TOTALINE P374-2900, P374-1 900 Installation Instruction

Page 1
INSTALLATION
INSTALLA TION
INSTRUCTIONS
INSTRUCTIONS
HEAT
HEAT
COOL
COOL
4
7
L
O
m
O
P
C
0
0
:
2
I
u
S
O
U
A
T
A
E
H
2
7
E
N
I
L O
A
T
T
PROGRAMMABLE
THERMOSTATTHERMOSTAT
P/N P/N
HEAT
HEAT
PUMP
PUMP
7-DAY
DIGITAL THERMOSTA T
Set Point Limiting Accepts EZ Programmer
3 Configurable Outputs
3 Configurable Outputs
Control up to 3 Heat &
Control up to 3 Heat &
2 Cool Stages
2 Cool Stages Adjustable 2nd & 3rd Stage Timers & Deadbands Backlit Display & Button Legends Aux Heat Indicator Dry Contact Equipped Outdoor Sensor Ready with High/Low Readouts for the Day
Accepts the
Accepts the
Use with most Air Conditioning & Heating Systems including: 1 or 2 Stage Electric Cooling & 3 Stage Gas Heating, Heat Pump, Electric or Hydronic Heat.
OPTIONAL
OPTIONAL
HUMIDITY MODULE
HUMIDITY MODULE
Economizer Control Preoccupancy Fan Purge Remote Averaging Programmable Output Light Activation Equipped Accepts Optional Humidity Module: Controls Humidification, Dehumidification and Reheat Accepts Optional IR Remote Control Optional Internet / Phone Control Accessory
COMMERCIALCOMMERCIAL
P374- P374- 29002900
Commercial Systems & Services Carrier Corporation 08/05
TOTALINE
Signature
Page 2
TOTALINE
CAUTION
Follow the Installation Instructions before proceeding. Set the thermostat mode to “OFF” prior to changing settings in setup or restoring Factory Defaults.
CAUTION
NEVER PUT MORE THAN ONE JUMPER ON THE SAME MISC JUMPER BLOCK!
THIS MAY DAMAGE YOUR THERMOSTAT AND VOID YOUR WARRANTY.
MISC3
OK
NOTE: Due to variations in environmental conditions, it is not
always possible to achieve the desired humidification or dehumidification setpoint.
This device complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) this device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation.
Thermostat P374-2900
Tested to Comply
c
with FCC Standards
C
F
4Z95
FOR HOME OR OFFICE USE
MISC3
Page i
Page 3
Page 4
Table of ContentsTable of Contents
TOTALINE
Preparation
Remove & Replace the Old Thermostat
Configuring the MISC Outputs
Wire Connections
Sample Wiring Diagrams
Test Operation
Calibrating the Thermostat Sensors
TroubleShooting
1 2 3 4 5 6 7 8
Page iii
Page 5
SECTION 1
PreparationPreparation
1
Proper installation of the thermostat will be accomplished by following these step by step instructions. If you are unsure about any of these steps, call a qualified technician for assistance.
Assemble tools
TOTALINE
Flat Blade Screwdriver
Make sure your Heater/Air Conditioner is working properly before beginning installation of the thermostat.
Carefully unpack the thermostat. Save the screws, bracket, and instructions.
Turn off the power to the Heating/Air Conditioning system at the main fuse panel. Most residential systems have a separate breaker for disconnecting power to the furnace.
Wire cutter & Stripper
Page 1.1
Page 6
SECTION 2
Remove & Replace the Old ThermostatRemove & Replace the Old Thermostat
TOTALINE
Remove the cover of the old thermostat. If it does not come off easily check for screws.
Loosen the screws holding the thermostat base or subbase to the wall, and lift away.
Disconnect the wires from the old thermostat. Tape the ends of the wires as you disconnect them, and mark them with the letter of the terminal for easy reconnection to the new thermostat.
Keep the old thermostat for reference purposes until your new thermostat is functioning properly.
2
Page 2.1
Page 7
SECTION 3
Configuring the MISC OutputsConfiguring the MISC Outputs
3
Section 3 Contents:
Configuring the Jumpers........3.2
Explanation of Jumper
Settings..................................3.3
TOTALINE
Page 3.1
Page 8
Configuring the JumpersConfiguring the Jumpers
TOTALINE
For additional flexibility, your thermostat has three configurable outputs. These outputs are designed to have different functions depending on how the jumpers are set (below). Each output, labeled MISC1, MISC2, and MISC3 may be set for one of the six choices available. In the diagram below, the MISC3 jumper has been set for HUM* (humidification) operation, the MISC2 jumper has been set for DEHUM* (dehumidification) operation, and the MISC1 jumper has been set for PROG (programmable) operation.
(FAN)
DEHUM
CKGND
PROG
ECON
MISC2
W3
HUM
W1
Y1
G
CK1
C
MISC3 MISC2 MISC1
R
ELEC
GAS
HP
GAS
2
4
INSTALL HUMIDITY
1
3
B
O
W2
MISC1
HUM
NO HUM
RS2
MISC3
RS+5
Z
8
6
X 1
RSGND
Y
579
Y2
(MISC1 ONLY)
MODULE WITH SENSING
ELEMENT OUTWARD
W3
PROG
HUM
DEHUM
ECON
MISC3 MISC2 MISC1
*The Humidity Module (sold separately) must be installed to operate a humidification and/or dehumidification system.
(MISC1
ONLY)
Y2
CAUTION
NEVER PUT MORE THAN
ONE JUMPER ON THE SAME
MISC JUMPER BLOCK!
DOING SO MAY DAMAGE
YOUR THERMOSTAT AND
VOID THE WARRANTY.
Page 3.2
MISC3
OK
MISC3
3
Page 9
TOTALINE
Explanation of Jumper SettingsExplanation of Jumper Settings
W3 JUMPER SETTING
3
If the jumper for MISC1, MISC2, or MISC3 is set to W3, the corresponding MISC screw terminal on the backplate will control a third stage of heat.
W3 MULTI-STAGE OPERATION EXPLAINED - SECTION 13 of the Owner’s Manual
The 3rd Stage of Heat is turned on when:
(A) The 1st and 2nd stages have been on for the time required (steps 27 and 28, page 13.6). It is adjustable from 0-60 minutes and the default
And
is two minutes. (B) The temperature from the setpoint is equal to or greater than: the set-
point plus the 1st stage deadband (step #24, 13.5), plus the 2nd stage deadband (step #25, 13.5) plus the 3rd stage deadband (step #26,
13.5). This 3rd stage deadband is adjustable from 0-10 degrees and
the default is two degrees.
3rd Stage
turn on
PROG JUMPER SETTING
If the jumper for MISC1, MISC2, or MISC3 is set to PROG, the corresponding MISC screw terminal on the backplate will control a pilot relay or other accessory.
2nd Stage
Heating
Deadband Deadband DeadbandDeadbandDeadband
1st Stage
turn on
turn on
DECREASE INCREASE
db 1 db 1db 2 db 2db 3
(adj. 1-6 )(adj. 0-10 )(adj. 0-10 ) (adj. 0-10 )(adj. 1-6 )
Heat
Setpoint
TEMPERATURE
Cool
Setpoint
PROGRAMMABLE OUTPUT - SECTION 14 of the Owner’s Manual
This jumper setting allows the MISC outputs to control a pilot relay by time, temperature, or a signal from the Internet/Phone. The following are three possible scenarios: By Time: A device that requires a start and stop time. An example of this would be an exterior lighting system that needed to be energized every day between the hours of 8pm and 1am. By Temperature: An exhaust fan that needs to energize whenever the temperature from RS2 rises above 90 degrees F. By Remote: Remotely arming a security system through the web or phone.
Page 3.3
Cooling
1st Stage
turn on
2nd Stage
turn on
Page 10
Explanation of Jumper Settings (continued)Explanation of Jumper Settings (continued)
TOTALINE
HUM JUMPER SETTING
If the jumper for MISC1, MISC2, or MISC3 is set to HUM, the corresponding MISC screw terminal on the backplate will control a humidification system.
HUMIDIFICATION OPERATION - SECTION 9 of the Owner’s Manual
If your HVAC unit is equipped with a humidification system and the Humidity Module (sold separately) has been installed, the thermostat will provide power to the MISC1, MISC2, or MISC3 terminal of the thermostat when the humidity in the home falls below the humidity setpoint you have chosen. The value for this setpoint ranges from 0% to 60%. If no humidity is desired or if a humidification system has not been installed, set the value to OFF.
DEHUM JUMPER SETTING
If the jumper for MISC1, MISC2, or MISC3 is set to DEHUM, the corresponding MISC screw terminal on the backplate will be connected to the dehumidification terminal of a furnace board. NOTE: Not all furnaces have a dehumidification terminal.
DEHUMIDIFICATION OPERATION - SECTION 10 of the Owner’s Manual
If your HVAC unit is equipped with a dehumidification system the thermostat will operate in one of two ways.
1) Normally Closed (NC): The thermostat will de-energize the MISC1, MISC2, or MISC3 terminal of the thermostat (this MISC terminal is connected to the DEHUM terminal on your furnace) to allow the fan to run in low speed when the humidity in the home is above the dehumidify setpoint you have chosen and there is a call for 1st stage cooling.
2) Normally Open (NO): MISC3 terminal of the thermostat (this MISC terminal is connected to the DEHUM terminal on your furnace) to allow the fan to run in low speed when the humidity in the home is above the dehumidify setpoint you have chosen and there is a call for 1st stage cooling.
The thermostat will energize the MISC1, MISC2, or
3
Page 3.4
Page 11
TOTALINE
Explanation of Jumper Settings (continued)Explanation of Jumper Settings (continued)
3
ECON JUMPER SETTING
If the jumper for MISC2 and MISC3 is set to ECON, the corresponding MISC screw terminal on the backplate will be connected to an economizer.
ECONOMIZER OPERATION - If your HVAC unit is equipped with an economizer system, the thermostat will provide power to the MISC1, MISC2, or MISC3 terminal of the thermostat when the thermostat is in an occupied time period. The MISC1, MISC2, or MISC3 terminal will be de-energized when the thermostat is in an unoccupied time period.
Y2 JUMPER SETTING
If the jumper for MISC1 is set to Y2 the MISC1 screw terminal on the backplate will control a second stage of cooling.
Y2 OPERATION - SECTION 13 of the Owner’s Manual
Control up to two Cool stages.
The 2nd Stage of heat or cool is turned on when: (A) The 1st Stage has been on for the time required (step #27, page 13.6). It is adjustable from 0-60 minutes and the default is two minutes.
And
(B) The temperature spread from the setpoint is equal to or greater than: the setpoint plus the deadband (step #24, page 13.5), plus the 2nd deadband (step #25, page 13.5). This 2nd deadband is adjustable from 0-10 degrees and the default is two degrees.
Cool
Setpoint
TEMPERATURE
Cooling
DeadbandDeadband
db 1 db 2
(adj. 0-10 )(adj. 1-6 )
1st Stage
turn on
INCREASE
2nd Stage
turn on
Page 3.5
Page 12
SECTION 4
Wire ConnectionsWire Connections
If the terminal designations on your old thermostat do not match those on the new thermostat, refer
to the chart below, or the wiring diagrams that follow.
Wire from the
old thermostat
terminal marked
G or F Fan G
Y1, Y or C
W1, W or H
C
O/B
W2
MISC1
MISC2
MISC3
RS+5
RSGND
RS2 RS2
CK1
CKGND
Function
Cooling Y1
Heating
PowerRh, R, M, Vr, A R
Common
Rev. Valve
2nd Stage Heat
Configurable Output #1
Configurable Output #2
Configurable Output #3
Remote Sensor +5vdc
Remote Sensor Signal
Remote Sensor Ground
Remote Sensor Signal #2
Dry Contact Switch 1
Dry Contact Switch 2
TOTALINE
Install on the
new thermostat
connector marked
W1/O/B
C
W1/O/B**
W2
MISC1
MISC2
MISC3
RS+5
RS1RS1
RSGND
CK1
CKGND
4
** O/B is used if your system is a Heat Pump.
Page 4.1
Page 13
SECTION 5
Sample Wiring DiagramsSample Wiring Diagrams
Section 5 Contents:
HVAC Equipment Wiring............5.2
5
MISC1, MISC2, and MISC3
Wiring........................................5.6
Remote Sensor and CK1-CK2
wiring for Time Clock...............5.8
TOTALINE
Page 5.1
Page 14
6 Wire, 1 Stage Cooling, 1 Stage Heat
Residential & Commercial 1 Stage Cooling, with 1st Stage Gas Heat
Commercial Heat Pump 1 Stage Cooling
OR
with 2 Stage Heat
TOTALINE
5
(FAN)
ELEC
GAS
HP
GAS
B
O
W3
PROG
HUM
DEHUM
ECON
MISC2
CK1
CKGND
24 vac common
24 vac return
Fan relay
Compressor relay
1st stage heat circuit
2nd stage heat circuit
W1
Y1
G
R
C
MISC3 MISC2 MISC1
W2 MISC1 RS2 MISC3 RS+5 RS1 RSGND
Y2
(MISC1 ONLY)
INSTALL HUMIDITY MODULE WITH SENSING ELEMENT OUTWARD
C
R
G
Y1
W1
W2
(FAN)
6 Conductor 18 gauge
ELEC
GAS
HP
GAS
unshielded cable from the
B
O
thermostat to the equipment.
W2
MISC1
HUM
NO HUM
RS2
MISC3
RS+5
RS1
RSGND
Page 5.2
W1/O/B
MISC2
CK1
CKGND
Y1
G
R
C
Page 15
6 Wire, 1 Stage Cooling, 1 Stage Heat
Residential & Commercial 1 Stage Cooling, with 1st Stage Electric Heat
5
TOTALINE
(FAN)
ELEC
GAS
HP
GAS
B
O
24 vac common
24 vac return
Fan relay
Compressor relay
1st stage heat circuit
2nd stage heat circuit
W2 MISC1 RS2 MISC3 RS+5 RS1 RSGND
(FAN)
6 Conductor 18 gauge
ELEC
W3
PROG
HUM
DEHUM
ECON
MISC3 MISC2 MISC1
W1
Y1
G
MISC2
CK1
CKGND
R
C
GAS
HP
GAS
unshielded cable from the
B
Y2
(MISC1
O
ONLY)
INSTALL HUMIDITY MODULE WITH SENSING ELEMENT OUTWARD
thermostat to the equipment.
W2
MISC1
HUM
NO HUM
RS2
MISC3
RS+5
RS1
RSGND
W1/O/B
MISC2
CK1
CKGND
Y1
G
R C
R C
G
Y1
W1
W2
Page 5.3
Page 16
6 Wire, 1 Stage Cooling, 2 Stage Heat
Residential Heat Pump with O Reversing Valve 1 Stage Cooling, with 2 Stage Heat
TOTALINE
5
(FAN)
ELEC
GAS
HP
GAS
B
O
W3
PROG
HUM
DEHUM
ECON
MISC2
CK1
CKGND
24 vac common
24 vac return
Fan Relay
Compressor Relay
Reversing Valve
2nd stage heat circuit
W1
Y1
G
R
C
MISC3 MISC2 MISC1
W2 MISC1 RS2 MISC3 RS+5 RS1 RSGND
Y2
(MISC1 ONLY)
INSTALL HUMIDITY MODULE WITH SENSING ELEMENT OUTWARD
R C
G
Y1
O
W2
(FAN)
6 Conductor 18 gauge
ELEC
GAS
HP
GAS
unshielded cable from the
B
O
thermostat to the equipment.
W2
MISC1
HUM
NO HUM
RS2
MISC3
RS+5
RS1
RSGND
Page 5.4
W1/O/B
MISC2
CK1
CKGND
Y1
G
R
C
Page 17
6 Wire, 1 Stage Cooling, 2 Stage Heat
Residential Heat Pump with b Reversing Valve 1 Stage Cooling, with 2 Stage Heat
5
TOTALINE
(FAN)
ELEC
GAS
HP
GAS
B
O
24 vac common
24 vac return
Fan Relay
Compressor Relay
Reversing Valve
2nd stage heat circuit
W2 MISC1 RS2 MISC3 RS+5 RS1 RSGND
(FAN)
6 Conductor 18 gauge
ELEC
W3
PROG
HUM
DEHUM
ECON
MISC3 MISC2 MISC1
W1
Y1
G
MISC2
CK1
CKGND
R
C
GAS
HP
GAS
unshielded cable from the
B
Y2
(MISC1
O
ONLY)
INSTALL HUMIDITY
MODULE WITH SENSING
ELEMENT OUTWARD
thermostat to the equipment.
W2
MISC1
HUM
NO HUM
RS2
MISC3
RS+5
RS1
RSGND
W1/O/B
MISC2
CK1
CKGND
Y1
G
R C
R C
G
Y1
b
W2
Page 5.5
Page 18
Adding a 2nd Stage of Cooling (MISC1), Exterior Lighting System (MISC2), and 3rd Stage of Heating (MISC3)
TOTALINE
5
W3
PROG
HUM
DEHUM
ECON
MISC3 MISC2 MISC1
3rd Stage Heat
2nd Stage Cooling
W2 MISC1 RS2 MISC3 RS+5 RS1 RSGND
Exterior Lighting
W3
Y2
Y2
(MISC1 ONLY)
Page 5.6
W3
PROG
HUM
DEHUM
ECON
MISC2
CKGND
W1
Y1
G
CK1
MISC3 MISC2 MISC1
R
C
W1/O/B
MISC2
CK1
CKGND
Y2
(MISC1 ONLY)
INSTALL HUMIDITY
MODULE WITH SENSING
ELEMENT OUTWARD
Y1
G
R C
(FAN) ELEC
GAS
HP
GAS
B
O
W2
MISC1
HUM
NO HUM
RS2
MISC3
RS+5
RS1
RSGND
Page 19
TOTALINE
Adding a Humidification System* (MISC1), Dehumidification System* (MISC2), and controlling an Economizer (MISC3).
5
W3
PROG
HUM
DEHUM
ECON
MISC3 MISC2
Economizer
MISC1
Dehumidification System
Humidification System
* Requires Humidity Module.
W2 MISC1 RS2 MISC3 RS+5 RS1 RSGND
(MISC1
ONLY)
W3
PROG
HUM
DEHUM
ECON
Y2
(MISC1
MISC3 MISC2 MISC1
ONLY)
W1
Y1
G
MISC2
CK1
CKGND
R
C
Y2
Page 5.7
2
INSTALL HUMIDITY
MODULE WITH SENSING
ELEMENT OUTWARD
1
HUM
NO HUM
8
4
6
3
579
W1/O/B
MISC2
CKGND
(FAN) ELEC
GAS
HP
GAS
B
O
W2
MISC1
RS2
MISC3
RS+5
Z
X
RS1
1
RSGND
Y
Humidity Module
Y1
G
CK1
R
C
HUM
NO HUM
(Sold Separately)
2
8
4
6
X 1
1
3
579
Z
Y
Page 20
Wired Remote Sensor and Time Clock
TOTALINE
5
2 conductor 18 gauge unshielded cable from the thermostat to the remote sensor.
RS-GND
RS
W2 MISC1 RS2 MISC3 RS+5 RS1 RSGND
W1/O/B
MISC2
CK1
CKGND
Y1
G
R C
Optional
RS+V
DRY CONTACT SWITCH - The terminals are ‘normally open’ (may be programmed for normally closed operation, see page 16.2 of the Owner’s Manual). Closing or completing the circuit will cause the thermostat
1) If Occupied 1 is selected in step #41 of the Advanced Setup (see page 16.4 of Owner’s Manual), when the dry contact is energized the thermostat will be forced into Occupied 1 setpoints (see Section 6 of Owner’s Manual).
2) If Service Pan is selected, when the dry contact is energized the thermostat will lockout Y1 (compressor) and write Service Pan on the display.
Remote Sensor
10
9
8
Page 5.8
12
11
1
2
3
4
5
7
6
to do one of the following:
Page 21
SECTION 6
Test OperationTest Operation
Turn the power on to the Heating/Air Conditioning system.
Press the MODE button repeatedly until the
6
HEAT icon appears on the display. Press the UP or DOWN buttons until the set temperature is 10 degrees above room temperature; The furnace should turn on.
Press the MODE button repeatedly until the COOL icon appears on the display. Press the UP or DOWN buttons until the set temperature is 10 degrees below room temperature; the air conditioner should turn on. NOTE: Most
equipment has a time delay of 5 minutes between cool cycles. This feature is defeatable on the thermostat. Consult the Owner's Manual under Setup, cycles per hour.
Press the UP button until the setpoint is equal to the room temperature. Press the FAN button to Fan On. The fan should turn on and run continuously.
TOTALINE
NOTE: Due to the Random Start feature, outputs may not energize for up to 30 seconds when the thermostat is first powered (see page 16.4 of the Owner’s Manual)
Page 6.1
Page 22
SECTION 7
Calibrating the Thermostat SensorsCalibrating the Thermostat Sensors
Under normal circumstances it will not be necessary to adjust the calibration of the temperature and humidity sensors. If calibration is required, please contact a trained HVAC technician to correctly perform the following procedure.
I2:00
Su
OFF
MODE
Place the thermostat in the OFF mode.
TOTALINE
Pm
72
MODE
FAN
PRESS
TWICE
Press the MODE button once. The
MODE
MODE
remote sensor temperature will be displayed and may be calibrated using the UP or DOWN buttons. If a remote sensor is not installed, only dashes will appear.
Press the MODE button once. The relative humidity at the thermostat will be displayed and may be calibrated using the UP or DOWN buttons.
After calibration is complete, press the MODE button twice to return to normal operation.
Press and hold the MODE button. While holding the MODE button, press and hold the FAN button for 5 seconds. All icons will appear on the display.
THERMOSTAT SENSOR
Press the UP and DOWN buttons at the same time twice. The thermostat temperature will be displayed and may be calibrated using the UP or DOWN buttons.
REMOTE SENSOR
HUMIDITY SENSOR
I8:88
SuMoTuWeThFrSa
Service Filter
Pan UV Light
AUTO
OFFON
Unoccupied
123
Override
FanOn
I88
Page 7.1
Am Pm
Program On
StartStop
DeHumidify
Outside
Setup
H I
88
COOL
Outside
Remote
AUXHEAT
L O
88
CALIBRATE
CALIBRATE
CALIBRATE
7
Page 23
SECTION 8
TroubleShootingTroubleShooting
SYMPTOM: The air conditioning does not attempt to turn on. CAUSE: The compressor timer lockout may prevent the air conditioner from turning on, for a period of time. REMEDY: Consult the Owner's Manual in the Setup section to defeat the cycles per hour and compressor timeguard.
8
SYMPTOM: The display is blank. CAUSE: Lack of proper power. REMEDY: Make sure power is turned on to the furnace
and that you have 24vac between R & W. If C is used, 24vac between R & C.
SYMPTOM: The air conditioning does not attempt to turn on.
CAUSE: The cooling setpoint is set too high. REMEDY: Consult the Owner's Manual in the Setup
section to lower the cooling setpoint limit.
SYMPTOM: The heating does not attempt to turn on. CAUSE: The heating setpoint is set too low. REMEDY: Consult the Owner's Manual in the Setup
section to raise the heating setpoint limit.
TOTALINE
NOTE: Due to the Random Start feature, outputs may not energize for up to 30 seconds when the thermostat is first powered (see page 16.4 of the Owner’s Manual)
Page 8.1
Page 24
TroubleShootingTroubleShooting
SYMPTOM: When controlling a residential heat pump, and asking for cooling, the heat comes on. CAUSE: The thermostat reversing valve jumper is set for “b”. REMEDY: Set the reversing valve jumper for “O”. See pages 5.4 and 5.5.
TOTALINE
SYMPTOM: When calling for cooling, both the heat and cool come on. CAUSE: The thermostat equipment jumper is configured for “HP” and the HVAC unit is a Gas/Electric. REMEDY: Set the equipment jumper for “Gas”. See pages 5.2 and 5.3.
NOTE: Due to the Random Start feature, outputs may not energize for up to 30 seconds when the thermostat is first powered (see page 16.4 of the Owner’s Manual)
Page 8.2
P/N 88-476 Rev. 2
8