated flexible duct through the opening until it is well extended and straight. Slide the duct inner vinyl sleeve over the hood collar and secure. See Fig. 9.
4. Pull the insulation over the duct and then the vapor barrier over the sleeve and secure with duct tape. See Fig. 9.
5. Push the hood into the opening. Attach the hood to the outside wall with mounting screws. See Fig. 10.
6. Using a caulking gun, seal around the hoods to prevent any leaks. See Fig. 11.
Step 5 — Install Ducting To Weather Hood Location —
was secured to the intake and exhaust weather hoods in Step 4. Run the other end of the flexible duct to the HRV installation location. See Fig. 12.
Clamp the end of the duct to the appropriate port on the
HRV. See Fig. 2.
The insulation should remain full and not be crushed. The outer liner, which acts as a vapor barrier must be completely sealed to outer wall and the HRV using tape and/or caulking. A good bead of high quality caulking (preferably acoustical seal­ant) will seal the inner flexible duct to both the HRV port and the weather hood prior to clamping.
To minimize airflow restriction, the flexible insulated duct that connects the two outside weather hoods to the HRV should be stretched tightly and be as short as possible. Twisting or folding the duct will severely restrict airflow.
The inner liner of the flexible insulated duct
Fig. 6 — Install Drain Nipple
Fig. 7 — Install P-Trap
Fig. 8 — Cut Holes for Weather Hoods
Fig. 9 — Install Duct and Sleeve
Fig. 10 — Install Hoods
3
Fig. 11 — Seal Hoods
Fig. 12 — Outdoor Ducting Installation
Step 6 — Install Indoor Ductwork System — To
maximize airflow in the ductwork system, all ducts should be kept short and have as few bends or elbows as possible. Forty­five degree elbows are preferred to 90 degree elbows. Use tees instead of 90 degree elbows whenever possible.
All duct joints must be fastened with screws or duct sealant and wrapped with a quality duct tape to prevent leakage. Aluminum foil duct tape is recommended. Galvanized ducting from the HRV to the living areas in the house is recommended whenever possible, although flexible duct can be used in moderation when necessary.
SUPPLY AIR DUCTING — In homes without a forced air furnace, fresh air should be supplied to all high-usage rooms including bedrooms and living areas. Air should be supplied from high wall or ceiling locations. Grilles that diffuse the air comfortably are recommended. To avoid possible noise transfer through the ductwork system, a short length (approximately 12 in.) of nonmetallic flexible insulated duct should be connect­ed between the HRV and the supply/exhaust ductwork system.
The main supply and return lines to and from the HRV must be 6 in. minimum. Branch lines to the individual rooms may be as small as 4 in., but 5 in. lines are preferred. If floor installation is the only option available, then special care should be taken in locating grilles. Installation areas, such as under baseboard heaters, will help to temper the air. In homes with a forced air furnace, it may be advisable to connect the HRV to the furnace ductwork (direct connection).
Building Codes and Combustion Appliance Installation Codes do not allow location of return air grilles or any opening such as a breathing tee in an enclosed room with spillage susceptible combustion appliances.
The fresh air inlet from the HRV must be a minimum distance of 3 ft from the furnace return drop to ensure proper air mixing and temperature at the furnace core.
Direct Connection
— A direct connection requires that the furnace fan run continuously. See Fig. 13. The fan may be inter-linked electrically (low voltage) with the HRV accessory control contacts for intermittent demand.
To hard duct the supply air directly into the cold air return of the furnace, remember to check the airflow balance of the HRV with the furnace fan both on and off to determine that it does not imbalance the HRV more than 10%. Make sure that the minimum distance from the supply air of the HRV to the furnace is followed. Refer to the local and National Building and Heating Codes for any variations in these notes.
EXHAUST AIR DUCTING — The stale air exhaust system is used to draw air from the points in the house where the worst air quality problems occur. It is recommended that return air ducts be installed in the bathroom, kitchen, and laundry room. Additional return air ducts from strategic locations (i.e., green­house, atrium, swimming pool, sauna, etc.) may be installed. The furnace return duct may be also used.
In this method, the exhaust air is not ducted back from bathrooms, kitchens, etc. to the HRV with dedicated lines.
This method has become popular and provides good ventilation when installed in accordance with the instructions. The furnace blower must be running when the HRV is operat­ing for this method to be effective.
INSTALL DUCTING — To install indoor ductwork, perform the following:
1. Begin with the duct collar on the HRV marked Exhaust Air In. Slide a short piece (12-in.) of flexible duct over the duct collar. Using duct tape, tape the flexible duct to the collar.
2. Run the flexible ducting to the main rigid duct trunk line, which connects to the remainder of the ducts going to and from rooms in the house. Repeat the steps for the Supply Air Out on the side of the HRV.
3. Working from a closet, attic or inside joist wall, run the length of ducting required for the proper grille location and cut a hole in the wall.
4. Fasten the mounting collar (field-supplied) to the duct­ing and fasten the collar to the wall or ceiling with screws.
5. The field supplied grille may be adjustable. It is rec­ommended that the grilles be completely opened at first and then adjusted later as needed.
6. Push the grille into the mounting collar or directly into installed elbow.
FROM HRV
Fig. 13 — Direct Duct Connection
4
INSTALLATION EXAMPLES — It is the responsibility of the installer to ensure all ductwork is sized and installed as designed to ensure the system will perform as intended. All air movement devices have a performance curve. The amount of air (cfm) that an HRV will deliver is directly related to the total external static pressure (E.S.P.) of the system. Static pressure is a measure of resistance imposed on the blower by length of duct work/number of fittings used in ductwork, duct heater etc.
BEDROOMS
Fully Dedicated System (New Construction)
—Staleairis drawn from key areas of home (bathroom, kitchen, laundry). Fresh air is supplied to main living areas. The HRV must be balanced. See Fig. 14.
Partially Dedicated System
— Stale air drawn from key areas of home (bathroom, kitchen, laundry) Fresh air supplied to main living areas via the forced air system. HRV must be bal­anced. See Fig. 15 and 16.
EXHAUST
BATHROOM
CENTRAL CONTROL
(OPTIONAL)
FRESH AIR TO
LIVING ROOM
FRESH AIR
BEDROOMS
1800 MM
EXHAUST AIR
460 MM
Fig. 14 — Fully Dedicated System
MIXED SUPPLY /
VENTILATION
AIR
HRV
EXHAUST CENTRAL CONTROL
(OPTIONAL)
BATHROOM
RETURN AIR
THERMOSTAT
SUPPLY EXHAUST
FURNACE
FRESH AIR
TWO SPEED
FURNACE
EXHAUST AIR
1800 MM
HRV
460 MM
Fig. 15 — Partially Dedicated System
5
HRV CONNECTION
Loading...
+ 11 hidden pages