Toshiba VN-250SE, VN-350SE, VN-500SE, VN-800SE, VN-1KSA Owner's Manual

Heat Exchange Ventilators
Owner’s Manual
VN-500SE
ENGLISHFRANÇAISDEUTSCHITALIANOESPAÑOLNEDERLANDSPORTUGUÊSΕΛΛΗΝΙΚΗ
Model No.
VN-250SE VN-350SE VN-500SE VN-800SE VN-1KSAE
Installation manual is attached separately.
Thank you very much for having purchased our “Heat Exchange Ventilator”. We hope you read through this instruction manual with care so that you can use the unit correctly. After reading it, please keep it so you can read it whenever necessary.
CONTENTS
Cautions on Safety..................................................................2–5
Features .......................................................................................5
Name of Each Part ......................................................................6
Specific Caution Items................................................................7
Model Installation........................................................................8
Maintenance Method.............................................................9–12
ENGLISHFRANÇAISDEUTSCHITALIANOESPAÑOLNEDERLANDSPORTUGUÊSΕΛΛΗΝΙΚΗ
After-sales Service....................................................................12
Specifications......................................................................13–14
1
Cautions on Safety
Described below are the way we are gaining your attention towhat you are supposed to observe to prevent dangers to the users or other people as well as lossto the property.
The degrees of danger or damagethat is likely to occur due to the wrong use ignoring the indications are categorized for explanation as marked below.
Never Fail to Observe
DANGEROUS WARNING CAUTION
Kinds of the itemsto beobserved are categorizedfor clarification with thefollowing pictorial symbols.(The marks describedbelow are samples.)
This pictorial indication shows “Prohibited”.
This pictorial indication shows “Forced Execution”.
The column with this mark shows“Impending Danger of Death orSerious Injury”.
The column with this mark shows “Conceivable Threat of Death or Serious Injury”.
The columnwith this mark shows “Likelihood of Damage or Loss to Materials only”.
Cautions for Operation
DANGEROUS
Do not use as an air circulators for open-type burners (heaters).
Prohibited
D on't push a finger or a stick into the open-air inlet or the exhaust outlet.
A fanwith a highrpm will injure you.
Prohibited
WARNING
If combustible gas leaks from theunit, ventilate the room by opening windows.
If operationwere to be attemptedinsucha situation, sparking at electrical contact points could cause an explosion.
When gas or oil stoves are used in the home,separate equipment for circulating the air shouldbe used.
When any abnormalcondition (scorching smell or others) is found, stop the operation immediately and keep theexclusive circuit breaker “OFF”.
If you continue the operation without removingthe cause, itcould causean electric shock or a fire.
When the system needs a repair ,
consult your dealer.
Modification of the system is strictly prohibited.
Improper practice of repair could cause a water leakage, an
Disassembly
Prohibited
When the system needs a repair,
consult your dealer.
electric shock or a fire.
Netting or something similar should be provided at the external air intake opening to prevent birds etc. interfering with the unit.
Nests orother foreign objects should be removed. That could lead to a lack of oxygenin the room.
If the supply cord is damaged,it must bereplaced by themanufacturer orits service agent ora similarly qualified person in order to avoid a hazard.
2
Cautions on Safety
Never Fail to Observe
Cautions for Installation
When Heat Exchange Ventilators are relocated, contact your dealer or a professional installer.
Improper practice of installationcould cause adropoftheunit,a
Prohibited
Ask the sales office or the
engineering shop to perform the work.
water leakage, an electric shock or a fire.
Cautions for Maintenance
WARNING
When the system is checked and the powercableundergoesmaintenance, stop the operation, and keep the exclusive circuit breaker "OFF".
ON
OFF
WARNING
The external air intake openingshould be positioned awayfrom the exhaust openings of combustion gases etc.
Theintakeofsuchgasses couldleadtoalackof oxygen in the room.
Cautions for Operation
CAUTION
Combustion apparatus should not be placed allow ing a direct exposure to wind of Heat Exchange Ventilators.
Incomplete combustion could occur on the apparatus.
Prohibited
ENGLISHFRANÇAISDEUTSCHITALIANOESPAÑOLNEDERLANDSPORTUGUÊSΕΛΛΗΝΙΚΗ
The external airintake opening should not be positionedwhere discharged air may directly enter it.
A situation like this will lead to the room being contaminatedand this may pose a health risk.
Do not wash Heat Exchange Ventilators withwater.
It couldcause an electric shock.
Keep from
water
Cleaning should never bedone while the internal fansare running withhigh speed.And whenusinga stepladder, etc., makesure to fixit properly.
It is strictly prohibited to place a containerof combustible gasor liquid near HeatExchange Ventilators or to spray it directly with the gas or liquid.
It couldcause a fire.
Prohibited
Do not use outside the rated voltage.
It couldcause a fireor an electric shock.
Prohibited
Don't blowdirectly againstanimals or plants.
I
Prohibited
Likely tocause bad effect on animals and plants.
Don't puta container of water onHeat Exchange Ventilators.
When water spills, it is likely toenter inside the unit and degrade electric
Prohibited
insulation, possibly resultinginanelectric shock.
Do not handle switches with a wet hand.
It could cause an electric shock.
Don’ttouch
with wet hands
If Heat ExchangeVentilators are not used for a long period of time, keep the exclusive circuitbreaker "OFF" for safety reasons.
ON
OFF
If the power is left on, any build-up of dust could cause a heatgenerationor afire.
3
Cautions on Safety
Cautions for Operation
Never Fail to Observe
CAUTION
The system should never be used for any other purposes than intendedsuch as for preservation of foods, floraand fauna, precision devices or work of art.
It could cause deterioration of foods or other problems.
Cautions for Installation
Install at a stable place of sufficient strength.
Please note that there mightbesomeplacesnot strong enough to install due thestructure of building.
Do not installin locationswhere harmful orcorrosive gassesmay be present (i.e. acidic,alkali, organic solvent, paint gasses etc. from machinery or factories)
Installationin such a location could cause a gas-poisoning and a
Prohibited
fire.
Provide an exclusive circuit breaker that can completely break contacts on all the polesby morethan3mm through direct connection to the power terminals. Depending upon the environmentfor installation,it becomes necessary to install an earth leakage breaker.
Askthesalesofficeorthe
engineering shop to perform the work.
D o not installin locations where oily smoke orsoot may bepresent.
Prohibited
Don't incline Heat Exchange Ventilators when taking them out.
Otherwise, water remaining inside is likelyto drop and wet the furnitureor other property.
Prohibited
Ask the salesoffice or the engineering shop to perform
the work.
CAUTION
Never fail toinstall the unit inside the heat insulting walls or, inother words, in the space insulated from the open air.
Unless the earth leakage breaker is installed, it could causeanelectricshock.
There isa possibility that oil will adhere to the filter, heat exchange element etc. and make operation impossible.
If you install it outside or in the space equivalent to the open-airconditions, dew is condensed insidethe body in the winterseason.
Do not install in locations with high humidity, such as close to bathroom etc.
Prohibited
External Air
Installation in such a location could cause a breakdown.
Insulated Walls
Unit Body
Duct
4
Cautions on Safety
Never Fail to Observe
Cautions for Maintenance
CAUTION
Don't use benzeneor metal brush when cleaning thefilter and heat exchange element.
Gasoline
Thinner
Prohibited
Metal brush
Otherwise, the unitwill getunfit foruse.
Benzene
The filter should be cleaned regularly. Dust or dirt building-up onit
canlead to alackof oxygen in the room.
Use gloves whencleaning the filter or heat exchange element.
Doing sowill reduce any possibility of injury.
Features
Main Features
1. Energy saving ventilation Thanks toefficient recovery of thermal energy lost during Ventilation (load incurred by outside air), you can save anair­conditioning fee.
2. Facility saving Thanks to a drastic reduction of load incurred by outside air, you can make air-conditioners more compact in parallel with the recovery ofthermal energy.
3. Humidity adjusting effect In a cooling mode, a highly humid open-air is brought nearto a dehumidified room atmosphere and then supplied. In a warming mode, aroom humidity is transferred tothe dried outside air and then supplied.
4. Comfortable and consistentventilation Ventilation isavailable with least possible fluctuation of a room temperature. Since exhaust and air intake areperformed simultaneously, a stable ventilationis possible even in a highly airtight room.
5. Sound shield effect The ducts of the unit and the heat exchange element are characteristic of sound shield effect. Thus, it prevents an outside noise from coming in the unit and also sound inside the unitfrom going out, so that the office and store environment canbe preserved.
ENGLISHFRANÇAISDEUTSCHITALIANOESPAÑOLNEDERLANDSPORTUGUÊSΕΛΛΗΝΙΚΗ
5
Name of Each Part
B
OA (Outside Air)
EA
(Exhaust
Air)
Heat Exchange Element
B
OA (Outside Air)
[Model No.] VN-250SE
VN-350SE VN-500SE
Inspection Cover
A
Filter
Electrical Equipment Box
SA
(Supply Air)
RA (Room Air)
[Model No.] VN-800SE
VN-1KSAE
Inspection Cover
A
Electrical Equipment Box
C
Model No. A B C VN-250SE 882 599 270 VN-350SE 882 804 270 VN-500SE 962 904 270 VN-800SE 1322 884 388
VN-1KSAE 1322 1134 388
Note: Dimensions of Ceiling Suspension
Fixtures arenot included.
RA (Room Air)
SA (Supply Air)
Unit: mm
EA
(Exhaust
Air)
Heat Exchange Element
Filter
SA
(Supply Air)
RA (Room Air)
C
EA (Exhaust Air)
OA (Outside Air)
Maintenance Space
450
Inspection Opening
6
Specific Caution Items
Checking Location of Installation
This Energy Recovery Ventilatorshave been des igned especially for use in offices, conference rooms,etc. Please check to ensure that neither themain unit nor the inlet-outlet grill are installed in any of the following locations.
Locationsexposedto high temperatures or direct flame.
Avoid installing the Heat Exchange Ventilators or theinlet-outlet grillin locationswhich reach temperatures of40°C or above. Usage underhigh temperature conditions may cause distortionof the filter or Heat Exchange Element or motor burn-out.
40°C
Make sure that access is provided so thatfilter and Heat Exchange Element maintenanceand periodic spot checks of the unit canbe easily carried out.(Refer to the Model Installation for its space)
If thereare any problems concerning the location or installationof the unit, please consult either storefrom which it was purchased or the agent who installed it.
Locations with high humidity.
Do notinstall in highhumidity locationssuch as bathrooms. Doing so may cause a breakdown of the unit or an electric shock.
Do not install the unit in locations such asmachinery or chemical plants where it will be exposed to noxious gases containing acids, alkali, organic solvents, paint fumes, etc.,to gases containing corrosive ingredients, or where dust or oil mist will be produced.
Locations with large amountsof oily smoke, such as food preparation areas.
The unit will become inoperable if the filter or Heat Exchange Element become clogged with oil.
Interior Intake Vent
Oily
smoke
ENGLISHFRANÇAISDEUTSCHITALIANOESPAÑOLNEDERLANDSPORTUGUÊSΕΛΛΗΝΙΚΗ
When Using
Always besure to usea filter. Failure to do so may cause dustand dirt to build upon the heat exchangeelement, lowering its efficiency and rendering it inoperable.
Operate the switch withcertainty. In particular, suddenly turning the switch on and off will not only causeimproper operation of the unit, but will also obversely affect the relay inside the switch, and maydamage it.
7
Model Installation
Supply Air Duct
Ceiling Suspension Bolt
Exhaust Air Duct
RA
(Room Air)
Inside Supply Opening (Supply/Exhaust Air Grill)
Note thatwhen installing a unit body upside down, itsprinted indication is in a reversed position.
Pipe Hood
OA
(Outside Air)
Outside Intake Duct
(Exhaust
Heat Insulation Material
Pipe Hood
Room Intake Duct
EA
Air)
Room Intake Opening (Supply/Exhaust Air Grill)
Method of Use
Use the operation switch to operate the unit.
0 (OFF)...............the unit stop.
1 (ON)................the unitoperates.
Use the Air Flow switch to set to the desiredair flow.
High....................Turns to high air volume.
Low.....................Turns to low air volume.
Use the Function Select switch to set the ventilation mode.
Heat ExchangeVentilationMode......... Open air is thermal-exchange withroom air to bring it closer to a room temperature and
humidity, before taking it in the room.
Normal Ventilation Mode......................To intake open air as it is.
SA
(Supply Air)
Maintenance Method
In order to prevent thereduced effectiveness of your Heat ExchangeVentilators, be sure toclean dirtand dust from the filter andHeat Exchange Element at regular intervals.
Caution
Be sure to turn the power off, andto keep the exclusive breaker off before carrying out maintenance activities.
Switch
Turn off
Do not use the following itemsfor cleaning. Avoid usingheat to dry the filter, as it may
Gasoline
Thinner
Benzene
Metal brush
Do notimmerse the filter or otherresin components in water 60°Corabove.
W
a
t
e
r
6
0
°
a
C
b
o
o
r
v
e
cause changes in shape or quality.
Filter
Never use water on the motor, the switch, or the Heat Exchange Element.
Motor
Switch
Heat
Heat
exchange element
Exchange Element
Always be sure to use a filter. Failure to do so may cause dustand dirt to build up on the heatexchange element, lowering its efficiency and rendering it inoperable.
8
Maintenance Method
Model No. VN-250SE/VN-350SE/VN-500SE
Stop the operation and keep the exclusive breaker "OFF".
Cleaning the filter (When required)
1) Enterthe ceiling from the InspectionOpening for the Heat
Exchange Ventilators, and remove the screw on the inspection cover.
2) Holding the Inspection Cover, turn two pieces of knob for 90° and
remove thecover.
3) There is a filterbelow the Heat Exchange Element at two places,
respectively. Pull it toward you.
4) Eitherlightly strike the removed filter with your hand or vacuumit
with a vacuum cleaner to remove the dirt. If itis very dirty, swish it back andforth in asolution of lukewarm water and dish-washing (neutral) detergent.
5) Install thefilter after thoroughly allowing it to dry naturally.
Caution
Avoid using heat todry the filter, as this may cause changesin the shape or quality of the filter.
Whenever the filterwas damaged, order the sales shopor the engineering office. (Separately sold)
Cleaning the Heat Exchange Element (If you find it too much stained, clean it.)
1) Remove the filters.
2) Removethe two HeatExchange Elements fromthe unit. (ModelNo.
VN-250SE has one Heat Exchange Element.)
Knob Position
When installed (Closed)
To remove (Open)
ENGLISHFRANÇAISDEUTSCHITALIANOESPAÑOLNEDERLANDSPORTUGUÊSΕΛΛΗΝΙΚΗ
Hook
Inspection Cover
Hook
Inspection Cover
Caution
The weight of the Heat Exchange Element is as shown in the table below. Hold itfirmly to ensure thatyou do not drop it.
Model No. Weight (kg /piece) Pieces tobe used VN-250SE 4.5 1 VN-350SE 3.4 2 VN-500SE 3.7 2
Filter
Heat Exchange Element
9
Maintenance Method (continued)
3) Usea vacuum cleaner to remove dust and dirtfrom the element's surface.
Caution
Use a brush attachment on the vacuum cleaner nozzle. Clean witha light, brushing action. Avoid using a hard nozzle as it maydisfigure theheat exchange foils.
Never use water to cleanthe Heat Exc hange Element.
Whenever the HeatExchange Element was damaged, order the sales
shop or the engineering office. (Separately sold)
4) When cleaning is completed, return the Heat Exchange Element and filter to their former positions, and close the Inspection cover and tighten the screw.
Caution
Make absolutely sure to install the filter with an indication of “”turned toward the Heat Exchange Element side.
Failure to do so will lead to clogging of the heat exchange foils and reduced performance.
Insert the heat exchange element right side up, with thelabel marked facing toward you.
Nozzle
Mark
10
Model No. VN-800SE/VN-1KSAE
Stop the operation and keep the exclusive breaker "OFF".
Cleaning the filter (When required)
1) Enterthe ceiling from the InspectionOpening for the Heat Exchange Ventilators, and remove the screw on the inspection cover.
2) Holding the Inspection Cover, turntwo pieces of knob for 90° and remove thecover.
3) There is a filterat two places, respectively. Pull it toward you.
4) Eitherlightly strike theremoved filterwith yourhand or vacuum it with a vacuumcleaner toremove the dirt.If itis verydirty, swish it back andforth in asolution of lukewarm water and dish-washing (neutral) detergent.
5) Install thefilter afterthoroughly allowing it to dry naturally. (Install them to fit well withthe grooved rail)
Caution
Avoid using heat to dry the filter, as this may cause changes in the shape or quality of the filter.
Whenever the filterwas damaged, order the sales shopor the engineering office. (Separately sold)
Cleaning theHeat Exchange Element.(If you find ittoo much stained, clean it.)
1) Remove the four Heat Exchange Elements from the unit. (Model
No. VN-800SE has three Heat Exchange Elements.)
Knob Position
When installed (Closed)
To remove
(Open)
Hook
Inspection Cover
ENGLISHFRANÇAISDEUTSCHITALIANOESPAÑOLNEDERLANDSPORTUGUÊSΕΛΛΗΝΙΚΗ
Hook
Inspection Cover
Filter
Caution
The weightof the HeatExchange Element isas shownin the table below. Hold itfirmly to ensure thatyou do not drop it.
Model No. Weight (kg /piece) Pieces to be used VN-800SE 4.0 3
VN-1KSAE 4.0 4
Grooved Rail
Heat Exchange Element
11
Maintenance Method (continued)
2) Usea vacuum cleaner to remove dust and dirtfrom the element's surface.
Caution
Use a brush attachment on the vacuum cleaner nozzle. Clean witha light, brushing action. Avoid using a hardnozzle as it may disfigure the heat exchange foils.
Never use water to cleanthe Heat Exc hange Element.
Whenever the HeatExchange Element was damaged, order the sales
shop or the engineering office. (Separately sold)
3) When cleaning is completed, return the Heat Exchange Element and filter to their former positions, and close the Inspection cover and tighten the screw.
Caution
Make absolutely sure to install the filter with an indication of “”turned toward the Heat Exchange Element side.
Failure to do so will lead to clogging of the heat exchange foils and reduced performance.
Nozzle
Please insert so that the stamp “”to be toward you.
Stamp
After-sales Service
Request for Spot Checks To ensure safe,correct usage, we suggest that you considera maintenance contract. For details, inquire at the store where you bought your unit,or at the agent which installed it.
If YouThink It’sBroken Examine the unit as shownin thetable below,and if you find any irregularities,shut it off immediately andcontact the store where you boughtyour unit or the agentwho installed it to requestservicing (orconsultation).
Symptom Where to look
No activity, even when the switch is on.
No air comes out.
Is the fuseblown or the breaker tripped?
Is the power out?
Check whetheror not there is dust on the filters andthe HeatExchange Element.
(Clean itaccording to the Maintenance Method mentioned onthe Pages 9 to 12.)
12
Specifications
3
3
/h)
/h)
Model No.
250/250 250/250 170/135 250/250 250/250 170/135
75/75 75/75 77/78 ———
Model No.
350/350 350/350 280/240 350/350 350/350 280/240
75/75 75/75 77/79 ———
Item Power Source 220– 240V~50Hz/220V~60Hz Ventilation Mode Heat Exchange Ventilation Normal Ventilation Notch (Extra high) High Low (Extra high) High Low Input (W) 104-119/128 99-114/118 79-90/78 103-119/128 98-114/118 79-90/77
Air Volume (m External Static Pressure (Pa) 90/125 80/100 37/30 90/125 80/100 37/30 Noise (dB) 27-28/28 26-27/26 21-22/21 27-28/28 26.5-27.5/26.5 21.5-22.5/21.5 Temperat ure Exchange
Efficiency (%) Dimensions (mm) Width 882 x Depth599 x Height 270 Weight (kg) 29
Item Power Source 220– 240V~50Hz/220V~60Hz Ventilation Mode Heat Exchange Ventilation Normal Ventilation Notch (Extra high) High Low (Extra high) High Low Input (W) 137-154/178 124-137/149 117-128/132 133-151/176 119-132/145 113-125/131
Air Volume (m External Static Pressure (Pa) 95/155 65/90 42/43 95/155 65/90 42/43 Noise (dB) 31-32/33 29-30/30 25-26/22 31-32/33 30-31/30 26-27/23 Temperat ure Exchange
Efficiency (%) Dimensions (mm) Width 882 x Depth804 x Height 270 Weight (kg) 37
VN-250SE
VN-350SE
ENGLISHFRANÇAISDEUTSCHITALIANOESPAÑOLNEDERLANDSPORTUGUÊSΕΛΛΗΝΙΚΗ
3
/h)
Model No.
500/500 500/500 370/310 500/500 500/500 370/310
75/75 75/75 77/79 ———
Item Power Source 220– 240V~50Hz/220V~60Hz Ventilation Mode Heat Exchange Ventilation Normal Ventilation Notch (Extra high) High Low (Extra high) High Low Input (W) 188-214/244 169-188/202 151-166/162 184-210/243 161-182/ 196 145-164/161
Air Volume (m External Static Pressure (Pa) 105/165 70/85 38/33 105/165 70/85 38/33 Noise (dB) 33-34/35 31-32/31 25-26/23 34-35/36 32-33/33 26.5-27.5/24 Temperat ure Exchange
Efficiency (%) Dimensions (mm) Width 962 x Depth904 x Height 270 Weight (kg) 43
VN-500SE
13
3
/h)
Model No.
800/800 800/800 650/575 800/800 800/800 650/575
75/75 75/75 76/77 ———
Item Power Source 220– 240V~50Hz/220V~60Hz Ventilation Mode Heat Exchange Ventilation Normal Ventilation Notch (Extra high) High Low (Extra high) High Low Input (W) 316-347/424 309-329/391 302-327/347 309-337/417 300-325/ 387 297-316/346
Air Volume (m External Static Pressure (Pa) 140/190 110/100 70/50 140/190 110/100 70/50 Noise (dB) 38-39/39 36.5-37.5/36 32-34/31 38.5-39.5/39.5 37-38/37 33-35/31 Temperat ure Exchange
Efficiency (%) Dimensions (mm) Width 1322 x Depth 884x Height388 Weight (kg) 71
VN-800SE
3
/h)
Model No.
1000 1000 810 1000 1000 1000
75 75 76 ———
Item Power Source 220– 240V~50Hz Ventilation Mode Heat Exchange Ventilation Normal Ventilation Notch (Extra high) High Low (Extra high) High Low Input (W) 399-445 360-399 332-367 392-438 358-392 329-362
Air Volume (m External Static Pressure (Pa) 90 55 35 90 55 35 Noise (dB) 37.5-38.5 36-37 31-33 38-39 36.5-37.5 31.5-33.5 Temperat ure Exchange
Efficiency (%) Dimensions (mm) Width 1322 x Depth 1134 x Height 388 Weight (kg) 83
VN-1KSAE
(Note) The ratings mentioned above shows the values underthe external static pressure.
(Only thenoise level shows the value underthe external static pressure: 0Pa) Noise Levelshall be measured 1.5 mbelow the center of the unit. (It shall be measured at the acoustic room.)
14
DECLARATION OF CONFORMITY
We, TOSHIBA CARRIER CORPORATION, 336 Tadewara, Fuji-shi, Shizuoka-ken, 416-8521,Japan, declare under oursole responsibility that the product, HeatExchange Ventilator, to which thisdeclaration relates is in conformity with the provisions of Council Directive 89/336/EEC Electromagnetic Compatibility and 73/23/EEC Low Voltage Directive.
TJ0290 PrintedinJapan
Loading...