TS MATCHING
CABINET SERIES
The TS cabinets are a line up and match series of pre packaged battery cabinets built specifically for Toshiba. They are
designed to hold the Power Battery PRC and TC series of VRLA
batteries. The TS4 has been designed to match the Toshiba
G8000 series in dimension, functionality and style. All of the
TS cabinets are pre-wired and 100% tested to meet Toshiba
and customer requirements upon delivery.
• Pre-configured to bolt together
• 360 VDC Configuration
• Circut breaker with auxiliary contacts and 24 VDC shunt
trip
• UL \ CUL Listed
• Designed for multi-cabinet daisy-chain connections
• UBC Seismic Zone 4 Certified
• Vented cabinet meets Nema 1 standards
• Integrated thermal management
• Front and rear removable panels for battery access
• Adjustable, insulated battery rails
• Matching permalux powder coat paint for durability
• Side, top and bottom knockouts for cable access
• Ground stud
• Floor mounting holes for anchoring
• Cable management restraints
• Battery restraints meet transportation
& seismic requirements
• Non Spillable - Non hazardous design
• Forklift access from all sides
• TC batteries meet UL 1778 requirements
T S 4
Toshiba G8000 Series
100-300 KVA
Introduction
Features
Dimensions and weights
Systems dimensions Weight
W D H Empty
36” 29.5” 78.7” 525 lbs
914 mm 749.3 mm 1999 mm 238 kg
• Floor loading plate for weight distribution
• Wall mounted junction box for multiple string termination
• Seismic Anchoring kit
Options
Maximum Quantity of PRC/TC Batteries per Cabinet
Cabinet
Model
TS4 30 30 30 30 30 30 30 30
PRC/TC 1225 PRC/TC 1235L PRC/TC 1255S PRC/TC 1265S PRC/TC 1290S PRC/TC 12100S PRC/TC 12120S PRC/TC12150C
TS MATCHING
CABINET SERIES
T S 4
Toshiba G8000 Series
100-300 KVA
FRONT VIEWSIDE VIEWBOTTOM VIEW
System Sizing Matrix
# OF TOSHIBA OVERALL DIMENSIONS WEIGHT
STRINGS SYSTEM MODEL (INCHES / MM) (LBS / KG)
1 G8-TSXXX5-HXXX 5 – – – 78.7 / 1999 29.5 / 749.3 36 / 914 2375 / 1080
2 2G8-TSXXX19-HXXX 19 10 – – 78.7 / 1999 29.5 / 749.3 2 x (36 / 914) 4750 / 2159
3 3G8-TSXXX47-HXXX 47 27 15 9 78.7 / 1999 29.5 / 749.3 3 x (36 / 914) 8788 / 3995
4 4G8-TSXXX69-HXXX 69 41 24 16 78.7 / 1999 29.5 / 749.3 4 x (36 / 914) 11684 / 5311
5 5G8-TSXXX133-HXXX 133 70 48 32 78.7 / 1999 29.5 / 749.3 5 x (36 / 914) 17475 / 7943
NUMBER Net*
G8-TSXXX6-HXXX 6 – – – 78.7 / 1999 29.5 / 749.3 36 / 914 2624 / 1193
G8-TSXXX9-HXXX 9 – – – 78.7 / 1999 29.5 / 749.3 36 / 914 2921 / 1328
G8-TSXXX16-HXXX 16 8 – – 78.7 / 1999 29.5 / 749.3 36 / 914 3495 / 1589
2G8-TSXXX22-HXXX 22 12 5 – 78.7 / 1999 29.5 / 749.3 2 x (36 / 914) 5248 / 2385
2G8-TSXXX27-HXXX 27 15 7 – 78.7 / 1999 29.5 / 749.3 2 x (36 / 914) 5842 / 2655
2G8-TSXXX41-HXXX 41 24 13 8 78.7 / 1999 29.5 / 749.3 2 x (36 / 914) 6990 / 3177
3G8-TSXXX65-HXXX 65 41 24 16 78.7 / 1999 29.5 / 749.3 3 x (36 / 914) 10485 / 4766
4G8-TSXXX89-HXXX 89 60 35 24 78.7 / 1999 29.5 / 749.3 4 x (36 / 914) 13980 / 6355
100 150 225 300
86.020 129.030 193.550 258.060
UPS KVA RATING
BATTERY KWB
RUN TIMES
Height Depth Width
* For shipping purposes, add 3% to weight.
Breaker Per String Sizing
# OF STRING
SOLUTION
1 H300 H600 – –
2 (2) H150 (2) H225 (2) H400 (2) H600
3 (3) H100 (3) H150 (3) H225 (3) H300
4 (4) H100 (4) H125 (4) H175 (4) H225
5 (5) H60 (5) H100 (5) H150 (5) H175
100KVA 150KVA 225KVA 300KVA
Notes:
1) All systems are 360 volts nominal. Batteries are sized to an end voltage of 1.67 VPC up to 90 minutes and to 1.75 above 90 minutes at 25°C.
2) All KWB ratings are calculated at 0.8 power factor. The inverter efficiency rating is 93%.
3) Toshiba Battery System Model Number example: a 100 KVA two string cabinet system with a breaker, auxiliary contacts and 24 volt shunt trip for a
runtime of 19 minutes : 2G8-TS10019-H150.
4) The TS series of cabinets are designed for multiple cabinet daisy-chain connections.