The instructions contained in this manual are not intended to cover all details or variations in equipment
types nor may it provide for every possible contingency concerning the installation, operations, or
maintenance of this equipment. Should additional information be required, contact your Toshiba
Customer Support Center.
The contents of this manual shall not become a part of or modify any prior or existing agreement,
commitment, or relationship. The sales contract contains the entire obligation of Toshiba Inte rnational
Corporation. The warranty contained in the contract between the parties is the sole warranty of Toshiba
International Corporation and any statements contained herein do not create new warrantie s or modify
the existing warranty.
Any electrical or mechanical modifications to this equipment without the prior written consent of
Toshiba International Corporation may void all warranties or other safety certifications.
Unauthorized modifications may also result in safety hazard or equipment damage.
Misuse of this equipment could result in injury and equipment damage. In no event will Toshiba
International Corporation be responsible or liable for direct, indirect, special, or consequential
damage or injury that may result from the misuse of this equipment.
de
T
Series D
olidState Soft Starters 1
1250A
About This Manual
Every effort has been made to provide accurate and concise information to you, our customer.
At Toshiba International Corporation we are continuously striving for better ways to meet the constantly
changing needs of our customers. E-mail your comments, questions, or concerns about this
publication to Toshiba.
This manual provides information on how to safely install, operate, maintain, and dispose of your TE
solid state starter. The information provided in this manual is applicable to the TE starter only.
This manual provides information on the various features and functions of this powerful device,
including:
• Installation
• Operation
• Mechanical and electrical specifications.
Included is a section on general safety instructions that describe the warning labels and symbols that
are used on the device and throughout the manual. Read the manual completely before installing,
operating, performing maintenance, or disposing of this equipment.
T
Series D
olidState Soft Starters 1
1250A
This manual and the accompanying drawings should be considered a permanent part of the equipment
and should be readily available for reference and review. Dimensions shown in the manual are in
imperial units and/or the metric equivalent. Connection drawings within this document convey the typical
topology of the TE starter.
Because of our commitment to continuous improvement, Toshiba International Corporation reserves the
right, without prior notice, to update information, make product changes, or to discontinue any product or
service identified in this publication.
Toshiba International Corporation (TIC) shall not be liable for direct, indirect, special, or
consequential damages resulting from the use of the information contained within this manual.
This manual is copyrighted. No part of this manual may be photocopied or reproduced in any form
without the prior written consent of Toshiba International Corporation.
TOSHIBA® is a registered trademark of Toshiba Corporation. All other product or trade references
appearing in this manual are registered trademarks of their respective owners.
Toshiba International Corporation’s Customer Support Center can be contacted to obtain hel p in
resolving any system problem that you may experience or to provide application information.
The Support Center is open from 8 a.m. to 5 p.m. (CST), Monday through Friday. The Center’s toll free
number is US (800) 231-1412/Fax (713) 937-9349 CAN (800) 872-2192 MEX 01 (800) 527-1204.
For after-hours support follow the directions of the outgoing message when calling.
You may also contact Toshiba International Corporation by writing to:
Toshiba International Corporation
13131 West Little York Road
Houston, Texas 77041-9990
olidState Soft Starters 1
1250A
For further information on Toshiba International Corporation’s products and services, please visit
our website.
TOSHIBA INTERNATIONAL CORPORATION
TE Solid State Starter
Complete the following information and retain for your records.
Model Number: _____________________________________________________________________
Serial Number: _______________________________________ ______________________________
Project Number (if applicable):_________________________________________________________
Date of Installation: _________________________________________________________________
Inspected By: ________________________________________ _____________________________
Name of Application: ________________________________________________________________
DO NOT attempt to install, operate, maintain, or dispose of this equipment until you have read and
understood all of the product safety information and directions that are contained in this manual.
Safety Alert Symbol
The Safety Alert Symbol is comprised of an equilateral trian gle enclosing an exclamation mark.
This indicates that a potential personal injury hazard exists.
Signal Words
olidStateSoft Starters 1
1250A
Listed below are the signal words that are used throughout this manual followed by their
descriptions and associated symbols. When the words DANGER, WARNING, and CAUTION are
used in this manual, they will be followed by important safety information that must be carefully
followed.
The word DANGER preceded by the safety alert symbol indicates that an imminently hazardous
situation exists that, if not avoided or if instructions are not followed precisely, will result in serious
injury to personnel or loss of life.
DANGER
The word WARNING preceded by the safety alert symbol indicates that a potentially hazardous
situation exists that, if not avoided or if instructions are not followed precisely, could result in serious
injury to personnel or loss of life.
WARNING
The word CAUTION proceeded by the safety alert symbol indicates that a potentially hazardous
situation exists that, if not avoided or if instructions are not followed precisely, may result in minor or
moderate injury.
DO NOT attempt to install, operate, perform maintenance, or dispose of this equipment, until you
have read and understood all of the product safety labels, and user directions, that are contained in
this manual.
Warning labels that are attached to the equipment will include the exclamation mark within a
triangle.
DO NOT remove or cover any of these labels. If the labels are damaged or if additional labels are
required, contact the Toshiba Customer Support Center.
Labels attached to the equipment are there to provide useful information or to indicate an imminently
hazardous situation that may result in serious injury, severe property and equipment damage, or
loss of life if safe procedures or methods are not followed as outlined in this manual.
olidStateSoft Starters 1
1250A
Qualified Personnel
Installation, operation, and maintenance shall be performed by Qualified Personnel ONLY. A
Qualified Person is one that has the skills and knowledge relating to the construction, installation,
operation, and maintenance of the electrical equipment and has received safety training on the
hazards involved (Refer to the latest edition of NFPA 70E for additional safety requirements).
Qualified Personnel shall:
• Have carefully read the entire manual.
• Be familiar with the construction and function of the starter, the equipment being driven, and the
hazards involved.
• Be able to recognize and properly address hazards associated with the application of motor-driven
equipment.
• Be trained and authorized to safely energize, de-energize, ground, lock-out/tag-out circuits and
equipment, and clear faults in accordance with established safety practices.
• Be trained in the proper care and use of protective equipment such as safety shoes, rubber gloves,
hard hats, safety glasses, face shields, flash clothing, etc., in accordance with established safety
practices.
For further information on workplace safety, visit www.osha.gov.
• Upon receipt of the equipment, inspect the packaging and equipment for shipping damage.
• Carefully unpack the equipment and check for parts that may have been damaged during shipping,
missing parts, or concealed damage. If any discrepancies are discovered, it should be noted with
the carrier prior to accepting the shipment, if possible. File a claim with the carrier if necessa ry and
immediately notify your Toshiba Customer Support Center.
• DO NOT install the starter if it is damaged or if it is missing any component(s).
• Ensure that the rated capacity and the model number specified on the nameplate conform to the
order specifications.
• Modification of this equipment is dangerous and is to be performed by factory trained personnel
ONLY. When modifications are required contact your Toshiba Customer Support Center.
• Inspections may be required after moving the equipment.
deTESeries D
olidStateSoft Starters 1
1250A
• Contact your Toshiba Customer Support Center to report discrepancies or for assistance if
required.
Handling and Storage
• Use proper lifting techniques when moving the breaker; including properly sizing up the load,
getting assistance, and using a forklift if required.
• Store in a well-ventilated location and preferably in the original packaging if the equipment will not
be used upon receipt.
• Store in a cool, clean, and dry location. Avoid storage locations with extreme temperatures, rapid
temperature changes, high humidity, moisture, dust, corrosive gases, or metal particles.
• The storage temperature range of the breaker is 23° to 104° F (-5° to 40° C).
• DO NOT store the unit in places that are exposed to outside weather conditions (e.g. wind, rain,
snow).
• Store in an upright position.
Disposal
Never dispose of electrical components via incineration. Contact your state environmental agency for detail s
on disposal of electrical components and packaging in your area.
General Description, Sizes and Ratings ......................................................................................................... 7
Dimensions and Weights ................................................................................................................................ 8
Receiving, Unpacking and Inspection ............................................................................................................. 9
SERVICE WA RNING! .................................................................................................................................... 9
Mounting, Clearances and Cleaning ............................................................................................................... 9
Power Connections ...................................................................................................................................... 11
Power Factor Correction Capacitors ............................................................................................................ 11
Power Terminals .......................................................................................................................................... 12
Control Connections ..................................................................................................................................... 13
AC Control Power Supply Connection ......................................................................................................... 13
Control Fusing .............................................................................................................................................. 14
Three-Wire Control Connection .................................................................................................................... 14
Seal In Contact ............................................................................................................................................. 14
Two Wire Control: Relay / PLC Connection ................................................................................................. 14
Fault Signal .................................................................................................................................................. 15
Dual Ramp and Jog Features ...................................................................................................................... 16
Jog / Remote Command .............................................................................................................................. 16
Bypass Contactor Control ............................................................................................................................ 17
Chapter 3: Sequence of Operation ........................................................................................................... 19
Starting and Stopping ................................................................................................................................... 19
Digital Interface ............................................................................................................................................ 20
Display and Program Modes ........................................................................................................................ 21
Program Function List .................................................................................................................................. 24
Your new TE Series Soft Starter is factory preset for a wide variety of applications and often can be used
with minimal adjustment.
Try these initial factory presets first and then adjust or enable the more advanced features to meet
your specific starting needs.
Three Step Process:
1. Connect L1, L2, L3 to power lines and T1, T2, T3 to motor (see page 11)
2. Connect control wires and control po wer ( see pages 13-17)
3. Program motor FLA (see page 20).
Your TE unit is ready to start!
Start-up Check List
MOT
OR FLA
(F001)
must be
programmed
unit to
operate!
Supply voltage matches the rated supply voltage of the unit.
Horsepower and current ratings of the motor and unit match or the unit is higher
rating.
Initial ramp time and torque adjustments have been checked.
Power lines are attached to the unit input terminals marked L1, L2 and L3 (R, S and
T).
Motor leads are connected to the lower terminals marked T1, T2 , and T3 (U, V and
W).
Appropriate control power is applied
Control connections have been made.
“Power on” light located on the front of the unit turns on when control power is
applied.
Four seven-segment LED readouts are visible.
The motor’s FLA has been programmed in function F001.
The thermal overload is properly set (use F003 and F004 to set OL Class).
The motor area and equipment are clear of people and parts before start-up.
This list provides only the bare minimum settings necessary to make your motor
run, and provides basic levels of motor protection. Safety precautions, listed
further on in this manual, must always be followed. Ra mp setting adj ustments and
additional protection features may be necessary. Please read further for additional
details.
The TE Series is a digitally programmable solid state reduced voltage soft starter using a six SCR design. It
features a voltage/current ramp for smooth load acceleration. The SCRs are sized to withstand starting
currents of 500% for 60 seconds for applications typical to NEMA / UL Class 30 overload trip curve. The TE Series features smooth stepless ramp control, which reduces motor inrush current and excessive wear on
the mechanical drive train components. The TE Series includes a programmable keypad for setting
operating parameters for the ideal starting cycle and protection features, plus easy to understand
diagnostic LEDs. Starting torque, ramp time, current limit, dual ramp, and Decel control are standard
features on the TE Serie s. The TE Series includes solid state electronic overload protection in addition to
numerous other protective features. It requires 120VAC (220VAC optional) control power and uses dry
contact inputs for
also included.
Sizes and Ratings
Model
Number
TE-18-BP
TE-28-BP
TE-39-BP
TE-48-BP
TE-62-BP
TE-78-BP
TE-92-BP
TE-112-BP
TE-150-BP
TE-160-BP
TE-210-BP
TE-275-BP
TE-361-BP
TE-450-BP
TE-550-BP
TE-600-BP
TE-862-BP
TE-900-BP
TE-1000-BP
TE-1250-BP
Table 1: TE Series selection
Start / Stop control. Programmable auxiliary contacts and provisions for interlocking are
The Toshiba TE Series starters are current rated controllers. Max.
Amp ratings are for continuous duty and must not be exceeded.
Always check the motor nameplate FLA and Service Factor (if used)
to ensure proper sizing. Each size has an adjustable range of current
from 50% to 100% of the Max Amp rating. Table 1 to the left shows
the Current Ratings available.
Upon receipt of the product, you should immediately do the following:
Carefully unpack the unit from the shipping carton and inspect it for shipping damage (if damaged,
notify the freight carrier and file a claim within 15 days of receipt).
Verify that the model number on the unit matches your purchase order.
Confirm that the ratings sticker on the unit matches or is greater than the motor’s nameplate Full Load
Current
(FLC or FLA) rating and Service Factor (if used). Choosing a Location
Proper location of the TE Series is necessary to achieve specified performance and normal operation lifetime.
The TE Series should always be installed in an area where the following conditions exi st:
Ambient operating temperature:
Panel (open chassis) unit: 0 to 50°C (32 to 122°F)
Enclosed unit: 0 to 40°C (32 to 104°F)
TE is to have protectio n from rain, moisture and dust.
Enclosed units should not be exposed to direct sun.
Humidity: 5 to 95% non-condensing
Free from metallic particles, conductive d ust and corrosive gas
Free from excessive vibration (below 0.5G)
Open panel units must be mounted in the approp riate ty pe of enclosure. Enclosure size and type must
be suitable to dissipate heat generated by the soft starter and any other components mounted inside with it.
Units with –BP Bypass Contactors produce less heat than units without. Throughout all sizes, maximum
heat dissipation of the TE…-BP Series electronics, contactor coils and fans is less than 50W.
NOTE: This does not include heat generated by cables, lugs or bus bars.
Initial Unit Inspection
Make a complete visual check of the unit for damage that may have occurred during shipping and handling.
Do not attempt to continue installation or start up the unit if it is damaged.
Check for loose mechanical assemblies or broken wires w hich may have occurred during transportation
or handling. Loose electrical connections will increase resistance and cause the unit to function
improperly.
Mounting, Clearances and Cleaning
When drilling or punching holes in the enclosure, cover the electrical assembly to prevent metal filings
from becoming lodged in areas which can cause clearance reduction or actually short out electronics. After
work is complete, thoroughly clean, vacuum the area, and re-inspect the unit for foreign material.
SERVICE WARNING!
Do not service equipment with voltage applied! The unit can
source of fatal electrical shocks! To avoid shoc k hazard, disconnect
main power and control power before working on the unit. Warning
labels must be attached to terminals, enclosure and control panel to
meet local codes. Use Lock Out tags such as the one shown when
servicing equipment.
Make sure there is sufficient clearance all around the unit for cooling, wiring and maintena nce purposes. To
conserve panel space, the TE Series – BP models were designed for close vertical clearances of only 1 inch
(25mm) on either side. A minimum horizontal clearance of 4” (100 mm) on the top and bottom is necessary to
maximize effective airflow and cooling. Also the unit must be installed with its heat sink ribs oriented vertically
and running parallel to the mounting surface. Keep in mind that these are minimums. Wiring may require
more clearance, particularly on the bottom.
Cleaning:
In dirty or contaminated atmospheres, the unit should be cleaned on a regular basis to ensure proper
cooling. Do not use any chemicals to clean the unit. To remove surface dust use clean, dry compressed
air only, 80 to 100 psi. A three inch, high quality, dry paintbrush is helpful to loosen up the dust prior to
using compressed air on the unit. Do not use wire brushes or other conductive cleaning materials.
1" minimum (25 mm)
Figure 2: TE minimum mounting clearances
WARNING!
Remove all sources of power before cleaning the unit.
Referring to local code standards for wire sizing and length, connect
power conductors to the unit input terminals marked L1, L2, L3 (R, S,
T for IEC users). Connection points are bus tabs with pre-drilled
holes (see section 2 of the Advanced Installation, Operation and
Programming Manual). Use appropriate compression or mechanical
lugs for termination to these bus tabs. Avoid routing power wires
over the control board or display. Connect the motor leads to the unit
.
terminals marked T1, T2, and T3 (U, V and W for IEC users). If
control power is present, but line power is disconnected from L1, L2
.
and L3, the display will show [n3PH] indicating “no 3 Phase”.
Caution!
Never interchange input and output connections to
the unit. This could cause excessive voltage in the
control logic circuit and may damage the unit.
G
Bypass Contactor
Bypass Contactors are integral (built-in) on all TE versions. See
sections 1.2.3, 3.1.3.c and Appendix 4 of the Advanced Installation,
Operation and Programming Manual for more details on contactor
control and overload protection details.
Power Factor Correction Capacitors
Power factor correction capacitors can be connected to motors
controlled by TE Series starters, however they must be off-line
during ramping. Connect PFC capacitors to the Line side of the
starter with a separate capacitor control contactor.
WARNING!
Never connect power factor correction capacitors on the load
side of the unit. The SCRs will be seriously damaged if
capacitors are located on the load side.
Grounding
Connect the ground cable to the ground terminal as labeled on the
unit. Refer to the National Electrical Code or your local Code for the
proper ground wire sizing and be sure that the ground connector is
connected to earth ground. In ungrounded systems, it is not
necessary to connect a ground to the unit; however, local codes
should always be consulted.
Connection points are bus tabs with pre-drilled holes (see below). Use appropriate compression or
mechanical lugs for termination to these bus tabs.
Suggested wire sizes and tightening torques for factory-supplied conne ctors for conductors rated for 75C are
shown in the chart below. Always consult local codes and industry standard pra c tices for proper wires sizes to
accommodate voltage drop and ambient conditions.
Table 3: TE Series Wire Ranges and Torque S pecifications. Note: TBD = To Be Determined at a later
date.
Tightening
Torque
in.-lbs.
35
45
80
200
Screw /
Bolt Size
1 x M5
(included)
1 x M8
(included)
1 x M8
(included)
1 x 0.38" hole
(M10)
for User supplied
lugs
Tightening
Torque
Nm
4
5
9
15
Suggested
Wire Size
ISOmm2
6
25
70
120
Remote Keypad Mounting
The keypad / operator interface unit can be remotely mounted up to 10’ (3 meters) away from the starter, i.e.
on the enclosure door. A remote mounting kit is necessary, which consists of an adaptor plate, a doorframe
for NEMA 12 enclosures and a pre-assembled ribbon cabl e available in 1-meter length increments. Detailed
assembly instructions and an enclosure cutout template are included with the kit. See Industrial Catalog for
part numbers of the available kits.
Control connections on the TE Series starter are divided into 2 groups. With the unit oriented vertically, TB1
is a 12-point DC terminal block (on the left), and TB2 is a 10 point AC terminal block (on the right side). These
are removable terminal blocks for ease of connection and servicing, and are provided with different spacin g
(pitch) between the header pins so they are not interchangeable. Following are description s of control
connection points.
Figure 5
Note:
Terminal numbers are shown on the side of the first and last terminal of each block. An additional
3 point terminal on the far left side is for serial communication connections.
AC Control Power Supply Connection
Separate AC Control Power supply is required to power the
electronics of the TE Series starter. 120VAC is standard; order 240
VAC (optional) if necessary for your line power supply configuration.
The control voltage must be connected to terminals marked A1 and
A2 of TB-2 as shown in figure 5.1 (these are also Terminal No.’s 21
and 22). This control voltage must be customer supplied, unless an
optional control power transformer (see table below) has been
supplied with the unit.
Table 4: TE Series AC Control Power VA Requirements
-BP:
TE …-BP
Model
TE-18 to 48 48 (Inc. in PCB) 95 9 100
TE-62 to 112 48 (Inc. in PCB) 220 17 250
TE-150 to 160 48 72 298 12.3 500
TE- 210 to 275 48 100 380 11.6 500
TE-361 to 450 48 150 571 14 750
TE-550 to 600 48 200 1000 29 750
PC
Boards
Fans
Bypass
Contactor
Inrush
-BP:
Bypass
Contact
or
Sealed
Recommend
ed min.
CPT
Rating
Control Power
Requirements
When sizing a control power
transformer for the TE…-BP Series starter use the chart
below for minimum sizes or
supply capacity. Any
additional control devices
powered by the same CPT
must be added to the above
values to ensure proper
operation of the Bypass
Contactor.
Output relays in TB2 must be protected from currents in excess of 5A, either with a fuse or with other
suitable current protection devices.
A dedicated fault output for use in PLC or interposing relay control is available on TB1. This opto-isolated
triac switch is rated for 50mA max., 10-250VAC. Any circuit connected to it must be fused accordingly.
Three-Wire Control Connection
For standard 3-wire control, connect dry (voltage free) contacts for the Stop / Start buttons as shown on the
diagram directly above the terminal strip. Connect the NO contact of the Start button to Terminal 1 (far left
terminal), the common point between the Stop and Start to Terminal 2 (2
Stop button to Terminal 3 (3
nd
from left) and the NC from the
rd
from left).
Seal-In Contact
The TE Series uses an internally pre-wired “seal-in” contact
around the Start button (Terminals 1 and 2). No external
relay or auxiliary output connection is necessary.
Two Wire Control: Relay / PLC Connection
An alternate connection for automated or unattended
operation replaces the start/stop push buttons by connecting
a dry (voltage free) maintained contact closure between
terminals 1 and 3 as shown in Figure 5.3. When this contact
is closed, the TE Series starter will start and run. When it is
opened, it is the same as a Stop command.
When a maintained contact is used for start/stop it is
Note:
advisable to set the overload relay to the manual reset
position. This will prevent the motor from restarting if the
thermal overload trips and then cools down.
CAUTION!
Control Terminals 1-10 of TB1 are configured using solid state devices po wered
internally with a 24VDC power supply. To prevent damage to the TE Series control
board, use dry (unpowered) contact closures only when connecting to these terminals.
If existing 120VAC or other powered control circuit must be interfaced, use isolating
relays and control the TE Series with 2 wire control as shown above.
Interlock Connection
TB1 provides a connection point for an external dry (voltage free) N.C. (Normally Closed) interlock device
between terminals 4 and 5. Examples where this interlock connection would be used include low oil, high
temperature, or excess vibration dropout from user supplied
devices. A factory-installed jumper is provided which allows
the TE Series unit to operate if external interlocks are not
used. If this jumper is removed and an interlock is not
the TE Series unit will not function.
The TE Series starter is provided with input terminals for connecting a PTC (Positive Temperature
Coefficient) Thermistor that may be imbedded in the motor. These
are specialized resistors imbedded in some motor windings that
increase in resistance as the temperature increases. Whe n the
TE Series detects that the PTC input resistance is too high, it
initiates a PTC trip, and displays [PTc] on the readout. This is
independent of the Thermal Register overload current protection
and provides supplemental protection for high motor ambient
temperature applications. Terminals for this input are provided
with a factory jumper that must be removed if the PTC input is
used. These are Terminals 9 and 10 located on TB1.
PTC resistors are also found in other devices such as bearings,
air receivers, oil or coolant reservoirs and air discharge systems that may require shutd own of the motor.
PTC Resistor Values:
The resistance must be less than or equal to 750 at 25ºC. If multiple resistors are used in the motor, the
sum of all resistors in series must equal or be less than this value.
Fault Signal
An optically isolated Triac output is dedicated as a fault indicator
on TB1, terminals 11 and 12, labeled “Opto”. The output Triac
switch is rated for 10 - 250VAC, 50 mA (maximum). If the three
programmable Output Auxiliary Relays are being used for other
functions, this output can easily be hooked up to a PLC or small
external relay to provide a Fault signal. This Fault Output
operation is permanently fixed at “Any Trip”, duplicating the
Relay setting 16 as shown in Table 5.6.10 of the Advanced
Installation, Operation and Programming Manual.
This output is permanently set to this function and is not programmable.
TB1 includes provisions for enabling the Dual Ramp and Jog functions by using external contact closures.
Both features use a common +24VDC from terminal 7 however, they can be used independently of each
other or together. See Section 5.6.2.and 5.6.3 of the Advanced Installation, Operation and Programming
Manual for full function description and setup.
Dual Ramp Command
Closing a dry (voltage free) contact between TB1, terminals 6 and 7 will enable Ramp 2, and the TE Series
starter will respond to the settings for Ramp 2 in F015 - F018. If no contact closure is present, the TE Series
starter defaults to the Ramp 1 parameters (F011 – F014). See
Section 5.6.2.of the Advanced Installation, Operation and
Programming Manual for full function description of how to setup the
Dual Ramp Feature.
The Dual Ramp feature is useful in instances where the load
changes significantly. Example: a loaded or unloaded conveyor belt.
The characteristics for starting an unloaded conveyor can be
programmed for ramp 1. The characteristics for starting a loaded
conveyor can be programmed for ramp 2. Ramp 2 can also be
programmed for Full Voltage / Across-the-Line starting by setting the
ramp time to 0 and Current to 600%.
Dual Ramp is also useful in 2-speed motor applications. Simply use an auxiliary contact from one of the
speed contactors to select Ramp 2 so that separate ramp profiles can be used.
Jog / Remote Command
Connecting a dry (voltage free) contact between TB1, terminals 7 and 8 will enable the Jog feature. A Start
command (Run Command or Start button) is required to activate the Jog feature. See Section 5.6.3 of the
Advanced Installation, Operation and Programming
Manual for full function description of how to setup of
the Jog Function.
The Jog feature can be used for tasks such as lining up
machines for blade or bit changes or inching belts
along to check tracking.
This input is also used to change the function of the
Serial Communications port control through F068. For
additional information, see user manual.
Three programmable auxiliary relays are on TB2. The TE Series starter comes with three programmable dry
relay output contacts. Outputs 1 and 2 are Form C (SPDT), with a Common, N.O. and N.C. Output 3 is a
Form A, (SPST), N.O. contact. It is not necessary to use the programmable output auxiliary relays in the Start
/ Stop circuit. An internal seal-in relay is provided elsewhere (see 4.2.2.a). Toshiba recommends fusing all
outputs with external fuses. The relays are rated for 240 VAC, 5 A and 1200 VA.
Factory default settings for these relays are as follows:
AUX 1 – Run / Stop (see F060).This contact changes
state upon a Start command, returns to normal on Stop
(or Begin Decel if active).
AUX 2 – At-Speed / Stop (see F061).This contact
changes state upon the TE Series detecting At-Speed,
and returns to normal on Stop. At-Speed is determined by
the TE Series detecting the current dropping after
reaching End-of-Ramp.
AUX 3 – Any Trip (see F062) this contact closes when
any trip condition 5 – 15 (as defined in Table 5.6.10 of the
Advanced Installation, Operation and Programming)
occurs.
All relays can be reprogrammed for a wide variety of
functions. See Section 5.6.9 of the Advanced
Installation, Operation and Programming Manual for additional relay programming details.
Note:
It is not necessary to use the programmable output auxiliary relays in the Start / Stop
circuit. An internal seal-in relay is provided elsewhere (see “Three Wire Control
Connections”).
Bypass Contactor Control
On TE…-BP starters, an internal dedicated connection is used at the factory for automatically controlling the
Bypass Contactor. Field wiring for Bypass Contactor operation is not required.
Independent Bypass Contactor Control
The TE…-BP Series starters use standard industrial contactors that can be controlled independent of the
starter electronics if necessary. When doing so, it is necessary to size the starter based upon the ATL
(Across-the-Line) selection chart so that the contactors are rated for ATL duty instead of normal Shunt Duty.
(See Section 1.2.3.of the Advanced Installation, Operation and Programming Manual). Supplemental
overload protection will be required (See Section 3.1.3.of the Advanced Installation, Operation and
Programming).
Units have external terminal blocks marked for this purpose (see Appendix 5 of the Advanced Installation,
Operation and Programming Manual for additional for drawings). Dry (voltage free) contact closure between
these terminals will close the bypass contactor immediately. The Bypass Contactor coil voltage is the same
as the control voltage (120VAC unless the optional 240VAC control is specified), and the voltage on these
terminals is the same as the coil voltage.
1. Apply three phase power to the unit. The motor should not run until a Start command is applied.
2. Apply control power and check that the “Power On” LED comes on.
3. Status Display should read [0000.] showing no current in Phase A (minor flickering of the first digit is
common).
4. Apply the Start (Run) command. The motor should begin to accelerate. Status display will read Phase A
Amps at an increasing rate.
5. When the motor reaches full speed, the “At-Speed” LED comes on and the Bypass Contactor will close.
Status display should show a sharp decrease in Phase A Amps.
6. If the motor does not fully accelerate, decelerates, or stops during the acceleration period, hit the Stop
button immediately and open the disconnect.
Stopping:
If Pump-Flex Decel is Disable d
1. Remove the Run Command (or hit the Stop button).
2. At-Speed LED will go out and Bypass Contactor will open. Status display should read [0000.] indicating
no current on Phase A.
3. Motor will coast to a stop according to load inertia and friction.
If Pump-Flex Decel is Enabled
1. Remove the Run Command (or hit the Stop button).
2. At-Speed LED will go out and Bypass Contactor will open. Status display should briefly read Phase A
Amps increasing
3. Motor should begin to slow down. Status display should begin to show decreasing
4. When motor reaches Stop Level, TE should turn off. Status display will again show [0000.]
If the unit does not follow this operational sequence please contact the factory o r refer to the TE Series
Troubleshooting Guide.
It is best to operate the motor at its full load starting conditions to achieve the proper time, torque and ramp
settings. Initial factory settings are set to accommodate general motor applications and provide basic motor
protection. Advanced features must be enabled via programming. The only parameter that MUST be set by
the user is motor FLA (F001).
Digital Interface: The TE Series Soft Starter includes a digital keypad with eight LEDs, seven
command keys, and an LED display with four alphanumeric digits.
Reset Clears the Trip indication and releases the Trip Relay.
Fn Enters or exits the Program Mode.
Up and Down
Arrows
Right and Left
Arrows
Power On Control power is available at A1 and A2
At-
Speed
Shunt
Trip
Shorted
SCR
Over
Current
Phase
Loss
Over
Temp
Over
Load
Navigates through the Status Display Mode, scrolls up
and down through the Function List, increases or
decreases the value of the active (flashing) digit and
scrolls through the fault history. When entering values,
holding the key down for more than 2 seconds will
activate Auto-step, which increases its rate the longer the
key is held down.
Each key press shifts the active (flashing) digit to the right
or left by one position, allowing you to change higher
values of functions without waiting to Auto-step though
large numbers.
The motor is at full power and the Bypass Contactor has
been commanded to pull in.
The SCRs are at full conduction and current has dropped.
Power is flowing to the motor in the Off mode. See section
5.6.8.a of the Advanced Installation, Operation and
Programming Manual for additional information.
There is no voltage drop across at least one SCR phase
assembly, indicating that at least one SCR is shorted.
See section 7 of the Advanced Installation, Operation and
Programming Manual for additional information.
Overcurrent LED lights for three sets of fault conditions:
1) During start, the unit saw current exceed the normal
rate of increase in the first 250ms.
2) During Run, current exceeded either the OC setting in
F042 for the delay set in F043. This LED will be
accompanied by oCA, oCC or oCd on the display.
3) The unit has seen a Short Circuit exceeding 10x FLA
for 12.5ms. This LED will be accompanied by SCA, SCC or SCD display.
One or more of the phase currents dropped below the
threshold during starting or running.
Starter has tripped due to excess heat sink temperature.
This will automatically reset.
Starter has tripped due to the Thermal Register reaching
0000. The Overload must reset before this fault can be
cleared.
4 digit 7 segment display with a decimal point on the right
side indicating Phase A.
There are three modes of display: The Status Display Mode, the Program Mode, and the Fault Mode.
Status Display Mode (Default Display)
The Status Display Mode displays seven “screens” of information. Motor Currents (3 phases), Remaining
Thermal Capacity, Ground Current, Remaining Time on the Process Timer, and Time Base of the Time Clock
Controller. This is also the entry screen for going into the Program Mode.
Status mode:
[0000.] The initial display on power up is four digits and the decimal. This indicates the motor current for
Phase A of the motor.
[0000] Scroll UP to display four digits only (no decimal). This indicates the motor current for Phase B. While
viewing Phase B, press the UP arrow again to view Phase C current.
[G000] Scroll UP to display the “G”. This shows the value of the current flowing to ground on the motor leads.
[H000] Scroll UP to display the “H”. This indicates the value of the remaining thermal capacity percentage of
the motor (i.e. H070 = 70% remaining thermal capacity).
Program Mode
The starter must be STOPPED in order to enter the
Program Mode. Use the Program Mode to view or change
Function (Fn) settings. To enter the Program Mode, press
the [Fn] key once from the Status Screen described in
section 5.3.1 of the Advanced Installation, Operation and Programming Manual. The first time you enter the
Program Mode after power has been cycled to the starter,
the initial function [F001] should be displayed with the
selected digit flashing. If the TE Series starter has been
programmed and power to the unit has not been cycled,
the readout will display the last function viewed or
changed. To change to a different function, use the arrow
keys.
Viewing Function Programming and Values
The programming of each individual Function can be
viewed without making changes (values can also be
viewed in the Run Mode however, no changes can be
made). Each Function is signified by the letter “F” in the
beginning of the data, the 4 digit value of the function
follows after pushing the [READ/ENTER] key
• [F001] “F” indicates the programmable Function.
• [0000] This is the present setting of the applicable
function.
This display may include decimals between digits depending on the function setting’s ra nge and incremental
steps.
[F001] - “F” indicates the programmable Function.
[0000] - This is the present setting of the applicable function. This display may include decimals between digits
depending on the function setting’s range and incremental steps.
Pressi ng the [Fn] key again will return to the Function display without making changes.
From the instructions above, after pressing the [READ/ENTER] key the display will show the value of that
function with one digit flashing (usually the rightmost digit). Flashing indicates this is the digit to be altered
(similar to cursor position). Use the UP arrow key to increment the value of the flashing digit. Use the DOWN
arrow key to decrement the value of the flashing digit. Use the LEFT or RIGHT arrow to select the next digit to
be altered. Values can only be changed within the Adjustment Range of the function parameter.
Pressing the [READ/ENTER] key again will store the new programming for that Function and return to the
Function display.
If the display shows [Inh] when trying to store the changes, the unit is running a nd must be Stopped, or a
Password has been set up to prevent access and must be entered first. See section 5.6.11 of the Advanced
Installation, Operation and Programming Manual for details about this feature.
Caution!
If the Fn key is pressed or power is lost before the [READ/ENTER] key is pressed, the TE
Series Starter will not store the selected value in memory.
Fault Mode
The Fault Mode Display provides information to the operator when a fault occurs and allows the operator to
review fault history. Refer to described in Section 7 of the Advanced Installation, Operation and Programming
Manual for details. Fault codes are displayed by 3 alpha characters. The first and second characters (rea ding
left to right) are the initials for the applicable English-language fault name. The third or right-most character
can be either A, c, or d to denote when the fault occurred: “A” denotes Acceleration, “c” denotes Constant
speed, and “d” denotes Decel or Stopped.
Viewing a Function’s Set Value
[0000.] Indicates Phase A is drawing no current
(unit is in “Off" mode).
Press the [Fn] key
[F001] Indicates this is Function 001 (Motor FLA).
Press [READ/ENTER] key to view the F001 value
[0048] Indicates the programmed motor FLA is 48
Amps. Right most digit (8) flashes, indicating that
this is the digit that you will alter (cursor position).
Press the UP Arrow key to increase this digit
value
[0049] Indicates you have increased the right most digit to a value of 9.
Press the LEFT Arrow key to shift left to the
next digit
[0049] Second digit from the right is now flashing,
indicating a new cursor position.
Press the UP Arrow key to increase this digit
value
nd
[0059] Indicates you have increased the 2
to
right digit to a value of 5 (10’s place).
Press [READ/ENTER] key to store the new value
[End] The word “End” will flash briefly to indicate
that the new value has been entered and accepted.
After flashing once, the display will revert to
showing the Function number.
Press the [Fn] key
[0000.] Returns to the Default Display, indicating Phase A
is drawing no current
Note: When first entering FLA into a new unit, pressing the Up arrow key will jump the readout value
immediately to ½ of the unit Max. Amp rating and it will never go below that again. Any unit thought to be
new which has a value other than 0000 in F001 upon setup, has been programmed previously and should
be reset to factory defaults before proceeding.
F013 Accel Ramp Time of Ramp 1 1-120 seconds 1 second 10 seconds
F014 Max Current Limit of Ramp 1 200 - 600% Motor Current 1% 350%
F015 Initial Torque (VR) of Ramp 2 0-100% Line Voltage 1% 60%
F016 Initial Torque (CR) of Ramp 2 0-600% Motor Current 1% 200%
F017 Accel Ramp Time of Ramp 2 1-120 seconds 1 second 10 seconds
F018 Max Current Limit of Ramp 2 200 - 600% Motor Current 1% 350%
F019
F020 Time of Voltage Jog 1 – 20 Seconds 1 second 10 seconds
F021 Current Jog 100 – 500% Motor Current 1% 150%
Fn # Group Function Description Adjustment / Display Range
F085
F086
F087
F088
F089 Time Stamp, Fault #2
F090 Date Stamp, Fault #2
F091 Fault History #3, Oldest Fault
F092 Time Stamp, Fault #3
F093 Date Stamp, Fault #3
F094 Run Time, Hours 000.0 – 999.9 hours 0.1 hours 0
F095
F096 Run Cycle Counter 0000 – 9999 times 1 times 0
F097
Fault History #1, Latest Fault
Time Stamp, Fault #1
Based on F078-80
Date Stamp, Fault #1
Based on F076-77
Fault History #2, Previous
Fault
Fault History and Run Data
Run Time,
1000 Hour Overflow
Run Cycle Counter
10K overflow
0 = No fault history, or
Fault # 1 - 27: see Fault code list
00.00-23.59 (hh.mm)
[hh = 00-23; mm = 00-59]
01.01 – 12.31 (MM.DD)
[MM = 01-12; DD = 01-31]
0 = No fault history, or
Fault # 1 - 27: see Fault code list
00.00-23.59 (hh.mm)
[hh = 00-23; mm = 00-59]
01.01 – 12.31 (MM.DD)
[MM = 01-12; DD = 01-31]
0 = No fault history, or
Fault # 1 - 27: see Fault code list
00.00-23.59 (hh.mm)
[hh = 00-23; mm = 00-59]
01.01 – 12.31 (MM.DD)
[MM = 01-12; DD = 01-31]
0000 – 9999 thousand hours 1 k-hour 0
0000 – 9999 10 thousand times 1 10k times 0
Setting
Increments
1 0
00.01 00.00
00.01 01.01
1 0
00.01 00.00
00.01 01.01
1 0
00.01 00.00
00.01 01.01
Factory
Setting
Setting
Function 51 Internal protection feature s
Several protection features in the TE Series are accomplished with internal hardware and use software
switches in Function 51 to enable or disable them. The following chart shows these functions and the
factory default settings. Refer to the A dvanced Installation, Operation and Programming Manual,
Section 5.6.8.a for details on how to change these settings.
Protection
Function
Phase Rotation
Trip
Expected Phase
Sequence
Phase Current
Loss
Shorted SCR
Lockout
Shunt Trip
PTC Input Trip PTC Trip function. This can be disabled so that a jumper is not required across the PTC inputs.
Line Loss Trip
Descriptio
Phase Rotation protection.
Phase rotation must match selection in Bit #2 below. Setting to Off (0) will make the TE
insensitive for use behind a reversing contactor
2 = A-B-C Phase Rotation Sequence Only
0 = A-C-B Phase Rotation Sequence Only
Phase Current Loss, any phase current reading is less than 8 - 20% (Depending on frame
size) of unit max amp rating after 3 seconds from Start command.
At least one SCR has shorted; there is no voltage drop across the SCR phase assembly.
Shunt Trip of the main Circuit Breaker or Isolation Contactor (if provided and wired to an Aux.
relay in F060-F061)). 2 or more SCRs have shorted in opposing phases so current was
flowing to the motor while the TE was in the Off state.
Protection against loss of input line voltage. Disabl e when using an In-Line Isolation
Contactor or any other system that normally removes line power from the starter. Resets
automatically when line voltage returns.
Rotation
Default
Settin
Off
A-B-C
On
On
On
On
On
Table 6: Function 51 table of Hardware Protection Features
Functions F060 through F062 provide the ability to program the functions of each of the 3 Output
Auxiliary Relays. Factory default programming is p rovided which covers a wide variety of applications,
but any of these relays can be changed as per the following chart.
Notes:
Check relay wiring before changing programming to avoid unintended consequences.
Relays programmed to some protection features will not operate if function is disabled
elsewhere.
Setting
1 Run / Stop (Changes on Start, resets on Stop) 14 Ground Fault Trip
2 At-Speed / Stop 15 Phase Rotation Trip
3 At-Speed / End of Dec e l 16 Any Trip (#5 - #15)
4 Start / End of Decel 17
5 Short SCR T ri p 18 Coast Do wn Time Lockout
6 Phase Loss Trip 19 Starts Per Hour Lockout
7 Shunt Trip 20 Time Between Starts Lockout
8 OL (Motor Thermal Overload) Trip 21 Any Lock out (# 1 8-# 20)
9 OT (Starter The rm al Over Tempe rat u re) Tri p 22 Run Timer (F03 0) Engaged
10 Short Circuit Trip 23 Run / Stop with On-delay from F063
11 Current Imbalance Trip 24 At-Speed / Stop with On-delay from F063
12 Over Current (Shear-Pin) Trip 25 At-Speed / End of Decel w/ On-delay from F063
13 Under Current Trip 26 Start / End of Decel with On-delay from F063
27
Relay Operation Description
Setting
Table 7: Aux. Relay Settings
*Note: Flash rate for Setting #17 is ½ second On and Off
The TE Series will automatically enter the Fault Mode when a fault occurs in the motor or starter and display
a code indicating the condition that caused a shutdown. Fault codes are three-digits in length and are
displayed in alpha characters. The first and second characters (reading left to right) are the initials for the
applicable English-language fault name. The third or right-most character can be either A, c, or d to denote
when the fault occurred: “A” denotes Acceleration, “c” denotes Constant speed, and “d” denotes Decel or
Stopped.
A Fault History of the past 3 events is stored and can be accessed by using the Up or Down Arrow keys
pressing the Reset button. The first (newest) event is indicated by the decimal point in the lower right
before
corner. A more detailed history with time and date stamps is also kept in Functions 85 through 93.
Fault Codes:
Basic common fault codes are shown in the chart below. For additional details refer to Chapter 7 of the
Installation, Operation and Maintenance Manual, or contact the factory for assistance.
Fault Condition Description
Over Current during Accel; Const speed; DecelocA; occ: ocd
Phase Loss during Accel; Const speed; Decel PLA; PLc; PLd
Over Temperature during Accel; Const speed; Decel otA; otc; otd
Overload during Accel; Const speed; Decel oLA; oLc; oLd
Shorted SCR during Accel; Const speed; Decel SSA; SSc; SSd
Shunt Trip during Accel; Const speed; Decel st
Current Imbalance during Accel; Const speed; Decel IbA; Ibc; Ibd
Under Current during Accel; Const speed; Decel UcA; Ucc; Ucd
Short Circuit during Accel; Const speed; Decel ScA; Scc; Scd
Ground Fault during Accel; Const speed; Decel GFA; GFc; GFd
Bypass Discrepancy during Accel; Const speed; Decel bP A; bPc; bPd
PTC Trip during Accel; Const speed; Decel PtA; Ptc; Ptd
Rotation Trip during Accel; Const speed; Decel rtA; rtc; rtd
Fault Display
Code
Reado
Fault Number Code
used in History,
F085, F088 and
F091
1; 2; 3Over Current
4; 5; 6 Phase Loss
7; 8; 9 Over Tem p
10; 11; 12 Over Load
13; 14; 15 Shorted SCR
16; 17; 18 Shunt Trip
19; 20; 21 --22; 23; 24 --25; 26; 27 Over Current
28; 29; 30 --31; 32; 33 --34; 35; 36 Over Load
37; 38; 39 ---
LED
Indicator
Additional codes that may be displayed
Display Code
Readout
nFLA No Full Load Amps set in F001
Inh
n3Ph No 3 Phase: No input line voltages on one or more phases
Loc
Err
Inhibit: Start er is still Run m ode when you are attem pting a change in program ming, or the st arter
has Password Protection enabled and you have not entered the password code.
Lockout: The unit has tripped on Overload and you are attempting to Reset before it is ready,
or one of the Duty Cycle Lockout protec tion features has been enabled.
Error: You are attempting to enter an invalid password
The TE Series Starter provides true U.L. listed I
the main digital processor for maximum motor protection. It simulates the tripping action of a bimetallic overload relay, with the accuracy and repeatability of a digital control system. It is adjustable
over a wide range and can be easily programmed for different trip curves.
Thermal Memory
The TE Series microprocessor u ses a sophisticated “Thermal Regi ster” in the digital memory to keep
track of motor heating and cooling over time regardless of the starter’s power status. By using nonvolat ile memory , th e TE Series does not “forget” that the motor has been running even if power to the
starter is turned off and back on. Continuous overload protection is provided based on the true thermal
condition of the motor.
Therm al Cap aci ty
The Thermal Register is displayed as a percentage. This percentage is the motor’s remaining
capacity. The percentage value begins at 100%; showing that the motor is cool (e.g. motor has 100% of
its capacity available). As the motor heats up or moves toward an overload condition, the percentage
begins to drop. The Thermal Capacity is derived from the programmed motor nameplate Full Load
Amps (FLA) in Function F001, the Service Factor rating in Function F002, and the Overload Trip Class
in Functions F003 and F004. Setting these functions to the proper values provides maximum protection
and eliminates nuisance tripping.
Examples:The Remaining Thermal Capacity can be viewed by using the UP or DOWN arrow
keys when in the Status Display mode. From the default Phase A Current screen (dot
on right side), press the UP arrow key 4 times to display [H100] meaning there is
H100
100% Thermal
Capacity remaining
at rest
H057
57% Thermal Capacity
remaining after starter
(43% used)
Disabling the Overload Protection
The Overload Protection feature can be disabled if necessary. Please refer to the Advanced
Installation, Operation and Programming Manual for instructions and considerations before
disabling the Overload Protection.
100% of the Thermal Capacity (H = Heat capacity) remaining in the motor. After
starting or running, the motor wi ll u se this capacity and the display will show a lower
number. For example, after a cold start, the display may read [H065] which indicates
that the motor has 65% of its thermal capacity remaining (35% used). The Status
Display screens cycle back to the beginning, so the Down arrow keys can get to this
display as well.
Motor Full Load (FLA) Setting
Use Function F001 to enter motor FLA as indicated on the motor nameplate. (Do not
calculate for service factor, this is programmed separately in F002).
Note:
All TE Ser ies starters are shipped from the factory with F001 set to a default value
of 0000. If F001 is left at the factory default, the unit will not operate. If the user
attempts to start the TE Series without entering the motor nameplate FLA, the
starter will Fault and the display will read “nFLA” (no Full Load Amps).
WARNING!
Do NOT disable Overload Protection unless another Thermal Overload
Protection device exists in the circuit for all three phases. Running a motor
without Overload Protection presents serious risk of motor damage or fire.
2
t Thermal Overload Protection as a built-in function of
Manual Reset
The factory default setting is Manual Reset. This means that when the Overload Trip is activated, the
starter cannot be restarted without pressing the Reset key. The Overload Trip will not reset until the motor
cools down (see 3.1.3.d). The Manual Reset function is also “trip free”. Holding in the Reset key will not
prevent the Overload Trip from activating and protecting the motor.
Note:
When the Overload Trip activates, the Overload LED will glow solid. When the motor
cools down, the LED will begin to flash, indicating that the Overload Trip can be reset.
Automatic Reset
If Autom atic Res et is necessar y, change from Manual Res et to Automatic Rese t by using F unc tion F005.
(See Section 5 of the full Installation, Operation and Maintenance for details). In this mode, a 3-wire
control circuit will be capable of restart when the TE Series has reset itself after the cool down period.
WARNING!
Two-wire control systems may restart without warning when Auto Reset
is selected. Extreme caution should be exercised. To prevent automatic
restarting with 2-wire control systems, use external interlocking to
provide sufficient warning and safety to operators. A Warning Label
similar to that shown below (and the one provided in the packet with
this manual) must be located where visible (on the starter enclosure
and/or the driven equipment) as required by local code.
WARNING: MOTOR CONNECTED TO THIS EQUIPMENT
MAY START AUTOMATICALLY WITHOUT WARNING
NEMA Class Trip Curves
NEMA Class trip curves are based on a common tripping point of 600% of motor Full Load Amps (FLA).
Curves vary by the amount of time before the unit trips. As an example, a Class 20 curve will trip in 20
seconds at 600% of FLA. The factory default setting of Class 10 will trip in 10 seconds at 600% of FLA.
Dual Overload Trip Curves
The TE Series Soft Starter provides two separate Overload Trip Protection Curves, one for starting and one
for running conditions. The starter’s At-Speed detection circuit determines when the motor has reached full
speed. When the At-Speed condition is reached, the overload trip curve will shift from the Start to the Run
level, as programmed in Functions F003 and F004. See Section 5.6.1 of the Advanced Installation,
Operation and Programming Manual for programming details.
Starting Overload Trip Curve
During the start mode, Overload Trip Curves are selectable from NEMA Class 5, 10, 15, 20, 25, and 30.
The default setting of Class 10 allows protection for the overload capacity of the soft starter as well as
the motor. Use a higher Trip Class only if nuisance tripping occurs with the default setting.
Running Overload Curv e
During the Run mode, Overload trip curves are selectable from NEMA Class 5, 10, 15, 20, 25, and 30.
Program the appropriate curve according to the characteristics of your motor and load.
Overload Protection During Bypass
When a Bypass Contactor is used to shunt power around the SCRs in the TE Series (a s in the TE…-BP
version), overload protection is maintained as long as the TE Series is directly controlling the contactor.
No additional Overload Relay is necessary for normal operation.
Special Consideration for Across-the-Line (Direct-on-Line) Contactors
When the Bypass Contactor on a TE…-BP Series has been selected to be used for Across-the-Line
resta rt , su p p l e men t a l ov e rl o ad p r o te c t i o n must be added. For t h is ap p l ic a ti o n , refe r t o th e E x te r n al
Overload Relay Applications supplement and wiring diagram in Appendix 5 and section 4.2.6.a of the full
Installation, Operation and Maintenance Manual for detailed instructions.