making the system nm at full capacity until the desired temperature is met.
NOTE: Smart recovery does not apply to cooling operation.
Set Current Day -The Change Day button will change
the day shown on the thermostat display to the next day. If a
schedule has been entered, the thermostat will follow the
schedule of the new selected day.
Set Current Time -The Set limerremp button allows
the user to change the time displayed on the thermostat. Press
the Set T1IDerremp button. The TIME annunciator will flash.
Press the Up and Down buttons until the correct time is shown.
Hold down the buttons to quickly move through the time display. The AM and PM annunciators will automatically change.
To ensure the schedules are properly followed, make sure that
AM or PM is correct for the time chosen. When the correct
time is shown, press the End button to exit the Set lime mode.
Reset Filter -The Reset FIlter function is initiated by
pressing the Hold and Occupied buttons simultaneously. The
Reset FIlter function is used to clear the "Clean Filter" icon on
the display screen. The "Clean Filter" icon reminds the user
when it is time to change or clean the filter of the unit.
Unoccupied Override -The Occupied button is only
active during unoccupied periods. The Occupied button is
inactive during occupied periods. If the thermostat is in unoccopied mode and the user presses the Occupied button, the set
points are changed to the OCI set points for heating and cooling. The OCI icon will flash to show the user that the thermostat is in ovenide.
The thermostat will remain in ovenide until the next scheduled time period or for the number of allowed override hours
programmed in the thermostat configuration (Option 18)
whichever comes first
NOTE: If the set point is changed during unoccupied ovenide,
the thermostat will change the unoccupied I (UNI) set point.
Programming Thermostat Schedules -Before
programming the thermostat, plan the thermostat daily schedule. The schedule is divided into 7 days (Monday through Sunday). Each day has 4 time periods (OCI, UNI, OC2, UN2).
Each time period has a start time, heating set point, and cooling
set point Fill in Table I below as an aid to programming the
daily schedules.
When choosing the times for OCI, UNI, OC2, and UN2,
the following rules must be followed:
.The maximum number of hours allowed from OCl to
UNl, or from OC2 to UN2 is 12 hours. For example, if
OCI has a value of 6:00 AM and UNl had a value of
5:00 PM, this would be acceptable. If however, OCI has
a value of 6:00 AM and UNI has a value of 7:00 PM, this
would not be acceptable because the difference is greater
than 12 hours.
.The value of UN2 must be greater than or equal to the
value of OC2, while the value of OC2 must be greater
than or equal to the value of UNl, and the value of UNl
must be greater than or equal to OC 1. For example,
acceptable values would be:
OCl UNl OC2 UN2
6:00 AM 5:00 PM 5:00 PM 10:00 PM
In the example above, the thermostat will be occupied from
6:00 AM to 10:00 PM. However, if the following values were
entered, the thermostat would not be occupied as one may
expect:
OCl UNl OC2 UN2
6:00AM 7:00 PM 6:00 PM 12:00AM
In the new example, the thermostat will display UN2 from
12:00 AM to 6:00 AM, then OCl from 6:00 AM to 6:00 PM,
then OC2 from 6:00 PM to 7:00 PM, then UNl from 7:00 PM
to 12:00 AM. The thermostat, in this example, would be occupied from 6:00 AM to 7:00 PM because OC2 has a value less
than the value ofUNl.
PROGRAMMING MODE- To program the daily schedules, perfonn the following procedw-e:
1. Enter programming mode by pressing the Program
button. The PROGRAMMING annunciator will
appear on the thermostat display. The current day of
the schedule will be displayed and the current programming time period of that day will be displayed.
The nME annunciator will flash.
NOTE: If a programming button is not pushed for 2 minutes,
the thennostat will exit programming mode and any changes
made will be saved.
2. Press the Up and Down buttons to set the start time for
the schedule day and period shown.
3. Press the Set Timeffemp button once the correct time
is shown. The TIME annunciator will stop flashing
and the HEAT annunciator will flash.
4. The heating and cooling set points can now be programmed The HEAT and COOL annunciators will
flash for the heating and cooling set points respectively. The Set Timeffemp button is used to toggle
between the time, heating, and cooling set points. Use
the Up and Down buttons to raise and lower the temperature set points.
NOTE: There must be at least 2 degrees difference between
the cooling and heating set points. The thermostat will automatically change any set points closer than 2 degrees.
5. Press the Program button to advance to the next time
period.
6. Perform Steps 2 through 5 until the times and temperature set points have been entered for the entire day.
Press the Change Day button to move to the schedule
for the next day.
Table 1 -Daily Schedule Planner
DAY OF
THE WEEK
OC1
Time I Heat I Cool
---o-N1
Time I Heat I Cool
OC2
Time I Heat I Cool
UN2
Time I Heat I Cool
Monday
Tuesday
Wednesday
Thursday
Friday
Saturday
Sunday
NOTE: The cooling temperature set point must be at least 2 degrees higher than the heating temperature set point.