TOTALINE Gold P274-1100, Gold P274-1200, Gold P274-1300 Installation And Operating Instructions Manual

TOTALINE
1c.eps
gold-1.pdf
INSTALLATION AND OPERATING INSTRUCTIONS
Par t No. P274-1100, 1200, 1300
Residential
Programmable
Thermostats
Page
SAFETY CONSIDERATIONS. . . . . . . . . . . . . . . . . . . . . . 1
GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
INSTALLATION CONSIDERATIONS . . . . . . . . . . . . . .1,2
Models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Outdoor Temperature Sensing . . . . . . . . . . . . . . . . . . . 1
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-14
Step 1 — Thermostat Location . . . . . . . . . . . . . . . . . . . 2
Step 2 — Set DIP Switches . . . . . . . . . . . . . . . . . . . . . . . 2
Step 3 — Install Thermostat . . . . . . . . . . . . . . . . . . . . . . 2
Step 4 — Space Temperature Averaging . . . . . . . . 10
Step 5 — Set Thermostat Configuration . . . . . . . . . 10
Step 6 — Check Thermostat Operation. . . . . . . . . . 12
Step 7 — Select Thermostat Operation
Settings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Step 8 — Set Current Time . . . . . . . . . . . . . . . . . . . . . . 13
Step 9 — Set Current Day . . . . . . . . . . . . . . . . . . . . . . . 13
Step 10 — Programming Thermostat
Schedules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Step 11 — Final Checklist . . . . . . . . . . . . . . . . . . . . . . . 13
OPERATION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14,15
Hold, Fan, and Mode Button Operation. . . . . . . . . . 14
Outdoor Temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Thermostat Output Assignments. . . . . . . . . . . . . . . . 14
Five-Minute Compressor Timeguard . . . . . . . . . . . . 14
Fifteen-Minute Cycle Timer. . . . . . . . . . . . . . . . . . . . . . 14
Fifteen-Minute Staging Timer. . . . . . . . . . . . . . . . . . . . 14
Three-Minute Minimum On Time . . . . . . . . . . . . . . . . 14
Heating/Cooling Set Points. . . . . . . . . . . . . . . . . . . . . . 14
Auto-Changeover Timer. . . . . . . . . . . . . . . . . . . . . . . . . 14
Power-On Check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Error Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Smart Recovery (Heating Mode Only) . . . . . . . . . . . 15
TROUBLESHOOTING. . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
PROGRAMMABLE THERMOSTAT
CONFIGURATION RECORD . . . . . . . . . . . . . . . . . . . 16
IMPORTANT: Read entire instructions before start­ing the installation.
SAFETY CONSIDERATIONS
Read and follow manufacturer instructions carefully. Fol-
low all local electrical codes during installation. All wiring must conform to l ocal and national electrical codes. Improper wiring or installation may damage the thermostat.
Recognize safety information. This is the safety al ert sym­bol . When the safety alert symbol is present on equipment or in the instruction manual, be alert to the potential for person­al injury.
Understand the signal words DANGER, WARNING, and CAUTION. These words are used with the safety alert symbol. DANGER identifies the most serious hazards which will result in severe personal injury or death. WA RNING signifies a ha z ard which could result in personal injury or death. CAUTION is used to identify unsafe practices which would result in minor personal injury or property damage.
-
GENERAL
T otaline® 7-day, programmable thermostats are wall-mount­ed, low-voltage thermostats which maintain room temperature by controlling the operation of an HVA C ( heating, vent ilation, and air-conditioning) system. Separate heating and cooling set points and auto-changeover capability allow occupied and un occupied programming for energy savings.
All programmable thermostats allow up to 4 t ime/tempera­ture settings to be programmed per 24-hr period. Each thermo­stat stores programs for 7 independent days. Batteries are not required. During power interruption, the internal memory stores comfort schedules for an unlimited time while the clock continues to run for at least 72 hours.
-
INSTALLATION CONSIDERATIONS
Models — There are 3 different models. Ensure the proper
thermostat is selected for the intended application. Refer to Fig. 1 for thermostat dimensions. Select from the following models:
1. P274-1100 (air conditioner [AC]) — 1-stage cool, 1-stage heat for air-conditioning systems only
2. P274-1200 (heat pump [HP]) — 1-stage cool, 2-stage heat for either heat pump or air conditioner systems with 2-stage heat
3. P274-1300 (2-speed) — 2-stage cool, 2-stage heat for
2-speed AC systems, or 2-stage cool, 3-stage heat for 2-speed HP systems, or 1-stage cool, 4-stage heat for 1-speed HP with special 3-stage electric heat
Outdoor Temperature Sensing — All programma-
ble thermostats can be equipped with an optional outdoor tem­perature sensor, part no. TSTATXXSEN01-B. If this option is to be installed, plan thermostat installation so that 2 wires can be run from the thermostat to an outdoor location. Refer to the installation instructions provided with the outdoor temperature sensor for necessary connections.
Manufacturer reserves the right to
discontinue, or change at any time,
specifications or designs without notice
and without incurring obligations.
REPLACEMENT COMPONENTS DIVISION LITERATURE NUMBER P274-8SI © CARRIER CORPORATION 2007 1-07 REPLACES: NEW PRINTED IN U.S.A. CATALOG NUMBER 570-502
HEIGHT (in.) WIDTH (in.) DEPTH (in.)
1
/
4
4
71/
2
13/
8
Fig. 1 — Totaline® Residential
Programmable Thermostat
INSTALLATION
Step 1 — Thermostat Location — The thermostat
should be mounted:
• approximately 5 ft from the floor
• close to or in a frequently used room, preferably on an inside partitioning wall
• on a section of wall without pipes or ductwork
The thermostat should not be mounted:
• close to a window, on an outside wall, or next to a door leading to the outside
• where exposed to direct light and heat from a lamp, the sun, a fireplace, or any other temperature-ra diating object which may cause a false reading
• close to or in direct airflow from supply registers or return air grilles
• in areas with poor air circulation (such as behind a door or in an alcove)
Step 2 — Set DIP Switches — To access the dual in-
line package (DIP) switches, remove the thermostat door from the front and unhinge the back half of the the rmostat from the front half.
There are 4 small DIP switches in the upper right of the cir­cuit board which must be configured by the installer. The ON position is indicated by small letters on the switch. Ignore the numbers (1-4) on the switches. The switch designation (A-D) is printed on the circuit board above the switches. To change a switch position, use the corner of a small screw driver to slide the switch ON or OFF.
Set the DIP switches before installing the thermostat and record the settings on page 16. Once switches are set, do NOT reassemble the halves of the thermostat . The bac k half will be mounted to the wall.
ZONING SELECT — SWITCH A (Active on All Models ) — Switch A controls the 4 cycles per hour limit and 5-minute compressor timeguard that MUST be enabled for normal oper ation. For zoning applications, turn the switch to ON and can­cel the timers as the zone contr ol c enter pe rforms t hes e timing functions.
TO SET: OFF — Normal operation, factory default ON — Zoned installations only
-
SETBACK RECOVERY — SWITCH B (Active on All Models) — Use Switch B to select eithe r normal or smart re
­covery from setback. Normal recovery changes to the new set point at the programmed time. Smart recovery, which is active in heating mode only, starts earlier and adjusts the set point slowly so that room temperature will arrive at the programmed temperature at the programmed time.
TO SET: OFF — Smart recovery, factory default ON — Normal recovery
HP/AC SELECT — SWITCH C (Active on 1200 and 1300 Models Only) — Use Switch C to select between AC and HP installations. The 1200 and 1300 models have an extra relay to control the HP reversing valve. When a 1200 model thermostat is placed in AC mode, this extra relay is converted to a second stage heat output. This allows thermostat control of 2-stage fur
­naces or 2-stage strip heat with AC systems (AC mode wiring also uses W rather than Y for first-stage heat).
TO SET: OFF — HP applications (extra re la y controls reversing valve), factory default ON — AC applications (extra output can be used for 2-stage heat)
INTELLIGENT HEAT STAGING SELECT — SWITCH D (Active on 1300 Models Only) — Use Switch D to convert a 2-speed heat pump thermostat with 1 stage of auxiliary heat into a 1-speed heat pump thermostat with 3 stages of auxiliary heat for additional heating capacity. It requires selected heaters with 2:1 ratio element sizes plus a variable-speed fa n coil. Re
­fer to fan coil literature for details.
TO SET: OFF — Normal 2-speed operation, factory default ON — Intelligent 3-stage heat with a variable-speed fan coil
Step 3 — Install Thermostat
Before installing thermostat, turn off all power to the unit. There may be more than one power disconnect. Electrical shock can cause injury or death.
4. Turn off all power to unit.
5. If an existing thermostat is being replaced: a. Remove the existing thermostat from the wall. b. Disconnect wires from the existing thermostat. Do
not allow the wires to fall back into the wall. As each wire is disconnected, record wire color and terminal connection.
c. Discard or recycle the old thermostat.
NOTE: Mercury is a hazardous waste and must be disposed of properly.
6. Locate the 2 mounting holes (1 on each side of the large hole) in the back half of the thermostat, which are already exposed from unhinging the front and back halves to set the DIP switches.
7. Route thermostat wires through the large hole in the back half of the thermostat. Remove the outer sheath from the wires for added flexibility. Standard so lid or multi-conductor thermostat wire should be used from the thermostat to the base unit. Size and length consid erations are as follows: for a maximum run length of 36 ft, use 22 AWG (American Wire Gage) wire; for a maximum run length of 100 ft, use 18 AWG wire.
-
2
NOTE: When a remote space temperature sensor or out­door-air sensor is used, an additional conductor should be provided for grounding of the shield.
Fig. 2-24 for proper wiring depending on model no. and intended application.
Terminals S2 and C are internally connected. Do not ground shield to terminal C of thermostat.
8. Level the back half of the thermostat against the wall and mark the wall through the 2 mounting holes.
9. If needed, drill two 3/16-in. mounting holes in the wall where marked. Otherwise, use the previous thermo stat’s mounting holes already drilled.
-
thermostat. Check to ensure wiring is correct before pro­ceeding with installation of unit.
12. Push excess wiring into the wall. Seal the hole in the wall to prevent drafts.
13. Snap the front and rear halves of the thermostat back together and snap the thermostat door back onto the front.
14. Turn on power to the unit. The thermostat will receive power from the unit. The thermostat will be powered
Improper wiring or installation may cause damage to the
Be careful not to drill into wiring in the wall. Electrical shock could result.
10. Secure the back half of the thermostat to the wall with 2 screws and anchors provided. Ensure all wires exit through the large hole.
11. Adjust wire l e ng th an d r outing to all ow pr o per c lo su re of the thermostat. Strip each wire at the end no more than 1/4-in. to prevent adjacent wires from shorting together. Match and connect wires to terminals on the thermostat. Refer to Table 1 for correct model usage depending on intended application. Table 1 references
by 24 v, nominal (18 to 30 vac) through terminal R (+24 v) and terminal C (commo n). Power co nsump tion is 5 va at 24 vac.
15. On power up, the thermostat display shows the selected setup mode for a few seconds, depending on DIP switch settings: AC — 1-speed air conditioner HP — 1-speed heat pump A2 — 2-speed air conditioner H2 — 2-speed heat pump HS — Intelligent heat staging with a variable-speed fan coil and 1-speed heat pump
Table 1 — Model No. and Proper Wiring for Intended Applications
MODEL NO. APPLICATION FIG. NO.
Single-Speed AC with Single-Stage Furnace Single-Speed AC with 2-Stage or Variable-Speed Furnace
1100
1200
1300
LEGEND
AC — Air Conditioner HP — Heat Pump
Single-Speed AC with Typical Fan Coil (Single-Stage Heat Control) Single-Speed AC with Variable-Speed Fan Coil Single-Speed Packaged AC with Single-Stage Gas Furnace Single-Speed Packaged AC with Single-Stage Electric Heat Single-Speed AC with 2-Stage or Variable-Speed Furnace Single-Speed AC with Typical Fan Coil (Dual-Stage Heat Control) Single-Speed HP with Typical Fan Coil Single-Speed AC with Variable-Speed Fan Coil Single-Speed Packaged AC with 2-Stage Electric Heat Single-Speed Packaged HP with Single-Stage Electric Heat Single-Speed Packaged Heat Pump with 2-Stage Electric Heat Single-Speed Packaged HP with Single-Stage Gas Furnace 2-Speed AC with Single-Stage Furnace 2-Speed AC with 2-Stage or Variable Speed Furnace 2-Speed AC with Typical Fan Coil 2-Speed HP with Single-Stage Furnace 2-speed HP with 2-Stage or Variable-Speed Furnace 2-Speed HP with Typical Fan Coil 2-Speed AC with Variable-Speed Fan Coil 2-Speed HP with Variable-Speed Fan Coil Single-Speed HP with Variable-Speed Fan Coil and Special 3-Stage Electric Heat
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
3
MODEL 1100
THERMOSTAT
24 VAC HOT
FAN
HEAT STAGE 1
COOL STAGE 1
N/A
N/A
R
G
W/W1
Y/Y2
O/W2
Y1/W2
SINGLE-STAG E
FURNACE
R
G
W
Y
SINGLE-SPEED
AIR CONDITIONER
Y
MODEL 1100
THERMO
24 VAC HOT
FAN
COOL STAGE 1
HEAT STAGE 1
N/A
N/A
STAT
R
G
Y/Y2
W/W1
O/W2
Y1/W2
TYPICAL
FAN COIL
R
G
Y
W2
3
W
E
AIR CONDITIONER
*
SINGLE-SPEED
Y
24 VAC COMM
N/A
OUTDOOR
SENSOR
CONNECTION
ON
ABCD
OFF OFF OFF OFF
C
B
S1
S2
SUGGESTED DIP
SWITCH SETTINGS
C
See Note 1 on page 9.
C
Fig. 2 — Single-Speed Air Conditioner with
Single-Stage Furnace — Model 1100 Thermostat
MODEL 1100
THERMOSTAT
24 VAC HOT
FAN
HEAT STAGE 1
COOL STAGE 1
N/A
N/A
24 VAC COMM
N/A
OUTDOOR
SENSOR
CONNECTION
R
G
W/W1
Y/Y2
O/W2
Y1/W2
C
B
S1
S2
TWO-STAGE OR
VARIABLE-SPEED
FURNACE
R
G
W/W1
Y/Y2
W2
HUM
C
See Notes 1 and 6 on page 9.
SINGLE-SPEED
AIR CONDITIONER
Y
C
24 VAC COMM
N/A
OUTDOOR
SENSOR
CONNECTION
ON
ABCD
OFF OFF OFF OFF
C
B
S1
S2
SUGGESTED DIP
SWITCH SETTINGS
C
See Notes 1 and 7 on page 9.
* May not be present on equipment.
Fig. 4 — Single-Speed Air Conditioner with Typical Fan Coil — Model 1100 Thermostat
(Single-Stage Heat Control)
MODEL 1100
THERMOSTAT EASY SELECT
24 VAC HOT
HEAT STAGE 1
N/A
FAN
N/A
COOL STAGE 1
24 VAC COMM
N/A
OUTDOOR
SENSOR
CONNECTION
Y1/W2
TERMINAL BOARD
R
W/W1 W1
O/W2
G G
Y/Y2 YY/Y2
C
B
S1
S2
DH
J1 JUMPER
R
J2 JUMPER
W2
Y1
O
C
See Notes 1 and 7 on page 9.
SINGLE-SPEED
AIR CONDITIONER
C
C
ON
SUGGESTED DIP
SWITCH SETTINGS
ABCD
OFF OFF OFF OFF
Fig. 3 — Single-Speed Air Conditioner with
2-Stage or Variable-Speed Furnace —
Model 1100 Thermostat
ON
SUGGESTED DIP
SWITCH SETTINGS
ABCD
OFF OFF OFF OFF
Fig. 5 — Single-Speed Air Conditioner with
Variable-Speed Fan Coil — Model 1100 Thermostat
4
MODEL 1100
THERMOSTAT
24 VAC HOT
FAN
HEAT STAGE 1
COOL STAGE 1
N/A
N/A
R
G
W/W1
Y/Y2
O/W2
Y1/W2
RED
GRN
WHT
YEL
SPLICE
BOX
MODEL 1200
THERMOSTAT
24 VAC HOT
FAN
HEAT STAGE 1
COOL STAGE 1
HEAT STAGE 2
N/A
R
G
W/W1
Y/Y2
O/W2
Y1/W2
TWO-STAGE OR
VARIABLE-SPEED
FURNACE
R
G
W/W1
Y/Y2
W2
HUM
SINGLE-SPEED
AIR CONDITIONER
Y
24 VAC COMM
N/A
OUTDOOR
SENSOR
CONNECTION
ON
ABCD
C
B
S1
S2
SWITCH SETTINGS
BRN
See Notes 1 and 9 on page 9.
SUGGESTED DIP
Fig. 6 — Single-Speed Packaged Air Conditioner
with Single-Stage Gas Furnace —
Model 1100 Thermostat
MODEL 1100
THERMOSTAT
N/A
FAN
HEAT STAGE 1
COOL STAGE 1
N/A
24 VAC HOT
Y1/W2
G
W/W1
Y/Y2
O/W2
R
GRN
WHT
YEL
RED
SPLICE
BOX
HEATER
CONTROL BOX
WHT
24 VAC COMM
N/A
OUTDOOR
SENSOR
CONNECTION
ON
ABCD
OFF OFF ON OFF
C
B
S1
S2
SUGGESTED DIP
SWITCH SETTINGS
C
See Note 2 on page 9.
Fig. 8 — Single-Speed Air Conditioner with
2-Stage or Variable-Speed Furnace —
Model 1200 Thermostat
MODEL 1200
THERMOSTAT
24 VAC HOT
FAN
HEAT STAGE 1
COOL STAGE 1
HEAT STAGE 2
N/A
R
G
W/W1
Y/Y2
O/W2
Y1/W2
TYPICAL
FAN COIL
R
G
W2
*
Y
W3
E
SINGLE-SPEED
AIR CONDITIONER
C
Y
24 VAC COMM
N/A
OUTDOOR
SENSOR
CONNECTION
ON
ABCD
OFF OFF OFF OFF
C
B
S1
S2
BRN
See Notes 1, 9, and 10 on page 9.
SUGGESTED DIP
SWITCH SETTINGS
Fig. 7 — Single-Speed Packaged Air Conditioner
with Single-Stage Electric Heat —
Model 1100 Thermostat
BRN
24 VAC COMM
N/A
OUTDOOR
SENSOR
CONNECTION
ON
ABCD
OFF OFF ON OFF
C
B
S1
S2
SUGGESTED DIP
SWITCH SETTINGS
C
C
See Notes 2 and 7 on page 9.
* May not be present on equipment.
Fig. 9 — Single-Speed Air Conditioner with Typical Fan Coil — Model 1200 Thermostat
(Dual-Stage Heat Control)
5
Loading...
+ 11 hidden pages