Tosot TM24HFDI User Manual

Submittal Data: TM24HFDI 24,000 BTU
Refrigerant Piping Data
Electrical Ratings
Units Specification & Data
System Ratings
All Rights Reserved
TOSOT Comfort 2017
1
Job Name Location Date Purchaser Engineer Submitted To For
Reference
Unit Designation Schedule No.
GENERAL FEATURES
-Quiet Operation -Multi-S peed Fan
-Medium Static Pressure Capability
-Internal Condensate Drain Pump
-Flexible Return Air From Bottom Or Rear
-XK-19 Wired Controllers
-Wireless Remote Controllers
-Sentry Condensate Overflow Protection
-Limited 5 yr. Parts Warranty
Cooling*
Rated Capacity 23,800 BTU/H
Wired Controller XK-19
Heating*
Rated Capacity 27,400 BTU/H
Approval
Construction
Sound Pressure (Hi/Lo)** Condensate Drain Lift (Height) 18-in Cooling 42/34 dbA 457-mm Heating 42/34 dbA
Drain Size (OD) 1.0-in Air Flow (min/max) 26-mm Indoor Fan 324/589 CFM
Ext Static Pressure (max/min) 0.040/0.035 inch wg
Fan Motor Refrigerant Type R410A
Output Power 124 W FLA 0.54 A Gas Pipe Size (OD) 5/8-in
Power Supply Liquid Pipe Size (OD) 3/8-in Normal Operational Voltage Voltage Range MCA Interconnecting Cable Wire Size
208/230 V, 1 Phase, 60 Hz
187 - 253 V Connection Method Flared
1.0 A
14-4 AWG
* Test conditions are based on AHRI 210/240.
**Sound Power ratings are per AHRI 270 and AHRI 350
DIMENSIONAL SPECIFICATIONS
24,000 BTUH MODEL
Model # 24,000 BTUH 230V
Dimensions
A B C D E F G H I J
(mm) 1124 491 1062 1020 1100 615 1182 156 200 635
(inches) 44.3 19.3 41.8 40.2 43.3 24.2 46.5 6.1 7.9 25.0
Weight (Net/Gross) 68/90 lbs
INDOOR FAN PEFORMANCE DATA
WG = inches of water guage
1. Recommended Interconnecting Cable Type Stranded Bare Copper Conductors THHN 600V Unshielded Wire
2. Power wiring cable size must comply with applicable national and local codes.
without notice or without incurring obligations. All rights reserved.
Specifications are subject to change without notice. Manufacturer reserves the right to discontinue or modify specifications or designs
All Rights Reserved
TOSOT Comfort 2017
2
TM24HFDI
Note: Size refrigerant lines based on evaporator port sizes.
Notes:
3. Test conditions are based on AHRI 210/240.
Loading...