Toshiba RAV-SP180AT2-UL User Manual

AIR CONDITIONER (SPLIT TYPE)
Installation manual
Outdoor Unit
RAV-SP180AT2-UL
For OUTDOOR USE only
Not accessible to the general public
Vente interdite au grand public
Kein öffentlicher Zugang
Non accessibile a clienti generici
No destinado alblico en general
Não acessível ao público em geral
Niet geschikt voor huishoudelijk gebruik
Μη προσβάσιμο από το γενικό κοινό
Недоступен для посторонних
Genel erişime açık değildir
Installation manual Air conditioner
Manuel d'installation Climatiseur
(Split type)
(Type split)
1
19
English
Français
Outdoor Unit
Please read this Installation Manual carefully before installing the Air Conditioner.
• This Manual describes the installation method of the outdoor unit.
• For installation of the indoor unit, refer to the Installation Manual attached to the indoor unit.
Installation Manual
ADOPTION OF NEW REFRIGERANT
This Air Conditioner uses R410A an environmentally friendly refrigerant.
Contents
1 DIMENSION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
2 ACCESSORY PARTS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
3 SYSTEM REQUIREMENTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
4 PRECAUTIONS FOR SAFETY. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
5 INSTALLATION OF NEW REFRIGERANT AIR CONDITIONER. . . . . . . . . . . . . . . . . . 7
6 REFRIGERANT PIPING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
7 ELECTRICAL CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
8 EVACUATE AND DEHYDRATE THE SYSTEM. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
9 FINISHING. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
10 TEST RUN. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
11 PERIODIC MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
12 UNIT PUMP DOWN. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
13 POWER SAVE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
1-EN
–1–
Outdoor Unit
1 DIMENSION
Installation Manual
(2-
Ø0.7"(20) × 3.5"(88) long hole)
2.1"(54)
1.5"(38)
0.4"(11)
12.6"(320)
Drain hole
12"(306)
12.6"(320) For anchor bolt)
(Long hole pitch
1.2"(30)
0.2"(5)19.1"(486)1.3"(33)
2"(51) 17.7"(449)
23.6"(600)
R0.6"(15)
2-Ø0.2"(6) hole
Product external line
Ø0.4"(11)×0.6"(14)
U-shape hole
A legs
11.4"(290)
Ø0.2"(6) hole pitch
Discharge guard
23.6"(600) 3.5"(90)
Drain hole(
2.4"(60)
B legs
19.1"(486) 10"(255)
19.7"(500)1.3"(32)
12.6"(320)
1.5"(38)
2.1"(54)
Ø1"(25))
4.3"(108)
30.7"(780)
Ø0.4"(11)×0.6"(14)
U-shape hole
Product external line
2-Ø0.2"(6) hole
R0.6"(15)
23.6"(600)
Details of B legsDetails of A legs
1.2"(30)
0.6"(16)
2.7"(69)
Discharge guide mounting hole
(4-Ø1.8"(4.5) embossing)
2.1"(54)4.9"(125)4.3"(108) 2-Ø0.4"(11)-0.6"(14)
U-shape hole
(For Ø0.3"(8)-0.4"(10)
8-Ø0.2"(6) hole
(For fixing outdoor unit)
2-Ø0.4"(11)×0.6"(14) long hole
(For Ø0.3"(8)-0.4"(10) anchor bolts)
0.9"(22)
1"(26)
3.5"(88)
anchor bolts)
Charge port
5.6"(141)
Space required for service
2-Ø0.4"(11)×0.6"(14) U-shape holes
(For Ø0.3"(8)-0.4"(10) anchor bolt)
5.9"(150) or more
12.6"(320)
19.7"(500) or more
6.2"(157) 3.1"(79)
13.5"(342)
23.6"(600)
Air intake
5.9"(150) or more
Air discharge
5.7"(145)
6.1"(155) Refrigerant pipe
connecting port (
Ø0.3"(6.4) flare at liquid side)
Refrigerant pipe connecting port (
11.8"(300) or more
(Minimum
distance up to wall)
2-Ø0.4"(11)×0.6"(14) long hole
(For Ø0.3"(8)-0.4"(10) anchor bol
0.8"(21)
2"(53)
Ø0.5"(12.7) flare at gas side)
–2–
EN
2-EN
Outdoor Unit
2 ACCESSORY PARTS
Part name Q’ty Shape Usage
Installation manual 1 This manual (Hand this directly to the customer.)
Drain nipple 1
Waterproof rubber cap 2
NOTE
Use drain nipple and waterproof rubber cap as necessary.
Installation Manual
3-EN
–3–
Outdoor Unit
3 SYSTEM REQUIREMENTS
Installation Manual
Piping (Field supplied)
• Minimum refrigerant line length between the outdoor unit and indoor unit is 16.5” (5 m)
• Maximum pipe lengths
Allowable
pipe length
(ft (m))
Total length LIndoor unit:
164’1” (50) 98’5” (30) 98’5” (30)
Figure of Single
Outdoor Unit
Height difference
(Indoor-outdoor H)
(ft (m))
Upper
Indoor Unit
Outdoor unit:
L
H
Lower
Number of
bent portions
10 or less
Refrigerant charge
Length of refrigerant
pipe connected to
indoor/outdoor unit
16’5” - 65’7”
(5 - 20 m)
*65’7” - 164’1”
(20 - 50 m)
Additional refrigerant
None
Add 0.22 oz/ft (20 g/m) of refrigerant for piping that exceeds 65’7” (20 m) up to 164’1” (50 m).
* Caution during addition of refrigerant
Max. amount of additional refrigerant is 1.8 lbs (800 g). Charge the refrigerant accurately. Overcharging may cause serious trouble with the compressor.
* Minimum refrigerant pipe is 16’5”(5 m).
This may cause a malfunction of the compressor or other devices.
Metering Device is an electronic EXV (PMV) in outdoor unit.
Connecting power and control cables (Field supplied)
Refrigerant sizes
Liquid side Gas side
Outer
diameter
Ø1/4”
(6.4 mm)
Thickness
0.03”
(0.8 mm)
Outer
diameter
Ø1/2”
(12.7 mm)
Thickness
0.03”
(0.8 mm)
Flare nuts and flaring
• The flare nuts and flaring are different from those for the conventional refrigerant. Use the flare nuts supplied with the air conditioner or those for R410A.
• Before performing flaring, carefully read “REFRIGERANT PIPING”
Insulation
Both lines need to be insulated. Use a minimum 0.4” (10 mm) wall thickness.
• The main power is supplied to the outdoor unit. The field supplied connecting cables from the outdoor unit to the indoor unit consist for 4 wires and provides the power for the indoor unit as well as the communication signal between the outdoor and indoor unit.
• Consult local building codes, NEC (National Electrical Code) or CEC (Canadian Electrical Code) for special requirements.
• The following are the electrical requirements.
Model RAV- SP180 Power supply 208/230 V~, 60 Hz MCA 17 A MOCP (MAX Fuse/CB) 30 A Breaker 20 A
Maximum 65’7” (20 m)
Power wire
System interconnection wires
MCA = Minimum Circuit Amps MOCP =Maximum Over Protection Device Amps.
2 x AWG12
Ground : AWG14
4 x AWG12
EN
–4–
4-EN
Outdoor Unit
Installation Manual
4 PRECAUTIONS FOR SAFETY
Installing, starting up, and servicing air--conditioning equipment can be hazardous due to system pressures, electrical components, and equipment location (roofs, elevated structures, etc.).
Only trained, qualified installers and service mechanics should install, start--up, and service this equipment. Untrained personnel can perform basic maintenance functions such as cleaning coils. All other operations should be performed by trained service personnel. When working on the equipment, observe precautions in the literature and on tags, stickers, and labels attached to the equipment. Follow all safety codes. Wear safety glasses and work gloves. Keep quenching cloth and fire extinguisher nearby when brazing. Use care in handling, rigging, and setting bulky equipment. Read these instructions thoroughly and follow all warnings or cautions included in literature and attached to the unit. Consult local building codes and National Electrical Code (NEC) for special requirements. Recognize safety information. This is the safety--alert symbol . When you see this symbol on the unit and in instructions or manuals, be alert to the potential for personal injury.Understand these signal words: DANGER, WARNING, and CAUTION. These words are used with the safety--alert symbol. DANGER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies hazards which could result in personal injury or death. CAUTION is used to identify unsafe practices which may result in minor personal injury or product and property damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation.
WARNING
Ask an authorized dealer or qualified installation professional to install/maintain the air conditioner. Perform installation work properly according to the Installation Manual.
Inappropriate installation may result in water leakage, electric shock or fire.
Be sure to ground the equipment
Improper grounding may cause an electric shock. Do not connect ground wires to gas pipes, water pipes, lightning rods or ground wires for telephone wires.
Turn off the circuit breaker before attempting any electrical work and maintenance.
Make sure the circuit breaker is off. Failure to do so may cause electric shock. Use an exclusive power circuit for the air conditioner. Use the rated voltage.
When moving the air conditioner for installation to another place, be very careful not to allow the specified
refrigerant (R410A) to become mixed with any other gaseous body into the refrigeration cycle.
If air or any other gas mixes with the refrigerant, the gas pressure in the refrigeration cycle will become abnormally high and it may result in the pipe bursting or personal injuries.
Do not modify this unit by removing any of the safety guards or by by-passing any of the safety interlock
switches.
Do not touch the intake or aluminium fins of the outdoor unit.
Doing so may result in injury.
Tighten the flare nut with a torque wrench in the specified manner.
Excessive tightening of the flare nut may cause a crack in the flare nut after a long period, which may result in refrigerant leakage.
Install the air conditioner securely in a location where the base can sustain the weight of the unit adequately.
If refrigerant gas has leaked during the installation work, ventilate the room immediately.
If the leaked refrigerant gas comes in contact with fire, noxious gas may be generated.
After the installation work, confirm that refrigerant gas does not leak.
If refrigerant gas leaks into the room and flows near a fire source, such as a cooking range, noxious gas may be generated.
Electrical work must be performed by a qualified electrician in accordance with the NEC and local code. Make
sure the air conditioner uses an exclusive power supply.
An insufficient power supply capacity or inappropriate installation may cause fire.
Use only the specified wiring during the unit installation. Ensure that all terminals are securely fixed, so
preventing any external forces having a negative effect on the terminals.
5-EN
–5–
Loading...
+ 14 hidden pages