Toss ROPEX RESISTRON RES-407 Operating Instructions Manual

RESISTRON
Exclusive Sales and Service:
www.tossheatseal.com
Exclusive Sales and Service:
www.tossheatseal.com
GB
RES-407
Operating
Instructions
Important features
Microprocessor technology
Automatic zero calibration (AUTOCAL)
Automatic optimization (AUTOTUNE)
Automatic phase angle compensation (AUTOCOMP, as of April 2005)
Automatic frequency adjustment
Large current and voltage range
Electrically isolated analog input for set point selection with potentiometer or 0…10 VDC
Electrically isolated 0…10VDC analog output for ACTUAL temperature
24VDC control signals for START, AUTOCAL and RESET with electrical isolation
Alarm function with fault diagnosis
Heatsealing band alloy and temperature range selectable as standard (as of June 2003)
19.11.07
Toss Machine Components, Inc.
Toss Machine Components, Inc. 539 S. Main Street, Nazareth. PA 18064
539 S. Main Street, Nazareth. PA 18064 Phone 610-759-8883 Fax 610-759-1766
Phone 610-759-8883 Fax 610-759-1766
E-Mail: info@tossheatseal.com
E-Mail: info@tossheatseal.com

Contents

1 Safety and warning notes . . . . . . . . . . . . . . 3
1.1 Use . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
1.2 Heatsealing band . . . . . . . . . . . . . . . . 3
1.3 Impulse transformer . . . . . . . . . . . . . . 3
1.4 Current transformer PEX-W2/-W3 . . . . 3
1.5 Line filter . . . . . . . . . . . . . . . . . . . . . . . 4
1.6 Warranty provisions . . . . . . . . . . . . . . . 4
1.7 Standards / CE marking . . . . . . . . . . . 4
2 Application . . . . . . . . . . . . . . . . . . . . . . . . . . 4
3 Principle of operation . . . . . . . . . . . . . . . . . 5
4 Description of the controller . . . . . . . . . . . 6
5 Accessories and modifications . . . . . . . . . 6
5.1 Accessories . . . . . . . . . . . . . . . . . . . . . 6
5.2 Modifications (MODs) . . . . . . . . . . . . . 7
6 Technical data . . . . . . . . . . . . . . . . . . . . . . 10
7 Dimensions . . . . . . . . . . . . . . . . . . . . . . . . 12
8 Installation . . . . . . . . . . . . . . . . . . . . . . . . . 12
8.1 Installation procedure . . . . . . . . . . . . 12
8.2 Installation steps . . . . . . . . . . . . . . . . 13
8.3 Power supply . . . . . . . . . . . . . . . . . . . 14
8.4 Line filter . . . . . . . . . . . . . . . . . . . . . . 15
8.5 Current transformer PEX-W3 . . . . . . 15
8.6 Auxiliary voltage . . . . . . . . . . . . . . . . 16
8.7 Wiring diagram (standard) . . . . . . . . . 16
8.8 Wiring diagram with booster
connection (MOD 26) . . . . . . . . . . . . 17
8.9 Wiring diagram with "Temp­erature reached" signal (MOD 40)
or „Temp. OK“ signal (MOD 46) . . . . 18
9 Startup and operation . . . . . . . . . . . . . . . . 19
9.1 View of the controller . . . . . . . . . . . . . 19
9.2 Controller configuration . . . . . . . . . . . 19
9.3 Heatsealing band . . . . . . . . . . . . . . . . 21
9.4 Startup procedure . . . . . . . . . . . . . . . 22
10 Controller functions . . . . . . . . . . . . . . . . . 24
10.1 Indicators and controls . . . . . . . . . . . 24
10.2 Temperature setting
(set point selection) . . . . . . . . . . . . . . 25
10.3 Temperature indication (actual value
output) . . . . . . . . . . . . . . . . . . . . . . . . 26
10.4 Automatic zero calibration
(AUTOCAL) . . . . . . . . . . . . . . . . . . . . 27
10.5 "START" signal (HEAT) . . . . . . . . . . . 28
10.6 "RESET" signal . . . . . . . . . . . . . . . . . 28
10.7 Measuring impulse duration
(as of April 2005) . . . . . . . . . . . . . . . . 29
10.8 Automatic phase angle compensation (AUTOCOMP)
(as of April 2005) . . . . . . . . . . . . . . . . 29
10.9 Temperature diagnosis
(as of April 2005) . . . . . . . . . . . . . . . . 30
10.10 Heatup timeout
(as of April 2005) . . . . . . . . . . . . . . . . 31
10.11 Diagnostic interface/visualization software
(as of April 2005) . . . . . . . . . . . . . . . . 31
10.12 System monitoring/alarm output . . . . 31
10.13 Error messages . . . . . . . . . . . . . . . . . 32
10.14 Fault areas and causes . . . . . . . . . . . 37
11 Factory settings . . . . . . . . . . . . . . . . . . . . . 38
12 Maintenance . . . . . . . . . . . . . . . . . . . . . . . . 39
13 How to order . . . . . . . . . . . . . . . . . . . . . . . . 40
14 Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Page 2 RES-407
Safety and warning notes

1 Safety and warning notes

This RESISTRON temperature controller is manufactured according to DIN EN 61010-1. In the course of its manufacture it passed through quality assurance, whereby it was subjected to extensive inspections and tests. It left the factory in perfect condition. The recommendations and warning notes contained in these operating instructions must be complied with, in order to guarantee safe operation. The device can be operated within the limits indicated in the "Technical Data" without impairing its operational safety. Installation and maintenance may only be performed by technically trained, skilled persons who are familiar with the associated risks and warranty provisions.

1.1 Use

RESISTRON temperature controllers may only be used for heating and temperature control of heatsealing bands which are expressly suitable for them, and providing the regulations, notes and warnings contained in these instructions are complied with.
In case of non-compliance or use contrary to
!
the intended purpose, there is a risk that safety will be impaired or that the heatsealing band, electrical wiring, transformer etc. will overheat. Ensuring such compliance is the personal responsibility of the user.
The RESISTRON temperature controller must be set and coded according to the temperature coefficient of the heatsealing band.
The use of incorrect alloys with a too low
!
temperature coefficient and incorrect coding of the RESISTRON temperature controller lead to uncontrolled heating and ultimately to burn-out of the heatsealing band!
The heatsealing bands that were originally supplied must be identified by detail specification, part number or some other means that will assure that replacement bands are identical.

1.3 Impulse transformer

A suitable impulse transformer is necessary to ensure that the control loop functions perfectly. This transformer must be designed according to VDE 0570/ EN 61558 (isolating transformer with reinforced insulation) and have a one section bobbin. When the impulse transformer is installed, suitable shock protection must be provided in accordance with the national installation regulations for electrical equipment. In addition, water, cleaning solutions and conductive fluids must be prevented from seeping into the transformer.
Incorrect installation of the impulse
!
transformer impairs electrical safety.

1.2 Heatsealing band

A basic prerequisite for reliable and safe operation of the system is the use of suitable heatsealing bands.
The resistance of the heatsealing band which
!
is used must have a positive minimum temperature coefficient in order to guarantee trouble-free operation of the RESISTRON temperature controller.
The temperature coefficient must be specified as follows:
TCR 104–×10 K
e.g. Alloy-20: TCR = 1100 ppm/K
NOREX: TCR = 3500 ppm/K
1–
RES-407 Page 3

1.4 Current transformer PEX-W2/-W3

The current transformer supplied with the RESISTRON temperature controller is an integral part of the control system.
Only the original ROPEX PEX-W2 or PEX-W3
!
current transformer may be used. Other transformers may cause the equipment to malfunction.
The current transformer may only be operated if it is connected to the RESISTRON temperature controller correctly (see section 9, "Startup and operation"). The relevant safety instructions contained in section 8.3, "Power supply", must be obeyed. External monitoring modules can be used in order to additionally increase
Application
operating safety. They are not included in the scope of supply of the standard control system and are described in a separate document.

1.5 Line filter

The use of an original ROPEX line filter is mandatory in order to comply with the standards and provisions mentioned in section 1.7 "Standards / CE marking" on page 4. This device must be installed and connected according to the instructions contained in section 8.3, "Power supply" as well as the separate documentation enclosed with the line filter.

1.6 Warranty provisions

The statutory provisions for warranties apply for a period of 12 months following the delivery date. All devices are tested and calibrated in the factory. Devices that have been damaged due to faulty connections, dropping, electrical overloading, natural wear, incorrect or negligent handling, chemical influences or mechanical overloading as well as devices that have been modified, relabeled or otherwise altered by the customer, for example in an attempt to repair them or install additional components, are excluded from the warranty. Warranty claims must be examined in the factory and approved by ROPEX.

1.7 Standards / CE marking

The controller described here complies with the following standards, provisions and directives:
DIN EN 61010-1 (VDE 0411-1)
DIN EN 60204-1 Electrical equipment of machines
EN 50081-1 EMC interference emissions
EN 50082-2 EMC interference immunity:
Compliance with these standards and provisions is only guaranteed if original accessories and/or peripheral components approved by ROPEX are used. If not, then the equipment is operated on the user's own responsibility. The CE marking on the controller confirms that the device itself complies with the above-mentioned standards. It does not imply, however, that the overall system also fulfils these standards. It is the responsibility of the machine manufacturer and of the user to verify the completely installed, wired and operationally ready system in the machine with regard to its conformity with the safety provisions and the EMC directive (see also section 8.3, "Power supply"). If peripheral components (e.g. the transformer or the line filter) from other manufacturers are used, no functional guarantee can be provided by ROPEX.
Safety provisions for electrical measuring, control and laboratory devices (low voltage directive). Overvoltage category III, pollution severity 2, safety class II.
(machinery directive)
according to EN 55011, group 1, class B
ESDs, RF radiation, bursts, surges.

2 Application

This RESISTRON temperature controller is an integral part of the "series 400", the outstanding feature of which is its microprocessor technology. All RESISTRON temperature controllers are used to control the temperature of heating elements (heatsealing bands, beaded bands, cutting wires, heatsealing blades, solder elements etc.), as required in a variety of heatsealing processes.
Page 4 RES-407
The controller is most commonly used for impulse­heatsealing PE and PP films in:
Vertical and horizontal f/f/s machines
Pouch, filling and sealing machines
Film wrapping machines
Pouch-making machines
Group packaging machines
•L-sealers
Principle of operation
•etc.
The use of RESISTRON temperature controllers results in:
Repeatable quality of the heatseals under any conditions

3 Principle of operation

The resistance of the heatsealing band, which is temperature-sensitive, is monitored 50x per second (60x at 60Hz) by measuring the current and voltage. The temperature calculated with the help of these measurements is displayed and compared with the set point. The primary voltage of the impulse transformer is adjusted by phase-angle control if the measured values deviate from the set point. The resulting change in the current through the heatsealing band leads to a change in the band temperature and thus also its resistance. This change is measured and evaluated by the RESISTRON temperature controller. The control loop is closed: ACTUAL temperature = SET temperature. Even minute thermal loads on the heatsealing band are detected and can be corrected quickly and precisely. The thermoelectric control loop which is formed has a highly dynamic response because purely electrical variables are measured at a high sampling rate. A very wide secondary current range can be controlled with only minimal power loss - a considerable advantage ­because power is controlled on the primary side of the
Increased machine capacity
Extended life of the heatsealing bands and teflon coatings
Simple operation and control of the sealing process
transformer. This allows optimum adaptation to the load and to the required dynamic range despite the exceptionally compact dimensions of the controller.
PLEASE NOTE!
RESISTRON temperature controller play a significant role in enhancing the performance of modern machines. However, the full benefit can only be obtained from the advanced technology offered by this control system if all the system components, in other words the heatsealing band, the impulse transformer, the wiring, the timing signals and the controller itself, are compatible with one another.
We will be pleased to
contribute our many
years of experience
towards optimizing your
heatsealing system.
Heatsealing band R = f (T)
U
2
sec.
Impulse transformer
Current transformer
U
1
prim.
RESISTRON controller
URI
R
R=f(T)
LINE
_
+
Actual value
Start
Set point
RES-407 Page 5
Indicators
and
controls
or
bus interface

4 Description of the controller

Description of the controller
The microprocessor technology endows the RESISTRON temperature controller RES-407 with previously unattainable capabilities:
Very simple operation thanks to AUTOCAL, the automatic zero calibration function.
Good dynamic response of the control system thanks to AUTOTUNE, which adapts automatically to the controlled system.
High precision thanks to further improved control accuracy and linearization of the heatsealing band characteristic.
High flexibility: The AUTORANGE function (as of April 2005) covers a secondary voltage range from
0.4V to 120 V and a current range from 30 A to 500A.
Automatic adjustment to the line frequency in the range from 47 Hz to 63Hz.
Increased protection against dangerous conditions, such as overheating of the heatsealing band.
The electrically isolated analog interfaces for the temperature set point and the actual temperature (0-10VDC) allow the temperature to be set either
directly on the machine PLC or by means of an external potentiometer (PD-x). Similarly, the real heatsealing band temperature can be visualized either on the display of the machine PLC or on an external temperature meter (ATR-x). The RESISTRON temperature controller RES-407 features an integrated fault diagnosis function, which tests both the external system (heatsealing band, wiring etc.) and the internal electronics and outputs a selective error message in case of a fault. To increase operational safety and interference immunity, all 24VDC logic signals are electrically isolated from the controller and the heating circuit. Coding switches on the temperature controller itself can be used to adapt to different heatsealing band alloys (Alloy A20, NOREX etc.) and set the required temperature range (0...300 °C, 0...500°C etc.) on all controllers manufactured as of June 2003. An external 24VDC auxiliary voltage is required to supply the isolating amplifiers and optocouplers. The compact design of the RESISTRON temperature controller RES-407 and the plug-in connections make this controller easy to install.

5 Accessories and modifications

A wide range of compatible accessories and peripheral devices are available for the RESISTRON temperature controller RES-407. They allow it to be optimally adapted to your specific heatsealing application and to your plant's design and operating philosophy.
Analog temperature meter ATR-x
For front panel mounting or mounting on a top hat rail (DIN TS35 rail). Analog indication of the ACTUAL temperature of the heatsealing band in °C. The meter damping of the unit is optimized for the abrupt temperature changes that occur in impulse mode.
Digital temperature meter DTR-x
For front panel mounting or mounting on a top hat rail (DIN TS35 rail). Digital indication of the ACTUAL temperature of the heatsealing band in °C, with HOLD function.

5.1 Accessories

The products described below are only a few of the wide range of accessories available for RESISTRON temperature controllers (ª"Accessories" leaflet).
Page 6 RES-407
Accessories and modifications
Designed according to VDE 0570/EN 61558 with a one-section bobbin.
Set point potentiometer PD-x
Front panel-mounting version for setting the required SET heatsealing temperature of the RESISTRON temperature controller. The number which appears on the display corresponds to the SET heatsealing temperature in °C.
Line filter
Essential in order to ensure CE conformity. Optimized for the RESISTRON temperature controller.
Impulse transformer
Optimized for impulse operation with RESISTRON temperature controllers. Specified according to the heatsealing application (ª ROPEX Application Report).
Communication interface CI-USB-1
Interface for connecting a RESISTRON temperature controller with diagnostic inter­face (DIAG) to the PC (USB port). Associated PC visualization software for dis­playing setting and configuration data, and for recording SET and ACTUAL tempe­ratures in real time.
Booster
External switching amplifier, necessary for high primary currents (continuous current > 5A, pulsed current > 25A).
Monitoring current transformer
For detecting frame short-circuits on the heatsealing band. Used as an alternative to the standard PEX-W2/-W3 current transformer.

5.2 Modifications (MODs)

Owing to its universal design, the RESISTRON temperature controller RES-407 is suitable for a very wide range of heatsealing applications. Various modifications (MODs) are offered for the RESISTRON temperature controller RES-407 for implementing special applications.
The modifications described here are just a few of the large number available. Separate documents are supplied for all modifications.
MOD 01
Amplifier for low secondary voltages
= 0.25…16VAC). This modification is necessary,
(U
R
for example, for very short or low-resistance heatsealing bands.
RES-407 Page 7
Accessories and modifications
MOD 21
Inverts the alarm signal (terminal 18). If an alarm is signaled, the alarm output is switched to open condition (LOW). If the controller does not report an alarm, a 24VDC voltage level (HIGH) is output at terminal 18.
MOD 26
Additional terminal for connecting an external switching amplifier (booster). This modification is necessary for high primary currents (continuous current > 5 A, pulsed current > 25A).
Switch
position
0 1 4 5 8
0 = Factory settings
Te mp .
range
300°C 300°C 500°C 500°C 300°C
Te mp .
coefficient
1100ppm/K 780ppm/K 1100ppm/K 780ppm/K 3500ppm/K
Band
alloy
e.g. Alloy-20 e.g. Alloy L e.g. Alloy-20 e.g. Alloy L e.g. NOREX
0
1
9
2
8
3
7
4
6
5
MOD 37 (until May 2003)
Additional rotary coding switch for the heatsealing band alloy and the temperature range. Various heatsealing band alloys (e.g. Alloy-20, NOREX) and temperature ranges (e.g. 300 °C, 500°C) can be selected.
This modification is supplied as standard
!
with all controllers manufactured as of June
2003 (ªªªª section 9.2.2 "Configuration of the rotary coding switch for the temperature range and alloy (as of June 2003)" on page 20).
0
1
9
8
7
4
6
5
SWITCH POS.
2
3
0 1 4 5 8
TEMP. RANGE
300°C 300°C 500°C 500°C 300°C
ALLOY
1100ppm/K
1100ppm/K (A20)
3500ppm/K
780ppm/K
780ppm/K
(A20)
(L)
(L)
(NOREX)
MOD 40
Additional terminal for "Temperature reached" signal. This output signal is activated when the ACTUAL temperature of the heatsealing band exceeds 95 % of the SET heatsealing temperature. It can be used to
monitor the process, for example, or to control the closure of the heatsealing bars.
MOD 40 cannot be used in combination with
!
MOD 26 (booster connection) manufactured
prior to March 2005.
Page 8 RES-407
Accessories and modifications
MOD 46 (as of April 2005)
Additional terminal for "Temperature OK" signal. If this modification is installed, the RES-407 checks whether the ACTUAL temperature is within a settable tolerance band ("OK" window) on either side of the SET temperature. The lower ( ) and upper ( ) tolerance band limits are configured in the
∆ϑ
upper
factory to -10 K and +10 K. These values can be set independently of one another in the ROPEX visualization software (ª section 10.11 "Diagnostic interface/visualization software (as of April 2005)" on page 31). If the actual temperature is inside the specified tolerance band when the "START" signal is activated, the output signal is activated as well (see graph below):
Set+∆ϑ
upper
Set
Set+∆ϑ
lower
∆ϑ
lower
Actual value
If the actual temperature leaves the tolerance band, the output signal is deactivated again. The output signal then remains deactivated, even if the actual tempera­ture subsequently returns to the tolerance band. It is thus possible to check - as part of the monitoring concept, for instance - whether the output signal is still active at the end of the heatsealing process, in other words whether the actual temperature has remained within the defined tolerance band throughout the entire process. The output signal is not deactivated again until the next "START" signal is activated or until an alarm is signaled.
MOD 46 ("Temperature OK" signal) cannot be
!
used in combination with MOD 40
("Temperature reached" signal).
Signal „Temp. OK“
Conductive
Not conduct.
Time
Time
RES-407 Page 9

6 Technical data

Type of construction Housing for installation in the electrical cabinet
Snaps onto a standard top hat rail (DIN TS35 rail, 35mm) acc. to DIN EN 50022 Dimensions: 90 x 75 mm; height: 135 mm (incl. terminals)
Line voltage All controllers manufactured as of April 2005:
115VAC version: 110VAC -15 %…120VAC +10% (equivalent to 94…132 VAC) 230VAC version: 220VAC -15 %…240VAC +10% (equivalent to 187…264 VAC) 400VAC version: 380VAC -15 %…415VAC +10% (equivalent to 323…456 VAC)
All controllers manufactured as of January 2004 up to March 2005: 115VAC version: 115VAC -15 %…120VAC +10% (equivalent to 98…132 VAC) 230VAC version: 230VAC -15 %…240VAC +10% (equivalent to 196…264 VAC) 400VAC version: 400VAC -15 %…415VAC +10% (equivalent to 340…456 VAC)
All controllers manufactured up to December 2003: 115VAC, 230 VAC or 400VAC, tolerance: +10% / -15 %
Technical data
Depending on the controller version (ª section 13 "How to order" on page 40)
Line frequency 47…63Hz, automatic adjustment to frequencies in this range
Auxiliary voltage
Terminals 12+13
Heatsealing band type and temperature range
24VDC, +20%, -10%, reverse polarity-protected Current input (up to March 2005): max. 50mA
(as of April 2005): max. 1.0A
All controllers manufactured as of April 2005: The temperature range and temperature coefficient settings can also be specified by means of the ROPEX visualization software (ª section 10.11 "Diagnostic interface/visualization software (as of April 2005)" on page 31) in addition to the rotary coding switch (see below):
Temperature range: 200°C, 300 °C, 400°C or 500 °C Temperature coefficient: 400…4000 ppm (variable setting range)
All controllers manufactured as of June 2003: Five different ranges can be set on the controller with a rotary coding switch:
Temperature coefficient 1100ppm, 0…300°C (e.g. Alloy A20), default Temperature coefficient 780 ppm, 0…300°C (e.g. Alloy L) Temperature coefficient 1100ppm, 0…500°C (e.g. Alloy A20) Temperature coefficient 780 ppm, 0…500°C (e.g. Alloy L) Temperature coefficient 3500ppm, 0…300 °C (e.g. NOREX)
All controllers manufactured up to May 2003: Default value 300°C, Alloy-20 The temperature range and alloy are selectable with MOD 37.
Analog input
(set point) Terminals 16+14
Analog output
(actual value) Terminals 17+14
Page 10 RES-407
0…10VDC, I Equivalent to 0…300 °C or 0…500°C or with an external PD-3 or PD-5 precision potentiometer (R = 2 kohms) 0…2kohms equivalent to 0…300 °C or 0…500°C
0…10VDC, I Equivalent to 0…300 °C or 0…500°C Accuracy: ±1% add. 50mV
= 5mA, electrically isolated
max
= 5mA, electrically isolated
max
Technical data
Reference voltage +10VDC / ±5 %, I
Digital logic levels
Terminals 5, 6, 7
LOW (0V): 0…2VDC, electrically isolated HIGH (24VDC): 12…30VDC (max. current input 6mA) Reverse polarity-protected
Switching output for "Temp. OK" signal (MOD 40)
Alarm output U
=30VDC
U
max
=50mA
I
max
U
< 2V (saturation voltage)
ON
< 3V (saturation voltage), electrically isolated,
ON
short-circuit proof Up to March 2005: I As of April 2005: I As of April 2005, the output can also be inverted by means of a plug-in jumper.
Maximum load
(primary current of
= 5A (duty cycle = 100%)
I
max
= 25A (duty cycle = 20 %)
I
max
impulse transformer)
Power dissipation max. 20W
Ambient
+5…+45°C
temperature
Degree of protection IP20
max
=5mA
max
max
=40mA =200mA
Installation If several controllers are installed on one top hat rail
(DIN TS35 rail), a clearance of at least 20mm should be allowed between them.
The moving clip required for fastening must be facing down for mounting on a horizontal top hat rail.
End holders to mechanical fix the controller must be fitted at both ends for mounting on a vertical top hat rail.
Weight Approx. 0.7 kg (incl. connector plug-in parts)
Housing material Plastic, polycarbonate, UL-90-V0
Connecting cables
Type / cross-sections
Rigid or flexible; 0.2…2.5mm² (AWG 24…12) Plug-in connectors
If ferrules are used, they must be crimped in accordance
!
with DIN 46228 and IEC/EN 60947-1.
This is essential for proper electrical contact in the terminals.
RES-407 Page 11

7 Dimensions

Dimensions
135.0
113.0
75.0 90.0

8 Installation

ª See also section 1 "Safety and warning notes" on page 3.
Installation and startup may only be
!
performed by technically trained, skilled persons who are familiar with the associated risks and warranty provisions.

8.1 Installation procedure

Proceed as follows to install the RESISTRON temperature controller RES-407:
1. Switch off the line voltage and verify that all circuits
are deenergized.
2. The supply voltage specified on the nameplate of
the RESISTRON temperature controller must be identical to the line voltage that is present in the plant or machine. The line frequency is
automatically detected by the temperature controller in the range from 47 Hz to 63Hz.
3. Install the RESISTRON temperature controller in the electrical cabinet on a standard top hat rail (DIN TS35 rail, according to DIN EN 50022). If several controllers are installed on one top hat rail, the minimum clearance specified in section 6 "Technical data" on page 10 must be allowed between them.
4. Wire the system in accordance with the instructions in section 8.3 "Power supply" on page 14, section 8.6 "Auxiliary voltage" on page 16 and the ROPEX Application Report. The information provided in section 8.2 "Installation steps" on page 13 must be heeded additionally.
Check the tightness of all the system
!
connections, including the terminals for the
impulse transformer windings.
5. Make sure that the wiring conforms to the relevant national and international installation regulations.
Page 12 RES-407
Installation

8.2 Installation steps

Heatseal element
with coppered ends
Sufficient wire
cross-section
Avoid long
cables
Dimension transformer correctly
- Secondary voltage
- Power
- Duty cycle
F
U (sec.)
2
Heatsealing band R= f (T)
No additional
resistance
in secondary
circuit
A
Impulse
transformer
Use heatseal bands with
suitable temperature coefficient
Note
number
of turns
Current transformer
U (prim.)
1
20mm clearance if several
controllers installed on
PEX-W2/-W3
Temperature
meter
ATR -x
Note
polarity
one top hat rail
Controller
No push-on connectors
Connect U measuring
heatsealing band ends
Twi sted
Current measuring
R
wires directly to
wires I
R
Line
Line filter
LF-xx480
Note
direction
of rotation
Digital potentiometer PD-x
Configure
DIP switches
correctly
(up to March 2005)
RES-407 Page 13

8.3 Power supply

Installation
L1
(L1)
N(L2)
GND/ Earth
ON
OFF
Short wires
1
LINE
Ka
U
K1
I
2
R
R
I
>
3
LINE
FILTER
ROPEX
temperature
controller
U
1
PRIM.
U
2
SEC.
R
Line
115VAC, 230 VAC, 400VAC 50/60Hz
Circuit breaker
Double-pole, C characteristic (ª ROPEX Application Report)
I
>
3
Kb
3
2
Short-circuit protection only.
!
RESISTRON temperature controller not protected.
Relay Ka
For "HEAT ON - OFF" function (all-pole) or "EMERGENCY STOP".
Line filter
The filter type and size must be determined according to the load, the transformer and the machine wiring (ª ROPEX Application Report).
Do not run the filter supply wires (line side) parallel
!
to the filter output wires (load side).
RESISTRON temperature controller belonging to the 4xx Series.
Relay Kb
Load break (all-pole), e.g. in combination with the alarm output of the temperature controller.
When using a series resistor RV-....-1 the relay Kb
!
shall be installed.
Impulse Transformer
Designed according to VDE 0570/EN 61558 (isolating transformer with reinforced insulation). Connect core to ground.
Use transformers with a one section bobbin. The
!
power, duty cycle and voltage values must be
determined individually according to the application (ª ROPEX Application Report and "Accessories" leaflet for impulse transformers).
Wiring
The wire cross-sections depend on the application (ª ROPEX Application Report). Guide values:
Primary circuit: min. 1.5mm², max. 2.5 mm² Secondary circuit: min. 4.0 mm², max. 25 mm²
c These wires must always be twisted (>20/m) d These wires must be twisted (>20/m) if several control
loops are laid together ("crosstalk").
e Twisting (>20/m) is recommended to improve EMC.
Page 14 RES-407
Installation

8.4 Line filter

To comply with EMC directives – corresponding to EN 50081-1 and EN 50082-2 – RESISTRON control loops must be operated with line filters. These filters damp the reaction of the phase-angle control on the line and protect the controller against line disturbances.
The use of a suitable line filter is part of the
!
standards conformity and a prerequisite of
the CE mark.
ROPEX line filters are specially optimized for use in RESISTRON control loops. Providing that they are
Large cross-section wire to ground
PE
LINE
installed and wired correctly, they guarantee compliance with the EMC limit values. You can find the exact specification of the line filter in the ROPEX Application Report calculated for your particular heatsealing application. For more technical information: ª "Line filter" documentation.
It is permissible to supply several
!
RESISTRON control loops with a single line filter, providing the total current does not exceed the maximum current of the filter.
The wiring instructions contained in section 8.3 "Power supply" on page 14 must be observed.
max. 1m
ROPEX
temperature
controller
Do not lay parallel
Large cross-section wire to ground
Large frame contact surface

8.5 Current transformer PEX-W3

The PEX-W3 current transformer supplied with the RESISTRON temperature controller is an integral part
24
23
terminal
wires
60
39
26
14
Mounting plate (galvanized)
of the control system. The current transformer may only be operated if it is connected to the temperature controller correctly (ª section 8.3 "Power supply" on page 14).
28
75
12
14
terminal
block
Snap-on for DIN-rail 35 x 7,5mm or 35 x 15mm (DIN EN 50022)
RES-407 Page 15
Installation

8.6 Auxiliary voltage

Since the inputs and outputs of the RES-407 are electrically isolated, a 24VDC auxiliary voltage must be applied to terminals 12+13. The auxiliary voltage has a
RES-407
AUTOCAL
with 24VDC signal
START (HEAT)
with 24VDC signal
RESET
with 24VDC signal
5
6
7
(also with MOD 01)
maximum current input of 1,0A and it is also protected against reverse polarity.

8.7 Wiring diagram (standard)

Line filter LF-xx480
1
LINE
2
3
4
U
1
prim.
GND
Ground
for 24VDC signals.
Must be grounded
externally to prevent
electrostatic
charging!
GND
Auxiliary
supply
+24VDC
ANALOG
INPUT
(set point)
+0...10VDC
ANALOG
OUTPUT
(real temperatur)
+0...10VDC
14
13
12
16
17
0V
(Internal ground)
No external
grounding allowed!
up to
production
date
March 2005
0V
(Internal ground)
No external
grounding allowed!
Impulse
transformer
8
U
R
9
10
11
Twi sted
I
R
Current transformer
PEX-W2/-W3
U
2
sec.
Heat-
R
sealing
band
ALARM
OUTPUT
+24VDC
U
REF
+10VDC
Page 16 RES-407
18
15
=
=
OPTION:
SET POINT
POTENTIOMETER
PD-3 or PD-5
2K
cw
14
16
15
Installation
8.8 Wiring diagram with booster connection (MOD 26)
RES-407
AUTOCAL
with 24VDC signal
START (HEAT)
with 24VDC signal
RESET
with 24VDC signal
5
6
7
(also with MOD 01)
1
2
Booster
20
IN OUT
19
NC
3
4
NC
Line filter LF-xx480
13
24
U
1
prim.
LINE
GND
Ground
for 24VDC signals.
Must be grounded
externally to prevent
electrostatic
charging!
GND
Auxiliary
supply
+24VDC
ANALOG
INPUT
(set point)
+0...10VDC
ANALOG
OUTPUT
(real temperature)
+0...10VDC
14
13
12
16
17
0V
(Internal ground)
No external
grounding allowed!
up tol
production
date
March 2005
0V
(Internal ground)
No external
grounding allowed!
Impulse
transformer
8
U
R
9
10
11
Twi sted
I
R
Current transformer
PEX-W2/-W3
U
2
sec.
Heat-
R
sealing
band
ALARM
OUTPUT
+24VDC
U
REF
+10VDC
18
15
OPTION:
SET POINT
=
=
RES-407 Page 17
POTENTIOMETER
PD-3 or PD-5
2K
cw
14
16
15
1
2
3
4
Additional terminals in housing cover for MOD 26 (booster connection)
ALARM HEAT OUTPUT AUTOCAL
BOOSTER
Installation
MOD 26 cannot be used in combination with
!
MOD 40 ("Temperature OK" signal)
manufactured up to March 2005.
19 20
8.9 Wiring diagram with "Temp­erature reached" signal (MOD 40) or „Temp. OK“ signal (MOD 46)
+24VDC
+24VDC
RES- 407
+
I
max. 50mA
GND GND
MOD 40 cannot be used in combination with
! !
MOD 26 (booster connection) manufactured
prior to March 2005.
1
2
3
4
Additional terminals in housing cover for MOD 40 (”Temp. reached” signal) or MOD 46 (”Temp. OK” signal)
MOD 46 cannot be used in combination with MOD 40.
ALARM HEAT OUTPUT AUTOCAL
Page 18 RES-407
Startup and operation

9 Startup and operation

9.1 View of the controller

Te rm in al s
Wiring diagram
LEDs
Nameplate

9.2 Controller configuration

The controller must be switched off in order
!
to configure the coding switches and the
plug-in jumpers.

9.2.1 Configuration of the DIP switches for secondary voltage and current

Automatic configuration (AUTORANGE) (as of April 2005)
The secondary voltage and current ranges are automatically configured by the automatic calibration function (AUTOCAL). The voltage is configured in the range from 0.4 VAC to 120VAC and the current in the range from 30 A to 500A. If the voltage and/or the
Coding switches and plug-in jumpers
current is outside the permissible range, a detailed error message appears on the controller (ª see section 10.13 "Error messages" on page 32).
Configuration with coding switches (up to March 2005)
Set the DIP switches for matching the secondary voltage U position for your application.
!
Report calculated for your particular application.
and the secondary current I2 to the correct
2
You can find the exact configuration of the DIP switches in the ROPEX Application
RES-407 Page 19
Startup and operation
F
F
O
1-10
)
V
2
ON
U (
3 4
SWITCH
5 4 3 2 1
F F
O
N O
O
2
1
N
U
2
1...10V
6...60V
20...120V
If the secondary current I2 is less than 30 A, the PEX-W2 or PEX-W3 current transformer must have two turns (ª ROPEX Application Report).
2x
Factory settings
4
5
3
DIP switch DIP switch
12
OFF
ON
OFF
OFF
ON
OFF
3
OFF
OFF
ON
I
2
30...100A
60...200A
120...400A
4
OFF
ON
ON
5
OFF
OFF
ON
9.2.2 Configuration of the rotary coding switch for the temperature range and alloy (as of June 2003)
Switch
position
0 1 4 5 8
9 PC-CONFIGURATION
0 = Factory settings
This configuration is supplied as standard
!
with all controllers manufactured as of June
2003. The settings are only possible on older
controllers in conjunction with MOD 37 (ªªªª section "MOD 37 (until May 2003)" on page 8).
Te mp .
range
300°C 300°C 500°C 500°C 300°C
Te mp .
coefficient
1100ppm/K 780ppm/K 1100ppm/K 780ppm/K 3500ppm/K
Band
alloy
e.g. Alloy-20 e.g. Alloy L e.g. Alloy-20 e.g. Alloy L e.g. NOREX
0
1
9
2
8
3
7
4
6
5
0 1 4 5 8
9
TEMP. RANGE
300°C 300°C 500°C 500°C 300°C
PC CONFIGURATION
SWITCH POS.
0
1
9
2
8
3
7
4
6
5
ALLOY
1100ppm/K
780ppm/K
1100ppm/K (A20)
780ppm/K
3500ppm/K
(A20)
(L)
(L)
(NOREX)
If the switch is set to "9" (as of April 2005), more temperature ranges and alloys can be selected by means of the ROPEX visualization software (ª see section 10.11 "Diagnostic interface/visualization software (as of April 2005)" on page 31).
Page 20 RES-407
Startup and operation
9.2.3 Configuration of the alarm output
(as of April 2005)
Alarm output opened (HIGH) by alarm/ PC-CONFIGURATION.
Alarm output closed (LOW) by alarm. (factory setting)
If the plug-jumper is not inserted - or if it is
!
incorrectly inserted - an error message
appears when the controller is switched on (ªªªª section 10.13 "Error messages" on page 32).
If the "Alarm output opened by alarm/PC CONFIGURATION" position is selected (as of April
2005), the behavior of the alarm output can be
configured in more detail by means of the ROPEX visualization software (ª see section 10.11 "Diagnostic interface/visualization software (as of April
2005)" on page 31).
DE-ENERGIZED / PC AT ALARM ENERGIZED
0
1
9
2
8
3
7
4
6
5
CONFIGURATION ALARM OUTPUT
corrected after a few heating cycles (ª section 9.3.2 "Burning in the heatsealing band" on page 21). One very important design feature is the copper or silver-plating of the heatsealing band ends. Cold ends allow the temperature to be controlled accurately and increase the life of the teflon coating and the heatsealing band.
An overheated or burned-out heatsealing
!
band must no longer be used because the
TCR has been altered irreversibly.

9.3.2 Burning in the heatsealing band

9.3 Heatsealing band

9.3.1 General

The heatsealing band is a key component in the control loop, since it is both a heating element and a sensor. The geometry of the heatsealing band is too complex to be discussed at length here. We shall therefore only refer to a few of the most important physical and electrical properties: The measuring principle applied for this system necessitates a heatsealing band alloy with a suitable temperature coefficient TCR, i.e. one whose resistance increases as the temperature rises. Too low a TCR leads to oscillation or uncontrolled heating. When heatsealing bands with a higher TCR are used, the controller must be calibrated for this. The first time the heatsealing band is heated to approximately 200…250°C, the standard alloy undergoes a once-only resistance change (burn-in effect). The cold resistance of the heatsealing band is reduced by approximately 2…3 %. However, this at first glance slight resistance change results in a zero point error of 20…30°C. The zero point must therefore be
If a new heatsealing band has been used, the zero point is first of all calibrated while the band is still cold by activating the "AUTOCAL" function on the controller. When the "AUTOCAL" function has finished, the controller outputs a voltage equivalent to a temperature of 20°C at the actual value output. Adjust the set point to approximately 250 °C and activate the "START" signal to heat for approximately 1 second. After recooling, the controller usually outputs an actual value of less than 20 °C. Repeat the "AUTOCAL" function. The heatsealing band has now been burned in and the change in the alloy stabilized. The burn-in effect described here does not occur if the heatsealing band has already been thermally pretreated by the manufacturer.

9.3.3 Replacing the heatsealing band

All power supply leads must be disconnected from the RESISTRON temperature controller in order to replace the heatsealing band.
The heatsealing band must be replaced in
!
accordance with the instructions provided by
the manufacturer.
RES-407 Page 21
Startup and operation
Each time the heatsealing band is replaced, the zero point must be calibrated with the AUTOCAL function while the band is still cold, in order to compensate production-related resistance tolerances. The burn-in procedure described above should be performed for all new heatsealing bands.

9.4 Startup procedure

Please also refer to section 1 "Safety and warning notes" on page 3 and section 2 "Application" on page 4.
Installation and startup may only be
!
performed by technically trained, skilled persons who are familiar with the associated risks and warranty provisions.

9.4.1 Initial startup

Prerequisites: The controller must be correctly installed and connected (ª section 8 "Installation" on page 12). Proceed as follows to start up the controller for the first time:
1. Switch off the line voltage and verify that all circuits
are deenergized.
2. The supply voltage specified on the nameplate of
the controller must be identical to the line voltage that is present in the plant or machine. The line frequency is automatically detected by the temperature controller in the range from 47 to 63 Hz.
3. In the case of controllers manufactured up to March
2005, the settings of the DIP switches on the controller are indicated in the ROPEX Application Report and depend on the heatsealing band that is used (section 9.2 "Controller configuration" on page 19).
4. Make sure that no START signal is present.
5. Apply the auxiliary voltage (24VDC).
6. Switch on the line voltage.
7. When the voltage is switched on, the yellow
"AUTOCAL" LED lights up for approximately
0.3 seconds to indicate that the controller is being powered up correctly.
As of SW-Revision 106:
!
If the red "ALARM" LED lights up for 0.3s in addition to the yellow "AUTOCAL" LED when the voltage is switched on, the configuration of this controller has been changed in the visualization software (ªªªª section 10.11 "Diagnostic interface/ visualization software (as of April 2005)" on page 31). In order to avoid malfunctions, please check the controller configuration before continuing the startup procedure.
8. One of the following states then appears:
"ALARM"
LED
OFF Short pulses
BLINKS fast (4Hz)
Lit continuously
9. Activate the AUTOCAL function while the
heatsealing band is still cold (terminals 5+14). The yellow "AUTOCAL" LED lights up for the duration of the calibration process (approx. 10…15s). A voltage of app. 0 V appears at the same time at the actual value output (terminals 17+14). If an ATR-x is connected, it indicates 0…3°C. When the zero point has been calibrated, the "AUTOCAL" LED goes out and a voltage of 0.66 V (300°C range) or 0.4 V (500°C range) appears at the actual value output instead. If an ATR-x is connected, it must be set to "Z". If the zero point has not been calibrated successfully, the red "ALARM" LED blinks slowly (1Hz). In this case the controller configuration is incorrect (ª section 9.2 "Controller configuration" on page 19 and ROPEX Application Report). Repeat the calibration after the controller has been configured correctly.
10.When the zero point has been calibrated
successfully, set a defined temperature at the set point input (terminal 16) and apply the "START" signal (HEAT). The "HEAT" LED then lights up. The heating and control process can be observed at the actual value output: The controller is functioning correctly if the temperature (which corresponds to the signal change at the analog output) follows a harmonious
"OUTPUT"
LED
every 1.2 s
OFF Go to 9
OFF Fault diagnosis
ACTION
Go to 9
(ª section 10.1
3)
Page 22 RES-407
Startup and operation
curve, in other words it must not jump abruptly, fluctuate or deviate temporarily in the wrong direction. This kind of behavior would indicate that
measuring wires have been laid incorrectly.
the U
R
If an error message is displayed, please proceed as described in section 10.13 "Error messages" on page 32.
11.Burn in the heatsealing band (ª section 9.3.2
"Burning in the heatsealing band" on page 21) and repeat the AUTOCAL function.
The controller is now
ready
9.4.2 Restart after replacing the
heatsealing band
To replace the heatsealing band, proceed as described in section 9.3.2 "Burning in the heatsealing band" on page 21 .
Always use a heatsealing band with the
!
correct alloy, dimensions and copper-plating in order to avoid malfunctions and overheating.
Continue with section 9.4.1, steps 4 to 11.
RES-407 Page 23

10 Controller functions

See also section 8.6 "Auxiliary voltage" on page 16.

10.1 Indicators and controls

Manufactured as of April 2005
Controller functions
1
2
3
ALARM HEAT OUTPUT AUTOCAL
4
RESISTRON
RES- 407
Temperature
controller
5 6
7
8
ROPEX
Tel:+49(0) 7142-7776-0
9
1 0
11
Made in Germany
Manufactured up to March 2005
1
2
3
4
POWER ON
AUTOCAL
OUTPUT
HEAT
ALARM
12 13 14 1516 17 18
Red LED, lights up or blinks to indicate ALARM.
Yellow LED, lit during heating phase.
Green LED, indicates pulses in measure-
ment mode. In control mode, luminous
intensity is proportional to heating current.
Yellow LED, remains lit for duration
of AUTOCAL process.
Green LED, lit continuously when
power supply is on.
Yellow LED, remains lit for duration
of AUTOCAL process.
Green LED, indicates pulses in measure-
ment mode. In control mode, luminous
intensity is proportional to heating current.
!
5
12 13 14 1516 17 18
6
RESISTRON
µP-Controller
7
8
Red LED, lights up or blinks to indicate ALARM.
9
1
ROPEX
INDUSTRIE - ELEKTRONIK
.
0
11
Page 24 RES-407
Yellow LED, lit during heating phase.
Controller functions
In addition to the functions shown in the diagram above, various controller operating states are indicated
LED Blinks slowly (1 Hz) Blinks fast (4Hz) Lit continuously
RESET active,
AUTOCAL
(yellow)
HEAT
(yellow)
OUTPUT
(green)
ALARM
(red)
START and AUTOCAL
functions are locked
(as of April 2005)
In control mode the luminous intensity is proportional to the heating current.
Configuration error,
AUTOCAL not possible

10.2 Temperature setting (set point selection)

by the LEDs. These states are described in detail in the table below:
AUTOCAL requested, but
function is locked (as of April 2005)
HEAT requested,
but function is locked
(as of April 2005)
Controller calibrated
incorrectly, run AUTOCAL
By connecting a 2 kohm potentiometer to terminals 14…16:
AUTOCAL executing
START executing
Fault, ª section 10.13
The heatsealing temperature of the RES-407 can be set in two ways:
By applying a 0…10VDC voltage to the analog input terminals 16 + 14:
RES-407
+
+
0…10VDC
-
The relationship between the applied voltage and the SET temperature is linear. Setting range: 0VDC Æ 0°C 10VDC Æ 300 °C or 500°C
(depending on the contr. configuration) Please refer to section 10.3 "Temperature indication (actual value output)" on page 26 for a circuit diagram.
16
14
GND
13
RES-407
15
U
10VDC
16
IN 0…10VDC
14
13
REF
3
1
2
±5%)
CW
2K
GND
Potentiometer with digital dial PD-x
15
14
16
In order to be able to select the set point with a potentiometer, the controller makes a +10 VDC ( reference voltage available at terminal 15. The relationship between the potentiometer setting and the SET temperature is linear. The connecting wires between the controller and the potentiometer must be shielded.
RES-407 Page 25
Controller functions
V
If a ROPEX PD-x precision potentiometer is used, the SET temperature can be adjusted exactly with the help of the digital display in the window of the dial. The number which appears on the display corresponds to the SET temperature in °C. The set point that is selected for the heatsealing temperature must be greater than 40°C. If not, the heatsealing band will not be heated up when the "START" signal is activated.
If a potentiometer is not connected or if 0VDC
!
is applied to the set point input, the set point is assumed to be zero. When you connect the potentiometer, please note the direction of rotation!
10.3 Temperature indication (actual
value output)
The RES-407 supplies an analog 0…10VDC signal, which is proportional to the real ACTUAL temperature, at terminals 17+14.
RES-407
Actual value output 0…10VDC
+
33ohms
max. 5mA
17
GND
14
°C
T
300
e r
u
270
t a
r
240
e p
210
m e T
180
150
120
20°C
°C
T
500
e r
u
450
t a
r
400
e p
350
m e T
300
250
200
150
100
90
60
0.66V
"ZERO"
0 - 300°C range
12345678910
oltage U
VDC
0 - 500°C range
13
-
Temperature
meter
e.g. ATR-x
Voltage values: 0VDC Æ 0°C 10VDC Æ 300 °C or 500°C
(depending on the contr. configuration) The relationship between the change in the output voltage and the ACTUAL temperature is linear.
Page 26 RES-407
0…10VDC
+
An indicating instrument can be connected to this output in order to visualize the temperature of the heatsealing band. The characteristics of the ROPEX ATR-x temperature meter (size, scaling, dynamic response) are ideally suited to this application and this instrument should therefore always be used (ª section 5 "Accessories and modifications" on page 6). It not only facilitates SET-ACTUAL comparisons, but also enables other criteria such as the heating rate, set point reached within the specified time, cooling of the heatsealing band etc. to be evaluated. This meter moreover permits disturbances in the control loop (loose connections, contacting or wiring problems) as well as any line disturbances to be
20°C
12345678910
0.4V
"ZERO"
Voltage U
VDC
Controller functions
observed extremely effectively and interpreted accordingly. The same applies if mutual interference occurs between several neighboring control loops.
If an alarm is signaled, this analog output is
!
used to display a selective error message
(ªªªª section 10.13 "Error messages" on page 32).
10.4 Automatic zero calibration
(AUTOCAL)
Owing to the automatic zero calibration (AUTOCAL) function, there is no need to adjust the zero point man­ually on the controller. This function matches the con­troller to the current and voltage signals that are pre­sent in the system. The zero point is calibrated in the factory to the initial temperature (ambient temperature, 20°C).
Variable initial temperature: On controllers manufactured as of April 2005, the initial temperature for the "AUTOCAL" function can be set in the 0…+40°C range in the visualization software (ª section 10.11 "Diagnostic interface/visualization software (as of April 2005)" on page 31). This setting is remembered if the controller is switched off and then on again. As of SW Revision 107, the "External calibration tem­perature" setting can also be selected in the visualiza­tion software. The initial temperature for this setting can be specified in the +3…+40°C range via the analog input (terminals 16+14) (ª section 10.2 "Temperature setting (set point selection)" on page 25). The value selected at the analog input must be present when the "AUTOCAL" function is activated. If the specified temperature is too high (greater than 40°C) or if the selected value varies, an error message appears (error codes 115 and 116; ª section 10.13 "Error messages" on page 32).
The "AUTOCAL" function is activated by means of a 24VDC pulse at terminals 5+14.
24VDC
AUTOCAL
+
-
HIGH:
LOW:
The automatic calibration process takes around 10…15seconds. The heatsealing band is not heated during this process. The yellow LED on the front panel lights up when the "AUTOCAL" function is active. The actual value output (terminals 14+17) is 0…3°C (corresponds to app. 0 VDC). If the temperature of the heatsealing band varies on controllers manufactured as of April 2005, the "AUTOCAL" function is executed a maximum of three times. If the function still cannot be terminated successfully, an error message appears (ª section 10.13 "Error messages" on page 32).
!
temperature) before activating the "AUTOCAL" function.
max. 6mA
GND
14
13
12VDC
2VDC
You should always wait for the heatsealing band and the bar to cool down (to ambient
RES-407
5
AUTOCAL
0.1…5s
Reasons for disabled "AUTOCAL" function:
1. The "AUTOCAL" function cannot be activated until 10seconds after the controller is switched on. If you attempt to activate it sooner, it will not work.
2. The "AUTOCAL" function cannot be not activated if the heatsealing band cools down at a rate of more than 0.1K/ s. If the control signal is activated, the function is executed automatically providing the cooling rate has fallen below the above-mentioned value.
RES-407 Page 27
Controller functions
3. If the "START" signal (24VDC) is active, the "AUTOCAL" function is not executed ("HEAT" LED lit).
4. If the "RESET" signal (24VDC) is active, the "AUTOCAL" function is not executed.
5. The "AUTOCAL" function cannot be activated if error codes 101…103, 201…203, 801 or 9xx (up to March 2005: error codes 1…3, 5…7) occur on startup (ª section 10.13 "Error messages" on page 32). If the controller has already operated correctly - at least once - after starting up, the "AUTOCAL" function cannot be activated with error codes 201…203, 801 or 9xx (up to March 2005: error codes 5…7).

10.5 "START" signal (HEAT)

When the "START" signal is activated, the controller­internal set/actual comparison is enabled and the heatsealing band is heated up to the SET temperature. It remains at this temperature until the signal is deactivated again. The "HEAT" LED on the front panel of the RES-407 is lit continuously for the duration of the heating phase. The "START" signal is activated by means of a 24VDC signal at terminals 6+14.
The set point that is selected for the heatsealing temperature must be greater than 40°C. If not, the heatsealing band will not be heated up. The alarm output is switched if the "START" signal is activated while an error message is indicating error codes 104…106, 111…114, 211, 302 or 303 (up to March 2005: error codes 8…12) (ª section 10.13 "Error messages" on page 32). The heatsealing band is no longer heated up.

10.6 "RESET" signal

The RESISTRON temperature controller RES-407 can be reset by means of an external "RESET" signal at terminals 7+14). As a result:
A heatsealing cycle is aborted if one is in progress
No more measuring impulses are generated
An error message is reset if one is present (Note: The error message is not reset until the
"RESET" signal is deactivated)
24VDC
RESET
+
max. 6mA
RES-407
7
24VDC
START
+
-
HIGH: 12VDC
LOW:
!
„RESET“ signal is active.
(HEAT)
max. 6mA
GND
14
13
2VDC
The "START" signal is disabled as long as the "AUTOCAL" function is executing or the
RES-407
6
START (HEAT)
-
HIGH:
2VDC
LOW:
As of SW revision 103, the controller actual value output changes to 0…3 °C (i.e. approximately 0 VDC) while the "RESET" signal is being activated. This may be interpreted by the higher-level controller (e.g. a PLC) as feedback. The "AUTOCAL" function is not aborted if the "RESET" signal is activated while it is still executing.
GND
12VDC
14
13
RESET
>0.1s
Page 28 RES-407
Controller functions
The controller performs an internal
!
initialization run lasting approximately 500ms after the "RESET" signal is deactivated. The next heatsealing process cannot be started until it has finished.
If a contactor Kb is used to deactivate the
!
control loop (ªªªª section 8.3 "Power supply" on page 14), it must be energized again 50ms at the latest after the "RESET" signal is deactivated. If it is energized too late, an error message will be output by the controller.
10.7 Measuring impulse duration
(as of April 2005)
The length of the measuring impulses generated by the controller can be set with the parameter. It may be necessary to set a measuring impulse that is longer than the default 1.7 ms for certain applications (ª ROPEX Application Report).
This parameter can only be set by means of
!
the ROPEX visualization software (ª section 10.11 "Diagnostic interface/ visualization software (as of April 2005)" on page 31).
If the interval between the two "AUTOCAL" functions is longer than 2.0 s, "AUTOCAL" is executed normally again the second time.
AUTOCAL signal
24VDC
0
Function
AUTOCAL
0
"AUTOCAL" LED
lit
off
"OUTPUT" LED
lit
<2.0s
AUTOCOMP
t
t
t
10.8 Automatic phase angle
compensation (AUTOCOMP) (as of April 2005)
It may be necessary to compensate the phase angle displacement between the U signals for special heatsealing applications (ª ROPEX Application Report). The "AUTOCOMP" function is provided for this purpose. The following settings are possible:
1. „OFF" (Factory settings)
The „AUTOCOMP“ function is deactivated.
2. „ON“
The „AUTOCOMP“ function is executed whenever the "AUTOCAL" function (ª section 10.4 "Automatic zero calibration (AUTOCAL)" on page 27) is run twice in quick succession. The interval between the end of the first "AUTOCAL" function and the start of the second "AUTOCAL" must be shorter than 2.0 s. The second "AUTOCAL" function only takes around 2.0s and incorporates the "AUTOCOMP" function.
and IR measuring
R
off
t
The "OUTPUT" LED blinks repeatedly when the "AUTOCOMP" function is executed and the actual value output (terminals 17+14) is set to 0…3 °C (i.e. app. 0 VDC).
3. „AUTO“
(as of software revision 108)
With this setting the „AUTOCOMP“ function is acti­vated automatically after the "AUTOCAL" function has been successfully executed.
RES-407 Page 29
Controller functions
AUTOCAL signal
24VDC
Function
„AUTOCAL“ LED
lit
OFF
„OUTPUT“ LED
lit
temperature. The lower ( ) and upper ( ) tolerance band limits are configured in the
∆ϑ
upper
„AC“
0
t
AUTOCOMP
AUTOCAL
0
t
t
factory to -10 K and +10K. These values can be set independently of one another in the ROPEX visualization software. If the actual temperature is inside the specified tolerance band when the "START" signal is activated, the temperature diagnosis is activated as well. If the ACTUAL temperature leaves the tolerance band, the corresponding error code (307 or 308) is indicated and the alarm output is switched (ª section 10.13 "Error messages" on page 32).
Set+∆ϑ
Set+∆ϑ
upper
Set
lower
∆ϑ
lower
Actual value
OFF
The "OUTPUT" LED blinks repeatedly when the "AUTOCOMP" function is executed and the actual value output (terminals 17+14) is set to 0…3 °C (i.e. app. 0 VDC).
The "AUTOCOMP" function must be
!
activated in the ROPEX visualization software (ª section 10.11 "Diagnostic interface/ visualization software (as of April 2005)" on page 31) (default setting: AUTOCOMP off).
t
10.9 Temperature diagnosis
(as of April 2005)
An additional temperature diagnosis can be activated in the ROPEX visualization software (ª section 10.11 "Diagnostic interface/visualization software (as of April
2005)" on page 31). The RES-407 checks whether the ACTUAL temperature is within a settable tolerance band ("OK" window) on either side of the SET
Time
Alarm
307
If the temperature diagnosis is not activated by the time the "START" signal is deactivated (i.e. if the ACTUAL temperature does not exceed the upper or lower tolerance band limit), the corresponding error code (309, 310) is indicated and the alarm output is switched. An additional delay time (0…9.9 s) can be set in the ROPEX visualization software. The first time the lower tolerance band limit is exceeded, the temperature diagnosis is not activated until the parameterized delay time has elapsed. The temperature diagnosis function can thus be explicitly deactivated, e.g. if the temperature drops temporarily owing to the closure of the sealing jaws.
The values that can be set in the ROPEX
!
visualization software for the upper and lower tolerance band are identical to those for the "Temperature OK" signal (MOD 46).
Page 30 RES-407
Controller functions
A

10.10 Heatup timeout (as of April 2005)

An additional heatup timeout can be activated in the ROPEX visualization software (ª section 10.11 "Diagnostic interface/visualization software (as of April
2005)" on page 31).
This timeout starts when the START signal is activated. The RES-407 then monitors the time required for the ACTUAL temperature to reach 95% of the SET temperature. If this time is longer than the parameterized time, the corresponding error code (304) is indicated and the alarm output is switched (ª section 10.13 "Error messages" on page 32).
Actual value
Set
95% of Set
Only a ROPEX comunication interface is
!
allowed to be connected to the diagnostic interface. Connecting another device (e.g. a telephone cable) could result in malfunctions or damage to the controller.
The ROPEX visualization software is described in a separate document.

10.12 System monitoring/alarm output

To increase operating safety and to avoid faulty heatsealing, this controller incorporates special hardware and software features that facilitate fault diagnosis and selective error messages. Both the external wiring and the internal system are monitored. These features assist the operator in identifying the cause of abnormal operations. A system fault is reported or differentiated by means of the following indications:
A.) Red "ALARM" LED on the controller with
three states:
Timeout
1. Blinks fast (4 Hz):
The "AUTOCAL" function should be executed (error
Heatup time Alarm
Time
304
codes 104…106, 211, 302, 303; up to March 2005: error codes 8+9).
2. Blinks slowly (1 Hz):
The system configuration is incorrect and the zero calibration ("AUTOCAL" function) was unsuccessful

10.11 Diagnostic interface/visualization software (as of April 2005)

(ª section 9.2 "Controller configuration" on page 19). It corresponds to error codes 110…114 (up to March 2005: error codes 10…12).
An interface with a 6-pole Western socket is provided for systemdiagnostics and process visualization. This interface allows a data connection to be set up to the ROPEX visualization software using the ROPEX communication interface CI-USB-1.
3. Lit continuously: A fault is preventing the controller from being started (error codes 101…103, 107, 108, 201…203, 307, 308, 801, 9xx; up to March 2005: error codes 1…7). Also in instances 1 and 2 if the "START" signal is activated simultaneously. As a rule, it refers to an external wiring fault.
DI
G
B.) Alarm output signal on the controller
(terminals 12+18):
0
1
9
2
8
3
7
4
6
5
This logic output is set in the factory as follows:
LOW (OPEN) in operating states A.1) and A.2), but high (closed) if a "START" signal is activated in one of these states.
HIGH (CLOSED) in operating state A.3)
RES-407 Page 31
Controller functions
If the alarm relay is configured opposite to the factory setting (ª section 9.2.3 "Configuration of the alarm output (as of April 2005)" on page 21), these states are reversed.
C.) Error code output via the 0 to 10 V DC
actual value output (terminals 17+14):
Since a temperature indication is no longer necessary if a fault occurs, the actual value output is used to display error messages in the event of an alarm. 13 voltage levels (up to March 2005: 12 voltage levels) are offered for this purpose in the 0…10VDC range, each of which is assigned an error code (ª section 10.13 "Error messages" on page 32). If a state that requires "AUTOCAL" occurs - or if the controller configuration is not correct - (error codes 104…106, 111…114, 211, 302, 303; up to March 2005: error codes 8…12), the actual value output jumps back and forth at 1 Hz between the voltage value which corresponds to this error and the end of the scale (10 V DC, i.e. 300 °C or 500 °C). If the "START" signal is activated in one of these states, the voltage value does not change any more. Selective fault detection and indication can thus be implemented simply and inexpensively using the analog input of a PLC with a corresponding error message (ª section 10.13 "Error messages" on page 32).
An alarm can only be reset by applying a
!
"RESET" signal or by switching the
controller off and then on again.
If an error message is reset using the
!
"RESET" signal, the "RESET" signal must be
deactivated first.
Invalid error messages may appear when the
!
controller is switched off owing to the undefined operating state. This must be taken into account when they are evaluated by the higher­level controller (e.g. a PLC) in order to avoid false alarms.

10.13 Error messages

The table below shows how the analog voltage values that appear at the actual value output correspond to the faults that have occurred. It also describes each fault and the required corrective action. The error messages are listed in two separate tables for controllers "up to March 2005" and "as of April 2005". The block diagram in section 10.14 "Fault areas and causes" on page 37 permits each fault to be cleared quickly and efficiently. 13 voltage levels for fault diagnostics appear at the actual value output of all controllers manufactured as of April 2005. The error messages are differentiated even more finely in the controller. The error codes described below can be displayed with the ROPEX visualization software (ª section 10.11 "Diagnostic interface/ visualization software (as of April 2005)" on page 31) to facilitate troubleshooting.
If the actual value output is evaluated in order
!
to identify an error message - in the higher­level controller, for instance - the tolerance window must be adjusted to prevent it from being incorrectly interpreted. Please note the tolerances of the actual value output (ªªªª section 6 "Technical data" on page 10).
Page 32 RES-407
Controller functions
Action if machine
already operating,
HS band not chang.
c
Fault area
Fault area e
Fault area dk
Fault area fgh
Check
(loose contact)
Check power supply
Run RESET
Replace controller
Replace controller
Replace controller
Replace controller
Replace controller
plug-in jumper
Action
if machine started
Cause
STATUS
of alarm outp.
for first time
(factory set.)
c
Fault area
signal missing
R
I
e
Fault area
signal missing
R
U
d
Fault area
signals missing
R
and I
R
U
fgh
Fault area
Temperature step, down
(loose contact)
Temperature step, up
Temperature too low/high
(ª section 10.9)
Replace controller
Int. faut, contr. defective
Check
plug-in jumper
output wrong
Plug-in jumper for alarm
Check
power supply
Frequency fluctuation,
inadmissible line frequency
HIGH
Run RESET
Replace controller
Replace controller
Replace controller
Replace controller
(ª section 10.10)
Heatup time too long
Triac defective
Int. faut, contr. defective
Int. faut, contr. defective
Int. faut, contr. defective
Part 1 of 3: Error messages as of April 2005
LED
ALARM
Temp.
500°C
Tem p .
300°C
output;
Act. value
code
Error
[°C]
[°C]
Volta ge [V]
33
20
0.66
(101)
1
66
40
1.33
(102)
2
100
60
2.00
(103)
3
Lit
uously
contin-
133
80
2.66
(107)
(108)
(307)
(308)
(309)
(310)
4
RES-407 Page 33
166
100
3.33
(201)
(202)
5
200
120
4.00
(203)
(304)
(901)
6
233
140
4.66
(913)
(914)
(915)
(916)
(917)
(918)
7
Action if machine
already operating,
HS band not chang.
fgh
Fault area
Controller functions
---
(loose contact)
Action
STATUS
if machine started
Cause
of alarm outp.
for first time
(factory set.)
ij
fgh
and/or
of transformer,
Check specification
Fault area
signals
R
Run AUTOCAL,
Run AUTOCAL
incorrect,
signals incorrect,
R
I
incorrect specification of
signals incorrect,
impulse-transformer
R
U
incorrect specification of
and/or I
R
impulse-transformer
U
LOW
Warning:
Fault:
incorrect specification of
impulse-transformer
HIGH
(voltage value
Temperature too low,
formed, loose contact,
AUTOCAL wasn’t per-
at actual
value output
then no longer
ambient temp. fluctuates
changes)
fault area
temperature too high,
(loose contact)
Run AUTOCAL
Data error
formed, loose contact,
AUTOCAL wasn’t per-
ambient temp. fluctuates
LED
ALARM
Temp.
500°C
Tem p .
300°C
[°C]
[°C]
Blinks
Warning:
alarm LED blinks; alarm output is LOW). When the "START" signal is activated, the warning changes to a fault
output;
Volt. [V]
Act. value
(actual value output no longer jumps back and forth, see bold italic values; alarm LED lit continuously; alarm output is HIGH).
NOTE: The specified error messages are initially output as warnings (actual value output jumps back and forth between two values;
code
(104)
Error
(105)
Part 2 of 3: Error messages as of April 2005
Page 34 RES-407
fast
(4Hz)
¯266«
ª500®
¯160«
ª300®
¯5.33«
ª 10 ®
(106)
8
Lit
Fault:
uously
contin-
¯300«
ª500®
¯180«
ª300®
¯6.00«
ª 10 ®
(302)
(303)
(211)
9
Controller functions
Action if machine
already operating,
Action
if machine started
Cause
HS band not chang.
for first time
---
j,
Fault area
signal incorrect,
R
I
check configuration
calibration not possible
---
i,
Fault area
signal incorrect,
R
U
check configuration
calibration not possible
ij,
Fault area
signals incorrect,
R
and I
R
U
---
check configuration
calibration not possible
Ext. calibration
temperature too high,
calibration not possible
Temperature fluctuates,
calibration not possible
Ext. calibration
temperature fluctuates
calibration not possible
STATUS
of alarm outp.
ALARM
Tem p .
500°C
Tem p .
300°C
(factory set.)
LED
[°C]
[°C]
¯333«
¯200«
ª500®
ª300®
¯366«
¯220«
ª500®
ª300®
LOW
Warning:
Warning:
¯400«
¯240«
Fault:
HIGH
at actual
(voltage value
Lit
Fault:
(1Hz)
Blinks
slowly
ª500®
ª300®
value output
contin-
¯433«
¯260«
changes)
then no longer
uously
ª500®
ª300®
alarm LED blinks; alarm output is LOW). When the "START" signal is activated, the warning changes to a fault
output;
Volt. [V]
¯6.66«
ª 10 ®
¯7.33«
ª 10 ®
¯8.00«
(actual value output no longer jumps back and forth, see bold italic values; alarm LED lit continuously; alarm output is HIGH).
Act. value
ª 10 ®
¯8.66«
ª 10 ®
NOTE: The specified error messages are initially output as warnings (actual value output jumps back and forth between two values;
(111)
code
Error
Part 3 of 3: Error messages as of April 2005
10
(112)
11
(113)
12
(114)
(115)
(116)
13
RES-407 Page 35
Controller functions
Action if machine
already operating,
Action
if machine started
Cause
HS-band not chang.
for first time
c
Fault area
c
Fault area
signal missing
R
I
Fault area e
Fault area e
signal missing U
fgh
Fault areas dk
(loose contact)
Fault areas
Check power supply
Run RESET
Replace controller
fgh
Fault area d
signals missing
R
R
and I
R
U
(loose contact)
Fault areas
Check power supply
Temperature step
Frequency fluctuation,
Run RESET
Replace controller
Internal fault
Internal fault,
inadmissible line frequency
fgh
---
Fault areas
Run AUTOCAL
signal
R
incorrect
and/or I
R
controller defective
U
Run AUTOCAL
Data error
---
j,
Fault area
signal incorrect,
R
I
---
i,
Fault area
check configuration
signal incorrect,
R
U
calibration not possible
---
ij,
Fault areas
check configuration
calibration not possible
check configuration
signals incorrect,
R
and I
calibration not possible
R
U
STATUS
of alarm outp.
LED
ALARM
HIGH
(factory set.)
Lit
Blinks
LOW,
fast
(4Hz)
gets HIGH
signal
with"START"
at analog
(voltage value
Blinks
output then
slowly
no longer
changes)
(1Hz)
Continuously
33
66
40
1.33
2
100
60
2.00
3
[°C]
Tem p .
500°C
20
[°C]
Temp.
300°C
0.66
output ;
Act. value
Voltage [V]
1
code
Error
Error messages up to March 2005
133
80
2.66
4
166
100
3.33
5
200
120
4.00
6
233
140
4.66
7
¯266«
¯160«
¯5.33«
¯300«
ª500®
¯180«
ª300®
¯6.00«
ª 10 ®
8
¯333«
ª500®
¯200«
ª300®
ª 10 ®
¯6.66«
9
10
ª500®
ª300®
ª 10 ®
¯365«
¯220«
¯7.33«
11
ª500®
ª300®
ª 10 ®
¯400«
¯240«
¯8.00«
ª500®
ª300®
ª 10 ®
12
Page 36 RES-407
Controller functions

10.14 Fault areas and causes

1229
5
6
3
Temperature
4
8
1
The table below explains the possible fault causes.
Fault area Explanation Possible causes
Load circuit interrupted after U
pickoff point
- Wire break, heatsealing band break
R
- Contact to heatsealing band defective
UR
IR
controller
HARDWARE
8
7
c
PEX-W2/-W3 current transformer signal interrupted
Primary circuit interrupted
measuring wires from current transformer interrupted
- I
R
- Wire break, triac in controller defective
- Primary winding of impulse transformer interrupted
d
Secondary circuit interrupted before U
pickoff point
R
- Wire break
- Secondary winding of impulse transformer interrupted
9
45
I2
8
32
U2
1
7
e
f
g
h
i
U
signal missing
R
Partial short-circuit (delta R)
Parallel circuit interrupted
Total short-circuit
U
signal incorrect
R
- Measuring wires interrupted
- Heatsealing band partially bypassed by conducting part (clamp, opposite heatsealing bar etc.)
- Wire break, heatsealing band break
- Contact to heatsealing band defective
- Heatsealing band installed incorrectly, insulation at heatsealing bar ends missing or incorrectly installed
- Conducting part bypasses heatsealing band completely
- Up to March 2005: DIP switches 1 - 3 configured incorrectly (U
range)
2
- As of April 2005: U
0.4…120VAC
RES-407 Page 37
outside permissible range from
2
Fault area Explanation Possible causes
- Up to March 2005: DIP switches 4 + 5 configured
incorrectly
(I
range)
2
- As of April 2005: I
outside permissible range from
2
j
signal incorrect
I
R
30…500A
Factory settings
Turns through PEX-W2/-W3 current transformer incorrect
- Check number of turns (two or more turns required for currents < 30 A)
- Hardware fault (replace controller)
k
Internal controller fault
- Plug-in jumper for alarm output not connected or incorrectly connected

11 Factory settings

The RESISTRON temperature controller RES-407 is configured in the factory as follows:
DIP switches
F
F
for secondary voltage
and current I
U
2
2
(up to March 2005)
O
2
4
1
O
N
3
U
=6…60VAC
2
=30…100A
I
2
DIP switches: 2 ON
5
1, 3, 4, 5 OFF
These switches are automatically set by the AUTORANGE function on all controllers manufactured as of April 2005.
Rotary coding switch for heatsealing band alloy and temperature range (as of June 2003)
Plug-in jumper for alarm output (as of April 2005)
Automatic phase angle compensation (AUTOCOMP) [X]
Heatsealing band alloy: Alloy A20 Temperature range: 300°C Maximum temperature: 300°C
SWITCH POS.
0 1
0
1
9
2
8
3
7
4
6
5
4 5 8
300°C
9
Rotary coding switch: "0" position
Output closes (HIGH) by alarm
SWITCH POS.
0 1
0
1
9
2
8
3
7
4
6
5
4 5 8
300°C
9
AUTOCOMP: OFF
Page 38 RES-407
Maintenance
Measuring impuse duration
[X]
„Temp. OK“ signal (as of April 2005:
With MOD 46 only
[X]
Temperature diagnosis
[X]
Heatup timeout
[X]
[X] As of April 2005: With ROPEX visualization software only.
Measuring impulse length: 1,7ms
Tolerance band: -10 K…+10K
Temperature diagnosis: OFF
Heatup timeout: OFF

12 Maintenance

The controller requires no special maintenance. Regular inspection and/or tightening of the terminals – including the terminals for the winding connections on
the impulse transformer – is recommended. Dust deposits on the controller can be removed with dry compressed air.
RES-407 Page 39

13 How to order

Contr. RES - 407 / . . . VAC
Scope of supply: Controller includes connector plug-in parts
Modification MOD . . (optional, if required)
Please indicate the article numbers of the controller and the required modifications (optional) in all orders,
How to order
115: Power supply 115 VAC, Art. No. 740701 230: Power supply 230 VAC, Art. No. 740702 400: Power supply 400 VAC, Art. No. 740703
(without current transformer)
e.g.
01: MOD 01, Art. No. 800001 (amplifier for low voltage) 26: MOD 26, Art. No. 800026 (booster connection) 40: MOD 40, Art. No. 800040 ("Temperature OK" signal)
e.g. RES-407/400 VAC + MOD 26
(controller for 400 VAC power supply with booster connection) Art. Nos. 740703 + 800026 must be ordered
Current transformer PEX-W3
Art. No. 885105
Line filter LF- . . 480
06: Continuous current 6 A, 480VAC, Art. No. 885500 35: Continuous current 35 A, 480VAC, Art. No. 885506
Impulse transformer
See ROPEX Application Report for design and ordering information
Communiction interface CI-USB-1
Art. No. 885650
Potentiometer PD- .
3: For 300°C range, Art. No. 881103 5: For 500°C range, Art. No. 881105
Scope of supply: Potentiometer with digital dial
Temp. meter ATR- .
3: 300°C range, Art. No. 882130 5: 500°C range, Art. No. 882150
Page 40 RES-407
How to order
Booster B- . . . 400
For more accessories: ª"Accessories" leaflet
075: Max. pulse load 75A, 400 VAC, Art. No. 885301 100: Max. pulse load 100 A, 400VAC, Art. No. 885304
RES-407 Page 41

14 Index

Index
A
Accessories 6 Actual value output 26 Alarm output 11 Alarm relay 21 Alloy 20 Ambient temperature 11 Analog input 10 Analog output 10 Analog temperature meter 6 Application 4 Application Report 12 AUTOCAL 6 AUTOCOMP 29 Automatic phase angle compensation 29 Automatic zero calibration 6 AUTOTUNE 6 Auxiliary voltage 10
, 23
, 31
, 15, 19
, 22, 27
, 22, 27
, 16
B
Booster 7, 8, 41 Burning in the heatsealing band 21
, 23
C
Circuit breaker 14 CI-USB-1 7 Communication interface 7 Controller configuration 19 Controls 24 Current transformer 7
, 31, 40
, 31, 40
, 15, 40
I
Impulse heatsealing method 4 Impulse transformer 7 Installation 11 Installation procedure 12 Installation regulations 12
, 12
, 14, 40
L
Line filter 7, 14, 15, 40 Line frequency 6 Line voltage 10
, 10
, 40
M
Maintenance 39 Measuring impulse duration 29 Modifications 7 MODs 7 Monitoring current transformer 7
, 17, 18, 40
, 17, 18, 40
O
Overheating of heatsealing band 6
P
PEX-W2/-W3 3 PEX-W3 15 Phase angle compensation 29 Potentiometer 7 Power dissipation 11 Power supply 14 Principle of operation 5
, 40
, 25, 40
D
Degree of protection 11 Diagnostic interface 31 Digital temperature meter 6 Dimensions 12 DIP switches 19
E
Error messages 32 External switching amplifier 7
F
Factory settings 38 Fault areas 37 Fault diagnosis 6
R
Reasons for locked "AUTOCAL" function 27 Reference voltage 11 Replacing the heatsealing band 21 "RESET" signal 28
S
Secondary current I219 Secondary voltage U Set point potentiometer 7 Set point selection 10 Signal „Temperatur erreicht“ 9 "START" signal 22 Startup 19 System diagnostics 31 System monitoring 31
H
HEAT 22, 28 Heatsealing band type 10 Heatup timeout 31 How to order 40
Page 42 RES-407
T
TCR 3, 21 Technical data 10 Temperature coefficient 3
2
, 28
, 23
19
, 25
, 25
, 21
Index
Temperature control 4 Temperature diagnosis 30 Temperature meter 6 Temperature OK signal 11 Temperature range 10 Temperature reached signal 8 Temperature setting 25 Transformer 3 Type of construction 10
, 7, 14, 40
, 26, 40
, 18
, 20
, 18
V
View of the controller 19 Visualization software 31
W
Wiring 12, 14 Wiring diagram 16
RES-407 Page 43
Loading...